Xantrex Technology Inc. is a world-leading supplier of advanced power electronics and controls with products from
50 watt mobile units to one MW utility-scale systems for wind, solar, batteries, fuel cells, microturbines, and backup
power applications in both grid-connected and stand-alone systems. Xantrex products include inverters, battery
chargers, programmable power supplies, and variable speed drives that convert, supply, control, clean, and distribute
electrical power.
Trademarks
Sine Wave Plus Long DC Conduit Box is a trademark of Xantrex International. Xantrex is a registered trademark of
Xantrex International.
Other trademarks, registered trademarks, and product names are the property of their respective owners and are used
herein for identification purposes only.
UNLESS SPECIFICALLY AGREED TO IN WRITING, XANTREX TECHNOLOGY INC. (“XANTREX”)
(a) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY
TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION.
(b) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSS OR DAMAGE, WHETHER DIRECT,
INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH
INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER’S RISK.
Date and Revision
July 2004 Revision A
Part Number
973-0032-01-01 Rev A
Contact Information
Telephone: 1 800 670 0707 (toll free North America)
Fax:1 800 994 7828 (toll free North America)
Email:customerservice@xantrex.com
Web:www.xantrex.com
1 360 925 5097 (direct)
1 360 925 5143 (direct)
About This Guide
Purpose
The purpose of this Owner’s Guide is to provide explanations and procedures for
installing the Long DC Conduit Box (DCCB-L) on a Sine Wave Inverter/charger.
Scope
The Owner’s Guide provides safety guidelines and procedures for installing the
Long DC Conduit Box.
Audience
The information in this Guide is intended for the experienced electrician who need
to install the Long DC Conduit Box into a power system. Only skilled personnel,
such as certified electricians and certified Renewable Energy technicians should
attempt installation of this equipment. Skills required include the ability to read
and understand how to follow single-line wiring diagrams.
Organization
This Guide consists of two chapters.
Chapter 1, “Introduction” provides basic information about the design and
purpose of the Sine Wave Plus Long DC Conduit Box.
Chapter 2, “Installation” provides installation and wiring instructions for the Sine
Wave Plus Long DC Conduit Box (DCCB-L).
Warranty and Product Information is provided at the end of the manual.
973-0032-01-01 Rev Aiii
About This Guide
Conventions Used
The following conventions are used in this guide.
WARNING
Warnings identify conditions that could result in personal injury or loss of life.
CAUTION
Cautions identify conditions or practices that could result in damage to the unit or other
equipment.
Important:
know, but not as serious as a caution or warning.
These notes describe things which are important for you to
Product Naming Conventions
DCCB-L refers to the Long DC Conduit Box without any factory installed wiring.
DCCB-L-175/L-250 refers to the Long DC Conduit Box with either a GJ175F or a
GJ250F Circuit Breaker installed. It includes some factory-installed wiring.
DCCB-RE describes a field-installed, dual-conduit box installation intended for
supporting multiple RE sources.
Long DC Conduit Box refers to all products and is used in situations where all
three products are treated the same.
iv973-0032-01-01 Rev A
Abbreviations and Acronyms
ACAlternating Current
AHJAuthority Having Jurisdiction
ASCAuthorized Service Center
AWGAmerican Wire Gauge
BSMBattery Status Meter
BTSBattery Temperature Sensor
CECCanadian Electrical Code
CSACanadian Standards Association
DCDirect Current
DCCB-LDC Conduit Box Long Version for the SW Plus Inverter/Charger
DCCB-L-175/L-250A DCCB-L that includes factory-installed hardware.
PVGFPPV Ground Fault Protection
NECNational Electrical Code (US)
RERenewable Energy
RMAReturn Material Authorization
ULUnderwriters Laboratory
About This Guide
Related Information
You can find more information about Xantrex Technology Inc. as well as its
products and services at www.xantrex.com.
973-0032-01-01 Rev Av
vi
Important Safety Instructions
WARNING
This chapter contains important safety and operating instructions for the Sine
Wave Plus Long DC Conduit Box (all models). Read and keep this Installation
Guide for future reference.
1. Installations of this equipment should only be performed by skilled personnel
such as qualified electricians and certified Renewable Energy (RE) system
installers to ensure adherence to the local and national electrical codes
applicable in your installation. For a list of Xantrex Certified RE dealers,
please visit our website at www.xantrexREdealers.com.
2. Before installing any components, read all instructions and cautionary
markings on the Long DC Conduit Box, the batteries, and all appropriate
sections of this guide.
3. The Long DC Conduit Box is designed to be permanently connected to your
Sine Wave Plus inverter to prevent accidental exposure to shock hazards.
4. Do not expose the Long DC Conduit Box to rain, snow, or spray. To reduce
risk of fire hazard, do not cover or obstruct the ventilation openings.
5. Do not install the Long DC Conduit Box in a zero-clearance compartment.
The Sine Wave Plus inverter that is attached may overheat. Minimum
clearance for ventilation around unit must be 12 inches (305 mm) at the end
and the top.
6. To avoid a risk of fire and electric shock, make sure that existing wiring is in
good condition and that wire is not undersized. Do not operate the inverter
with damaged or substandard wiring.
7. To reduce the risk of electrical shock, disconnect both AC and DC power
from the system before attempting any maintenance or cleaning or working
on the Long DC Conduit Box.
8. The Long DC Conduit Box is provided with an equipment-grounding bar that
must be connected to the inverter equipment ground and the system ground.
9. Do not store any flammable materials near the primary system panel.
973-0032-01-01 Rev Avii
Safety
Explosive gas precautions
1. Working in the vicinity of lead-acid batteries is dangerous. Batteries generate
explosive gases during normal operation. Therefore you must read this guide
and follow the instructions exactly before installing the DCCB-L.
2. To reduce the risk of battery explosion, follow these instructions and those
published by the battery manufacturer and the manufacturer of the equipment
in which the battery is installed.
Figure 2-21 DC Wiring for a Dual Inverters, Dual Long DC Conduit Box System with Multiple RE 2–30
Figure 2-22 Installing the BSM on the Long DC Conduit Box - - - - - - - - - - - - - - - - - - - - - - - - - -2–31
Figure 2-23 Wiring the C-Series Multifunction Charge Controllers to the Long DC Conduit Box
Chapter 1, “Introduction” provides basic information about the
design and purpose of the Sine Wave Plus Long DC Conduit Box.
The following topics are covered in this chapter.
For this topic:See...
“Introduction”page 1–2
“Specifications”page 1–3
“Blockoff Plates”page 1–5
“Options/Accessories”page 1–6
Introduction
Introduction
The Sine Wave Plus Long DC Conduit Box (DCCB-L) connects to the DC side of
the inverter and accepts DC conduit runs. The conduit box provides protection to
the DC cables connected to the inverter and provides a centralized location for the
DC circuit breakers and PV Ground Fault Protection (GFP) breakers. It is also
designed to incorporate cabling from up to two Multi-function DC Charge
Controllers, such as the Xantrex C-Series Charge Controllers, and cabling from a
battery meter, such as the Xantrex Battery Status Meter.
The Long DC Conduit Box is available in three different configurations.
•The DCCB-L Basic provides an internal ground bar only and space to add
additional circuit breakers; three large and six small.
•The DCCB-L-175 includes a 175 amp GJ, F-Type, circuit breaker, a DC
negative bus bar and 500A/50 mV shunt, battery cables (1 set) and a ground
wire connected to the ground bar.
•The DCCB-L-250 includes a 250 amp GJ, F-type, circuit breaker a DC
negative bus bar and 500A/50 mV shunt, battery cables (1 set) and a ground
wire connected to the ground bar.
For expandability, the Long DC Conduit Boxis designed so that a second DCCBL (any model) can be added on for additional breaker spaces, wiring, room and
controller mounting spaces. Dual configurations have been certified to meet
UL1741-2001 (First Edition) standards when using the field-installable
accessories as listed page 1–6.
Blockoff
Plates
Upper
Lower
DCCB-L includes:
A
❐ Front Cover
❐ Blockoff Plates (top and bottom)
B
C
❐ DC Ground Bar
D
❐ 6CF/3GJ Mounting Plate
E
❐ Battery Meter Mounting Box
Figure 1-1
1–2973-0032-01-01 Rev A
Sine Wave Plus Long DC Conduit Box
B
B
Front Cover
A
D
C
DCCB-L
DCCB-L-175 or DCCB-L-250 adds:
F
❐ One GJ175F or GJ250F Circuit Breaker
G
❐ DC Negative Bus Bar and Shunt
H
❐One Positive (+) Battery Cable
I
❐One Negative (–) Battery Cable
J
❐ One length green GROUND wire
E
H
I
F
J
G
DCCB-L-175 or
DCCB-L-250
Specifications
Specifications
The following table provides the operational and environmental specifications for
the Long DC Conduit Box (all models).
Table 1-1
Operational and Environmental Specifications for the Long DC Conduit Box
DCCB-L BasicDCCB-L-175DCCB-L-250
Dimensions33" (H) x 13 1/2" (W) x 8 7/8" (D)
(384 mm x 343 mm x 225 mm)
Weight22 lbs (10 kg)33 lbs (15 kg)33 lbs (15 kg)
Shipping
Weight
Factoryinstalled
hardware
Factoryinstalled
wiring
Rated
Temperature
Storage
Temperature
EnclosureIndoor rated, Galveneel, White,
25 lbs (11.5 kg)36 lbs (16.5 kg)36 lbs (16.5 kg)
• DC Ground Bar (with 12 holes,
accepts #2 - 14 AWG wires)
• 6CF/3GJ Mounting Plate
• Mounting box for BSM (w cover)
None• One - Ground Wire (#4 AWG, 18",
0 to 25 °C
(32 to 77 °F)
-55 to +100 °C
(-67 to 212 °F)
Powdercoat Finish
33" (H) x 13 1/2" (W) x 8 7/8" (D)
(384 mm x 343 mm x 225 mm)
• DC Ground Bar (with 12 holes,
accepts #2 - 14 AWG wires)
• 6CF/3GJ Mounting Plate
• Mounting box for BSM (w cover)
• DC Negative Bus Bar
• 500 A/50 mV Shunt
• GJ175F Circuit Breaker
rated to 105 °C, stranded copper) (
• One - Positive (+) Battery Cable
(#2/0 AWG, 16" Cable)
• One - Negative (–) Battery Cable
(#2/0 AWG, 30" Cable)
0 to 25 °C
(32 to 77 °F)
-55 to +100 °C
(-67 to 212 °F)
Indoor rated, Galveneel, White,
Powdercoat Finish
33" (H) x 13 1/2" (W) x 8 7/8" (D)
(384 mm x 343 mm x 225 mm)
• DC Ground Bar (with 12 holes,
accepts #2 - 14 AWG wires)
• 6CF/3GJ Mounting Plate
• Mounting box for BSM (w cover)
• DC Negative Bus Bar
• 500 A/50 mV Shunt
• GJ250F Circuit Breaker
• One - Ground Wire (#4 AWG, 18",
rated to 105 °C, stranded copper)
• One - Positive (+) Battery Cable
(#4/0 AWG, 16" Cable)
• One - Negative (–) Battery Cable
(#4/0 AWG, 30" Cable)
0 to 25 °C
(32 to 77 °F)
-55 to +100 °C
(-67 to 212 °F)
Indoor rated, Galveneel, White,
Powdercoat Finish
Ratings• 160 Vdc maximum (Open Circuit)
• 250 amps maximum each inverter
• 250 amps max. renewable energy
Charge
Controllers
RegulatoryCertified by CSA to UL 1741-2001
Accommodates: 2 Charge
Controllers, 60 amps max. each
(First Edition) and CSA C22.2
No. 107.1-01
• 160 Vdc maximum (Open Circuit)
• 250 amps maximum each inverter
• 250 amps max. renewable energy
Accommodates: 2 Charge
Controllers, 60 amps max. each
Certified by CSA to UL 1741-2001
(First Edition) and CSA C22.2
No. 107.1-01
• 160 Vdc maximum (Open Circuit)
• 250 amps maximum each inverter
• 250 amps max. renewable energy
Accommodates: 2 Charge
Controllers, 60 amps max. each
Certified by CSA to UL 1741-2001
(First Edition) and CSA C22.2
No. 107.1-01
973-0032-01-01 Rev A1–3
Introduction
Table 1-1
Optional
hardware
available at
Xantrex
Operational and Environmental Specifications for the Long DC Conduit Box
DCCB-L BasicDCCB-L-175DCCB-L-250
• Charge Controllers (60 A max ea.)
• Charge Controller Kit (CC PCK)
• Power Distribution Blocks
(PDB-6 or PDB-12)
• PVGFP-CF (-1, -2, -3, -4)
• GJ175F or GJ250F Circuit
Breakers
• GJ175F-PCK (includes wiring)
• GJ250F-PCK (includes wiring)
• Battery Status Meter (TM500A,
TM500A-NS, and TM48)
• CF60 Circuit Breakers
• CF Mounting Plate (CFMP)
• DC Negative Bus Bar with shunt
(DCBUSBAR)
• Battery Temperature Sensor (BTS)
• BC-L2-175 (#2/0 AWG cable)
• BC-L2-250 (#4/0 AWG cable)
Inverter Side
• Charge Controllers (60 A max ea.)
• Charge Controller Kit (CC PCK)
• Power Distribution Blocks
(PDB-6 or PDB-12)
• PVGFP-CF (-1, -2, -3, -4)
• GJ175F or GJ250F Circuit
Breakers
• GJ175F-PCK (includes wiring)
• GJ250F-PCK (includes wiring)
• Battery Status Meter (TM500A,
TM500A-NS, and TM48)
• CF60 Circuit Breakers
• CF Mounting Plate (CFMP)
• DC Negative Bus Bar with shunt
(DCBUSBAR)
• Battery Temperature Sensor (BTS)
• BC-L2-175 (#2/0 AWG cable)
• BC-L2-250 (#4/0 AWG cable)
DCCB-L Base
• Charge Controllers (60 A max ea.)
• Charge Controller Kit (CC PCK)
• Power Distribution Blocks
(PDB-6 or PDB-12)
• PVGFP-CF (-1, -2, -3, -4)
• GJ175F or GJ250F Circuit
Breakers
• GJ175F-PCK (includes wiring)
• GJ250F-PCK (includes wiring)
• Battery Status Meter (TM500A,
TM500A-NS, and TM48)
• CF60 Circuit Breakers
• CF Mounting Plate (CFMP)
• DC Negative Bus Bar with shunt
(DCBUSBAR)
• Battery Temperature Sensor (BTS)
• BC-L2-175 (#2/0 AWG cable)
• BC-L2-250 (#4/0 AWG cable)
Outside
Figure 1-2
0.265 x 1”
(Obround x4)
0.188”
(fits up to #8
screw x2)
Long DC Conduit Box Dimensions (Not To Scale)
1–4973-0032-01-01 Rev A
Blockoff Plates
Blockoff Plates
Upper and Lower Blockoff Plates are included to enclose the open portions of the
Long DC Conduit Box chassis. In the event that an inverter is removed, the
Blockoff Plates secure the enclosure to prevent accidental contact with any AC
power within the Long DC Conduit Box.
Remove the Blockoff Plate (upper or lower) from its position for the inverter used
in your installation. The Blockoff Plates will not be needed at all in a dual SW
Plus inverter installation.
See “Installing or Removing the Blockoff Plates” on page 2–6 for additional
information.
Important:
single-inverter systems to use the upper mounting location for the inverter. Mounting an
inverter in the lower mounting position for a single-inverter system will required sitefabricated cables.
The cable lengths provided in the DCCB-L-175/L-250 were designed for
WARNING: Shock Hazard
Be sure to disconnect all DC and AC power before removing the inverter and installing the
blockoff plate.
Upper Blockoff
Plate
Lower Blockoff
Plate
Knockout panel
(if needed)
Figure 1-3
973-0032-01-01 Rev A1–5
The Blockoff Plates
Introduction
Options/Accessories
The following CSA-approved accessories are available through Xantrex to
expand or monitor the DC side of the system.
•C-Series Multi-function DC Controllers (C35, C40, C60)
•GJ-F Series Flag Style Circuit Breakers 175A or 250A (without wiring)
(GJ175F, GJ250F)
•GJ Series Flag Style Breakers 175A or 250A (with battery cables to connect
second inverter) (GJ175F-PCK, and GJ250F-PCK)
•Dual-pole or Triple-pole GJ Flag Terminal Bus bars (GJ-FT2, GJ-FT3)
•CF Breaker Mounting Plate (CFMP)
•60 Amp CF Series Circuit Breakers for loads (CF60)
•Power Distribution Blocks 6:1 and 12:1 (PDB-6 or PDB-12)
•Battery Status Meter (TM500A-NS without shunt) or (TM500A with shunt)
•Battery Temperature Sensors (BTS)
•Battery Cables for adding a second inverter (BC-L2-175 or BC-L2-250).
These battery cables are the same as those included with the appropriate
breaker with the GJF175-PCK or GJF250-PCK.
•DC Negative Bus Bar (DCBUSBAR)
Important:
configuration. Other components may be used, but may not allow continuous operation of
the SW Plus Inverter and should be approved by the AHJ.
The components shown in this section are to be used in a DCCB-L-RE
Charge Controllers or Diversion Load Controllers
If charge control or diversion control is required, spaces are provided for
mounting up to two DC controllers on the top of the DCCB-L chassis. Xantrex
offers the C-Series Multi-function DC Controller to provide either charge control
or diversion control.
Charge controllers not purchased from Xantrex may be used also, but might not fit
the mounting holes on the top of DCCB-L. If this occurs, the non-Xantrex
supplied charge controllers will need to be mounted somewhere off the DCCB-L
chassis.
Any charge controllers used on this component (Xantrex and Non-Xantrex)
should not exceed 60 A each (120 A total).
If more charge controllers are required, then it may be desirable to have two
DCCB-Ls (any model combination) installed in a dual-configuration.