WB-BB-LP-750-*
* 1 = One Pump, 2 = Two Pumps, 3 = Three Pumps
LOW PROFILE 3/4 HP GLYCOL LINE CHILLER
REFRIGERATION: Air-Cooled: 3/4 HP, R134a Condensing Unit
air flow maintenance.
ELECTRICAL: One Pump: 208 Volt AC, 60 hZ, 1 phase, 12.0 Full Load Amps
Dedicated 20 Amp circuit is required
Maximum Fuse / HACR Breaker: 20 Amp
Includes six foot cord with NEMA 6-15P grounded plug.
Dedicated 25 Amp circuit is required
Maximum Fuse / HACR Breaker: 25 Amp
Includes six foot cord with NEMA 6-20P grounded plug.
Three Pumps: 208 Volt AC, 60 hZ, 1 phase, 16.6 Full Load Amps
Dedicated 25 Amp circuit is required
Maximum Fuse / HACR Breaker: 25 Amp
Includes six foot cord with NEMA L6-30P grounded plug.
RECIRCULATING PUMP: 100 GPH, Brass Recirculation Duty
RECIRCULATING MOTOR: 1/3 hp (2.3 Amp each)
DIMENSIONS: Height: 17-1/2"
Width: 38"
Depth: 27"
WEIGHT: Shipping: 320#
Operating: 350#
COOLANT CAPACITY: 10 U.S. Gallons **
(5 gallons glycol plus 5 gallons water)
MAXIMUM CONDUIT LENGTH: 350'
OPTIONS: 6" Adjustable Legs (up to 7")
Additional Recirculating Pump and Motor Kit
**Add one gallon of coolant mixture (50% glycol plus 50% water) per 100 feet of Conduit
NOTE: 12" clearance required on on sides for optimum
Two Pumps: 208 Volt AC, 60 hZ, 1 phase, 14.3 Full Load Amps
4700 BTU Output
JOB:____________________ ITEM:_________
WB-BB-LP-750-1
Includes:
Six-foot long
cord
with
NEMA 6-15P
grounded plug.
WB-BB-LP-750-2 WB-BB-LP-750-3
Six-foot long
cord
NEMA 6-20P
grounded plug.
Includes:
with
Includes:
Six-foot long
cord
with
NEMA L6-30P
grounded plug.
WB-BB-LP-750-1 and WB-BB-LP-750-2 WB-BB-LP-750-3
BB750 LP SPECS. pub
8
REV061108