Wolf KG 20, KG 15, KG 25F, KG 40F, KG 63 Installation And Maintenance Instructions Manual

...
Installation and Maintenance Instructions
KG / KGW Standard air-conditioning units
Wolf GmbH · 84048 Mainburg · Postfach 1380 · Telefon 08751/74-0 · Telefax 08751/741600
Art.-Nr. 30 40 530
10/00 TV GB
1
Contents ...................................................................................... Page
Warnings / Notes on safety.................................................................. 3
Standards ............................................................................................ 4
Delivery to site / Transportation ............................................................ 5
Notes on installation........................................................................ 6-12
Connection to electricity supply .................................................... 13-14
Initial operation.............................................................................. 15-17
Maintenance ................................................................................. 18-19
Protection against frost ...................................................................... 19
2
Warnings / Notes on safety
General
Warnings
Notes on safety
Caution
These Installation and Maintenance Instructions apply only to WOLF KG and KGW Standard air-conditioning units.
The persons charged with the installation, initial operation or maintenance of the equipment must read these instructions before commencing work. Compliance with these instructions is mandatory.
Non-compliance with the installation or maintenance instructions voids the WOLF guarantee.
The following symbols and warnings are used in these Installation and Mainte­nance Instructions:
Non-compliance with notes marked in this way can endanger persons. Non-compliance with notes marked in this way can result in damage to the air-
conditioning unit or its components. In addition to the warnings in these Installation and Maintenance Instructions,
adhesive warning labels are affixed to the air-conditioning unit. Compliance with these warnings, too, is mandatory.
- Installation, initial operation, maintenance and operation of the air-conditioning unit must be entrusted to adequately qualified and trained persons.
- All work on electrical systems must be performed by a trained and qualified electrician.
- Work on electrical systems is subject to VDE regulations and the regulations of the local power utility.
- Operate the air-conditioning unit only within the nominal range specified in the WOLF technical documentation.
- Use as designated by the manufacturer is use solely for the purposes of ventilation. Atmospheric air is the only permitted medium. This air must be free of noxious, flammable, explosive, aggressive, corrosion­promoting or otherwise hazardous constituents. (Air-conditioning units rated "Ex-Schutz" in compliance with VDMA Guideline 24169/1 (suitable for use in hazardous environments) can be used to handle air mixed with explosive gases, vapours or mists in accordance with the equipment ratings for hazardous-environment classes 1 and 2).
- Do not remove or bypass safety devices or monitoring devices, or render such devices ineffective in any other way.
- Do not operate the air-conditioning unit unless it is in perfect working order. Faults and damage detrimental to or potentially detrimental to safety must be repaired immediately by a specialist.
- Use only genuine WOLF components as replacements for damaged or defective parts and components.
3
Standards
Standards
The standards and regulations applicable to the KG 15-250 Standard series and the KG/KGW 630-1000 series air-conditioning units are as follows:
- EC Directive 89/392/EC with Addendum 93/44/EC (9th Ordinance, Equipment Safety Law)
- E Directive 89/336/EC with Addendum 92/31/EC (Law concerning Electromagnetic Compatibility of Devices)
- EC Directive 73/23/EC (Low Voltage Directive) (1st Ordinance, Equipment Safety Law)
- DIN 31001/1 Safety design of technical products
- DIN EN 292 Safety of machinery, basic concepts
- DIN EN 294 Safety of machinery, safety distances
- DIN EN 349 Safety of machinery, minimum gaps
- DIN ISO 1940/1 Mechanical vibration, balance quality requirements
- VDMA 24167 Fans; safety requirements
- VDE 0100 Erection of power installations with rated voltages below
1000V
- VDE 0105 Operation of power installations
- VDE 0700/Part 500 Safety of household and similar electrical appliances
- VDE 0701/Part 1 Repair, modification and inspection of electrical
appliances
- VBG 5 Powered equipment
- VBG 7w Fans
Plus the following, only for special air-conditioning units for use in hazardous environments:
- VDMA 24169/1 Guideline for fans for handling atmosphere containing
flammable gases, vapours or mist.
Plus the following, only for weatherproofed air-conditioning units:
- VDMA 24175 Roof-mounted air-handling units
4
Delivery to site / Transportation
Delivery to site
Transport
Caution
KG 15-250 and KG/KWG 630-1000 series air conditioners are delivered to site in transportable units. Check all incoming goods for signs of damage in transit. Make a note of all damage or suspected damage on the waybill and have this damage report countersigned by the delivering freight forwarder. Immediately report the situation to WOLF.
The equipment must always be transported right way up, in other words in the position corresponding to the as-installed position. Exception: KGXD 160/250 upright is transported on its side (turned through 90°).
Use straps of adequate load-bearing strength to carry the suspended load. If you use a fork-lift or rollers to move the equipment, always make sure that the
forks or rollers are beneath the frame sections, not beneath the floor panels. If you suspend the load by means of eyebolts (on request), make sure that the
length of each rope run is at least equal to the distance between the eyebolts L. Make sure all ropes are the same length.
The weatherproofed KGW 630 to 1000 air-conditioning units are fitted with lifting eyes as standard.
Always use cross-bars when lifting items of equipment fitted with more than four eyebolts.
Clearances
Clearance on the operating side should be at least equal to the width of the unit to permit access for installation, operation and maintenance (see list below).
Space required for installation, operation and maintenance:
Fan section 0.8 x width of unit Chiller, heater section, KVS 1 x width of unit + 250 mm Filter section up to KG 100 1 x width of unit
KG 160 and larger 0.5 x with of unit
In a side-by-side configuration, allow the clearances as stated above for installa­tion, operation and maintenance on each side.
Those units which require a siphon (washer, humidifier, chiller, KGX/KGXD, drip separator) must be installed in such a way as to ensure correct installation and operation of the siphon (do not forget to allow for height of foundation).
In Germany, special statutory conditions apply to extractor systems for en­closed parking lots. Comparable legislation may apply in other countries.
5
Notes on installation
Foundation Install the units and components on a surface which is smooth, level and of
Caution
adequate load-bearing strength.
KG 40-250:
The base frames must be horizontal and the foundations must be smooth-topped and horizontal. Make sure that the bottom of the frame is in full-face contact with the supporting surface: spot support is not permissible.
Insulating strips
(by others)
Permanently elastic inserts must be placed between supporting surface or foundation and air-conditioning unit or, more accurately, base frame, in order to prevent the operating noise of the air-conditioning unit carrying into the building as structure-borne sound. By prefence, these inserts should be in the form of insulating strips placed lengthways under the sectional frame members.
KG/KGW 630-1000:
Base frame, delivered
in advance
Base frame,
installed
KGW 630-1000:
min. 200
Strip foundation
X
Base frame
55
Insulation by others
Insulating strips, supplied by others
The units and components must be installed on a base frame or strip foundation.
Height to suit local snowfall, min. 200 mm. X = width or length of unit, as appropriate - 20 mm
The base frames must be horizontal and the foundations must be smooth-topped and horizontal. Make sure that the bottom of the frame is in full-face contact with the supporting surface: spot support is not permissible.
Permanently elastic inserts must be placed between supporting surface or foundation and air-conditioning unit or, more accurately, base frame, in order to prevent the operating noise of the air-conditioning unit carrying into the building as structure-borne sound. By prefence, these inserts should be in the form of insulating strips placed lengthways under the sectional frame members.
Do not set down the unit on a flat surface, as this would damage the drip nose (see drawing). Use wooden battens of adequate thickness as supports to avoid this difficulty.
Wooden batten
6