Wolf FunctionLine CHK, ComfortLine CHU, FunctionLine CHU, ComfortLine CHU-CB, FunctionLine CHU-CB Installation And Maintenance Instructions Manual

...
Installation and maintenance instructions
ComfortLine FunctionLine
Cast iron boilers up to 60 kW
GBPart.-No. 3060918_1203 Subject to modications
Wolf GmbH · Postfach 1380 · 84048 Mainburg · Tel. +49 8751/74-0 · Fax +49 8751/741600 · Internet: www.wolf-heiztechnik.de
2
3060918_1203
Index
Index .......................................................................................................Page
Safety instructions / Reference symbols ......................................................3
Standards / Regulations ............................................................................. 4-5
ComfortLine cast iron boilers ..........................................................................6
FunctionLine cast iron boilers .........................................................................7
Installation ................................................................................................. 8-9
Boiler installation on a plinth .........................................................................10
Boiler installation on a horizontal DHW cylinder ........................................... 11
Boiler assembly ...................................................................................... 12-15
ComfortLine decorative panel installation............................................... 16-17
FunctionLine decorative panel installation....................................................18
Flue pipe installation .....................................................................................19
Central heating to boiler connections ...........................................................20
DHW cylinder to boiler pipework ..................................................................21
Filling the heating system ....................................................................... 22-23
Draining the heating system .........................................................................24
Pressure jet oil burner installation / Electrical supply ...................................25
Initial start-up .......................................................................................... 26-27
Maintenance ........................................................................................... 28-29
Maintenance log ..................................................................................... 30-31
Specication ........................................................................................... 32-33
Dimensions ............................................................................................. 34-35
Troubleshooting ............................................................................................36
33060918_1203
Reference symbols / Safety instructions
The following symbols are used in conjunction with these important in­structions concerning personal safety and technical reliability.
“Safety instructions“ are
instructions with which you must comply exactly, to prevent injury and material losses.
Danger through “live“ elec-
trical components. Please note: Switch OFF the ON/OFF switch before remo­ving the casing.
Never touch electrical com-
ponents or contacts when the switch is in the ON position. This creates a risk of elec­trocution, which may cause injury or death.
The main supply terminals are
“live“ even when the ON/OFF switch is in the OFF position.
This indicates technical in-
structions which you must observe to prevent material losses and boiler malfunc­tions.
In addition to the installation instructions, operating instructions and adhesive labels
are included or tted to the boiler. These
must also be observed.
Note
General
Authorised personnel should read these instructions before any installation, com­missioning or maintenance work. Adhere to the instructions given in this document. Non-observance of these installation instructions voids any guarantee offered WOLF.
Safety instructions
• Only use qualied and trained personnel
for the installation, commissioning and maintenance of the boiler.
• In accordance with DIN EN 50110-1,
work on electrical components (e.g. control units) may only be carried out
by qualied electricians.
• The regulations of VDE/ÖVE and those
of your local electricity supplier as well as all other local regulations are appli­cable to electrical installation work.
• Only operate the boiler within its output range which is stated in the specication
supplied by WOLF.
• Appropriate use of the boiler refers to
the exclusive use for hot water heating systems in accordance with DIN 4751.
• Never remove, bypass or otherwise disable any safety or monitoring equip-
ment.
• The boiler may only be operated in per­fect technical condition. Any faults and damage which may impact on safety which might limit the safe use of the
equipment must be remedied immedi­ately by a qualied contractor.
• Only replace faulty components or equipment with original WOLF spare
parts.
4
3060918_1203
Standards / Regulations
Standards and regulations
Observe all current Building Regulati­ons and other local requirements.
Only recognised heating contractors may install WOLF boilers. This heating contrac­tor will also be responsible for the proper installation and the commissioning of the heating system.
The boilers described in these installation instructions are low temperature boilers
according to HeizAnlV and 92/42/EEC (Efciency of Hot Water Boilers).
Locate the enclosed operating instructions in a clearly visible position in the boiler room.
Boilers may only be installed and ope­rated in boiler rooms which are suitable
according to the Landes-FeuVo [or local
regulations].
The following regulations, rules and guide­lines must be observed during installation:
• Boiler room guidelines or Building Regu-
lations relating to the construction and installation of central boiler rooms and fuel storage facilities.
• Energy Savings Act (EnEG) and related
directives (Heating Systems Order).
Note: Please read these instructions
carefully before the installation and keep them in a secure place.
• DIN standards
DIN 1988 Technical rules for DHW
installations
DIN 4701 Rules for
calculating the heat demand of buildings
DIN 4751 Part 3 - Safety Equipment
for heating systems with ow
temperatures up to 95 °C.
DIN 18160 Domestic chimneys
• VDE requirements: VDE 0100 General information
regarding the installation of
HV systems with rated voltages up to 1000V.
VDE 0105 Operation of HV
systems, general considerations.
VDE 0722 Electrical equipment of
non-electrically heated heat generators.
VDE 0470/ Protection through
housings
EN 60529
EN 60335-1 Safety of electrical
equipment for domestic use and similar purposes.
53060918_1203
Standards / Regulations
Cast iron boilers
acc. to DIN EN 303 as well as in accordance with EC Directive 90/396/EEC (gas
consuming equipment), 73/23/EEC (Low Voltage Directive), 89/336/EEC (EMC Directive), 92/42/EEC (Ef­ciency of Hot Water Boilers) and 93/68/EEC (Identication Directive) for heating systems with heating circuit pumps and ow temperatures up to 110 °C and 3 bar
permissible operating pressure in accordance with DIN 4751 and DHW cylinder pres­sure (max. 10 bar) in accordance with DIN 4753.
For the operation with pressure jet gas burners, the following gas device categories apply:
The NO
x
limits required by the 1st BImSchV para. 7(2) are maintained.
Country abbreviation Country Gas device category
DE Germany II
2ELL3B/P
AT Austria II
2H3B/P
LU Luxembourg I2E or I
3+
6
3060918_1203
ComfortLine cast iron boilers
Oil and gas-red cast iron boilers, type
CHK
(boiler plinth, accessory)
Oil and gas-red cast iron boilers, type
CHK-CB
incl. DHW cylinder
Oil-red cast iron Unit boiler, type CHU
incl. pressure jet oil burner
(boiler plinth, accessory)
Oil-red cast iron Unit boiler, type CHU-CB
incl. DHW cylinder
and pressure jet oil burner
73060918_1203
FunctionLine cast iron boilers
Oil and gas-red cast iron boilers, type FHK
(boiler plinth, accessory)
Oil and gas-red cast iron boilers, type
FNK-FB/FE incl. DHW cylinder
Oil-red cast iron Unit boiler, type FHU
incl. pressure jet oil burner
(boiler plinth, accessory)
Oil-red cast iron Unit boiler, type FHU-FB/FE
incl. DHW cylinder
and pressure jet oil burner
8
3060918_1203
Installation
The ventilation air supply must be ensured and comply with local regulations or those re­lating to gas installations. We recommend that you supply the boiler with fresh air directly from
the outside. An insufcient fresh
air supply can lead to fuel gas escaping, which represents a risk to life (poisoning/suf­focation).
Clearances towards walls and combustible materials must comply with local re regula­tions, and should be at least 200mm, otherwise there is a high risk of re.
General tips regarding location
• Install the boiler with or without the
DHW cylinder on a level surface which is substantial enough to carry its weight.
• Position the boiler and DHW cylinder (if
installed) horizontally or slightly rising
towards the back to ensure adequate
venting of any trapped air (level with adjustable feet).
Only install the boiler and DHW cylinder (if installed) in a room safe from the risk of frost. Drain the boiler, the DHW cylinder and the entire heating system if there is a risk of frost, when the system has been shutdown, to prevent pipes from bursting.
Boilers should not be installed in areas subject to aggressive vapours, very dusty or highly humid conditions (workshops, washrooms, hobby rooms etc.). This prevents the optimum burner function from being achieved.
The combustion air supplied to the pressure jet oil burner must be free from halogenated hy­drocarbons (e.g. as contained in sprays, solvents, cleaning
uids, paints and adhesives).
Under the most unfavourable conditions, these may lead to pitting of the boiler and even
the ue gas system.
Never store or use combustible
material or liquids near the
boiler.
Note
Note
93060918_1203
Installation
Recommended minimum wall clearance
Maintain a minimum clearance between the boiler sides and walls of 400 mm to
enable the boiler door with tted burner
to be opened.
Ensure that sufcient space is available
for cleaning and maintenance.
1000
900
400
Recommended minimum wall clearance
Transportation into the boiler room
To ease the transportation into the boiler room, lifting slings with lifting hooks are offered as accessories.
Only lift the boiler using all four lifting slings.
Note
Lifting eyes for lifting slings
Boiler installation on adjustable feet
At the factory the boiler is equipped with
four adjustable bolts
• Level the boiler with adjustable feet
(accessory) horizontally or with a slight incline to the rear.
Feet
(accessory)
Adjustable
bolt
Adjustable bolt/ feet
10
3060918_1203
15
11 11
4
8
10
6 6
3
5
7
2
1
13
13
14
12
9
Boiler installation on a plinth
Boiler
Boiler door
Thermal insulation, boiler
Thermal insulation, boiler back
Thermal insulation, boiler front
Side casing
Control unit bracket
Back wall casing
Control unit housing
Casing cover
Spring shackles
Front casing
Type plate
Wolf logo
Plinth (accessory)
113060918_1203
15
11 11
4
8
10
6 6
3
5
7
2
1
13
13
14
12
9
Boiler installation on a horizontal DHW cylinder
Boiler
Boiler door
Thermal insulation, boiler
Thermal insulation, boiler back
Thermal insulation, boiler front
Side casing
Control unit bracket
Back wall casing
Control unit housing
Casing cover
Spring shackles
Front casing
Type plate
Wolf logo
Horizontal DHW cylinder
12
3060918_1203
Boiler assembly
Boiler
• Install the plinth or the DHW
cylinder in accordance with the enclosed installation instructions.
• Position the boiler with adjustab-
le bolts fully inserted using the lifting slings on the fully assembled plinth or DHW cylinder.
• To secure the boiler to the plinth
or DHW cylinder, tapped holes are provided at the front sides of the
boiler. Additional xings are not required.
• Check the horizontal level of the
boiler together with the plinth and DHW cylinder and adjust, with a slight incline to the rear, if necessary.
Screws for securing the boiler
Screws for securing the boiler to the plinth
Screws for securing the boiler
Fixing screws on the DHW cylinder
Position the thermal boiler insulation
around the boiler (overlapping) and secure with spring clips.
Position the thermal boiler insula­tion for the boiler back over the rear
connections and on the back wall of the boiler.
Secure the boiler door
with the four M10x45 screws and washers supplied. Insert the door hinge pins into the door bracket on the l.h. or r.h. side, subject to door opening.
Boiler door installation
M10x45 screws
133060918_1203
Boiler assembly
Fixing plugs
Thermal insulation, boiler front
Thermal insulation, boiler front
Position the thermal insulation loosely at the boiler front
and secure with xing plugs (4 no.).
Control unit bracket
Side casing
Hooks
Control unit bracket installation
Locate the control unit bracket
centrally and push parallel forward, until both recesses in the side casing click into the control unit bracket tabs.
and t the lower folded edge into
both notches of the boiler (view X).
Boiler notch
Lower folded edge of the side casing
View X
Side casing installation
Side casing
into the boiler front pushing the spring
clip
behind the boiler bracket
Side casing installation
Spring shackle
Bracket
14
3060918_1203
Boiler assembly
Locking tabs
Control unit bracket
Secure tightly
Control unit housing installation
Push the control unit housing
with locking tabs into the apertures on the control unit bracket and pull forward to its end stop. Secure the control unit housing with the two self-tapping screws supplied to the control unit at the l.h. and r.h. rear, working from top to bottom.
Route the boiler sensor to the front and push into the sensor well in any arrangement, then secure with the circlip.
Rear wall installation
Back wall notches
Self-tapping screws
Locate the back wall casing
with tabs into the notches in the side casing, and secure with the self-tapping screws (4 no.) supplied.
Side casing xing screws
Self-tapping screws
Secure the control unit bracket and side casing with the self-tapping screws supplied (6 no.).
153060918_1203
Boiler assembly
Afx the type plate
in a clearly visible position.
Clip the Wolf logo
into the front casing (only for FunctionLine).
Type plate / Wolf logo
Type plate
Wolf logo
Push the front casing
with open control unit lid with the
prole screws against the spring shackles
, until they click into
place.
Front casing installation
Position the casing cover
onto both side casings and push towards the control unit bracket.
Cable clip
Cover cap
Burner cable holder
Guide the burner cable through the
aperture in the control unit bracket (l.h. or r.h. subject to boiler door opening).
Clip a cover cap into the control unit bracket to protect the burner cable.
Secure the cable clip with the burner cable at the l.h. or r.h. side (bottom) of the boiler.
16
3060918_1203
In addition, all ComfortLine boilers require
the following work to be undertaken.
ComfortLine decorative panel installation
Decorative panel
Position the decorative panel with the document wallet on the holes and push against the front casing, until the clips click into place.
Decorative panel installation
Decorative panel installation, single boiler
Decorative frame
(CHK 22-60 single boiler)
Click the plastic clips
(4 no., black) into the front casing. Position the decorative frame onto the clips and push down to their end stop.
173060918_1203
ComfortLine decorative panel installation
Decorative frame
(CHU 22-29 Unit boiler)
With the dome at the top, push the silencer hood into the decorative frame, then secure the silencer hood with four self-tapping screws from the inside to the decorative frame.
Self-tapping screws
Silencer hood
Decorative frame
Joining the decorative frame and the silencer hood
Large silencer hood installation
Large silencer hood
(CNU 37-60 Unit boiler)
Click the plastic clips (4 no., orange) into the front casing. Position the large silencer hood onto the clips and push down to their end stop.
Click both top plastic clips (black) from the outside into the front casing. Click both lower plastic clips (black) from the inside into the front casing. Hook the decorative frame with the silencer hood into the top clips and secure in the lower plastic clips.
Decorative panel installation, Unit boiler
18
3060918_1203
FunctionLine decorative panel installation
For models FHU-TH/22/29, the following additional work should be undertaken.
Decorative panel
Click the plastic clips
(4 no., grey) into
the front casing.
Decorative panel installation
Decorative panel
193060918_1203
Flue pipe installation
Flue pipe silencer (accessory)
Install the ue pipe silencer with ue pipe extension in accordance with the gure
shown.
Flue pipe extension
Flue pipe silencer
Flue pipe extension/silencer
Flue pipe outlet
Clean-out covers
Clean-out covers
in ue pipe elbows
The ue pipe cross-section must match that of the boiler ue outlet.
Reducing the ue pipe size is only
permitted, if the satisfactory function
has been veried (by calculation) in
accordance with DIN 4705.
Keep the ue pipe as short as
possible and inclined towards the chimney stack.
• Thoroughly seal in the ue pipe.
• Use ue pipe elbows with clean-out
covers to facilitate the cleaning of the
ue pipe.
20
3060918_1203
Central heating boiler connections
Central heating boiler connections
Boiler return
Connection for venting
and safety ow
Filling / Draining
Boiler return
Connect the heating ow and return to the respective boiler ttings. For connections,
see below. Install a check valve downstream of the boiler circuit pump(s) to prevent incorrect circulation.
Install a safety assembly com­prising a safety valve with a response pressure of 3 bar and an automatic air-vent valve.The pipework between the boiler and the safety valve must not be able to be shut off. Severely excessive boiler pressure due to excessive boiler temperatures, can burst the boiler body or the boiler pipework, which would lead to a sudden excape of hot water (risk of scalding).
Connect any underoor heating
system via a three or four-way mixer.
Return temperature raising facility
Heating systems with large water volume (above 20 litres per kW output) require a re­turn temperature of 30 °C, as otherwise the longer heat-up time of such systems would create condensate and run an increased risk of boiler body corrosion.
Note
Provide system separation by means of a heat exchanger, when using pipes which are not impermeable to oxygen.
This boiler is only suitable for heating systems with pumped heating circuits. If no heating circuit pump has been installed,
sufcient circulation through the
radiators cannot be ensured, putting the room heating in
question.
Recommendation: Convert open systems into sealed systems.
Note
213060918_1203
DHW cylinder to boiler pipework
Install the pipework between the boiler and the DHW cylinder in accordance with the illustration below.
The DHW cylinder loading pump must supply from the top to bottom.
Note
Boiler return
Boiler ow
Hoses with gaskets
Sensor well for DHW
cylinder sensor
Cold water inlet
DHW circulation
DHW outlet
Filling / Draining
Cylinder loading pump incl. gaskets
Ferrule with union nut
Gravity brake
Elbows
DHW cylinder to boiler pipework
22
3060918_1203
Filling the heating system
Fill the system and vent it properly to safe­guard the perfect boiler function.
Before connecting the boiler
to the heating system, ush
the entire system to remove residues such as welding pearls, hemp, putty, etc. from the pipework.
The boiler and central heating
system may only be lled, if a
type-tested safety valve (ope­ning pressure maximum 3 bar) has been installed.
Note
Note
Filling the heating system
Connection for venting
and safety ow
Filling
• With the boiler in a cold condition, ll the heating system slowly via the ll
and drain valve, until 1 bar pressure is indicated. Inhibitors are not permissible.
Automatic air-vent valve
Locking cap
Automatic air-vent valve
• Open the cap of the quick-action air-vent
valve of the safety assembly (accessory) by one revolution, but do not remove the cap.
Boiler ll and drain valve
Hose connection
• Connect a water hose to the lling/drain
valve (on-site).
233060918_1203
Filling the heating system
• Observe the pressure gauge of the
safety equipment assembly when lling
the system with water.
Safety assembly pressure gauge
Pressure gauge
• For boilers with DHW cylinder, vent
the heating coil at a system pressure of approximately 0.50 bar or less by starting the DHW cylinder loading pump (operating time approximately 2 minutes).
• Check the entire system for water leaks.
• Check the safety valve function.
• Ventilate the boiler (e.g. via an automatic
air-vent valve).
• Fill the system to 1 bar pressure.
In operation, the pressure gauge must indicate between 1 and 2.5 bar.
• Top up with water when the system
pressure falls severely.
In constant mode, the boiler automati-
cally vents via the air-vent valve.
24
3060918_1203
Draining the heating system
Boiler ll and drain valve
Hose connection
Draining the heating system
Connection for venting
and safety ow
Drain
• Switch OFF the heating system (see
operating instructions) and let it cool down to a maximum of 40 °C, to prevent
the risk of scalding.
• Open the drain tap on the boiler.
• Open the radiator bleed valves.
• Drain the heating water off.
253060918_1203
Pressure jet oil burner installation / Electrical supply
Electrical supply
Do not route sensor leads with
230 V mains cables.
Connect the heating circuit pump(s) and the DHW cylinder loading pump(s) on-site via contactor, if:
• The burner and pump draw more than
2 A each.
• The total control unit power consumption
is exceeded.
Observe the control unit installation and operating instructions.
Note
Electrical supply
Cable grommets
Pressure jet oil burner installation
The Unit pressure jet oil burner installation instructions are included in the burner packaging.
Only use bolts when securing
the burner to the boiler ange,
whose thread penetrates the
boiler ange by a maximum of
15 mm. Only use pressure jet gas burners compliant with EC Directive 90/396/EEC.
Boiler ange
Burner ange holes
1NT1 T2 S3 B4
BS MV
Burner plug wiring diagram
26
3060918_1203
Initial start-up
Only qualied personnel may
carry out the commissioning and operation of the boiler and the instruction of the user.
• Check the boiler and system for leaks.
Close the water outlet - danger of overheating and scalding.
• Check that all ue gas accessories have
been correctly installed.
• Open the shut-off valves on ow and
return.
• Switch ON the system ON/OFF switch
on the control unit.
Note:
When the heating system is started, the display of the weather-compensated
control unit indicates all superuous (not
connected) sensors as fault messages. For removing these fault messages see the control unit operating instructions.
• If the system water pressure falls below
1.0 bar, top up with water until a pressure of 1.0 to max. 2.5 bar has been achieved.
• An error code will ash in the display, if
the boiler/burner fails to start properly. For details about error codes see the
quick-start operating instructions.
• Instruct the customer in the operation of
the boiler. Complete the commissioning log and hand over the instructions.
• Position the operating instructions in
the boiler room where they are clearly visible.
Saving energy
• Instruct the customer about energy-
savings options.
• Use this opportunity for reducing the
heating temperature night operation using control accessories.
• Adjust the temperature so you are
comfortable; every degree of room tem­perature reduction will achieve energy savings of up to 5%.
• Reduce the room temperature in unoc-
cupied rooms as far as possible; please observe frost protection.
• Ensure that all thermostatic radiator
valves are fully opened in rooms where room thermostats are installed.
The room thermostat must not be ob-
structed by furniture or curtains.
Function checks
• During commissioning, check all control, regulating and safety equipment for their
correct function and settings.
273060918_1203
Commissioning report
Commissioning steps
Test values and
conrmation
1.) Water connections checked for leaks?
2.) Vented boiler and system?
3.) System pressure 1 - 2.5 bar?
4.) Function test carried out?
5.) Flue gas test:
Gross ue gas temperature
___________
tA [°C]
Ventilation air temperature
___________
tL [°C]
Net ue gas temperature
_______
(tA - tL ) [°C]
Carbon dioxide content (CO2) or oxygen content (O2)
______________
%
Carbon monoxide content (CO), free of air
____________
ppm
6.) Casing tted?
7.) System user trained, technical documents handed over?
8.) Conrm commissioning
28
3060918_1203
Maintenance
Note:
To ensure the reliable and safe function
of a heating system, users are required to
have it checked and cleaned on an annual basis by an approved heating contractor (check local regulations). Switch OFF the boiler when cleaning the boiler room.
We would recommend a maintenance contract.
Front casing
Front casing removal
• Switch OFF the heating system (see
operating instructions) and let it cool down.
• Remove the front casing from the boiler.
• Pull the burner plug.
• Release the boiler door screws.
Boiler door screws
Boiler door removal
293060918_1203
Maintenance
Turbulators
Pulling out the turbulators
• Open the boiler door.
• Pull out the turbulators.
Cleaning using the cleaning brush
• Remove soot/sulphur deposits with the
cleaning brush supplied.
• Assemble in reverse order.
30
3060918_1203
Maintenance log
• Please tick the maintenance steps carried out and enter the test values into this log.
Maintenance steps Date Date
1. Cleaned the boiler?
2. Leak test carried out during operation?
3. Function test carried out?
4. Flue gas test:
Gross ue gas temperature tA [°C] ________ tA [°C] ________
Ventilation air temperature t
L
[°C] ________ tL [°C] ________
Net ue gas temperature (t
A
- tL ) [°C] ____ (tA - tL ) [°C] ____
Carbon dioxide content (CO
2
) or % ___________ % ___________
Oxygen content (O
2
) % ___________ % ___________
Carbon monoxide content (CO), free of air ppm _________ ppm _________
5. Conrm maintenance
(company stamp, signature)
313060918_1203
Maintenance log
Date Date Date Date
tA [°C] ________ tA [°C] ________ tA [°C] ________ tA [°C] ________
t
L
[°C] ________ tL [°C] ________ tL [°C] ________ tL [°C] ________
(t
A
- tL ) [°C] ____ (tA - tL ) [°C] ____ (tA - tL ) [°C] ____ (tA - tL ) [°C] ____
% ___________ % ___________ % ___________ % ___________
% ___________ % ___________ % ___________ % ___________
ppm _________ ppm _________ ppm _________ ppm _________
32
3060918_1203
Specication
* Values for upper/lower boiler output, relative to a CO2 content of 13 % (fuel oil EL) and
an average boiler water temperature of 60 °C. The chimney stack dimensions must
be calculated in accordance with DIN 4705. For ue gas temperatures below 160 °C,
connect the boiler to highly insulated chimney stacks (heat conductivity resistance
class I acc. to DIN 18160 T1) or suitable, moisture-resistant ue gas systems, which
have been type-approved.
CHK / FHK / CNU-Premio / CHU-TH / FHU-TH 22 22 CHK-CB / FHK-FB / FHK-FE / CHU-Premio-CB
CHU-TH-CB / FHU-TH-FB / FHU-TH-FE
22/155 22/200
Output rangeexcl. burner, incl. TH burner kW 15-221 5-22 incl. Premio burner kW 19-22 19-22 Set-up burner output kW 21 21 DHW cylinder capacity CB & FB / FE litres 155/150 200 Constant DHW cylinder output CB & FB litres/h 540 540 FE litres/h 540 540 Performance factorCB & FB NL60 2.8 4.4 FE NL60 2.8 4.1 Number of boiler sections 3 3 Water content litres 29 29 Boiler gas content litres 33 33 Heating water pressure drop (at ∆T=20K) mbar 2 2 Maximum permissible boiler pressure bar 4 4 Maximum permissible DHW cylinder pressure bar 10 10 Rel. standby losses Boiler % 1.15 1.15 Boiler+DHW cylinder % 1.7 1.9 Required boiler draught Pa 10 10 Flue gas temperature* ° C 130/170 130/170
Flue gas mass ow rate* kg/h 25/37 25/37 Boiler, safety ow (female thread) Rp 1¼“ 1¼“
Boiler return (female thread) Rp 1¼“ 1¼“ Filling, draining, safety return (female thread) Rp ½“ ½“ Flue pipe diameter mm 129 129 Combustion chamber depth mm 350 350 Combustion chamber diameter mm 290 290 Weight Boiler kg 167 167 Burner kg 10 10 CHW cylinder CB and FB kg 66 83 DHW cylinder FE kg 98 121 Electrical supply Maximum current (control unit and accessories) Maximum current (in total, excluding pumps) Switching capacity pumps, mixer, burner Control unit fuse (maximum current) Optional connection for mixer motors
333060918_1203
Specication
29 29 37 45 60
29/155 29/200 37/200 45/200 60/200
22-29 22-29 29-37 37-45 48-60 25-29 25-29 29-37 37-45 48-59
27 27 34 41 55
155/150 200 200 200 200
710 710 910 1100 1225 710 710 910 940 940
3.1 4.6 4.8 4.9 5.0
3.1 4.3 4.5 4.5 4.5 4 4 5 6 8
35 35 41 47 59 43 43 53 63 83
4 4 6 8 14 4 4 4 4 4
10 10 10 10 10
1.05 1.05 0.95 0.85 0.7
1.6 1.8 1.6 1.4 1.2
13 13 16 19 0
140/170 140/170 150/170 150/170 155/175
37/49 37/49 49/62 62/75 80/100
1¼“ 1¼“ 1¼“ 1¼“ 1¼“ 1¼“ 1¼“ 1¼“ 1¼“ 1¼“
½“ ½“ ½“ ½“ ½“ 129 129 149 149 149 450 450 550 650 850 290 290 290 290 290 198 198 229 260 322
10 10 15.5 15.5 15.5
66 83 83 83 83
98 121 121 121 121
230 V / 50 Hz / 10A
5 VA
15 VA
230 V, 4(2) A each
M 6.3 A
230V, 50Hz, optimum time 4 - 7 minutes
34
3060918_1203
C
B
D
A
E
F
2
G
H
J
F
1
C
B
D
A
E
G
H
J
Dimensions
Observe the height of adjustable feet/bolts 20 mm ±10mm.
CHK / FHK / CHU-Premio CHU-TH / FHU-TH
22 29 37 45 60
Boiler height A mm 835 835 835 835 835 Width B mm 660 660 660 660 660 Length C mm 640 740 840 940 1040 Plinth height D mm 280 280 280 280 280 Overall height incl. control unit E mm 1280 1280 1280 1280 1280 Silencer hood depth F
1
mm 336 336 345 345 345
Burner hood depth F
2
mm 235 235 235 260 275
Central heating return G mm 397 397 397 397 397 Smoke tube connector H mm 859 859 859 859 859 Central heating ow J mm 997 997 997 997 997
353060918_1203
C
B
D
A
E
F
2
H
K
J
L
M
G
F
1
C
B
D
A
E
H
K
J
L
M
G
Dimensions
Observe the height of adjustable feet/bolts 20 mm ±10mm.
CHK-CB / FHK-FB / FHK-FE / CHU-Premio-CB CHU-TH-CB / FHU-FB / FHU-FE
37 45 60 45 60
Boiler height A mm 835 835 835 835 835 Width B mm 660 660 660 660 660 Length of 155 l DHW cylinder C mm 987 987 - - ­Length of 200 l DHW cylinder C mm 1262 1262 1262 1262 1262 DHW cylinder height D mm 625 625 625 625 625 Overall height incl. control unit E mm 1625 1625 1625 1625 1625 Silencer hood depth F1 mm 336 336 345 345 345 Burner hood depth F2 mm 235 235 235 260 275 Central heating return G mm 742 742 742 742 742 Smoke tube connector H mm 1204 1204 1204 1204 1204 Central heating ow J mm 1342 1342 1342 1342 1342 Cold water inlet K mm 90 90 90 90 90 CB/FB DHW circulation L mm 412 412 412 412 412 FE DHW circulation L mm 312 312 312 312 312 DHW connection M mm 534 534 534 534 534
36
3060918_1203
Troubleshooting
Fault Cause Remedy Burner does not start or
enters a fault state
No voltage present at the control unit
Fuse, electrical connections, Check the position of the ON/ OFF switch and heating sys. emergency stop switch.
Oil tank empty / Gas supply
line shut off
Fill oil tank / Open gas supply line.
Burner fault Press the reset button at
burner control unit (see burner installation instructions)
Safety temperature Press the reset button at the
control cut-out activated unit.
Oil lter clogged Replace oil lter.
Heating circuit pump does not start
System in summer mode Check summer/winter switch
position.
Heating circuit pump locked upTurn the pump shaft with a
screwdriver.
Heating circuit pump faulty Replace the heating circuit
pump.
Cylinder loading pump does not run
DHW cylinder thermostat faulty
Check DHW cylinder thermo­stat and replace, if necessary.
Cylinder loading pump seized upTurn the pump shaft with a
screwdriver.
Cylinder loading pump faulty Replace the DHW loading
pump.
Heating system operational, but room temperature too low
Adjust maximum boiler tem­perature set too low.
Raise maximum boiler tem­perature.
Heat-up takes too long Heating water temperature
too low
(check at DHW cylinder ow,
not at the boiler)
Raise the temperature (adjust thermostat)
Too little heating water (creates wider spread, i.e. return temperature too low)
Install larger DHW cylinder loading pump
Indirect coil not vented Vent indirect coil with loading
pump OFF
Indirect coil scaled up Descale indirect coil
DHW temperature too low Thermostat switches OFF too
soon
Adjust thermostat
Return temperature too low (e.g. spread too wide)
Return temperature too low (e.g. spread too wide)
Loading...