Wolf CRL evo max Series, CRL-iD-9000, CRL-iD-4800, CRL-iD-6200, CRL-iH-1300 Installation And Maintenance Instructions Manual

...
GB
Installation and maintenance instructions
COMFORT VENTILATION UNIT WITH THERMAL WHEEL HEAT EXCHANGER
CRL / CRL evo max (Translation of the original)
English | subject to modications!
3064361_201811
Table of contents
Table of contents
1 General / Safety information ................................................................... 3
2 Standards, regulations / disposal ........................................................... 5
3 CRL-iD unit layout .................................................................................. 6
4 CRL-iD appliance versions ..................................................................... 8
5 CRL-iH unit layout .................................................................................. 9
5.1 CRL-iH evo max unit layout ...................................................................11
6 CRL-iH appliance versions ................................................................... 13
7 CRL-iDH unit layout .............................................................................. 14
8 CRL-iDH appliance versions ........................................................................16
9 CRL-A unit layout ................................................................................. 17
9.1 CRL-A evo max unit layout ................................................................... 19
10 CRL-A appliance versions .................................................................... 21
11 Delivery / Handling ............................................................................... 22
12 Unit splitting for handling purposes - CRL ............................................ 24
13 Assembly - CRL evo max ..................................................................... 29
14 Installation information for external units .............................................. 32
15 Siting .................................................................................................... 33
16 Electrical connection ............................................................................ 35
17 Commissioning .................................................................................... 37
18 Maintenance shutdown ........................................................................ 46
19 Hygiene checklist ................................................................................. 47
20 Maintenance ......................................................................................... 48
21 Notes .................................................................................................... 51
1 General / Safety information
General information These installation and maintenance instructions only apply to WOLF CRL / CRL
evo max ventilation units. Authorised personnel should read these instructions
before any commissioning or maintenance work. Comply with the specications
in this document. Installation, commissioning and maintenance work must only be carried out by trained personnel.
These instructions should be considered an integral part of the unit supplied, and should always be easily accessible.
Failure to observe these installation and maintenance instructions voids any WOLF GmbH warranty.
Reference symbols The following reference symbols are used in these instructions. This
important information concerns personal and operational safety as well as operational reliability.
“Safety information" identies instructions that must be observed to the letter, to prevent risks and injuries to individuals and damage to the
appliance.
Danger through 'live' electrical components. Please note: Turn off the ON/OFF switch before removing the casing.
Never touch electrical components or contacts when the ON/OFF switch
is in the ON position. There is a danger of electrocution, resulting in a
risk to health or death.
The main terminals are 'live', even when the ON/OFF switch is in the OFF
position.
Note
Safety information In addition to installation and maintenance instructions, there are notes attached
"Please note" designates technical instructions which you must observe to prevent the unit malfunctioning or being damaged.
to the unit in the form of labels. These must also be observed.
Only qualied and trained personnel may be appointed for the installation,
commissioning, maintenance and operation of the unit.
Only qualied electricians are permitted to work on the electrical system.
VDE regulations [or local regulations] and those of your local power supply utility are applicable to electrical installation work. Only operate the unit within its output range, which is stated in the technical documentation supplied by WOLF. Only operate the appliance if it is in perfect technical condition. Any faults or damage that impact or might impact upon the safety or correct function of the
unit must be remedied immediately by qualied personnel.
Only replace faulty components and equipment with original WOLF spare parts.
Note
It may only be used for handling air. This air must not contain any harmful,
combustible, explosive, aggressive, corrosive or otherwise dangerous
substances, as these would be distributed throughout the duct system
or building, where they could cause a risk to the health of, or even kill the occupants, animals or plants living there.
33064361_201811
1 General / safety information
In accordance with DIN 1886, tools are required to open the unit. Wait for the fan to reach standstill (2 minutes wait). When the doors are opened, negative pressure may draw in loose objects, which could destroy the fan or even cause a risk to life if items of clothing are drawn in.
Electrical connection Make the electrical connection in accordance with local regulations.
Once electrical connection work is complete, the installation must be subjected to a safety test in accordance with VDE 0701-0702 and VDE 0700 part 500, as otherwise there would be a risk of electric shock that could result in injury or death.
Before working on the unit, shut it down via the isolator.
Even when the unit has been shut down, voltage will still be present at terminals and connections of the EC fans. This means there is a risk of electric shock that could result in injury or death.
Do not touch the EC fans for ve minutes after disconnecting the power across
all poles.
Intended use Wolf CRL / CRL evo max ventilation units are designed to heat and lter normal
air. Max. Max. air intake temperature: +40 °C. The use of these units in wet rooms or rooms with explosive atmospheres is not permissible. Handling very dusty or aggressive media is not permissible.
Any onsite modication or improper use of the unit is not permissible and WOLF
GmbH accepts no liability for any damage caused as a result. Ventilation units intended for internal installation must be placed in rooms that meet the requirements of VDI 2050 (VDI 2050, Requirements for technical equipment rooms - Planning and execution).
Fire The unit does not present a direct risk of re.
The small numbers of seals tted inside the unit can burn away if subjected to external inuences. Wear respiratory equipment if you ght a re. The usual
extinguishing agents such as water, extinguishing foam or extinguishing powder
can be used to extinguish res. As there are only a small number of ammable seals, the level of pollutants that could be released in a re is minimal.
Warnings
Recommended temperatures The ventilation unit is designed for air intake temperatures between -20 °C
Other technical documents - Operating instructions WRS-K
Removal and disabling of safety and monitoring equipment is prohibited. The system must only be operated if it is in perfect technical condition. Ensure
that any faults or damage that may impact on safety are rectied immediately.
and +40 °C. For safety reasons, the room temperature in technical equipment rooms must not fall below 5 °C (risk of frost) or exceed 40 °C. The unit should be operated in room conditions of between 22 °C and 28 °C at approx. 55 % relative humidity.
- MicroMax 370W TWHE control unit operating instructions
- Wiring diagram
- Conguration assistant WRS-K
- Commissioning report / parameter list
2 Standards, regulations / disposal
Standards and regulations - Machinery Directive 2006/42/EC
- Low Voltage Directive 2014/35/EU
- EMC Directive 2014/30/EU
- ErP Directive 2009/125/EC
- EN ISO 12100 Safety of machinery; general principles
- DIN EN ISO 13857: Safety of machinery; safety distances
- DIN EN 349 Safety of machinery; minimum
- DIN EN 953 Safety of machinery; Guards
- DIN EN 1886 Ventilation for buildings; central air-
- DIN ISO 1940-1 Mechanical vibration; balance quality
- VDMA 24167 Fans; safety requirements
- DIN EN 60204-1 Safety of machinery - Electrical
for design
clearances
handling units
requirements
equipment of machines
- DIN EN 60730 Automatic electrical controls
- DIN EN 61000 -6-2+3 Electromagnetic Compatibility
In addition, ÖVE regulations and the local building code apply to Austria.
The following standards and regulations apply to installation and operation:
- DIN EN 50106 (VDE 0700-500) Safety of electrical appliances; tests
- DIN VDE 0100 Regulations regarding the installation of high voltage systems up to 1000 V
- DIN EN 50110-1 (VDE 0105-1) Operation of electrical installations
- DIN VDE 0105-100 Operation of electrical systems; general stipulations
Disposal and recycling When the unit reaches the end of its service life, it must only be dismantled by
qualied personnel. Before starting to dismantle the unit, disconnect the power supply. Power cables must be removed by qualied electricians. Sort and dispose
of metal and plastic parts according to material types and in compliance with local regulations. Dispose of electrical and electronic components as electrical waste.
53064361_201811
3 CRL-iD unit layout
CRL-iD Comfort thermal wheel heat exchanger ventilation unit for internal installation with vertical/
horizontal duct connection (example provided is CRL-iD-3500 with boost damper)
1 Outdoor air damper with servomotor 2 Filter pre-dryer (accessory) 3 Differential pressure switch for lter monitoring 4 EC fan, extract air 5 Ventilation air damper with servomotor 6 Repair switch 7 BMK programming unit 8 control panel 9 TWHE control unit
10 Compact lter, extract air
11 Differential pressure switch for lter monitoring 12 Electric reheating coil available for
CRL-1300/-2500/-3500 (accessory) 13 EC fan, supply air 14 Adjustable feet 15 Boost damper with servomotor optional
for CRL-1300/-2500/-3500 16 TWHE thermal wheel heat exchanger 17 Compact lter, outdoor air
3 CRL-iD unit layout
1 3
L2*
128
122
2
1 Outdoor air 2 Exhaust air
4
L1
L2
3 Supply air
L1
TWHE with boost
damper
4 Extract air
Total
H
H
170
T
L
Type CRL-iD-1300 CRL-iD-2500 CRL-iD-3500
Unit layout Single piece Single piece Three piece Length L mm 1525 / 1525* 1626 / 1626* 1626 / 1830* Length L1 mm - - 508 Length L2 (rotor part) mm - - 610 / 814* Depth D (incl. locks) mm 750 950 1155 Total height mm 1315 1722 1722 Height H mm 1017 1424 1424 Foot height mm 170 170 170 Control unit height mm 122 122 122 Duct connection dimensions,
horizontal air routing Duct connection dimensions, vertical
air routing
mm int. 612x409 Intl 815x612 Intl 1019x612
mm Intl 596x307 Intl799x307 Intl1019x408
470 / 490*
Weight kg 266 / 266* 381 / 381*
(130+210+130)
(130+230+130)*
Nominal flow rate m³/h 1300 at 460 Pa (ext.) 2500 at 600 Pa (ext.) 3500 at 980 Pa (ext.)
* with boost damper
Type CRL-iD-4800 CRL-iD-6200 CRL-iD-9000
Unit layout Three piece Three piece Three piece Length L mm 1728 1932 2136 Length L1 mm 610 712 814 Length L2 (rotor part) mm 508 508 508 Depth D (incl. locks) mm 1360 1665 2070 Total height mm 1722 1722 1925 Height H mm 1424 1424 1627 Foot height mm 170 170 170 Control unit height mm 122 122 122 Duct connection dimensions,
horizontal air routing Duct connection dimensions, vertical
air routing
Weight kg
mm intl 1222 x 612 intl 1527 x 612 intl 1934 x 714
mm intl 1222 x 510 intl 1527 x 612 intl 1934 x 714
590
(180+230+180)
715
(220+275+220)
845
(275+295+275)
Nominal flow rate m³/h 4800 at 450 Pa (ext.) 6200 at 680 Pa (ext.) 9000 at 1000 Pa (ext.)
73064361_201811
4 CRL-iD appliance versions
Access side in supply air direction, left Access side in supply air direction, right
1
1
1
1
1
For CRL-1300/-2500/-3500, these versions are available with a boost damper.
5 CRL-iH unit layout
CRL-iH Comfort thermal wheel heat exchanger ventilation unit for internal installation with horizontal duct
connection (example provided is CRL-iH-3500 with boost damper)
1 Outdoor air damper with servomotor 2 Filter pre-dryer (accessory) 3 Differential pressure switch for lter monitoring 4 EC fan, extract air 5 Ventilation air damper with servomotor 6 Repair switch 7 BMK programming unit 8 control panel 9 TWHE control unit
10 Compact lter, extract air
11 Differential pressure switch for lter monitoring 12 Electric reheating coil available for
CRL-1300/-2500/-3500 (accessory) 13 EC fan, supply air 14 Adjustable feet 15 Boost damper with servomotor optional
for CRL-1300/-2500/-3500 16 TWHE thermal wheel heat exchanger 17 Compact lter, outdoor air
93064361_201811
5 CRL-iH unit layout
L2*
4
2
1
3
H
122
Total
H
L1
L2
L1
170
T
L
TWHE with boost
1 Outdoor air 2 Exhaust air
3 Supply air 4 Extract air
damper
Type CRL-iH-1300 CRL-iH-2500 CRL-iH-3500
Unit layout Single piece Single piece Three piece Length L mm 1525 / 1525* 1626 / 1626* 1626 / 1830* Length L1 mm - - 508 Length L2 (rotor part) mm - - 610 / 814* Depth D (incl. locks) mm 750 950 1155 Total height mm 1309 1716 1716 Height H mm 1017 1424 1424 Foot height mm 170 170 170 Control unit height mm 122 122 122 Duct connection dimensions,
horizontal air routing
mm int. 612x409 Intl 815x612 Intl 1019x612
470 / 490*
Weight kg
266 / 266*
381 / 381*
(130+210+130)
(130+230+130)*
Nominal flow rate m³/h 1300 at 460 Pa (ext.) 2500 at 600 Pa (ext.) 3500 at 980 Pa (ext.)
* with boost damper
Type CRL-iH-4800 CRL-iH-6200 CRL-iH-9000
Unit layout Three piece Three piece Three piece Length L mm 1728 1932 2136 Length L1 mm 610 712 814 Length L2 (rotor part) mm 508 508 508 Depth D (incl. locks) mm 1360 1665 2070 Total height mm 1716 1716 1919 Height H mm 1424 1424 1627 Foot height mm 170 170 170 Control unit height mm 122 122 122 Duct connection dimensions,
horizontal air routing
Weight kg
mm intl 1222 x 612 intl 1527 x 612 intl 1934 x 714
590
(180+230+180)
715
(220+275+220)
845
(275+295+275)
Nominal flow rate m³/h 4800 at 450Pa (ext.) 6200 at 680Pa (ext.) 9000 at 1000Pa (ext.)
11
13
17
5.1 CRL-iH evo max unit layout
CRL-iH evo max Comfort thermal wheel heat exchanger ventilation unit for internal installation with
horizontal duct connection (example provided is CRL-iH-11000 evo max with boost damper)
4
5
6 7
8
9
3
10
2
12
1
1 Outdoor air damper with servomotor 2 Differential pressure switch for lter monitoring 3 Ventilation air damper with servomotor 4 EC fan, extract air 5 TWHE thermal wheel heat exchanger 6 Repair switch 7 Panel for onsite cable entry 8 Differential pressure switch for lter monitoring 9 control panel
18
16
10 Extract air lter 11 BMK programming unit 12 EC fan, supply air 13 Base frame 14 Test connector for ow rate calculation 15 Boost damper with servomotor (optional) 16 Control TWHE 17 Outdoor air lter 18 Filter pre-dryer incl. control cabinet (accessory)
15
14
113064361_201811
5 CRL-iH evo max unit layout
H
1
1
4
H
H
Total
H
2
2
1 Outdoor air 2 Exhaust air
3
L1
L2
L3
3 Supply air 4 Extract air
250
L
T
Type CRL-iH-11000 evo max CRL-iH-13500 evo max
Unit layout Five piece Five piece Length L mm 2950 / 2950* 2950 / 2950* Length L1 mm 1424 1424 Length L2 (rotor part) mm 814 / 814* 814 / 814* Length L3 mm 712 712 Depth D (incl. locks) mm 1970 1970 Total height mm 2284 2894 Height H mm 2034 2644 Internal frame (optional) mm 250 250 Height H1 / H2 mm 1017 1322 Duct connection dimensions,
horizontal air routing
Weight of standard unit kg
mm Intl 1832x917 Intl 1832x1222
1370
(590+460+320)
1550
(660+490+400) Weight of base frame kg 60 90 Nominal flow rate m³/h 11000 at 1000 Pa (ext.) 13500 at 800Pa (ext.)
* with boost damper
Type CRL-iH-16500 evo max CRL-iH-19500 evo max
Unit layout Five piece Five piece Length L mm 2950 / 2950* 2950 / 2950* Length L1 mm 1424 1424 Length L2 (rotor part) mm 814 / 814* 814 / 814* Length L3
712 712
Depth D (incl. locks) mm 2275 2580 Total height mm 2894 2894 Height H mm 2644 2644
Internal frame (optional) mm 250 250 Height H1 / H2 mm 1322 1322
Duct connection dimensions, horizontal air routing
Weight of standard unit kg
mm Intl 2137x1222 Intl 2442x1222
1790
(710+630+450)
2020
(790+720+510) Weight of base frame kg 110 120 Nominal flow rate m³/h 16500 at 750 Pa (ext.) 19500 at 950 Pa (ext.)
* with boost damper
6 CRL-iH appliance versions
Access side in supply air direction, left Access side in supply air direction, right
1, 2
1, 2
1, 2
1, 2
1For CRL-iH-1300/-2500/-3500, these versions are available with a boost damper. 2CRL-IH evo max types are available in these versions
133064361_201811
7 CRL-iDH unit layout
CRL-iDH Comfort thermal wheel heat exchanger ventilation unit energy efcient and comfortable
ventilation with vertical/horizontal duct connection (example provided is CRL-iDH-3500 with boost damper)
1 Outdoor air damper with servomotor 2 Filter pre-dryer (accessory) 3 Differential pressure switch for lter monitoring 4 EC fan, extract air 5 Ventilation air damper with servomotor 6 Repair switch 7 BMK programming unit 8 control panel 9 TWHE control unit
10 Compact lter, extract air 11 Differential pressure switch for lter monitoring 12 Electric reheating coil available for
CRL-1300/-2500/-3500 (accessory) 13 EC fan, supply air 14 Adjustable feet 15 Boost damper with servomotor optional for
CRL-1300/-2500/-3500 16 TWHE thermal wheel heat exchanger 17 Compact lter, outdoor air
7 CRL-iDH unit layout
L1
L2
L1
1
L2*
128
3
H
H
H
2
4
Total
170
T
L
122
1 Outdoor air 2 Exhaust air
3 Supply air 4 Extract air
TWHE with boost
damper
Type CRL-iDH-1300 CRL-iDH-2500 CRL-iDH-3500
Unit layout Single piece Single piece Three piece Length L mm 1525 / 1525* 1626 / 1626* 1626 / 1830* Length L1 mm - - 508 Length L2 (rotor part) mm - - 610 / 814* Depth D (incl. locks) mm 750 950 1155 Total height mm 1315 1722 1722 Height H mm 1017 1424 1424 Foot height mm 170 170 170 Control unit height mm 122 122 122 Duct connection dimensions,
horizontal air routing Duct connection dimensions, vertical
air routing
mm int. 612x409 Intl 815x612 Intl 1019x612
mm Intl 596x307 Intl799x307 Intl1019x408
470 / 490*
Weight kg 266 / 266* 381 / 381*
(130+210+130)
(130+230+130)*
Nominal flow rate m³/h 1300 at 460 Pa (ext.) 2500 at 600 Pa (ext.) 3500 at 980 Pa (ext.)
* with boost damper
Type CRL-iDH-4800 CRL-iDH-6200 CRL-iDH-9000
Unit layout Three piece Three piece Three piece Length L mm 1728 1932 2136 Length L1 mm 610 712 814 Length L2 (rotor part) mm 508 508 508 Depth D (incl. locks) mm 1360 1665 2070 Total height mm 1722 1722 1925 Height H mm 1424 1424 1627 Foot height mm 170 170 170 Control unit height mm 122 122 122 Duct connection dimensions,
horizontal air routing Duct connection dimensions, vertical
air routing
Weight kg
mm intl 1222 x 612 intl 1527 x 612 intl 1934 x 714
mm intl 1222 x 510 intl 1527 x 612 intl 1934 x 714
590
(180 + 230 + 180)
715
(220 + 275 + 220)
845
(275 + 295 + 275)
Nominal flow rate m³/h 4800 at 450 Pa (ext.) 6200 at 680 Pa (ext.) 9000 at 1000 Pa (ext.)
153064361_201811
8 CRL-iDH appliance versions
Access side in supply air direction, left Access side in supply air direction, right
1
1
1
1
Other versions available; see the WOLF sizing program.
1
For CRL-1300/-2500/-3500, these versions are available with a rapid heat-up damper.