Winland Electronics WB800 User Manual

Electronic Water Detection Device
CONTENTS
This package contains:
• 1 WB-800
• 4 Surface Probes - Supervised (W-S-S)
• 1 Standard 3-Gang Metal Mounting Box
• 4 Phillips screws for mounting
• 1 Installation/Operating Instruction Guide
Tech Support 8:00am - 5:00pm Central Time
(800) 635-4269 • +1-507-625-7231 P
www.winland.com
WB-800
© 2012 Winland Electronics, Inc.
D-011-0008 Rev F (08/2012)
SPECIFICATIONS
Power Requirement 12/24 VDC 100 mA 12/24 VAC 200 mA
Probe Sensitivity Will not alarm due to high humidity or condensation. Operating Temp 32˚ to 130˚F (0˚ to 54˚C); non-condensing environment Indoor use only. Output 1 Form C Relay (SPDT) 1 Amp @ 24 VDC, resistive
Buzzer 85dBA @ 10 cm @ 12 VDC, 2.4kHz pulsed (with silence feature)
Probe Options Includes 4 Standard Supervised Surface Probe (W-S-S) Accepts up to 8 Supervised (W-S-S or W-UC-S) or up to 16 Unsupervised Probes (W-S-U or W-UC-U) Probes may be either Surface or Under Carpet
Max Cable Length 500’ (152.4 m) max Probe Cable Probes include 15” (4.6 m) cable. Extend using 22-18 AWG twisted pair.
Console Weight 1 lb (0.45 kg) Console Dimensions 6.55 x 4.70 x 1” (16.6 x 11.9 x 2.5 cm) Probe Dimensions Surface: 2 x 3 x 0.88” (5.1 x 7.6 x 2.2 cm) Under Carpet: 2 x 3 x 0.18” (5.1 x 7.6 x 0.5 cm)
Mounting Included standard 3-gang box Case Material ABS Warranty 1 Year Limited
ADDITIONAL PROBES AND ACCESSORIES
W-S-S WB Surface Probe Supervised (Up to 8 per WB-800 console)
W-UC-S WB Undercarpet Probe Supervised (Up to 8 per WB-800 console)
W-S-U WB Probe Unsupervised (Up to 16 per console)
W-UC-U WB Probe Undercarpet Unsupervised (Up to 16 per console)
12VDCT 12VDC Transformer Wall Mount Power Supply
BZ-1 Remote Annunciator
Note: Supervised probes are recommended for new WB-800 installations.
MONITORING THE ABSENCE OF WATER:
The WB-800 is not recommended to be used to detect absence of water. The WB-200 is recommended for this type of application.
ONE YEAR LIMITED WARRANTY
Winland Electronics, Inc. (“Winland”) warrants to the end user/purchaser that each product of its manufacture shall be free from defects in material and fac tory workmanship for a period of one year from the date of purchase, when properly installed and operated under normal conditions according to Winland’s instruction.
Winland’s obligation under this warranty is limited to correcting, without charge, at its factory any part or par ts thereof which shall be returned to the factory, by the original purchaser, transportation charges prepaid, within one year of the date of purchase and which upon examination, shall disclose to Winland’s satisfaction to have been originally defective. Correction of such defects by repair to, or supplying replacements for, defective parts shall constitute fulfillment of all Winland’s obligations to purchaser under this limited warranty. Repair service performed by Winland after one year from date of purchase will be for a reasonable service charge.
This limited warranty shall not apply to any of Winland’s products which have been subject to misuse, negligence or accident or which have been repaired or altered outside of Winland’s factory. The warranty is void if the Product’s housing or cover is removed.
Winland shall not be liable for loss, damage or expense resulting, directly or indirectly, from the use of its products or any other cause.
This warranty shall be null and void in its entirety if: (i) the product is altered or modified in any way that is not consistent with the manufacturer’s instructions, or (ii) the product is used with or connected to a device: (a) that such product is not intended to be used with or connected to, (b) is not otherwise consistent with the manufacturer’s instructions, or (c) is not otherwise approved by the manufacturer.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING, WITHOUT LIMITATION, ANY WARRANTIES OF MERCHANTABILITY, FITNESS FOR PARTICULAR PURPOSES, NON-INFRINGEMENT AND TITLE, AND ANY WARRANTIES ARISING FROM COURSE OF DEALING, USAGE OF TRADE OR OTHERWISE. ALL OTHER REPRESENTATIONS MADE TO THE END USER/PURCHASER BY ANY OTHER PARTY ARE ALSO EXCLUDED.
WINLAND SHALL NOT BE LIABLE TO ANY PERSON FOR INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY DESCRIPTION, WHETHER ARISING OUT OF WARRANTY OR OTHER CONTRACT, NEGLIGENCE OR OTHER TORT, OR OTHERWISE. Under no circumstances shall Winland’s liability under this limited warranty exceed the purchase price paid by the end user/purchaser for the product.
No person, agent or dealer is authorized to give warranties on behalf of Winland nor to assume for Winland any other liability in connection with any of its products.
SYSTEM OVERVIEW
WATER
WATER
WATER
WATER
The WB-800 is a completely electronic water detector which is designed to detect only nonflammable conductive liquids (distilled and deionized water cannot be detected). The WB-800 is designed with the control console mounted on the wall and the remote probes placed in locations where water seepage is most probable.
Option # 2 Surface Mounting with Mounting Box
In areas where no hollow interior walls are available, the included standard 3-gang surface mounting box can be secured to any wall. The installed profile of the WB-800 with this option is about 2½“ out from the wall.
INSTALLATION - POWER AND PROBE CONNECTIONS
The unit includes four (4) supervised surface probes (W-S-S). In addition to detecting water with this probe, the unit will alarm when the supervised probe line becomes disconnected.
A film of moisture forming a bridge between the two metallic contacts on any remote probe is all that is needed for the unit to signal an alarm condition (Figure 1). The relay output is non-latching, but will remain closed until the moisture bridge between the two contacts is broken. As sensitive as the WB-800 is, it will not alarm due to high humidity or condensation. The WB-800 is ideal for use around homes, office buildings, computer rooms, boats, etc. Additional features include:
• Accepts 12V, 24V AC/DC power input
• Eight alarm LED indicators to identify the probe zone in alarm.
• Supervised probe line option. Unit will alarm on open probe condition and an indicator will light. Up to 8 supervised probes per console (W-S-S or W-UC-S). Probe lines up to 500ft.
• One “Form C” SPDT Relay for alarm output.
• Built in audible alarm and remote buzzer output with silence feature (adjustable 3 seconds to 150 minutes)
Four Probe Contacts
Mount the probe to
ensure these four stainless steel contacts are against the surface
to be monitored.
Step 1 - Power Connections
The WB-800 will operate on 12V, 24V AC/DC. Refer to Figure 3 for proper connections.
Note: Before making wire connections, set jumper “JP3” to either 12V or 24V depending on your power supply output.
Connect your power input to two of the three positions on the terminal block. Regardless of your voltage input, connect the negative side to “V-“. If your supply is 12V AC/DC or 24VAC, connect the positive side to the position marked “12VAC/DC, 24VDC”. If using 24VAC input, connect to the 24VAC input.
When the power is applied, the green ON power indicator should be on.
Note: If the built-in buzzer sounds, it can be disabled by moving jumper “JP2” to the OFF position. If desired, toward the end of installation, it can be reactivated.
Important: If you are not using Winland’s 12VDCT power supply accessory with this product, ensure that your power supply does not have a connection to earth ground. If the WB-800’s power is connected to earth ground, it’s possible that the sensor will fail to alarm when wet due to the possibility of a ground loop that may exist from the sensor terminals through the earth back to the power supply. This will change the system’s voltage reference, which will, in turn, change its trip point. In all cases, test the system to ensure it will trip as expected when water is encountered.
Step 2 - Probe Connections
ALARM NO ALARM
Figure 1
CONSOLE MOUNTING CONSIDERATIONS
Select A Site For The Console
Probe cable lengths and power source locations should be considered. Maximum cable length for the water probes is 500 ft.
Option #1 Surface Mounting Without Mounting Box
It is possible to install the console on a soft wall (sheet rock, panel, etc.) without the use of a mounting box. This is the fastest mounting method and it gives the control console a nice looking low profile. In selecting a site to mount the console, keep in mind that it must be placed in a secure, dry location with an ambient temperature of 32˚ to 130˚F (0˚ to 54˚C). For this option, drill a ½” diameter hole(s) in the wall which will be opposite the wiring terminal strip on the console. This hole will provide access for all wiring. Next, carefully mark the location of the four corner screw holes on the console. Then drive four wall anchors into the proper locations and complete by attaching the console to the wall.
Option 1 - Supervised Probe Mode
The unit includes four supervised surface probes (W-S-S). Additional probes (surface [W-S-S] or under carpet [W-UC-S]) may be purchased separately.
With no probes attached to unit and with the 8 position DIP switch settings (SW1) in the down position, zone alarm indicators 1-8 and the probe line alarm indicator should be on. When the probe line alarm indicator is on, it shows there is an open probe line. When the zone alarm indicator is on, it shows that a specific zone is in alarm (either water detected or open probe line).
For zones that are not planned to be used, the supervised mode can be disabled (i.e. open probe line alarm turned off) by pushing the DIP switches up for the corresponding zones.
The WB-800 has two terminal blocks (TB1 and TB2) that are the locations for connecting the probe inputs. There is no polarity to the probes. The probes are included with 15’ (4.5 m) of cable. The probe cables can be increased to 500’ (152.4 m) with additional cable (22-18 AWG twisted pair, is recommended). Be sure that all splices are moisture proof.
Note: For probe placement and mounting, see Figures 1 and 2.
Caution: If a supervised probe is used, and the zone DIP switch is inadvertently left
in the “up” position (supervised mode disabled) the probe will still be operational to detect water, however, the open probe line alarm will not be operational. Verify the
DIP switch is in the “down” position for zones being used.