Wilbur Curtis WB-10-12 Service Manual

MODELS INCLUDED
WB-10-12
WB-10-60
Wilbur Curtis Company, inC.
Service Manual – WB-10 Water Boiler
Important Safeguards/Symbols
This equipment is designed for commercial use. Any servicing other than cleaning and routine maintenance should be performed by an authorized Wilbur Curtis Company service technician.
• DO NOT immerse the unit in water or any other liquid
• To reduce the risk of re or electric shock, DO NOT open service
panels. There are no user serviceable parts inside.
• Keep hands and other items away from hot areas of the unit dur-
ing operation.
• Never clean with scouring powders or harsh chemicals.
Symbols:
CAUTION: Please use this setup
procedure before attempting to use this appliance. Failure to follow the instructions can result in injury or the voiding of the warranty.
CAUTION: DO NOT
connect this unit
to hot water. The inlet valve is not rated for hot water.
WARNING: DO NOT place this water boiler closer than
six [6] inches from wall. Unit must have adequate cross-ventilation.
WARNING HOT
LIQUID, Scalding
may occur. Avoid
splashing.
WARNINGS – To help avoid personal injury
Important Notes/Cautions – from the factory
Sanitation Requirements
INSTALLATION
This Curtis unit is pre-set and ready to go from the factory.
System Requirements:
• Water Supply 20 – 90 PSI (MINIMUM FLOW RATE of 2 GPM)*
• Electrical: See electrical schematic.
Factory Settings:
• Water Temperature 200ºF • Volume 10 Gallons
NSF requires the following water connection:
1. A quick disconnect or additional coiled tubing (at least 2x the depth of the unit) is required so that the unit can be moved for cleaning.
2. This unit must be installed with adequate backow protection to comply with applicable federal, state and local codes.
3. Water pipe connections and xtures directly connected to a portable water supply shall be sized, installed and maintained in accordance with federal, state, and local codes.
SETUP STEPS
C
ISO 9001:2008 REGISTERED
WILBUR CURTIS CO.
6913 Acco Street,
Montebello, CA 90640-5403
For the latest information go to
www.wilburcurtis.com
Tel: 800/421-6150
Fax: 323/837-2410
1. The unit should be level (left to right - front to back), on a secure surface.
2. Install the supplied water faucet on the faucet shank in front of the unit.
NOTE: A water ltration system must be used to help maintain trouble-free operation. In areas with extremely hard water, we highly recommend the use of a Curtis approved water lter. (For our full line of lters, please log on to www.wilburcurtis.com) A water ltration system will greatly prolong the life of the unit and enhance the quality and taste of the product.
FOR THE LATEST SPECIFICATIONS AND INFORMATION GO TO WWW.WILBURCURTIS.COM
Setup Steps Continued
3. Connect the water line to the water inlet tting on the rear of the unit. Water volume going to the machine should be consistent. Use tubing sized sufciently to provide a minimum ow rate of two gallons per minute.
4. Connect the unit to electrical outlet with appropriate amperage rating (refer to schematic for power requirements).
5. Turn on the circuit running power to unit. The water inlet valve will open, lling the unit. When the boiler has lled, turn on boiler at the thermostat, twisting the knob clockwise.
6. Heating tank will require 50 to 60 minutes to attain operating temperature. Thermostat indicator will light at this time.
Parts List
INDEX №
1
2
3
4
5
6
7
8
9
10
11
12
13
14
PART №
WC-5602
WC-1800HW
WC-3705HW
WC-1902
WC-1903
WC-1906
WC- 511
WC-5502-01
WC-3914
WC-2966
WC-5386
WC- 922-04
WC- 501
WC-3220
DESCRIPTION
LID WITH KNOB
FAUCET, “S” SERIES HOT WATER 1-1/32-14 UNS
KIT, FAUCET S SERIES HOT WATER
SHANK, FAUCET PLAIN W/NUTS
NUT, UNION SHANK WB-10
“C” RING .917 X .760 X .090
THERMOMETER, DIAL RU’S
KIT, PROBE, WATER LEVEL W/HEX FITTING, O-RING, NUT
LABEL, “HOT WATER” (WB-10)
FITTING, WATER INLET WB-10
TUBING ASSEMBLY, WATER INLET
ELEMENT, HEATING 3.5KW 220V W/NUTS & WASHERS
THERMOSTAT, CAPILLARY DPST 277V 30A RU/WB
BEZEL, THERMOSTAT ELECTRIC
15
16
17
18
19
19A
20
21
WC-3217
WC- 608-101
WC-5611
WC-2401
WC- 801
WC- 858
WC-3700
WC- 813
KNOB, ELECTRIC THERMOSTAT
CONTROL BOARD, LIQUID LEVEL 120/240VAC
COVER, BOTTOM WB-10
ELBOW, 3/8 NPT X 1/4 FLARE PLATED
VALVE, INLET BRASS .50 GPM 120V 10W WB-10-12
VALVE, INLET BRASS .50 GPM 220V 10W WB-10-60
KIT, INLET VALVE REPAIR
FLOW WASHER, .5 GPM .5” S45
2
Illustrated Parts List
1
8
7
3
2
4
5
6
9
10 11
12
13
14 15 16 17
21
20
19
18
3
TROUBLE SHOOTING
PROBLEM: WATER WILL NOT REFILL
POSSIBLE CAUSE
1. Water line closed or
clogged lter
Check the water system at your facility to make sure the line is open. Replace the water lter.
SOLUTION
2. Valve coil burned out
3. Grounded probe
4. Defective water level
control board
PROBLEM: WATER OVERFLOWING.
POSSIBLE CAUSE
1. Defective water inlet
valve
2. Liquid level probe
limed up
Turn machine off. Disconnect wires from water inlet coil terminals and connect a power cord to the terminals. Plug cord into a 120V outlet and verify if water ows when plugged in and stops when power is disconnected. If valve fails this test, replace valve.
When the water level gets below the probe tip, water should automatically rell the unit. If not, pull wire off the probe terminal. Water should now start owing into the water boiler.
Disconnect wire from probe terminal. With a voltmeter, check voltage at the water inlet coil termi­nals. This should read 110-120 volts. If no voltage is present, check liquid level control (L.L.C.) board. Make sure the L.L.C. board is supplied by 120V across terminals NEU and L1 120V. The L.L.C. board is grounded to the body of the machine by contacting the board to the mounting bracket. Make sure board is grounded here. Check for loose connections at terminals. Replace the L.L.C. board.
Turn power off and observe water level. If water continues to ow into the heating tank, clean or replace leaky valve.
Disconnect wire from probe terminal. Touch the body of the heating tank with the terminal at the end of this wire. If the ow of water stops, there is and issue with the probe. Clean the probe and recon­nect the wire. If water continues to ow, replace the liquid level probe.
SOLUTION
3. Non-grounded or loose terminal connections at liquid level control board
PROBLEM: WATER DOES NOT REACH PROPER TEMPERATURE
POSSIBLE CAUSE
1. Thermostat is turned
OFF (or set too low)
PROBLEM: WATER OVERHEATS, ELEMENTS DO NOT SHUT OFF
POSSIBLE CAUSE
1. Defective thermostat
Liquid level control board must be securely grounded through the back of the board and the mount­ing bracket. Check for loose connections at the terminals. Check for voltage across the inlet valve terminals. If there is 110 to 120 volts present at the inlet valve terminals when water level is touching the probe tip, replace the L.L.C. board.
Check the thermostat adjustment to make sure the knob is rotated clockwise to the desired tem-
perature setting.
Replace the thermostat. You can sometimes operate temporarily by turning the thermostat knob
to off until the boiling stops.
SOLUTION
SOLUTION
4
TROUBLE SHOOTING CONTINUED:
PROBLEM: WATER DOES NOT REACH PROPER TEMPERATURE
POSSIBLE CAUSE
2. Defective thermostat
3. Heating element burned out.
Electric Thermostat Adjustment
SOLUTION
Replace thermostat if contacts are open when knob is fully clockwise and water temperature is less than 190º F. You will measure 120 volts (approximately) to ground from both thermostat terminals when it is ON and from only one terminal when it is OFF.
In this water boiler there are two elements in parallel. Failure of either will cause very slow heat­ing. Perform the following tests:
a. Clamp-on ammeter test: If both elements are good, you will measure about 21 amps at 240
volts, 24 amps at 208 volts or 29 amps at 120 volts. If you measure only 10 to 12 amps, check the current to each element to identify the defective part.
b. Ohmmeter or continuity test: Disconnect all power by unplugging unit. Disconnect one
terminal to measure each element. They should each have continuity or measure about 20
ohms.
ELECTRIC THERMOSTAT ADJUSTMENT
On electric water boilers, thermostats are set at the factory to cut off at 200ºF. We do not recommend changing this. If necessary, adjustment is as follows:
1. Rotate the thermostat knob to the right to the BOIL position. Pull off the knob.
2. Locate the tiny adjustment screw, inside the stem (see gure 1). Using a small screw­driver, adjust the temperature up or down:
a. By turning the screw ¼ turn to the left will increase the temperature about 20°F.
b. Turning ¼ to the right will decrease the temperature by 20°F.
c. To set the thermostat precisely at 200°F, insert a thermometer probe into the
water jacket through the steam hole (just under the sprayhead). Turn the screw ½
turn to the left.
d. When the thermometer reaches 200°F, slowly turn the adjustment screw to the
right until the pilot light turns off.
CLEANING
Regular cleaning and preventive maintenance is essential in keeping your water boiler looking and working like new. To clean the water boiler, prepare a mild solution of dish detergent and warm water. Turn the thermostat dial to OFF and allow the unit to cool.
CAUTION – Do not use cleansers, bleach liquids, powders or any other substance containing chlorine. These products pro­mote corrosion and will pit the stainless steel. USE OF THESE PRODUCTS WILL VOID THE WARRANTY.
DAILY CLEANING
1. Wipe exterior surfaces with a damp cloth, removing spills and debris.
2. Remove the lid and clean it with a cloth soaked in a mild detergent solution.
3. Rinse and dry the lid.
4. Wipe off any traces of the cleaning solution with a cloth dampened with water.
5. Dry the cabinet surfaces.
6. Rub a stainless steel polish on the outside surfaces to protect the cabinet.
5
ELECTRICAL SCHEMATIC DUAL VOLTAGE 120V/220V
6
ELECTRICAL SCHEMATIC 220V
7
Product Warranty Information
The Wilbur Curtis Company certies that its products are free from defects in material and workmanship under normal use. The following limited warranties and conditions apply:
3 Years, Parts and Labor, from Original Date of Purchase on digital control boards.
2 Years, Parts, from Original Date of Purchase on all other electrical components, ttings and tubing.
1 Year, Labor, from Original Date of Purchase on all electrical components, ttings and tubing.
Additionally, the Wilbur Curtis Company warrants its Grinding Burrs for Forty (40) months from date of purchase or 40,000 pounds of coffee, whichever comes rst. Stainless Steel components are warranted for two (2) years from date of purchase against leaking or pitting and replace­ment parts are warranted for ninety (90) days from date of purchase or for the remainder of the limited warranty period of the equipment in which
the component is installed.
All in-warranty service calls must have prior authorization. For Authorization, call the Technical Support Department at 1-800-995-0417. Effective date of this policy is April 1, 2003. Additional conditions may apply. Go to www.wilburcurtis.com to view the full product warranty information.
CONDITIONS & EXCEPTIONS
The warranty covers original equipment at time of purchase only. The Wilbur Curtis Company, Inc., assumes no responsibility for substitute replace­ment parts installed on Curtis equipment that have not been purchased from the
Wilbur Curtis Company, Inc. The Wilbur Curtis Company will not accept any responsibility if the following conditions are not met. The warranty does not cover and is void under the following circumstances:
1) Improper operation of equipment: The equipment must be used for its designed and intended purpose and function.
2) Improper installation of equipment: This equipment must be installed by a professional technician and must comply with all local electrical,
mechanical and plumbing codes.
3) Improper voltage: Equipment must be installed at the voltage stated on the serial plate supplied with this equipment.
4) Improper water supply: This includes, but is not limited to, excessive or low water pressure, and inadequate or uctuating water ow rate.
5) Adjustments and cleaning: The resetting of safety thermostats and circuit breakers, programming and temperature adjustments are the
responsibility of the equipment owner. The owner is responsible for proper cleaning and regular maintenance of this equipment.
6) Damaged in transit: Equipment damaged in transit is the responsibility of the freight company and a claim should be made with the carrier.
7) Abuse or neglect (including failure to periodically clean or remove lime accumulations): Manufacturer is not responsible for variation
in equipment operation due to excessive lime or local water conditions. The equipment must be maintained according to the manufacturer’s recommendations.
8) Replacement of items subject to normal use and wear: This shall include, but is not limited to, light bulbs, shear disks, “0” rings, gaskets, silicone tube, canister assemblies, whipper chambers and plates, mixing bowls, agitation assemblies and whipper propellers.
9) Repairs and/or Replacements are subject to our decision that the workmanship or parts were faulty and the defects showed up under normal use. All labor shall be performed during regular working hours. Overtime charges are the responsibility of the owner. Charges incurred by delays, waiting time, or operating restrictions that hinder the service technician’s ability to perform service is the responsibility of the owner of the equipment. This includes institutional and correctional facilities. The Wilbur Curtis Company will allow up to 100 miles, round trip, per in-warranty service call.
RETURN MERCHANDISE AUTHORIZATION: All claims under this warranty must be submitted to the Wilbur Curtis Company Technical Support Department prior to performing any repair work or return of this equipment to the factory. All returned equipment must be repackaged properly in the original carton. No units will be accepted if they are damaged in transit due to improper packaging. NO UNITS OR PARTS WILL
BE ACCEPTED WITHOUT A RETURN MERCHANDISE AUTHORIZATION (RMA). RMA NUMBER MUST BE MARKED ON THE CARTON OR SHIPPING LABEL. All in-warranty service calls must be performed by an authorized service agent. Call the Wilbur Curtis Technical Sup-
port Department to nd an agent near you.
ECN 11526 . 7/26/13@9.0 . revF
WILBUR CURTIS CO., INC. 6913 Acco St., Montebello, CA 90640-5403 USA Phone: 800/421-6150 Fax: 323-837-2410 Technical Support Phone: 800/995-0417 (M-F 5:30A - 4:00P PST) E-Mail: techsupport@wilburcurtis.com Web Site: www.wilburcurtis.com
8
FOR THE LATEST SPECIFICATION INFORMATION GO TO WWW.WILBURCURTIS.COM
Printed in U.S.A. 7/2013 F-1984 Rev F
Loading...