Operating Instructions Temperature Indicating Controller CS4H / CS4L
Preface
Thank you for the purchase of our microcomputer based temperature indicating controllers CS4H or CS4L.
This manual contains instructions for the mounting, functions, operations and notes when operating the
CS4H or CS4L.
For model confirmation and unit specifications, please read this manual carefully before starting operation.
To prevent accidents arising from the misuse of this controller, please ensure the operator using it receives
this manual.
Caution
• This instrument should be used according to the specifications described in the manual.
If it is used according to the specifications, it may malfunction or cause fire.
• Be sure to follow the warnings, cautions and notices. If not, it could cause serious injury or malfunction.
• Specifications of the CS4H and CS4L and the contents of this instruction manual are subject to change
without notice.
• Care has been taken to assure that the contents of this instruction manual are correct, but if there are any
doubts, mistakes or questions, please inform our sales department.
• This instrument is designed to be installed in a control panel. If not, measures must be taken to ensure that
the operator cannot touch power terminals or other high voltage sections.
• Any unauthorized transfer or copying of this document, in part or in whole, is prohibited.
• WIKA is not liable for any damages or secondary damages incurred as a result of using this product, including any indirect damages.
SAFETY PRECAUTIONS
(Be sure to read these precautions before using our products.)
The safety precautions are classified into categories: “ Warning” and “ Caution”.
Depending on circumstances, procedures indicated by “
sure to follow the directions for usage.
Caution” may be linked to serious results, so be
Warning
Procedures, which may lead to dangerous conditions and cause death or serious injury, if not carried
out properly.
V1.1 • 05/2006 - 2 -
Caution
Procedures which may lead to dangerous conditions and cause superficial to medium injury or
physical damage or may degrade or damage the product, if not carried out properly.
Operating Instructions Temperature Indicating Controller CS4H / CS4L
1. Installation precautions
Caution
This instrument is intended to be used under the following environmental
conditions (IEC61010-1):
Overvoltage category
Mount the controller in a place with:
• A minimum of dust, and an absense of corrosive gasses
• No flammable, expolsive gasses
• No mechanical vibrations or shocks
• No exposure to direct sunlight, an ambient temperature of 0 ... 50°C (32 ... 122°F) that does
not change suddenly
• An ambient non-condensing humidity of 35 ... 85%RH
• No large capacity electromagnetic switches or cables through which large current is
flowing.
• No water, oil or chemicals or where the vapors of these substances can come into direct
contact with the unit
Note: Do not install this instrument near flammable material even though the case of this
instrument is made of flame resisting resin. Avoid setting this instrument directly on
flammable material.
2. Wiring precautions
, Pollution degree 2
Caution
• Use the solderless terminal with an insulation sleeve that fits in the M3 screw when wiring
the CS4H or CS4L.
• The terminal block of this instrument is designed to be wired from the left side.
The lead wire must be inserted from the left side of the terminal, and fastened with the terminal screw.
• Tighten the terminal screw within the specified torque.
If excessive force is applied to the screw when tightening, the screw or case may be damaged.
• Do not apply a commercial power source to the sensor which is connected to the input
terminal nor allow the power source to come into contact with the sensor, as the input circuit may be burnt out.
• This controller has no built-in power switch, circuit breaker or fuse. It is necessary to install
them near the controller.
(Recommended fuse: Time-lag fuse, rated voltage 250V AC, rated current 2A)
• When using a 24V AC/DC for the power source, do not confuse the polarity when it is DC.
3. Running and maintenance precautions
Caution
• It is recommended that PID auto-tuning be performed on the trial run.
Do not touch live terminals. This may cause electric shock or problems in operation.
•
• Turn the power supplied to the instrunment OFF when retightening the terminal and
cleaning. Working or touching the terminal with the power switched ON may result in Electric Shock causing severe injury or death.
• Use a soft, dry cloth when cleaning the instrument.
(If paint thinner is used, it might deform or tarnish the unit.)
• As the display section is vulnerable, do not strike or scratch it with a hard object or press
hard on them
V1.1 • 05/2006 - 3 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
List of contents
1. Model informations
1.1 Model name ····················································································································· 6
10.3 Control ·························································································································· 49
11. Character table ··········································································································· 49
V1.1 • 05/2006 - 5 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
1. Model informations
1.1 Model name and order code
CS4 - 3 A / M - B - - -... Series name CS4_
Model
Control
characteristic
Alarm 1 (A1) A Process value monitoring, output relay
Control output
Input M Multi-function input (input configuration setable)
Case colour B Black
Options
(1) PID, PI, PD, P and ON/OFF action are programmable.
(2) 9 types of alarm action, no alarm action and energized/deenergized are selectable by key operation.
(3) The input configuration can be selected from the user by the front keys.
(4) Only 2 options can be added from Alarm output 2, Heater burnout alarm and 2. control output.
(5) For control output analogue current signal heater burnout alarm cannot be added.
(6) When serial communication is added, SV1/SV2 external selection (standard function) does not work.
(7) 2. control output and heater burnout alarm cannot be added, when transmitter supply DC 24 V is added.
H
L
CS4H: W48 x H96 x D100mm
CS4L: W96 x H96 x D100mm
3 PID (setable control parameter)
R Relay
S Logic level (DC 0/12 V) for solid state relay
A Analogue current signal (4 ... 20 mA)
H AC 100 ... 240 V, 50 ... 60 Hz Power supply
L AC/DC 24 V
B Factory adjustment Instrument configuration
# (?) To customers specification
(4)
2AS
Alarm output 2: process value monitoring
(4)
2AR
Alarm output 2: control loop monitoring
(4)
2AL
Alarm output 2: process value and control loop moni-
toring with common terminals
Heater burnout alarm for 1 phase (max. 5 A)
Heater burnout alarm for 1 phase (max. 10 A)
Heater burnout alarm for 1 phase (max. 20 A)
Heater burnout alarm for 1 phase (max. 50 A)
2. control output (three step control) relay
2. control output (three step control) logic level
DC 0/12 V for solid state relay
2. control output (three step control) analogue current
signal (4 ... 20 mA)
Serial interface RS 485
Transmitter supply DC 24 V max. 30 mA
Shunt resistor 50
Ω for input signals 0/4 ... 20 mA
W10
W11
W12
W15
DR2
DS2
DA2
CR5
P24
R50
(4) (5)
(4) (5)
(4) (5)
(4) (5)
(4)
(4)
(4)
(6)
(7)
KAB Terminal cover
(1)
(2)
(3)
V1.1 • 05/2006 - 6 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
1.2 Rated input
Input type Input range Resolution
K
J
–200 ... 1370 °C –320 ... 2500 °F 1 °C (°F)
–199.9 ... 400.0 °C –199.9 ... 750.0 °F 0.1 °C (°F)
–200 ... 1000 °C –320 ... 1800 °F 1 °C (°F)
R 0 ... 1760 °C 0 ... 3200 °F 1 °C (°F)
S 0 ... 1760 °C 0 ... 3200 °F 1 °C (°F)
B 0 ... 1820 °C 0 ... 3300 °F 1 °C (°F)
E
–200 ... 800 °C –320 ... 1500 °F 1 °C (°F)
T –199.9 ... 400.0 °C –199.9 ... 750.0 °F 0.1 °C (°F)
N –200 ... 1300 °C –320 ... 2300 °F 1 °C (°F)
PL- 0 ... 1390 °C 0 ... 2500 °F 1 °C (°F)
C(W/Re5-26) 0 ... 2315 °C 0 ... 4200 °F 1 °C (°F)
Pt100
JPt100
4 … 20 mA DC –1999 ... 9999
0 … 20 mA DC –1999 ... 9999
0 … 1 V DC
0 … 5 V DC
1 … 5 V DC –1999 ... 9999
0 … 10 V DC –1999 ... 9999
–199.9 ... 850.0 °C –199.9 ... 999.9 °F 0.1 °C (°F)
–200 ... 850 °C –300 ... 1500 °F 1 °C (°F)
–199.9 ... 500.0 °C –199.9 ... 900.0 °F 0.1 °C (°F)
–200 ... 500 °C –300 ... 900 °F 1 °C (°F)
–1999 ... 9999
–1999 ... 9999
(1)(2)
1
(1)(2)
1
(1)
1
(1)
1
(1)
1
(1)
1
(1) For DC input, input range and decimal point place can be changed.
(2) Connect 50 Ω shunt resistor (sold optionally) between input terminals.
V1.1 • 05/2006 - 7 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
2. Name and functions of the sections
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(14)
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(14)
(12)
(13)
(15)
(12)
(13)
(15)
(Fig. 2-1)
Indications:
(1) PV: PV display
Indicates the process variable (PV) with a red LED.
(2) SV: SV display
Indicates the setting value (SV) or manipulated variable (MV) with a green LED.
(3) SV1: Set value 1 indicator
When set value 1 (SV1) is selected, a green LED lights.
(4) SV2: Set value 2 indicator
When set value 2 (SV2) is selected, a yellow LED lights.
(5) OUT1: Control output 1 (OUT1) indicator
When OUT1 or Heating output is ON, a green LED lights.
(In the case of DC current output type, it blinks in a 0.25 second cycle corresponding
to the output manipulated variable.)
(6) OUT2: Control output 2 (OUT2) indicator
When OUT2 is ON, a yellow LED lights.
(In the case of DC current output type, it blinks in a 0.25 second cycle corresponding
to the output manipulated variable.)
(7) HB: HB indicator
When Heater burnout alarm output or Sensor burnout alarm output is ON, a red LED lights.
(When Heater burnout Alarm is added, a red LED also lights when the indication is
overscale or underscale)
(8) AT: Auto-tuning (AT) indicator
When Auto-tuning or Auto-reset is active, a yellow LED blinks.
(9) TX/RX: TX/RX indicator
When serial communication TX (transmitting) is outputted, a yellow LED lights.
(10) A1: Alarm 1 (A1) indicator
When A1 output is ON, a red LED lights.
(11) A2/LA: Alarm 2 (A2/LA) indicator
When A2 output is ON, a red LED lights.
V1.1 • 05/2006 - 8 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
Keys:
(12)
▲: Increase key
Increases numeric value of the setting value.
(13)
▼: Decrease key
Decreases numeric value of the setting value.
(14) MODE: Mode key
Switches the setting mode and registers the setting value and selected value.
(Setting value and selected value are registered by pressing the mode key.)
(15)
OUT
• When
OUT
/
:
/
OFF
key
OFF
OUT
/
function is selected in the
OFF
off. By pressing
OUT
OUT
/
key function selection, control output can be turned on or
OFF
/
key for approx. 1 second from any mode, control output OFF function works.
OFF
Once the control output OFF function is enabled, the function cannot be released even if the power to
the instrument is turned OFF and ON again. Control output OFF function keeps working. To cancel the
function, press the
• When Auto/Manual control function is selected in the
starts when the power to the controller is turned on. If the
manual control starts. If the
OUT
/
key again for approx. 1 second.
OFF
OUT
/
key is pressed again during manual control, the control reverts to
OFF
OUT
/
key function selection, automatic control
OFF
OUT
/
key is pressed again in this status,
OFF
automatic one. However, Auto/Manual function can be switched only in the PV/SV display mode.
Notice
When setting the specifications and functions of this controller, connect the terminals 2 and 3
for power source first, then set them referring to “5. Setup” before performing “3. Mounting to
control panel” and “4. Wiring connection”.
V1.1 • 05/2006 - 9 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
3.Mounting to control panel
3.1Site selection
This instrument is intended to be used under the following conditions (IEC61010-1):
Overvoltage category
Mount the controller in a place with:
(1) A minimum of dust, and an absence of corrosive gases
(2) No flammable, explosive gasses
(3) No mechanical vibrations or shocks
(4) No exposure to direct sunlight, an ambient temperature of 0 ... 50°C (32 ... 122°F) that does not
change suddenly
(5) An ambient non-condensing humidity of 35 ... 85%RH
(6) No large capacity electromagnetic switches or cables through which large current is flowing.
(7) No water, oil or chemicals or where the vapors of these substances can come into direct contact with
the unit
3.2 External dimension
• CS4H
• CS4L
, Pollution degree 2
Gasket AScrew type mounting bracket
96
48
11.598.5
(Fig. 3.2-1)
Gasket AScrew type mounting bracket
9611.598.5
(Fig. 3.2-2)
91
91
106.2
106.2
V1.1 • 05/2006 - 10 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
3.3 Panel cutout
• CS4H
0
+0.8
92
130
0
+0.8
92
n x 48-3
+0.5
0
Lateral close mounting, n: Number of units mounted
45
+0.5
0
Caution: When lateral close mounting is used for the controller,
IP66 specification is not fulfilled.
(Fig. 3.3-1)
• CS4L
+
130
n×96-3
0.5
0
+0.8
92
0
92
+ 0.8
0
Lateral close mounting, n: Number of units mounted
Caution: When lateral close mounting is used used for for the
Operating Instructions Temperature Indicating Controller CS4H / CS4L
3.5 Mounting (both CS4H and CS4L)
Warning
As the case is made of resin, do not use excessive force while screwing in the mounting bracket,
or the case could be damaged.
The torque is approximately 0.12 Nm.
To fulfill the Dust-proof/Drip-proof IP66 specification, mount this unit vertically and check the rigidity of the
panel where this unit is mounted. If rigidity is not enough, Dust-proof/Drip-proof IP66 specification may not
be guaranteed.
Mounting panel thickness: Within 1 ... 15 mm
Insert this unit from the front side of the panel. Attach the mounting brackets by the holes at the top and
bottom of the case and secure the controller in place with the screws.
Down
(Fig. 3.5-1)
Up
Up
Down
V1.1 • 05/2006 - 12 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
4. Wiring connection
Warning
Turn the power supply to the instrument off before wiring or checking.
Working or touching the terminal with the power switched on may result in Electric Shock
causing severe injury or death.
Moreover, the instrument must be grounded before the power supply to the instrument is
turned on.
4.1 Terminal arrangement
POWER
SUPPLY
24V AC/DC
2
3
GND
POWER
SUPPLY
100to240V AC
1
2
3
OUT1
4
5
6
NC
NO
3A
250V AC
A1
7
8
NO
3A
250V AC
P24
(Fig. 4.1-1)
24V DC
30mA
OUT2
/HB
9
10
NO
3A
250V AC
DC
mA
• OUT1 : Control output 1 (Heating)
• OUT2 : Control output 2 (Cooling)
• A1 : Alarm 1 output
• A2/LA : Alarm 2/Loop break alarm output
• HB : Heater burnout alarm output
• P24 : Transmitter supply output
• RS-485 : Serial communication (RS-485)
• SV2 : Second set value (external selection)
• CT : CT input
• TC : Thermocouple
• RTD : Resistance temperature detector
• DC : DC voltage (DC V) or DC current (DC mA)
• 50 Ω: Shunt resistor 50 Ω for input DC current
RS-485
50Ω
DC
YA (-)
YB (+)
SV2
SG
V
RTD
A2/LA
(HB)
CT
A
B
B
TC
11
12
13
14
15
16
17
18
19
20
NO
3A
250V AC
V1.1 • 05/2006 - 13 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
Caution
• The terminal blocks of the CS4H and CS4L are designed to be wired from the left side.
The lead wire must be inserted from the left side of the terminal, and fastened with the terminal screw.
• Dotted lines show options. If the option is not designated, there are no terminals.
• When A2 (option) and Heater burnout alarm (option) are applied together, use terminals 12-13 for A2,
and 9-10 for Heater burnout alarm.
• When Heating/Cooling control (option) and Heater burnout Alarm (option) are applied together, use
terminals 9-10 for the Heating/Cooling control and 12-13 for the Heater burnout alarm.
• When A2 (option) and LA (option) are applied, they use common output terminals.
• When Isolated power output (option) is applied, Heating/Cooling control (option) and Heater burnout
Alarm (option) cannot be applied with it.
Lead wire solderlessterminal
Use a solderless terminal with isolation sleeve that fits in the M3 screw as shown below.
Designate the torque 0.6 Nm to 1.0 Nm.
3.2mm3.2mm
5.8mm or less
(Fig. 4.1-2)
4.2 Wiring connection example
5.8mm or less
Caution
• Use a thermocouple and compensating lead wire according to the sensor input specifications of this controller.
• Use a 3-wire RTD system according to the sensor input specifications of this controller.
• This controller has no built-in power switch or fuse. It is necessary to install them in the circuit
near the external controller.
(Recommended fuse: Time-lag fuse, rated voltage AC 250V, rated current 2A)
• When using a AC/DC 24V for the power source, do not confuse the polarity when it is DC.
• When using a relay contact output type, use a relay according to the capacity of the load to protect the built-in relay contact.
• When wiring, keep input wires (thermocouple, RTD, etc.) away from AC sources or load wires to
avoid external interference.
• Use a thick wire (1.25 … 2.0 mm
2
) for the earth ground.
V1.1 • 05/2006 - 14 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
[Heater burnout alarm output]
(1) This alarm is not available for detecting
heater current under phase control.
15
CT input terminal
16
(2) Use current transformer (CT) provided,
and pass one lead wire of heater
circuit into the hole of the CT.
CT
Power source
(3) When wiring, keep CT wire away from
any AC sources and load wires to avoid
the external interference.
Heater
(Fig. 4.2-1)
[CS4H-R/M]
3-phase
Electro-
magnetic
switch
Alarm unit
Heater
Electric furnace
Thermocouple
(Fig. 4.2-2)
• To prevent the unit from harmful effects of unexpected high level noise, it is recommended that a
surge absorber be installed between the electromagnetic switch coils.
• AC or DC is available to supply voltage 24 V. Do not confuse the polarity when it is DC.
V1.1 • 05/2006 - 15 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
5. Setup
For the thermocouple and RTD inputs, the sensor input characters and temperature unit are indicated on the
PV display and the input range high limit value is indicated on the SV display for approximately 3 seconds
after the power is turned on (Table 5-1).
For DC input, the sensor input characters are indicated on the PV display and the scaling high limit value is
indicated on the SV display for approximately 3 seconds after the power is turned on (Table 5-1).
If any other value is set in the scaling high limit setting, the set value is indicated on the SV display.
During this time, all outputs and the LED indicators are in OFF status.
Control will then start and the input value will be indicated on the PV display and main setting value will be
indicated on the SV display. While control output OFF function is working,
play. To cancel control output OFF function, press the
OUT
/
key for approximately 1 second.
OFF
(Table. 5-1)
Sensor input
K
J
R
S
B
E
T
N
PL-
C (W/Re5-26)
Pt100
JPt100
4 … 20 mA DC
0 … 20 mA DC
0 … 1 V DC
0 … 5 V DC
1 … 5 V DC
0 … 10 V DC
PV display SV display PV display SV display
°C °F
Scaling high limit value
is indicated on the PV dis-
V1.1 • 05/2006 - 16 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
5.1 Setup flow chart
MODE
PV/SV display mode
OUT
/
OFF
(Approx. 1s)
Control output OFF
function [] (*1)
MODE(Approx. 3s)
MODE
▲+ MODE ▼+ MODE (Approx. 3s)
[Main setting mode] [Sub setting mode] [Auxiliary function setting mode1]
Output manipulated
variable
SV 1
AT setting/Auto-reset
[
]
setting [/]
Setting value lock
selection []
MODE MODE MODE
SV 2
OUT1 proportional
[
]
band setting [ ]
SV high limit setting
[]
MODE MODE MODE
OUT2 proportional
band setting [
SV low limit setting
]
[]
MODE MODE
Integral time setting
Sensor correction
[
]
setting []
MODE MODE
Derivative time setting
Communication
[
]
protocol []
MODE MODE
ARW setting
Instrument number
[
]
setting []
MODE MODE
OUT1 proportional
cycle setting [
Data transfer rate
]
selection []
MODE MODE
OUT2 proportional
cycle setting [
Heater burnout Alarm
]
setting [. ]
Parity selection
[]
MODE MODE MODE
A1 setting
Loop break Alarm
[
]
action time []
Stop bit selection
[]
MODE MODE MODE
A2 setting
Loop break alarm
[
]
action span []
MODE MODE
▲+ MODE: Press the MODE key, while the ▲ key is being pressed.
•
•
▼+ MODE (Approx. 3s): Press the MODE key for approx. 3s, while the ▼ key is being pressed.
•
▲+▼+ MODE (Approx. 3s): Press the MODE key for approx. 3s, while the ▲ and ▼ keys are being pressed.
• Dotted lines show options, which are indicated only when the options are applied.
(*1) If Auto/Manual control function is selected in the
OUT
/
key function selection, even though the
OFF
OUT
/
OFF
key is
pressed, control output OFF function does not work, but manual control is selected.
V1.1 • 05/2006 - 17 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
[Auxiliary function setting mode2]
▲+▼+ MODE (Approx. 3s)
Sensor selection
[
MODE
Scaling high limit setting
[
MODE MODE MODE
Scaling low limit setting
[
MODE MODE MODE
Decimal point place
selection [
MODE MODE MODE
PV filter time constant
setting [
MODE MODE MODE
OUT1 high limit setting
[
MODE MODE MODE
OUT1 low limit setting
[
MODE MODE MODE
OUT1 ON/OFF action
hysteresis setting [
MODE MODE MODE
OUT2 action mode
selection [
MODE MODE MODE
OUT2 high limit setting
[
MODE MODE
]
OUT2 low limit setting
]
Overlap/Dead band setting
]
OUT2 ON/OFF action
]
]
]
]
]
]
]
hysteresis setting []
A1 action selection
A2 action selection
A1 Energized/Deenergize
selection []
A2 Energized/Deenergized
selection []
A1 hysteresis setting
A2 hysteresis setting
[]
[]
[]
[]
[]
A1 action delayed timer set-
ting []
A2 action delayed timer set-
[]
Direct/ Reverse action
AT bias setting
SVTC bias setting
SV2 indication selection
Output status selection when
OUT/OFF key function
ting []
selection []
input burnout []
selection []
[]
[]
[ ]
V1.1 • 05/2006 - 18 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
5.2 Main setting mode
If the MODE key is pressed, main setting mode is selected.
The setting value (numeric value) can be increased or decreased by pressing the
▲ or ▼key.
If the MODE key is pressed, the setting value is registered and the controller will revert to the PV/SV
display mode.
SV1 [ ]
• Sets SV1.
• Setting range: SV low limit to SV high limit or
Scaling low limit value to Scaling high limit value
• Default: 0 °C
SV2 []
• Sets SV2.
• Setting range: SV low limit to SV high limit or
Scaling low limit value to Scaling high limit value
• Default: 0 °C
5.3 Sub setting mode
By pressing the MODE key while holding down the
▲ key, Sub setting mode can be selected.
The ▲ or ▼ key increases or decreases the setting value (numeric value).
By pressing the MODE key, setting value is registered and the next setting item is selected.
AT setting/ Auto-reset setting [/]
• Sets AT (Auto-tuning) or Auto-reset (offset correction).
• Auto-reset can be performed only during PD and P action.
(Not available for PID, PI and ON/OFF action)
• Default: Both Auto-tuning and Auto-reset Cancellation
[Auto-tuning]
• If the auto-tuning performance is designated, AT indicator blinks and the controller reverts to the
PV/SV display mode.
• After auto-tuning ends, AT indicator is turned off and P, I, D and ARW values are automatically
set.
• During auto-tuning, none of the settings can be performed.
• If the auto-tuning is released during the process, P, I, D and ARW values revert to their former
value.
OUT
/
• If the
OUT
/
OFF
key is pressed during auto-tuning, control output OFF function is activated, and if the
OFF
key is pressed again, PID auto-tuning is cancelled.
[Auto-reset]
• If the auto-reset is performed, offset correction immediately starts and the controller reverts to
the PV/SV display mode. (The corrected value is automatically set and AT indicator blinks)
• During 4 minutes of auto-reset performing, other settings cannot be performed to prevent key
misoperations.
• After auto-reset ends, AT indicator is turned off and all settings can be carried out.
OUT1 proportional band setting [ ]
• Sets OUT1 proportional band.
ON/OFF action when set to 0 or 0.0.
• Setting range: 0 … 1000 °C (0 … 2000 °F)
With a decimal point: 0.0 … 999.9 °C (0.0 … 999.9 °F)
DC input: 0.0 … 100.0 %
• Default: 10 °C
OUT2 proportional band setting []
• Sets OUT2 proportional band.
ON/OFF action when set to 0 or 0.0.
• Not available when 2. control output (option) is not applied or when OUT1 is ON/OFF action
• Setting range: 0.0 … 10.0 times (multiplying factor to OUT1 proportional band)
• Default: 1.0 times
V1.1 • 05/2006 - 19 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
Integral time setting [
]
• Sets the integral time.
Setting the value to 0 disables the function. (PD action)
• Not available when OUT1 is ON/OFF action
• Setting range: 0 … 1000 seconds
• Default: 200 seconds
Derivative time setting [ ]
• Sets the derivative time.
Setting the value to 0 disables the function. (PI action)
• Not available when OUT1 is ON/OFF action
• Setting range: 0 … 300 seconds
• Default: 50 seconds
ARW (Anti-reset windup) setting [ ]
• Sets the anti-reset windup.
• Available only for PID action
• Setting range: 0 … 100 %
• Default: 50 %
OUT1 proportional cycle setting [ ]
• Sets OUT1 proportional cycle.
Not available for ON/OFF action and DC current output type
• For the relay contact output type, if the proportional cycle time is decreased, the frequency
of the relay action increases and the life of the relay contact is shortened.
• Setting range: 1 … 120 seconds
• Default: 30 seconds for Relay contact output type,
3 seconds for Non-contact voltage output type
OUT2 proportional cycle setting []
• Sets OUT2 proportional cycle.
Not available for ON/OFF action and DC current output type
• Not available when 2. control output (option) is not added or when OUT2 is ON/OFF action
• Setting range: 1 … 120 seconds
• Default: 30 seconds for Relay contact output type,
3 seconds for Non-contact voltage output type
A1 setting []
• Sets the action point of A1 output.
Setting the value to 0 or 0.0 disables the function.
(Excluding process high alarm and process low alarm)
• Not available when No alarm action is selected in the A1 action selection
• Setting range: Refer to (Table 5.3-1).
• Default: 0 °C
A2 setting []
• Sets the action point of A2 output.
Setting the value to 0 or 0.0 disables the function.
(Excluding process high alarm and process low alarm)
• Not available when option [2AS] or [2AL] is not added or when No alarm action is selected in the
A2 action selection
• Setting range and default value are the same as those of A1 setting.
V1.1 • 05/2006 - 20 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
HB (Heater burnout alarm) setting [
and X.X are indicated in turn.]
• Sets the heater current value for Heater burnout alarm.
Setting the value to 0.0 disables the function.
• Available only when Heater burnout alarm (option) is added
• When OUT1 is OFF, heater current value shows the same value as when OUT1 was on.
• It is recommended to set approx. 80 % of the heater current value (setting value) considering the
voltage fluctuation.
• Self-holding is not available for the alarm output.
• Setting range: Rating 5 A: 0.0 … 5.0 A
Rating 10 A: 0.0 … 10.0 A
Rating 20 A: 0.0 … 20.0 A
Rating 50 A: 0.0 … 50.0 A
• Default: 0.0 A
LA (Loop break alarm) action time setting []
• Sets the action time to assess the Loop break alarm.
• Available only when option [2AR] or [2AL] is added
• Setting range: 0 … 200 minutes
• Default: 0 minutes
LA (Loop break alarm) action span setting []
• Sets the action span to assess the Loop break alarm.
• Available only when option [2AS] or [2AL] is added
• Setting range: 0 … 150 °C (°F), however, with a decimal point 0.0 … 150.0 °C (°F)
For DC input, 0 … 1500 (The placement of the decimal point follows the selection.)
• Default: 0 °C
[A1, A2 setting range]
(Table 5.3-1)
Alarm action Setting range
High limit alarm –Input span to Input span °C (°F) *1
Low limit alarm –Input span to Input span °C (°F) *1
High/Low limits alarm 0 to Input span °C (°F) *1
High/Low limit range alarm 0 to Input span °C (°F) *1
Process high alarm Input range low limit to Input range high limit*2
Process low alarm Input range low limit to Input range high limit*2
High limit alarm with standby –Input span to Input span °C (°F) *1
Low limit alarm with standby –Input span to Input span °C (°F) *1
High/Low limits alarm with standby 0 to Input span °C (°F) *1
• When the input has a decimal point, the negative low limit value is –199.9, and the positive high limit
value is 999.9.
*1: For DC input, the Input span is the same as the Input range scaling span.
*2: For DC input, Input range low (high) limit value is the same as the Input range scaling low (high)
limit value.
V1.1 • 05/2006 - 21 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
5.4 Auxiliary function setting mode 1
In the PV/SV display mode, if the MODE key is pressed while the
3 seconds, Auxiliary function setting mode 1 can be selected.
The setting value can be increased or decreased by pressing the
If the MODE key is pressed, the setting value is registered and the next setting item is selected.
Setting value lock selection []
• Mode to lock the setting value to prevent setting errors.
The setting item to be locked depends on the designation.
• When designating Lock, designate Lock 1, 2 or 3 after setting the necessary items in the status
Unlock.
• Selection item:
(Unlock): All setting values can be changed.
(Lock 1): None of setting values can be changed.
(Lock 2): Only main setting value can be changed.
(Lock 3): All setting values can be changed. However, do not change the setting
items in the Auxiliary function setting mode 2.
The changed value returns to the former value after the power is turned off
because the value is not written in the non-volatile memory.
Since it has no relation to the memory life, this is suitable when used with
WIKA programmable controller (with SVTC).
• Default: Unlock
SV high limit setting []
• Sets SV high limit.
• Setting range: SV low limit to input range high limit value
For DC input, SV low limit to scaling high limit value
(The placement of the decimal point follows the selection.)
• Default: Input range high limit value or scaling high limit value
SV low limit setting []
• Sets SV low limit.
• Setting range: Input range low limit value to SV high limit
For DC input: Scaling low limit value to SV high limit
(The placement of the decimal point follows the selection.)
• Default: Input range low limit value or scaling low limit value
Sensor correction setting []
• Sets the sensor correction value.
(Effective within the input rating value regardless of the sensor correction value)
• Setting range: –100.0 … 100.0 °C (°F)
For DC input: –1000 … 1000
(The placement of the decimal point follows the selection.)
• Default: 0.0°C
Communication protocol selection []
• Selects communication protocol of this instrument.
• Available only when the option Serial interface [CR5] is applied
• Selection item:
• Default: WIKA protocol
Instrument number setting []
• Sets the instrument number of this unit. (The instrument number should be set individually when
communicating by connecting plural instruments in serial communication, otherwise it is impossible to communicate)
• Available only when the option Serial interface [CR5] is applied
Operating Instructions Temperature Indicating Controller CS4H / CS4L
Data transfer rate selection [
]
• Selects the data transfer rate of this unit. (The data transfer rate of this unit must be equal to the
rate of the host computer, otherwise it is impossible to communicate)
• Available only when the option Serial interface [CR5] is applied
• Selection items:
(2400 bps)
(4800 bps)
(9600 bps)
(19200 bps)
• Default: 9600 bps
Parity selection []
• Selects the parity of this unit.
• Not available when the option Serial interface [CR5] is not applied or when WIKA protocol is
selected in the Communication protocol selection
• Selection item:
(WIKA protocol)
(Modbus RTU mode)
(Modbus ASCII mode)
• Default: WIKA protocol
Stop bit selection []
• Selects the stop bit of this unit.
• Not available when the option Serial interface [CR5] is not applied or when WIKA protocol is
selected in the Communication protocol selection
• Selection item:
(1)
(2)
• Default: 1
V1.1 • 05/2006 - 23 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
5.5 Auxiliary function setting mode 2
In the PV/SV display mode, if the MODE key is pressed while the
approx. 3 seconds, Auxiliary function setting mode 2 can be selected.
The setting value can be increased or decreased by pressing the
If the MODE key is pressed, the setting value is registered and the next setting item is selected.
If Lock 3 is selected in the Setting value lock selection, release Lock 3 to Unlock, and then change
each setting value in the Auxiliary function setting mode 2.
▲ and ▼ keys are being pressed for
▲ or ▼ key.
Sensor selection [
• An input type from thermocouple (10 types), RTD (2 types), DC current (2 types),
DC voltage (4 types) and the unit °C/°F can be selected.
• When changing the input from DC voltage to other inputs, remove the sensor con-
nected to this controller, then change for the input. If the input is changed with the
sensor connected, the input circuit may be broken.
• Default: K (–200 … 1370 °C)
Input type Input range
K
J
R
S
B
E
T
N
PL-
C(W/Re5-26)
Pt100
Pt100
JPt100
JPt100
4 … 20 mA DC
0 … 20 mA DC
0 … 1 V DC
0 … 5 V DC
1 … 5 V DC
0 … 10 V DC
Scaling high limit setting []
• Sets scaling high limit value.
• Available only for the DC input
• Setting range: Scaling low limit value to Input range high limit value
(The placement of the decimal point follows the selection.)
• Default: 9999
Scaling low limit setting []
• Sets scaling low limit value.
• Available only for the DC input
• Setting range: Input range low limit value to scaling high limit value
(The placement of the decimal point follows the selection.)
Operating Instructions Temperature Indicating Controller CS4H / CS4L
Decimal point place selection [
]
• Selects the decimal point place.
• Available only for DC input
• Selection item:
(No decimal point)
(1 digit after the decimal point)
(2 digits after the decimal point)
(3 digits after the decimal point)
• Default: No decimal point
PV filter time constant setting []
• Sets PV filter time constant.
However, if the setting value is too large, it affects to the control result due to the delay of re-
sponse.
• Setting range: 0.0 … 10.0 seconds
• Default: 0.0 seconds
OUT1 high limit setting []
• Sets the high limit value for OUT1.
Not available for ON/OFF action
• Setting range: OUT1 low limit value to 100 % (Control output Relay or Logic level DC 0/12 V)
OUT1 low limit value to 105 % (Control output Analogue current
signal (4 ... 20 mA))
• Default: 100 %
OUT1 low limit setting []
• Sets low limit value for OUT1.
Not available for ON/OFF action
• Setting range: 0 % to OUT1 high limit value (Control output Relay or Logic level DC 0/12 V)
–5 % to OUT1 high limit value (Control output Analogue current
signal (4 ... 20 mA))
• Default: 0 %
OUT1 ON/OFF action hysteresis setting []
• Sets ON/OFF action hysteresis for OUT1.
Available only for ON/OFF action
• Setting range: 0.1 … 100.0 °C (°F) For DC input, 1 … 1000 (the placement of the
decimal point follows the selection)
• Default: 1.0 °C
OUT2 action mode selection []
• Selects OUT2 cooling action from air cooling, oil cooling and water cooling.
Not available when 2. control output (option) is not added or when OUT2 is ON/OFF action
• Selection item:
(Air cooling, linear characteristic)
(Oil cooling, 1.5th power of the linear characteristic)
(Water cooling, 2nd power of the linear characteristic)
• Default: Air cooling
OUT2 high limit setting []
• Sets the high limit value for OUT2.
• Not available when 2. control output (option) is not added or when OUT2 is ON/OFF action
• Setting range: OUT2 low limit value to 100 % (2. control output Relay or Logic level DC 0/12 V)
OUT2 low limit value to 105 % (2. control output Analogue current
signal (4 ... 20 mA))
• Default: 100 %
OUT2 low limit setting []
• Sets the low limit value for OUT2.
• Not available when 2. control output (option) is not added or when OUT2 is ON/OFF action
• Setting range: 0 % to OUT2 high limit value (2. control output Relay or Logic level DC 0/12 V)
–5 % to OUT2 high limit value (2. control output Analogue current
signal (4 ... 20 mA))
• Default: 0 %
V1.1 • 05/2006 - 25 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
Overlap band/Dead band setting [
]
• Sets Overlap band/Dead band for OUT1 and OUT2.
+ setting value: Dead band
– setting value: Overlap band
• Not available for ON/OFF action or when 2. control output (option) is not added
• Setting range: –100.0 … 100.0 °C (°F)
for DC input, 1 … 1000
(the placement of the decimal point follows the selection)
• Default: 0.0 °C
OUT2 ON/OFF action hysteresis setting []
• Sets ON/OFF hysteresis for OUT2.
• Available only when 2. control output (option) is added
• Setting range: 0.1 … 100.0°C (°F)
For DC input, 1 … 1000
(the placement of the decimal point follows the selection)
• Default: 1.0 °C
A1 action selection []
• Selects A1 action.
• Selection item:
No alarm action :
High limit alarm :
Low limit alarm :
High/Low limits alarm :
High/Low limit range alarm :
Process high alarm : Process low alarm : High limit alarm with standby :
Low limit alarm with standby :
High/Low limits alarm with standby :
• Default: No alarm action
A2 action selection []
• Selects A2 action.
• Available only when option [2AS] or [2AL] is added
• Selection item, default value are the same as those of A1 action selection.
A1 action Energized/Deenergized selection []
• Selects A1 action Energized/Deenergized.
• Not available when No alarm action is selected in the A1 action selection
• Not available when No alarm action is selected in the A2 action selection or when
option [2AS] or [2AL] is not added
• Selection item and default value are the same as those of A1 action Energized/
Deenergized selection.
A1 hysteresis setting []
• Sets A1 hysteresis.
• Not available when No alarm action is selected in the A1 action selection
• Setting range: 0.1 … 100.0 °C (°F)
For DC input, 1 … 1000
(the placement of the decimal point follows the selection)
• Default: 1.0 °C
A2 hysteresis setting []
• Sets A2 hysteresis.
• Not available when No alarm action is selected in the A2 action selection or when option [2AS] or
[2AL] is not added
• Setting range and default value are the same as those of A1 hysteresis setting.
V1.1 • 05/2006 - 26 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
A1 action delayed timer setting [
]
• Sets the action delayed timer for A1.
When setting time has passed after the input enters the alarm output range, the alarm is activated.
• Not available if No alarm action is selected in the A1 action selection
• Setting range: 0 … 9999 seconds
• Default: 0 seconds
A2 action delayed timer setting []
• Sets the action delayed timer for A2.
When setting time has passed after the input enters the alarm output range, the alarm is activated.
• Not available if No alarm action is selected in the A2 action selection or if option [2AS] or [2AL] is
not applied
• Setting range and default value are the same as those of A1 action delayed timer setting.
Direct/Reverse action selection []
• Selects Reverse (Heating) or Direct (Cooling) action.
• Selection item:
(Reverse)
(Direct)
• Default: Reverse (Heating)
AT bias setting []
• Sets the bias value when PID auto-tuning is performing.
• Not available for the DC input
• Setting range: 0 … 50 °C (0 … 100 °F)
With a decimal point, 0.0 … 50.0 °C (0.0 … 100.0 °F)
• Default: 20 °C
SVTC bias setting []
• Control desired value adds SVTC bias value to the value received by the SVTC command.
• Available only when the serial interface (option) is added
• Setting range: Converted value of ±20 % of the rated value or ±20 % of the scaling span (DC
input) (the placement of the decimal point follows the selection.)
However, the negative minimum value is –1999, –199.9, –19.99 or –1.999.
• Default: 0
SV2 indication selection [ ]
• Selects whether SV2 is indicated or not.
• Available only when serial interface (option) is added
• Selection item:
(Indication)
(No indication)
• Default: Indication
Output status selection when input burnout []
• Selects output status when input is burnt out.
Available only for control output analogue current signal (4 ... 20 mA) with DC inputs
• Selection item:
(Output OFF)
(Output ON)
• Default: Output OFF
OUT/OFF key function selection []
• Selects the
• Selection item:
OUT
/
key function.
OFF
(OUT/OFF function)
(Auto/Manual control function)
• Default: OUT/OFF function
V1.1 • 05/2006 - 27 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
[Sensor correction function]
This corrects the input value from the sensor.
When a sensor cannot be set at a location where control is desired, the sensor measuring temperature
may deviate from the temperature in the controlled location.
When controlling with plural controllers, sometimes the temperatures measured (input value) do not
concur with the same setting value due to difference in sensor accuracy or dispersion of load capacities.
In such a case, the control can be set at the desired temperature by adjusting the input value of sensors.
However, it is effective within the input rating range regardless of the sensor correction value.
[Loop break alarm]
The alarm will be activated when the process variable (PV) does not rise as much as the span or greater
within the time it takes to assess the loop break alarm after the manipulated variable has reached 100 %
or the output high limit value.
The alarm will also be activated when the process variable (PV) does not fall as much value as the span
or greater within the time it takes to assess loop break alarm after the manipulated variable has reached
0 % or the output low limit value.
When the control action is Direct (Cooling), read “fall” for “rise” and vice versa.
[Energized/Deenergized]
When alarm action energized is selected, the alarm output (between terminals 7-8, or 12-13) is conducted
(ON) while the alarm output indicator is lit.
The alarm output is not conducted (OFF) while the alarm output indicator is not lit. See (Fig. 5.5-1).
When alarm action deenergized is selected, the alarm output (between terminals 7-8, or 12-13) is not
conducted (OFF) while the alarm output indicator is lit.
The alarm output is conducted (ON) while the alarm output indicator is not lit. See (Fig. 5.5-2).
A1 hysteresis
A1 hysteresis
ON
ON
OFF
High limit alarm (when Energized is set) High limit alarm (when Deenergized is set)
SV setting+ A1 set point
OFF
SV setting
+ A1 set point
(Fig. 5.5-1) (Fig. 5.5-2)
[SV1/SV2 external selection]
SV1 or SV2 can be selected by the external operation.
Terminals between 14 and 17 open: SV1 can be selected.
Terminals between 14 and 17 closed: SV2 can be selected.
SV1 or SV2 cannot be changed during setting mode or PID auto-tuning.
V1.1 • 05/2006 - 28 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
5.6 Control output OFF function
Control output OFF function [
]
• A function to pause the control action or turn the control output of the unused instrument of the
plural units OFF even if the power to the instrument is supplied.
] is indicated on the PV display while the function is working.
[
• Pressing the
Pressing the
OUT
/
key for approx. 1 second from any mode turns the control output OFF.
OFF
OUT
/
key again for approx. 1 second cancels the control output OFF function.
OFF
• Once the control output OFF function is enabled, the function cannot be released even if the
power to the instrument is turned OFF and ON again.
OUT
To cancel the function, press the
/
OFF
5.7 Auto/Manual control function
PV/SV display mode (Manual control)
• To use manual control function, Auto/Manual control function must be selected in the
function selection.
OUT
/
First, press the
manipulated variable (MV) using the
key. Control can be performed by increasing or decreasing the output
OFF
▲ or ▼ key.
• The 1st decimal point from the right on the SV display blinks.
OUT
/
• By pressing the
key again, the mode reverts to the PV/SV display (automatic control)
OFF
mode. Whenever the power to the controller is turned on, automatic control starts.
• If control action is switched from automatic to manual or vice versa, balanceless-bumpless
function works to prevent sudden change of manipulated variable.
• If Auto/Manual control function is selected, control output OFF function is disabled.
5.8 Output manipulated variable indication
key again for approx. 1 second.
OUT
/
OFF
key
Output manipulated variable indication
• Output manipulated variable is indicated on the SV display by pressing the MODE key for approx.
3 seconds in the PV/SV display mode.
While output manipulated variable is being indicated, the 1st decimal point from the right on the
SV display blinks at a cycle of every 0.5 second. When the MODE key is pressed again, the mode
reverts to the PV/SV display.
V1.1 • 05/2006 - 29 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
6. Running
After the controller has been mounted to the control panel and wiring is completed, it can be started in the
following manner.
(1) Turn the power supply to the CS4H, CS4L ON.
For thermocouple and RTD inputs, for approx. 3 seconds after the power is switched ON, sensor input
character and temperature unit are indicated on the PV display, and the input range high limit value is
indicated on the SV display.
See (Table 6-1).
For the DC input, for approx. 3 seconds after the power is switched ON, sensor input character is indicated on the PV display, and the scaling high limit value is indicated on the SV display.
See (Table 6-1).
However, if the scaling high limit value has been changed in the Scaling high limit setting, the changed
value is indicated on the SV display. (During this time, all outputs and the LED indicators are in OFF
status)
After that, the process variable is indicated on the PV display, and SV1 or SV2 is indicated on the SV di
splay and the control starts.
(When the Control output OFF function is working, [
(Table 6-1)
Sensor input
K
PV display SV display PV display SV display
°C °F
J
R
S
B
E
T
N
PL-
C (W/Re5-26)
Pt100
JPt100
4 … 20 mA DC
0 … 20 mA DC
0 … 1 V DC
0 … 5 V DC
Scaling high limit value
1 … 5 V DC
0 … 10 V DC
] is indicated on the PV display)
(2) Input each setting value.
Input each setting value, referring to “5. Setup”.
(3) Turn the load circuit power ON.
Starts the control action so as to keep the controlled object at the main setting value.
V1.1 • 05/2006 - 30 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
7. Action explanation
7.1 OUT1 action
Control action
ON
Heating (reverse) actionCooling (direct) action
Proportional band
Proportional band
ON
R/
S/
A/
Indication
(OUT1) Green
: Acts ON (lit) or OFF (unlit).
OFF
SV setting
4
H
5
C
6
L
Cycle action is performed according to deviation.
5
+
12V DC
6
-
Cycle action is performed according to deviation.
5
+
20mA DC
6
Changes continuously according to deviation.
Lit
4
H
5
C
6
L
5
+
12/0V DC
6
5
+
20 to 4mA DC
6
4
H
5
C
6
L
5
+
0V DC
6
5
+
4mA DC
6
SV setting
4
H
5
C
6
L
Cycle action is performed according to deviation.
5
+
0V DC
6
Cycle action is performed according to deviation.
5
+
4mA DC
6
Changes continuously according to deviation.
4
H
5
C
6
L
5
+
0/12V DC
6
5
+
4 to 20mA DC
6
4
H
5
C
6
L
5
+
12V DC
6
5
+
20mA DC
6
OFF
LitUnlitUnlit
7.2 Heater burnout alarm action (option)
Heater burnout
alarm action
Heater burnout
alarm output
Indication
(HB) red
ON
OFF
Heater burnout alarm set point
Small
Load current
9
10
LitUnlit
Large
9
10
When the 2. control output (option) is applied, terminals 12 and 13 are used for the Heater burnout alarm.
V1.1 • 05/2006 - 31 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
7.3 OUT1 ON/OFF action
Control action
Indication
(OUT1) Green
S/
A/
R/
ON
OFF
4
H
5
C
6
L
5
+
12V DC
6
5
+
20mA DC
6
Lit
Heating (reverse) action
Hysteresis
SV setting
Cooling (direct) action
Hysteresis
SV setting
4
H
5
C
6
L
5
+
0V DC
6
5
+
4mA DC
6
UnlitLit
H
C
L
+
+
Unlit
4
5
6
5
0V DC
6
5
4mA DC
6
4
H
5
C
6
L
5
+
12V DC
6
5
+
20mA DC
6
ON
OFF
: Acts ON (lit) or OFF (unlit).
V1.1 • 05/2006 - 32 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
Operating Instructions Temperature Indicating Controller CS4H / CS4L
When setting Dead band
Control action
R/
DR
S/
Heating P-band
ON
Heatng
action
OFF
SV setting
4
H
5
C
6
L
Cycle action is performed according to deviation.
4
H
5
C
6
L
Dead band(Cooling P-band)
4
H
5
C
6
L
9
10
Cycle action is performed according to deviation.
5
+
12V DC
6
Cycle action is performed according to deviation.
5
+
12/0V DC
6
5
+
6
0V DC
10
ON
(Cooling
action)
OFF
9
9
10
Indication
(OUT1) Green
Indication
(OUT2) Yellow
DS
5
+
A/
DA
: Acts ON (lit) or OFF (unlit).
: Represents Heating control action.
: Represents Cooling control action.
20mA DC
6
Changes continuously according to deviation.
Lit
Unlit
20 to 4mA DC
9
+
0V DC
10
Cycle action is performed according to deviation.
5
+
6
+
+
5
4mA DC
6
9
4mA DC
10
Changes continuously according to deviation.
9
+
0/12V DC
10
9
+
4 to 20mA DC
10
9
+
12V DC
10
9
+
20mA DC
10
Unlit
Lit
V1.1 • 05/2006 - 34 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
When setting Overlap band with Relay contact output.
Control action
R/
Indication
(OUT1) Green
Indication
(OUT2) Yellow
Heating P-band
ON
Heating
action
OFF
4
H
5
C
6
L
Cycle action is performed according to deviation.
9
DR
Cycle action is performed according to deviation.
Lit
Unlit
: Acts ON (lit) or OFF (unlit).
: Represents Heating control action.
: Represents Cooling control action.
10
Cooling P-band
Overlap
band
SV setting
4
H
5
C
6
L
9
10
H
C
L
ON
(Cooling
action)
OFF
4
5
6
9
10
Unlit
Lit
V1.1 • 05/2006 - 35 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
7.5 A1 and A2 actions
High limit alarmLow limit alarm
A1 hysteresis
ON
Alarm action
A1 hysteresis
ON
Alarm output
Alarm action
Alarm output
Alarm action
OFF
+ side
side
ON
OFF
OFF
Alarm
set point
High/Low limits alarmHigh/Low limit range alarm
Alarm
set point
Process high alarmProcess low alarm
ON
OFF
Setting
A1 hysteresis
Setting
A1 hysteresis
Alarm
set point
+ Alarm
set point
Alarm
set point
+ side
side
ON
OFF
Alarm
set point
ON
OFF
Alarm
set point
A1 hysteresis
Alarm
set point
Setting
Setting
+ Alarm
set point
A1 hysteresis
Alarm
set point
Alarm output
High limit alarm with standbyLow limit alarm with standby
Alarm action
Alarm output
ON
OFF
+ side
side
Alarm
set point
Setting
A1 hysteresis
+ Alarm
set point
+ side
V1.1 • 05/2006 - 36 -
: A1 output terminals between 7 and 8 is ON.
: A1 output terminals between 7 and 8 is ON or OFF.
: A1 output terminals between 7 and 8 is OFF.
: Standby functions.
ON
OFF
side
Alarm
set point
A1 hysteresis
Setting
+ Alarm
set point
Operating Instructions Temperature Indicating Controller CS4H / CS4L
High/Low limits alarm with standby
A1 hysteresis
ON
Alarm action
Alarm output
OFF
set point
A1
SV setting
A1
set point
: A1 output terminals between 7 and 8 is ON.
: A1 output terminals between 7 and 8 is ON or OFF.
: A1 output terminals between 7 and 8 is OFF.
: Standby functions.
For A2 output, terminals 12 and 13 are used.
A1 and A2 indicators light up when between the output terminals is ON, and goes out when between them
is OFF.
7.6 SV1/SV2 external selection action
SV1/SV2
external
selection
Indication
Green
SV1SV2
14
17
SV1
Lit
SV2SV1
Unlit
14
17
SV2
LitUnlit
If the serial communication is applied, this function is disabled.
8. Control action explanations
8.1 PID
(1) Proportional band (P)
Proportional action is the action which the control output varies in proportion to the deviation between
the setting value and the processing temperature.
If the proportional band is narrowed, even if the output changes by a slight variation of the processing
temperature, better control results can be obtained as the offset decreases.
However, if the proportional band is narrowed too much, even slight disturbances may cause variation
in the processing temperature, control action changes to ON/OFF action and the so called hunting
phenomenon occurs.
Therefore, when the processing temperature comes to the balanced position near the setting value and
a constant temperature is maintained, the most suitable value is selected by gradually narrowing the
proportional band while observing the control results.
(2) Integral time (I)
Integral action is used to eliminate offset. When the integral time is shortened, the returning speed to the
setting point is accelerated. However, the cycle of oscillation is also accelerated and the control becomes unstable.
(3) Derivative time (D)
Derivative action is used to restore the change in the processing temperature according to the rate of
change. It reduces the amplitude of overshoot and undershoot width.
If the derivative time is shortened, restoring value becomes small, and if the derivative time is made
longer, an excessive returning phenomenon may occur and the control system may be oscillated.
V1.1 • 05/2006 - 37 -
p
Operating Instructions Temperature Indicating Controller CS4H / CS4L
8.2 PID auto-tuning of this controller
In order to decide each value of P, I, D and ARW automatically, this system forcibly fluctuates the object
being controlled.
(1) When the difference between the setting value and processing temperature is large as the
temperature rises.
Fluctuation is applied at the temperature 20 °C lower than the setting value.
Setting
value
Temperature 20 °C (°F) lower than the setting value
(4)
(1) Calculating PID con-
stant
(2) PID constant
calculated
(3) Controlled by the PID
Temperature
constant set by auto-
tuning.
(4) AT bias value
AT starting point
(1)
(2)(3)
Time
(Fig. 8.2-1)
(2) When the control is stable or when control temperature is within ±20 °C (°F) of setting value.
Fluctuation is applied at the setting value.
(1) Calculating PID con-
Setting
value
stant
(2) PID constant
calculated
Temperature
(3) Controlled by the PID
constant set by
auto-tuning.
AT starting point
(1)
(2)
Time
(3)
(Fig. 8.2.2)
(3) When the control temperature is 20 °C (°F) or higher than the setting value.
Fluctuation is applied at the temperature 20 °C (°F) higher than the setting value.
erature 20 °C(°F) higher than the setting value
Te m
Temperature
(1) Calculating PID const
ant
Setting
value
(4)
(2) PID constant calculat
ed
(3) Controlled by the PID
constant set by auto-t
AT starting point
Time
uning.
(4) AT bias value
(1)
(2)
(3)
(Fig. 8.2.3)
V1.1 • 05/2006 - 38 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
8.3 Auto-reset (offset correction)
Auto-reset is performed to correct the offset at the point at which PV indication is stabilized within the
proportional band during the PD action.
Since the corrected value is internally memorized, it is not necessary to perform the auto-reset
long as the process is the same.
However, when the proportional band is set to 0, the corrected value is cleared.
Auto-reset is performed
Setting
value
Offset span
Temperature
Offset is corrected
again as
(Fig. 8.3-1)
Time
V1.1 • 05/2006 - 39 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
CS4H PV display : Red LED 4 digits, character size, 11.2 x 5.4 (H x W) mm
SV display : Green LED 4 digits, character size, 11.2 x 5.4 (H x W) mm
CS4L PV display : Red LED 4 digits, character size, 18 x 8 (H x W) mm
SV display : Green LED 4 digits, character size, 12.6 x 6(H x W) mm
Input
Thermocouple : K, J, R, S, B, E, T, N, PL- , C (W/Re5-26)
RTD : Pt100, JPt100, 3-wire system
Allowable input lead wire resistance, 10
DC current : 0 … 20 mA DC, 4 … 20 mA DC
Input impedance, 50
[50
between input terminals]
Allowable input current 50 mA or less
[If 50
DC voltage : 0 … 1 V DC
Input impedance, 1 M
Allowable input voltage 5 V or less
Allowable signal source resistance 2 k
0 … 5 V DC, 1 … 5 V DC, 0 … 10 V DC,
Input impedance, 100 k
Allowable input voltage 15 V or less
Allowable signal source resistance 100
: Flush
External resistance, 100
however, for B, 40
Ω Shunt resistor (sold optionaly) must be connected
Ω or less,
Ω or less
Ω
Ω Shunt resistor (sold optionaly) is used]
Ω or greater
Ω or less
Ω or greater
Ω or less per wire
Ω or less
Rated input
4 ... 20 mA DC
0 ... 20 mA DC
0 ... 1 V DC
0 ... 5 V DC
1 ... 5 V DC
0 ... 10 V DC
*1: For DC input, input range and decimal point place are changeable.
*2: 50
Input type Input range Resolution
K
J
–200 ... 1370 °C –320 ... 2500 °F 1 °C (°F)
–199.9 ... 400.0 °C –199.9 ... 750.0 °F 0.1 °C (°F)
–200 ... 1000 °C –320 ... 1800 °F 1 °C (°F)
R 0 ... 1760 °C 0 ... 3200 °F 1 °C (°F)
S 0 ... 1760 °C 0 ... 3200 °F 1 °C (°F)
B 0 ... 1820 °C 0 ... 3300 °F 1 °C (°F)
E
–200 ... 800 °C –320 ... 1500 °F 1 °C (°F)
T –199.9 ... 400.0 °C –199.9 ... 750.0 °F 0.1 °C (°F)
N –200 ... 1300 °C –320 ... 2300 °F 1 °C (°F)
PL- 0 ... 1390 °C 0 ... 2500 °F 1 °C (°F)
C(W/Re5-26) 0 ... 2315 °C 0 ... 4200 °F 1 °C (°F)
Pt100
JPt100
–199.9 ... 850.0 °C –199.9 ... 999.9 °F 0.1 °C (°F)
–200 ... 850 °C –300 ... 1500 °F 1 °C (°F)
–199.9 ... 500.0 °C –199.9 ... 900.0 °F 0.1 °C (°F)
–200 ... 500 °C –300 ... 900 °F 1 °C (°F)
–1999 ... 9999 *1 *2 1
–1999 ... 9999 *1 1
Ω Shunt resistor (sold optionally) must be connected between input terminals.
V1.1 • 05/2006 - 40 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
Accuracy (Setting, indication)
Thermocouple : Within ±0.2 % of input range full scale ±1 digit or
within ±2 °C (4 °F), whichever is greater
However, R, S inputs, 0 … 200 °C (0 … 400 °F): Within ±6 °C (12 °F)
B input, 0 … 300 °C (0 … 600 °F): Accuracy is not guaranteed.
K, J, E, T, N inputs, less than 0 °C (32 °F): Within ±0.4 % of input
range full scale ±1 digit
RTD : Within ±0.1 % of input range full scale ±1 digit or
within ±1 °C (2 °F), whichever is greater
DC Voltage and Current:
Within ±0.2 % of input range full scale ±1digit
Input sampling period : 0.25 seconds
Control output (OUT1)
Relay contact : Control capacity, 3 A, 250 V AC (resistive load)
1 A, 250 V AC (inductive load cos ø = 0.4)
Electrical life 100,000 times
Logic level DC 0/12 V for solid state relay:
12
+ 2
V DC maximum 40 mA (short circuit protected)
- 0
Analogue current signal : 4 … 20 mA DC
Load resistance, maximum 550
Ω
A1 output
When A1 action is set as energized, the alarm action point is set by ±deviation to the main setting
(except Process alarm).
When the input exceeds the range, the output turns ON or OFF (in the case of High/Low limit
range alarm).
When the alarm action is set as deenergized, the output acts conversely.
Setting accuracy : The same as the Indicating accuracy
Action : ON/OFF action
Hysteresis : Thermocouple and RTD inputs, 0.1 … 100.0 °C (°F)
DC current and DC voltage inputs, 1 … 1000
(The placement of the decimal point follows the selection)
Output : Relay contact 1a
Control capacity 3 A, 250 V AC (resistive load)
Electrical life 100,000 times
Control action
• PID action (with auto-tuning function)
• PI action: When derivative time is set to 0
• PD action (with auto-reset function): When integral time is set to 0
• P action (with auto-reset function): When integral and derivative times are set to 0
• ON/OFF action
OUT1 proportional band (P):
Thermocouple, 0 ... 1000°C (0 ... 2000°F)
RTD, 0.0 ... 999.9°C (0.0 ... 999.9°F)
DC current and voltage, 0.0 ... 100.0%
(ON/OFF action when set to 0°C (°F), 0.0°C (°F) or 0.0%)
Integral time (I) : 0 ... 1000 s (off when set to 0)
Derivative time (D) : 0 ... 300 s (off when set to 0)
OUT1 proportional cycle : 1 ... 120 s (Not available for control output analogue current signal)
ARW : 0 ... 100 %
OUT1 hysteresis : Thermocouple and RTD inputs, 0.1 ... 100.0 °C (°F)
DC current and voltage inputs, 1 ... 1000
(The placement of the decimal point follows the selection)
SV1/SV2 external selection: SV1 and SV2 can be selected by external contact.
Contact open between terminals 14 and 17 : SV1
Contact closed between terminals 14 and 17 : SV2
Contact current: 6mA
V1.1 • 05/2006 - 41 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
Supply voltage : 100 ... 240 V AC 50/60Hz or
24 V AC/DC 50/60Hz
Allowable voltage fluctuation range
100 ... 240 V AC : 85 ... 264 V AC
24 V AC/DC : 20 ... 28V AC/DC
Ambient temperature : 0 ... 50 °C (32 ... 122 °F)
Ambient humidity : 35 ... 85 %RH (no condensation)
Power consumption
: Approx. 8 VA or 8 W
Circuit Isolation configuration
Ground
1
2
Power
source
3
A2 output, Heater
burnout alarm output
or Look break alarm
output
12
13
11
Communication
14
D
17
SV2
14
C
17
4
5
OUT1
6
7
A1 output
8
A
Isolation
CT input
15
16
18
alarm output or
10
Insulated power output
B
OUT2, Heater burnout
9
Input
19
20
• When OUT1 is Logic level DC 0/12 V or Analogue current signal (4 ... 20 mA) and OUT2 is Logic level
DC 0/12 V or Analogue current signal (4 ... 20 mA), between A to B is non-isolated.
• When OUT1 is Logic level DC 0/12 V or Analogue current signal (4 ... 20 mA), between A to C and A
to D are non-isolated.
When OUT2 is Logic level DC 0/12 V or Analogue current signal (4 ... 20 mA), between B to C and B
to D are non-isolated.
Isolation resistance
10 MΩ or greater at 500 V DC for other combinations except the above mentioned
Dielectric strength
Between input terminal and ground terminal, 1.5 kV AC for 1 minute
Between input terminal and power terminal, 1.5 kV AC for 1 minute
Between output terminal and ground terminal, 1.5 kV AC for 1 minute
Between output terminal and power terminal, 1.5 kV AC for 1 minute
Between power terminal and ground terminal, 1.5 kV AC for 1 minute
Mass : CS4H (approx. 250 g), CS4L, (approx. 370 g)
External dimension : CS4H, 48 x 96 x 100 mm (W x H x D)
CS4L, 96 x 96 x 100 mm (W x H x D)
Material : Case, Flame resistant resin
Color : Case, black
Drip-proof/Dust-proof : IP66 for the front part
V1.1 • 05/2006 - 42 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
Attached functions
[Sensor correction function]
[Setting value lock function]
[Input burnout indication]
• For thermocouple or RTD input, if the input value exceeds the Indication range high limit value, the
PV display blinks “
display blinks ”
” and if the input value exceeds Indication range low limit value, the PV
”.
If the input value exceeds the Control range, OUT1 and OUT2 are turned OFF (for control output
Analogue current signal (4 ... 20 mA), OUT1 low limit value, OUT2 low limit value).
(However, for manual control, it outputs the preset manipulated variable)
Input Input range Indication range Control range
K,T
R,S
PL-
C(W/Re5-26)
–199.9 ... 400.0 °C –199.9 ... 450.0 °C –205.0 ... 450.0 °C
• For DC current and voltage inputs, if the input value exceeds the Indication range high limit value,
the PV display blinks “
PV display blinks “
” and if the input value exceeds Indication range low limit value, the
”.
If the input value exceeds the Control range, OUT1 and OUT2 are turned ON or OFF which has
been selected in [Output status selection when input burnout] (for control output Analogue current
signal (4 ... 20 mA), OUT1 high or low limit value, OUT2 high or low limit value).
(However, for manual control, it outputs the preset manipulated variable)
Indication range : [Scaling low limit value – Scaling span x 1 %] to
[Scaling high limit value + Scaling span x 10 %]
However, if the input value exceeds the range –1999 ... 9999,
the PV display blinks “
” or “”.
Control range : [Scaling low limit value – Scaling span x 1 %] to
[Scaling high limit value + Scaling span x 10 %]
•
DC input burnout: When DC input is burnt out, PV display blinks “” for 4 ... 20 mA DC
and 1 ... 5 V DC inputs, and “
” for 0 ... 1 V DC input.
For 0 ... 20 mA DC, 0 ... 5 V DC and 0 ... 10 V DC inputs, the PV display
indicates the corresponding value for which 0 mA or 0 V is inputted.
V1.1 • 05/2006 - 43 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
[Burnout]
When the thermocouple or RTD input is burnt out, OUT1 is turned off (for control output Analogue
current signal (4 ... 20 mA), OUT1 low limit value) and the PV display blinks “
[Self-diagnosis]
The CPU is monitored by a watchdog timer, and when any abnormal status is found on the CPU,
the controller is switched to warm-up status.
[Automatic cold junction temperature compensation] (Thermocouple input type)
This detects the temperature at the connecting terminal between thermocouple and the instrument,
and always keeps it on the same status as when the reference junction is located at 0 °C [32 °F].
[Power failure countermeasure]
The setting data is backed up in non-volatile IC memory.
[Warm-up indication]
With thermocouple and RTD inputs, for approx. 3 seconds after the power is switched ON, sensor
input character and temperature unit are indicated on the PV display, and the input range high limit
value is indicated on the SV display.
With the DC input, for approx. 3 seconds after the power is switched ON, sensor input character is
indicated on the PV display, and scaling high limit value is indicated on the SV display.
(However, if the scaling high limit value has been changed in the Scaling high limit setting, the
changed value will be indicated on the SV display.)
[Auto/Manual control switching]
If Auto/Manual control function is selected during
can be switched to manual control or vice versa by pressing the
OUT
/
key function selection, automatic control
OFF
OUT
/
When the control action is changed from automatic to manual control and vice versa, the balanceless-bumpless function works to prevent sudden change of manipulated variable.
When the control action is changed from automatic to manual control, the 1
the right on the SV display blinks.
The manipulated variable (MV) on the SV display can be increased or decreased by pressing the
or
▼ keys and the control is performed. (When the power supply to the instrument is turned on,
automatic control starts)
Accessories
: Instruction manual 1 copy
Screw type mounting bracket 1 set
CT (current transformer)
CTL-6S 1 piece [when option W10/W11/W12 is added]
CTL-12-S36-10L1 1 piece [when option W15 is added]
Ter m in al co v er
CS4H 1 piece (when the option KAB is added)
CS4L 2 pieces (when the option KAB is added)
OFF
key.
st
decimal point from
”.
▲
V1.1 • 05/2006 - 44 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
9.2 Optional specifications
Alarm output 2 (A2) process value monitoring [option codes: 2AS or 2AL]
When A2 action is set as Energized, the alarm action point is set by ±deviation to OUT1 setting (except
Process alarm).
When the input exceeds the range, the output turns ON or OFF (in the case of High/Low limit range
alarm).
When the alarm action is set as Deenergized, the output acts conversely.
When option Alarm output 2 is added, one more option Heater burnout alarm or 2. control output can be
added.
When the option [2AL] process value and loop monitoring is selected, the output terminal is common.
Setting accuracy : The same as the Indicating accuracy
Action : ON/OFF action
Hysteresis : For thermocouple and RTD inputs, 0.1 ... 100.0 °C (°F)
For DC current and voltage inputs, 1 ... 1000
(The placement of the decimal point follows the selection)
Output : Relay contact
Control capacity 3 A, 250 V AC (resistive load)
Electrical life 100,000 times
Detects the breaking status on the loop such as heater burnout, sensor burnout or actuator trouble.
When option Alarm output 2 is added, one more option Heater burnout alarm or 2. control output can be
added.
When the option [2AL] process value and loop monitoring is selected, the output terminal is common.
Setting range : Loop break alarm action time: 0 ... 200 minutes
Loop break alarm action span: 0 ... 150 °C (°F), 0.0 ... 150.0 °C (°F),
For DC input, 0 ... 1500 (The placement
of the decimal point follows the selection)
Output : Relay contact 3 A, 250 V AC (Resistive load)
Watches the heater current with CT (current transformer), and detects the heater burnout.
Heater burnout alarm is activated when sensor is burnt out or when indication is overscale or underscale.
When the option Heater burnout alarm is applied, one more option Alarm output 2 or 2. control output
can be added.
This option cannot be applied to control output Analogue current signal (4 ... 20 mA).
Heater rated current : 5 A, 10 A, 20 A, 50 A, Must be specified
Setting accuracy : Within ±5 % of heater rated current
Action : ON/OFF action
Output : Relay contact
Control capacity 3 A, 250 V AC (resistive load)
Electrical life 100,000 times
V1.1 • 05/2006 - 45 -
( )
Operating Instructions Temperature Indicating Controller CS4H / CS4L
Heating/Cooling control [option codes: DR2, DS2, DA2]
When the option 2. control output is added, one more option Alarm output 2 or Heater burnout alarm can
be added.
OUT2 proportional band : 0.0 ... 10.0 times OUT1 proportional band (ON/OFF action when set to 0.0)
OUT2 integral time : The same as that of OUT1
OUT2 derivative time : The same as that of OUT1
OUT2 proportional cycle : 1 ... 120 seconds
Overlap band/Dead band : For thermocouple and RTD inputs, –100.0 ... 100.0 °C (°F)
For DC current and voltage inputs, –1000 ... 1000
(The placement of the decimal point follows the selection)
OUT2 ON/OFF action hysteresis
For thermocouple and RTD inputs, 0.1 ... 100.0 °C (°F)
For DC current and voltage inputs, 1 ... 1000
(The placement of the decimal point follows the selection)
Output Relay contact output [DR2]
Control capacity 3 A, 250 V AC (resistive load)
1 A, 250 V AC (inductive load cos ø = 0.4)
Electrical life 100,000 times
Logic level DC 0/12 V [DS2]
12
+ 2
V DC maximum 40 mA (short circuit protected)
- 0
Analogue current signal (4 ... 20 mA) [DA2]
Load resistance, maximum 550
Ω
OUT2 action mode selection function:
One cooling mode can be selected by the key operation from the following.
• Air cooling (Linear characteristic)
• Oil cooling (1.5th power of the linear characteristic)
• Water cooling (2nd power of the linear characteristic)
Serial communication [option code: CR5]
When this option is added, SV1/SV2 external selection function is disabled.
The following operations can be carried out from the external computer.
(1) Reading and setting of SV, PID values and each setting value
(2) Reading of PV and action status
(3) Change of the functions
Communication circuit : Based on EIA RS-485
Communication method : Half-duplex communication start stop synchronous
Data transfer rate : 2400, 4800, 9600, 19200 bps (Selectable by key)
Parity : Even, Odd and None (Selectable by key)
Stop bit : 1 and 2 (Selectable by key)
Data format
Communication
WIKA protocol Modbus ASCII Modbus RTU
protocol
Start bit 1 1 1
Data bit 7 7 8
Parity Even Selection (Even) Selection (None)
Stop bit 1 Selection (1) Selection (1)
: Basic setting value
Data bit is automatically changed depending on the selection of communication protocol.
Digital external setting:
Receives digital setting value from WIKA programmable controller (with option SVTC).
(It is necessary to set the Setting value lock function to Lock 3 for the CS4H and CS4L.)
When the data from WIKA programmable controller exceeds SV high limit or SV low limit, the CS4H or
CS4L ignores the value, and performs the control with SV high limit or SV low limit.
Transmitter supply (isolated power output) [option code: P24]
Output voltage : 24 ±3 V DC (when load current is 30 mA)
Ripple voltage : Within 200 mV (when load current is 30 mA)
Maximum load current : 30 mA
Terminal cover [option code: KAB]
Electrical shock protecting terminal cover
V1.1 • 05/2006 - 46 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
10. Troubleshooting
If any malfunctions occur, refer to the following items after checking the power of the controller.
Warning
Turn the power supply to the instrument off before wiring or checking.
Working or touching the terminal with the power switched on may result in Electric Shock
causing severe injury or death.
10.1 Indication
Problem Presumed cause and solution
The PV display is indica
ting [
].
[] is blinking on t
he PV display.
[] is blinking
on the PV display.
• Control output OFF function is working.
Press the
OUT
/
key for approx. 1 second to release the function.
OFF
• The sensor for thermocouple, RTD and DC voltage (0 ... 1 V DC) input
may be burnt out.
Replace each sensor.
How to check sensor burnout
[Thermocouple]
If the input terminal of the instrument is shorted, and if nearby room
temperature is indicated, the instrument should be normal and the
sensor may be burnt out.
[RTD]
If approx. 100
Ω resistance is connected to the input terminals be-
tween A-B of the instrument and between B-B is shorted, and if
nearby 0 °C (32 °F) is indicated, the instrument should be normal and
the sensor may be burnt out.
[DC voltage (0 ... 1 V DC)]
If the input terminal of the instrument is shorted, and if scaling low limit
value is indicated, the instrument should be normal and the signal wire
may be burnt out.
• Is the input terminal of thermocouple, RTD or DC voltage (0 ... 1 V DC)
securely mounted to the instrument terminal?
Connect the sensor terminal to the instrument terminal securely.
• The sensor for DC voltage (1 ... 5 V DC) or DC current (4 ... 20 mA DC)
input may be burnt out.
Replace each sensor.
How to check sensor burnout
[DC voltage (1 ... 5 V DC)]
If the input to the input terminal of this controller is 1 V DC and if
scaling low limit value is indicated, the controller should be normal
and the signal wire may be burnt out.
[DC current (4 ... 20 mA DC)]
If the input to the input terminal of this controller is 4 mA DC and
scaling low limit value is indicated, the controller should be normal
and the sensor may be burnt out.
• Is the input terminal of DC voltage (1 ... 5 V DC) and DC current (4 ... 20
mA DC) securely connected to the input terminal of this controller?
Connect the sensor terminal to the controller terminal securely.
• Polarity of thermocouple or compensating lead wire is reversed?
Do codes (A, B, B) of RTD agree with the controller terminal?
Wire them properly.
V1.1 • 05/2006 - 47 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
Problem Presumed cause and solution
The value set during
the Scaling low limit
setting remains on the
PV display.
• Is the sensor for DC voltage (0 ... 5 V DC, 0 ... 10 V DC) or DC current
(0 ... 20 mA DC) input burnt out?
Replace each sensor.
[How to check sensor burnout]
[DC voltage (0 ... 5 V DC, 0 ... 10 V)]
If the input to the input terminal of this controller is 1 V DC and if the
value corresponding to1 V DC is indicated, the controller should be
normal and the sensor may be burnt out.
[DC current (0 ... 20 mA DC)]
If the input to the input terminal of this controller is 1 mA DC and if the
value corresponding to 1mA DC is indicated, the controller should be
normal and the sensor may be burnt out.
• Is the input terminal for DC voltage (0 ... 5 V DC, 0 ... 10 V DC) and DC
current (0 ... 20 mA DC) securely connected to the controller terminal?
Connect the sensor terminal to the controller terminal securely.
The indication of PV
display is abnormal or
unstable.
• Designation of the sensor input or temperature unit (°C or °F) is im-
proper.
Set the sensor input and the temperature unit properly.
• Sensor correcting value is unsuitable.
Set the value suitably.
• Sensor specification is improper.
Set the sensor specification properly.
• AC may be leaking into the sensor circuit.
Change the sensor for the ungrounded type.
• There may be equipment which produces an inductive fault or noise
near the controller.
Keep equipment which produces an inductive fault or noise away from
the controller.
PV display blinks
[
].
The internal memory is defective.
Please contact our main office or dealers.
10.2 Key operation
Problem Presumed cause and solution
Settings (main setting
value, P, I, D,
proportional cycle,
alarm, etc.) are
impossible.
• Setting value lock (Lock 1 or Lock 2) is designated.
Release the lock designation.
• During PID auto-tuning or auto-reset.
Cancel the auto-tuning if necessary.
Auto-reset ends in 4 minutes after started.
The value does not
change by the
▲ or ▼-
key.
The setting indication
does not change in the
rated input even if the
• SV high limit or low limit may be set at the point the value does not
change.
Set it again during Auxiliary function setting mode 1.
▲ or ▼- key is
pressed, and settings
are impossible.
V1.1 • 05/2006 - 48 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
10.3 Control
Problem Presumed cause and solution
Process variable (temperature) does not rise.
• The sensor is out of order.
Replace the sensors.
• Is sensor terminal or control output terminal securely mounted to the
instrument terminal?
Mount them securely.
• Is wiring of sensor terminal or control output terminal correct?
Wire them correctly.
If the control output
remains ON status.
• OUT1 low limit value is set to 100 % or greater in Auxiliary function setting mode 2.
Set the value appropriately.
If the control output
remains OFF status.
• OUT1 high limit value is set to 0 % or less in Auxiliary function setting
mode 2.
Set the value appropriately.
If any unexplained malfunctions occur, make inquiries at our agency or us.
11. Character table
[Main setting mode]
Character Setting item Default value Data
[Sub setting mode]
Character Setting item Default value Data
SV1 0 °C
SV2 0 °C
AT setting Cancellation
Auto-reset setting
OUT1 proportional band setting 10 °C
OUT2 proportional band setting 1.0 times
Integral time setting 200 s
Derivative time setting 50 s
ARW setting 50 %
OUT1 proportional cycle setting 30 s or 3 s
OUT2 proportional cycle setting 30 s or 3 s
A1 setting 0 °C
A2 setting 0 °C
HB (Heater burnout alarm) setting 0.0 A
LA (Loop break alarm) action time setting 0 minutes
LA (Loop break alarm) action span setting 0 °C
V1.1 • 05/2006 - 49 -
Operating Instructions Temperature Indicating Controller CS4H / CS4L
[Auxiliary function setting mode 1]
Character Setting item Default value Data
Setting value lock selection Unlock
SV high limit setting Input range high limit value
SV low limit setting Input range low limit value
Sensor correction setting 0.0 °C
Communication protocol selection WIKA protocol
Instrument number setting 0
Data transfer rate selection 9600 bps
Parity selection Even
Stop bit selection 1
[Auxiliary function setting mode 2]
Character Setting item Default value Data
Sensor selection K: –200 ... 1370 °C
Scaling high limit setting 9999
Scaling low limit setting –1999
Decimal point place selection No decimal point
PV filter time constant setting 0.0 seconds
OUT1 high limit setting 100 %
OUT1 low limit setting 0 %
OUT1 ON/OFF action hysteresis 1.0 °C
OUT2 action mode selection Air cooling
OUT2 high limit setting 100 %
OUT2 low limit setting 0 %
Overlap band/Dead band setting 0.0 °C
OUT2 ON/OFF action hysteresis 1.0 °C
A1 action selection No alarm action
A2 action selection No alarm action
A1 action Energized/Deenergized Energized
A2 action Energized/Deenergized Energized
A1 hysteresis setting 1.0 °C
A2 hysteresis setting 1.0 °C
A1 action delayed timer setting 0 seconds
A2 action delayed timer setting 0 seconds
Direct (Cooling)/Reverse (Heating) action Reverse (Heating) action
AT bias setting 20 °C
SVTC bias setting 0
SV2 indication selection Indication
Output status selection when input burn-
Output OFF
out
OUT/OFF key function selection OUT/OFF function
V1.1 • 05/2006 - 50 -
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.