Whitfield Profile 20 FS, Profile 30 INS, Profile 30 FS Installation And Operation Manual

Page 1
AND INSERT
PELLET FIRED
STOVES
INSTALLATION AND OPERATION
MANUAL
RETAIN THESE
INSTRUCTIONS
FOR FUTURE
REFERENCE
These appliances must be properly installed and operated in order to prevent the possibility of a house fire. Please read this entire owner's manual before installing and using your pellet stove. Failure to follow these instructions could result in property damage, bodily injury or even death. Contact your local
CUS
building or fire officials to obtain a permit and information on any installation restrictions and inspection requirements in your area.
Freestanding Model
Profile
20 FS
Insert Model
Profile
30 INS
Freestanding Model
Profile
30 FS
PAGE 1
P/N 775023M, Rev. A, 01/02
Page 2
IMPORTANT WARNINGS
CAUTION: Read this manual thoroughly before starting installation. For your safety, follow the installation, op­eration and maintenance instructions exactly without deviation. Failure to follow these instructions may result in a possible fire hazard and will void the warranty. If this appliance is not properly installed, a house fire may result. Contact local building or fire officials about restrictions and installation inspection in your area.
1. DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE CONNECTED TO ANOTHER APPLIANCE.
2. Do not connect this appliance to air ducts or any air distribution system.
3. Do not install a flue damper in the exhaust venting system of this appliance.
4. Do not use class B venting intended for gas appli­ances as a chimney or connector pipe on a pellet fired appliance.
5. The minimum clearances must be m aintained for all combustible surfaces and materials including; furni­ture, carpet, drapes, clothing, wood, papers, etc. Do not store firewood within this clearance space.
6. INSTALLATION DISCLAIMER - This stoves exhaust system works with negative combustion chamber pressure and a slightly positive chimney pressure. Therefore, it is imperative that the exhaust s ystem be gas tight and installed correctly. Since Lennox Hear th Products has no control over the ins tallation of your stove, Lennox Hearth Products grants no warranty, implied or stated for the installation or maintenance of your stove, and assumes no responsibility for any consequential damage(s).
7. Burning any kind of fuel consum es oxygen. If outs ide air is not ducted to the appliance, ensure that there is an adequate source of fresh air available to the room where the appliance is installed.
8. T his stove is not intended for use in com mercial in­stallations other than where the stove is being sold without prior approval from Lennox Hearth Products.
9. The stove will not operate using natural draft, nor without a power source for the blower and f uel feed­ing systems.
10. Never use gas oline, gasoline-type lantern fuel, kero­sene, charcoal lighter fluid, or similar liquids to start or "freshen up" a fire in this heater . Keep all s uch liq­uids well away from the heater while it is in use.
11. CONTINUOUS OPERATION: When operated cor­rectly, this appliance cannot be overfired. Continu­ous operation at a maximum burn can, however, shorten the life of the electrical components ( blowers, motors, and electronic controls), and is not recom­mended. Typical approved operation would include running at the low to mid range setting with occa­sional running on the maximum setting during the coldest periods of the winter. The blower speed con­trol should be turned to high when operating the stove on the high heat setting.
12. CAUTION: NEVER PUT FINGERS NEAR AUGER. Pellet fuel is fed to the UltraGrate by a screw auger. This auger is driven by a high torque motor.
13. The auger is capable of doing serious harm to fin­gers. Keep pellets in the hopper at all times and keep fingers away from auger. The auger can start and stop automatically at any time while the stove is running.
14. CAUTION: HOT WHILE IN OPERATION. An appliance hot enough to warm your home can severely burn any­one touching it. Keep children, clothing and furniture away. Contact may cause skin burns. Do not let children touch the appliance. Train them to s tay a safe distance from the unit.
15. APPROVED FUEL: This appliance is designed specifi­cally for use only with pelletized wood fuels only. With its advanced UltraGrate technology, this appliance is de­signed and approved for the burning of wood residue pellets with up to 3% ash content. This appliance is NOT approved to burn cardboard, nut hulls, cherry pits, corn, etc. regardless if it is in pellet form. Failure to com ply with this restriction will void all warranties and the safety listing of the stove. Consult with your authorized Lennox Hearth Products dealer for more information on ap­proved pellet fuels and the proper UltraGrate for the fuels in your area.
16. FLYASH BUILD-UP: For all wood pellet fuel-burning heaters, the combustion gas es will contain small parti­cles of fly ash. This will vary due to the ash c ontent of the fuel being burned. Over time, the f ly ash will collect in the exhaust venting system and restrict the flow of the flue gases. The exhaust venting system should be in­spected regularly and cleaned as necessary.
17. SOOT FORMATION Incomplete combustion, such as occurs during startup, shutdown, or incorrect operation of the room heater will lead to some soot formation which will collect in the exhaust venting system. A pre­cautionary inspection on a regular basis is advisable to determine the necessity of cleaning. The exhaus t vent­ing system should be inspected regularly and cleaned as necessary.
18. DISPOSING OF ASHES: Any ashes removed from the pellet stove must be deposited in a metal container with a tight-fitting lid. The closed container of ashes s hould be placed on a noncombustible floor or on the ground, well away from all combustible materials, outs ide of the dwelling pending final disposal. If the ashes are dis­posed of by burial in soil or otherwise locally dispersed, they should be retained in the closed container until all cinders have been thoroughly cooled.
19. SAVE THESE INSTRUCTIONS.
20. See the listing label located on the back of stove (or see Safety / Listing Labels on pages 45 and 46).
PAGE 2
Page 3
TABLE OF CONTENTS
Important Warnings ................................................ 2
Testing / Listing, EPA, Using this Manual ............... 3
Planning Your Installation......................................4-8
Manufactured (Mobile) Home Installation ................ 8
Installation .......................................................... 9-19
Care and Operation...........................................20-25
Routine Maintenance.........................................26-28
Annual Maintenance..........................................29-30
Specifications ....................................................31-33
Definitions............................................................... 34
Wiring Diagram ...................................................... 35
Troubleshooting................................................. 36-37
Replacement Parts List / Diagrams................... 38-43
Optional Accessories.............................................. 44
Safety / Listing Label and EPA Label................45-46
Ownership Records................................................ 47
LISTING / TESTING
Listing: The listing laboratory is ITS (Intertek Testing Services) and the listing mark is Warnock Hersey.
Testing: In accordance with the specifications and proce­dures listed in UL 1482 & ASTM E1509 for s olid fuel room heater, this appliance has been independently tested to UL, ULC and CSA standards. UL 1482 states requirem ents for installations as a freestanding room heater, or hear th insert for masonry or listed factory built (zero clearance) fireplac es . The safety-listing label is located on an inside hopper sur­face of the pellet stove. Please read this safety label care­fully. It contains important inform ation about installation and operation of this appliance. This appliance is tested and listed for residential installation acc ording to current national and local building codes as:
A Freestanding Room Heater
A Manufactured (mobile) Home Heater
EPA (Environmental Protection Agency)
Status: EPA Exempt - Pellet appliances that are designed with the combustion air supply exceeding the 35 to 1 (by weight) ratio are exempt from EPA regulations and are “non-affected facilities.”
PRODUCT IS SUBJECT TO CHANGE WITHOUT NOTICE.
CONGRATULATIONS ON THE PURCHASE OF YOUR NEW PELLET STOVE MANUFACTURED BY LENNOX HEARTH PRODUCTS.
When you purchased your new pellet stove, you joined the ranks of thousands of concerned indi­viduals whose answer to their home heating needs reflects their concern for aesthetics, efficiency and our environment. We extend our continued support to help you achieve the maximum benefit and enjoy­ment available from your new pellet stove.
It is our goal at Lennox Hearth Products to provide you, our valued customer, with an appliance that will ensure you years of trouble free warmth and pleas­ure.
Thank you for selecting a Lennox Hearth Products stove as the answer to your home heating needs.
Sincerely, All of us at Lennox Hearth Products
PACKAGING LIST
The assembled pellet s tove model Profile
20 FS, Profile 30-FS and Profile 30 INS are packaged with an acc essory package which contains the following:
One - Installation and operation instructions manual. One - Warranty. One - Power cord. One- Control board – Profile One - Screw, #8 x ½” tek (for mounting contro l board)
– Profile
30 INS only. One - Grate scraper. One - Heat exchange tube brush – P r of i le
30 INS only.
30 Series
only. One - Lower trim One - Wall thermostat. One - Roll of thermostat wire. Two- Leveling bolts, ¼-20 x 3” – Profile
Surround Kit (For Profile

30 INS Only)
30 INS only.
(Purchased separately, see page 44) kit is packaged with:
One - Top surround panel. One - Left surround panel. One - Right surround panel with door. One - Left side trim. One - Right side trim. One - Top trim. Two - Corner keys (“L” shaped brackets).
USING THIS MANUAL
Please read and carefully follow all of the instructions found in this manual. Please pay special attention to the safety instructions provided in this manual. The home­owner’s Care and Operation Instructions included here will assure you have many years of dependable and en­joyable service from your appliance.
PAGE 3
Page 4
PLANNING YOUR INSTALLATION
QUESTIONS TO ASK LOCAL BUILDING OFFICIAL
A correct installation is c ritical and im perative f or reduc­ing fire hazards and perilous conditions that can arise when wood pellet burning appliances are improperly installed. The installer m ust follow all of the m anufactur­ers’ instructions.
The installation of this appliance m ust conform to local codes and applicable state and federal requirements. Familiarity with these requirements before ins tallation is essential. Important consider ations to discuss with loc al building officials include:
1. Applicable codes (i.e. Uniform Mechanical Code, State or Regional Codes.)?
Electrical codes: In USA, NEC, ANSI / NFPA 70-1987. In Canada, CSA C22.1
Power Supply Requirements – The power cord must be plugged into a standard, 115 volt, 60 Hz grounded electrical outlet. The approximate power requirement is 200 watts, and will peak up to 700 watts for approximately 6 minutes when the self ­igniter is operating (it will turn off 2 minutes after flame detection). The power c ord must be routed to avoid contact with any of the hot or sharp exte­rior surface areas of the stove. When installed into a manufactured (mobile) home, the appliance must be electrically grounded to the steel chassis (see page 8, Manufactured [Mobile] Home Re- quirements). These requirements must be met unless otherwise specified by state or local authorities.
WARNING - Electrical Grounding Instruc­tions: This appliance is equipped with a three-prong (grounding) plug for your protec­tion against shock hazard and should be plugged directly into a properly grounded three-prong receptacle. Do not cut or remove the grounding prong from this plug.
2. Local amendments?
3. Is a permit required - cost? (you may wish to contact your insurance company to ask if they require this).+
4. Is outside combustion air required?
5. Rooms where the installation is not allowed?
INSTALLATION / MAINTENANCE STANDARDS
National Fire Protection Association – The primary NFPA standard that refers to installation and mainte­nance of pellet appliances and venting is NFPA 211: Chimneys, Fireplaces, Vents, and Solid Fuel appli­ances, Latest Edition.
SELECTING A LOCATION
The design of your home and where you place your stove will determine its value as a source of heat. A wood stove depends primarily on air circulation (con­vection) to disperse its heat, and therefore, a central location is often best. There ar e other practical consid­erations, which must be considered before a f inal selec­tion of locations is made.
Existing Chimneys Pellet Fuel Storage Aesthetic Considerations Roof Design (rafter locations & roof pitch) Room Traffic Proximity to Combustibles Electrical Wiring
The installation of this stove will requir e some r esearch. Once your options are determined, consult with your local building department who will be able to give you the necessary installation requirements for your area (Is a building permit required? Rooms where installation may not be allowed, etc.).
Warning: Check all local building and safety codes before installation. The installation instructions and appropriate code requirements must be followed exactly and without compromise. Alterations to the stove are not allowed. Do not connect the stove to a chimney system serving another stove, appliance, or any air distribution duct. Failure to follow these instructions will void the manufacturers warranty.
SMOKE DETECTORS
Since there are always several potential sources of fire in any home, we recommend installing smoke detectors. If possible, install the sm oke detector in a hallway adja­cent to the room (to reduce the pos sibility of occasional false activation from the heat produced by the stove). If your local code requires a smok e detector be installed within the same room, you must f ollow the requirements of your local code. Check with your local building de­partment for requirements in your area.
PAGE 4
Page 5
PLANNING YOUR INSTALLATION
FLOOR PROTECTION - Profile 20 FS & Profile 30 FS
These appliances require non-combustible floor pro-
Top View
tection. The floor protector must be a 3/8" ( minimum) UL approved hearth pad or equivalent. If the floor pro­tection is to be stone, tile, brick, etc., it must be m or­tared or grouted to form a continuous non-combust­ible surface (see Using
Alternate Material as Floor Protector on this page). If a
chimney connector extends horizontally over the floor, the protection must cover the floor under the connector and at least 2" to either side.
A non-combustible floor protector must fully cover the area beneath the appliance and extend 6” to the front, 6” to the sides, and 1” from the back (see il­lustration bellow).
FLOOR PROTECTION / HEARTH EXTENSION USING AL­TERNATE MATERIAL AS FLOOR PROTECTOR (also see
Floor Protection above for freestanding models and Hearth Requirements, page 7 for an insert model)
The alternate material used as a floor protector or hearth extension must be cons tructed of a dur able non­combustible m aterial having an equal or better insulat­ing value (lower k value) of k = 1.28 BTU / IN FT or a thermal resistance that equals or exceeds r = 78 HR °F FT
2
IN / BTU. With these values, deter mine the
2
HR °F
minimum thickness / material required us ing the f ormula and the table shown here (see chart - Alternative Floor Protection Materials).
Note: Any noncombustible material having a thickness of 1” whose k value is less than 1.28 or whose r value is more than .78 is acceptable. If the alternate material used has a higher k value or lower r value will require a greater thickness of the material used. In some c as es, if the k value is less or the r value higher, a thinner m ate­rial may be used.
Methods of determining floor protection equivalents To determine the thickness required for any material
when either the k or r values are known: T
= Thickness of material in inches
M
K
= K value of desired material
M
T
= Minimum listed thickness
L
Example: Micore CV230 is to be used for the floor pr o­tection. How thick must this material be?
The following formulas give the means of determining minimum thickness required of alternate materials.
Using the k formula:
Desired thickness k value of desire Minimum thickness of the alternate = material (per inch) x of listed material k value of listed material
TM (inches) = K
material (per inch)
M
x T
L
1.28
T
(inches) = 0.43* x 1”
M
1.28
Answer using k = 0.34 x 1” = 0.34 = 3/8” 3/8” thickness Micore will be required.
Using the r formula: TM (inches) = 0.78 x T
r
M
L
TM (inches) = 0.78 x 1”
2.33*
Answer using r = 0.34 x 1” = .034 = 3/8” 3/8” thickness Micore will be required.
At times it is important to know what combination of materials are acceptable for use as floor pr otection. T he “R values” are used to determ ine acceptable combina­tions of materials because “R values” ar e additive where r and k values are not.
“R value” = 1 = r x thickness of material used
k
ALTERNATIVE FLOOR PROTECTION MATERIALS Listed Values Min. Thick Material k
(per inch)r (per inch)
T
L
Millboard 1.28 0.78 1” Alternative Values Min. Thick Materials k
(per inch)r (per inch)
T
L
Wonderboard 1.92 0.56 1 1/2” Common brick 5.00 0.20 3 7/8” Cement mortar 5.00 0.20 3 7/8” Ceramic tile 12.5 0.08 9 3/4” Marble 11.0 0.09 8 5/8” Micore CV230
0.43 2.33 3/8” (U.S. Gypsum) Ceraform 126
0.27 3.70 1/4” (Johns-Manville)
Example: Given that the required “R value” for a suitable floor protector used must be equal to or greater than: “R” = r x T
= 0.78 x 1” = 0.78.
L
PAGE 5
Page 6
PLANNING YOUR INSTALLATION
Clearances to combustibles are determined from testing to applicable standards for allow­able heat transfer. The clearances allowed as shown here, do not take into account operation or serviceability requirements.
CLEARANCES
Profile
20 FS and Profile 30 FS - Standard residential
or manufactured ( mobile) home installation. T hese appli­ances require the following minimum clearances to com­bustibles:
MINIMUM CLEARANCES TO COMBUSTIBLES

Profile
! Clearance to
20 FS
Combustibles
Manufactured (Mobile) Home or Residential Installation Horizontal Flue – Di­rectly Through Wall
Interior Vertical Flue
inch / millimeter inch / millimeter
A - Sidewall to unit ♦4” / 102 mm ♦4” / 102 mm B – Backwall to unit 1” / 26 mm 9” / 229 mm C – Sidewall to unit
Corner
D – Max. Depth of
Alcove
E – Flue to Wall 3” / 77 mm 3” / 77 mm
Measured to fuel hopper lid in alcove.
Minimum Alcove Measurements - Height 48” / 1220 mm
1” / 26 mm 1” / 26 mm
24” / 610 mm 24” / 610 mm
Width 31” / 788 mm
Rear Wall or Alcove - Profile
Corner - Profile

20 FS and Profile

20 FS

30 FS

Profile
30 FS
Clearance to Combustibles
Manufactured (Mobile) Home or Residential Installation Horizontal Flue – Di­rectly Through Wall
Interior Vertical Flue
inch / millimeter inch / millimeter
A - Sidewall to unit ♦6” / 153 mm ♦6” / 153 mm B – Backwall to unit 1” / 26 mm 9” / 229 mm C – Sidewall to unit
Corner
D – Max. Depth of
Alcove
E – Flue to Wall 3” / 77 mm 3” / 77 mm
Measured to fuel hopper in alcove.
Minimum alcove measurements - Height 48” / 1220 mm
1” / 26 mm 1” / 26 mm
16” / 407 mm 16” / 407 mm
Width 38” / 966 mm
! Minimum clearances specified may not allow for
ease of operation and maintenance (please take this in to account when planning the installation). If installed to the minimum clearances, removal of the appliance may be necessary for servicing.
Corner - Profile

30 FS
PAGE 6
Page 7
PLANNING YOUR INSTALLATION
Clearances to combustibles are determined from testing to applicable standards for allow­able heat transfer. The clearances allowed as shown here, do not take into account operation or serviceability requirements.
MASONRY AND ZERO CLEARANCE FIREPLACES
The model Profile
30 INS is approved for installation into a solid fuel burning fireplace, either a mas onry fire­place or an approved factory-built / zero clearance fire­place (see pages 18 and 19 for additional infor mation on venting).
Dimensions Into a Fireplace
Height 20 1/8” / 512 mm Width @ Front 32” / 814 mm (extends back 1 ½”) Width @ back 24 5/8” / 626mm Depth 17 ¾” / 452 mm
HEARTH REQUIREMENTS / FLOOR PROTECTION Profile
The area directly in front of the Profile

30 INS
30 INS must be protected by a noncombustible material or a fireplace hearth or hearth extension as follows:
Combustible flooring must be protected by non­combustible material in Canada and 10 millimeter (3 / 8 inches) millboard or equivalent non-combustible in U.S. extending beneath the heater and to the front as indicated or to the nearest p ermitted combustible ma­terial. See page 5 for requirements when using alter­nate material as hearth extension.
The protected area must extend 6” to the front of the face of the Profile
30 INS.
MINIMUM CLEARANCES TO COMBUSTIBLES
inches / millimeters A - Insert to side wall 6” / 153 mm B - Insert to side trim 1” / 26 mm C - Hearth extension 6” / 153 mm D - Insert to mantel 18” / 458 mm E - Insert to top trim 1” / 26 mm
CAUTION: The fireplace in which the Profile 30 INS is to be installed must be thoroughly cleaned if it has been used to burn wood or synthetic logs. Have the chimney and all inside surfaces of the fireplace brushed and vacuumed so that no soot, embers, or loose combustion deposits can be drawn into the heat circulation blower and blown into the living area. If any portion of the chimney system shows signs of structural or mechanical weaknesses, such as: c rac k s , leaky joints, corroded or warped surfaces, the faulty portion must be re­paired or replaced prior to installing this appliance.
IMPORTANT: When installing the Profile
30 INS into a factory built fireplace, the firebox m ust accept the insert without modification other than removing bolted or screwed together pieces such as smoke shelf / deflectors, ash lips, screen or door tracks and damper assemblies. Any fireplace component which is removed m ust be retained so they can be reinstalled to restore the fireplace to its original op­erating condition. The removal of any part must not alter the integrity of the outer shell of the pre­engineered fireplace cabinet in any way.
Top View
Side View
PAGE 7
Page 8
PLANNING YOUR INSTALLATION
MANUFACTURED (MOBILE) HOME INSTALLATION
Freestanding Models – Profile
20 FS and Profile 30 FS In addition to the standard installation instructions, the following instructions may be required by local, state or federal building codes:
Stove must be permanently bolted to the floor.
An outside air inlet must be provided f or combustion
and be unrestricted while unit is in use.
Stove must be permanently electrically grounded to
the steel chassis of the hom e. The location selected for ground attachment to the stove m ust be dedicated for this purpose.
See pages 12 through 17 for additional infor m ation on
venting requirements.
Do not install appliance in a sleeping room.
The structural integrity of the manufactured home
floor, walls, ceiling and roof must be maintained.
NOTE:The grounding of this product, at installation,
must comply with NFPA-70 standards, CSA C22.1 in Canada, as well as any local codes.
Models – Profile

20 FS and Profile

30 FS
MANUFACTURED (MOBILE) HOME EXHAUST VENT PIPE INSTALLATION GUIDELINES
Use only listed type “PL” pellet vent pipe. Pipe should extend at least 3 feet above the part of the roof through which it passes. The top of the pipe should be at leas t 2 feet above the highest required elevation of any part of the manufactured (mobile) home within 10 feet of the pipe.
If the exhaust vent exits the manufactured (mobile) home at a location other than the roof, and exits at a point 7 feet or less above the ground level on which the manufactured (mobile) home is position a guard or method of enclosing the pipe shall be provided at the point of exit for a height of up to 7 f eet. The openings, if any, in this guard shall not allow a 3/4” rod to pass through. A 1/2” rod could pass through but should not be able to touch the pipe when inserted through the opening a distance of 4 inches.
PAGE 8
Page 9
INSTALLATION
REMOVING APPLIANCE FROM PALLET
1. After removing the pack aging from the stove, lif t the
hopper lid, and remove all pre-packaged items that were shipped in the hopper. Next, open the stove door and remove all pre-packaged items.
2. Using a 7/16” socket or open end wrench, remove
the bolts which secure stove to pallet. The bolts are located on the underside of the wooden pallet.
Remove the three bolts from underneath the pallet.
NOTE: Bolts may be used in manufactured (mobile) home installation to permanently secure stove to floor (see previous page).
INSTALLATION CHECK LIST
It is strongly recommended that you have an authorized Lennox Hearth Products dealer install your stove. If you install your stove yourself, you should review your instal­lation plan with an authorized Lennox Hearth Products dealer.
Check list:
Check off each item as you proceed with the installation process.
"
Read the ENTIRE stove installation section first
"
Read the Insert or Freestanding section (whichever applies).
"
Determine the appropriate measurements and loca­tions for your installation.
"
Follow the general installation directions under Stove Installation and the installation section appropriate to your stove.
"
Be sure to pre-fit all items bef ore you install, fasten, or set up the stove permanently.
Prior to lighting your stove:
"
Review the safety precautions section.
"
Review the pellet fuels section.
"
Review the Operating Instructions.
"
Follow the Operating Instructions.
"
Plug power cord connector into corresponding con­nector on the back of appliance ( see illustrations on page 11 showing connector locations). Note: Profile
30 INS – Route power cord behind side
surround panel.
After you have begun operation of your stove:
"
Review the routine cleaning / maintenance informa­tion.
"
Enjoy the warmth from your new Lennox Hearth Products pellet stove!
It is important to level the appliance. In some installa­tions such as a recess ed firebox floor (if the existing fire­place floor is lower than the hearth), install the 2 leveling bolts (1/4-20 x 3” long) into the threaded holes at the rear base of the Profile
30 INS. Adjust bolts until appliance is
level.
INSTALLING SURROUND ASSEMBLY - Profile

30
INS (to be done after venting system is installed)
This appliance comes with a set of m etal panels that en­close the fireplace opening when fitted together. There is also a trim assem bly that frames the surround assem bly to give it an attractive finished appearance. Put the sur­round assembly together according to the following in­structions (ref. see illustration on page 44).
1. Remove panels from package.
2. Open the hopper lid on Profile
30 INS so it is out of the
way for when panels are installed.
3. Install the control board onto the right side panel (with door) using the TEK screw (#8 x ½”) provided.
4. Position the power cord s o that it will be behind either the right or left side surround panel when they are in­stalled.
5. Install right side sur round panel onto right side of the Pro-
file
30 INS body by sliding the 2 flanges on side of panel
into corresponding slots on the Profile
6. Connect the wiring harness from the Profile corresponding connector on control board.
7. Loc ate dam per rod on lef t side of the Prof ile
30 INS.
30 INS into
30 INS. Ro­tate angled arm of rod so it is pointing down. Remove damper knob and set aside.
8. Install the left-hand panel onto the lef t side of Profile 30 INS body by sliding the 2 flanges on side of panel into corresponding slots on the Profile
30 INS.
9. Reach behind lef t surround panel and rotate damper arm so that end is inserted into the upper right hand slot of left surround panel (see illustration on page 10,
Profile
30 INS).
10. Reinstall damper knob by threading it onto end of damper rod.
11. Set the top surround panel in place over the two s ide panels. Position the 2 tabs on bottom of top surr ound panel so they slide into corresponding clips on the
Profile
30 INS. Connect the top surround panel to the side panels by pressing pins from side panels into corresponding holes on top panel.
12. Remove the surround trim from its packaging. As­semble it together using the c orner keys (“L” shaped brackets) provided. Slide assem bled trim over the top surround panel and slide it down over the side panels.
13. Push the Profile
30 INS back into place so the sur-
round is flush with the face of the hearth.
PAGE 9
Page 10
INSTALLATION
g
Profile
illustrated below and explained on page 9 (see, Install­ing Surround Assembly – Profile

30 INS (Only) – Install damper rod knob as
30 INS).
Install Damper Knob during Surround Installation (see
page 9)
Damper Locations
See ‘Opening Side Panels’, page 30 for instructions on opening the side panels for models Profile
Profile
30 FS. See ‘Installing Surround Assembly’ for
20 FS &
instructions on side surround panel access for model Profile 30 INS.
CLOSED
Fig. A
For initial setup, push the damper all the way in (when facing the front of the stove, in is to the center of the stove, and out is away from the center of the stove) and slowly pull back three to four notches (see figure B). This setting should provide an adequate air to fuel r atio for most installations.
OPEN 4 NOTCHES
Profile
20 FS - The damper is located behind the right-hand
side panel.
Profile
30 FS - The damper is located behind the lef t-hand
side panel.
Profile
30 INS - The damper rod is located on the left sur-
round panel.
Damper Adjustment
It is very important to preset your damper prior to burn­ing your pellet stove.
The damper plate contains nine notc hes spaced in 1/8” increments that aid in positioning (see figures A & B).
Fi
. B
PAGE 10
Page 11
INSTALLATION
THERMOSTAT INSTALLATION: NOTE: Always Disconnect Power Before Performing The Thermostat Installation.
A 24 volt wall thermostat and 20 feet of 18- gage thermos tat wire is included in your stoves acces sory package. It is rec­ommended that the thermostat and thermostat wire be installed by an authorized Lennox Hearth Products dealer. Installation Steps:
1. Unplug stove power cord from the wall outlet.
2. Locate the thermostat terminal block (see illustrations below).
3. Loosen the two terminal screws on the terminal block and remove the jumper.
4. Connect the two wires from your therm ostat to the term inals (one per term inal) . Ens ure that the pur ple wires from the harness remain connected to the term inal block and tighten the terminal sc rews. Make sure the wires are firm ly con­nected to the thermostat.
5. Plug in the stove and you are ready to operate with your thermostat!
NOTE: If the wall thermostat provided is not used, the jumper is required for the stove to operate.
Model: Profile

30 FS
Model: Profile

30 INS
NOTE: Also see page 35 for additional information on terminal blocks.
PAGE 11
Model: Profile

20 FS
Page 12
INSTALLTION
VENTING REQUIREMENTS
It is recommended that only an authorized dealer install your pellet stove. The specified installation r equirements must be followed to ensure conformity with both the safety listing of the appliance and local building codes. All clearances, installation instructions and precautions specified by the vent manufacturer must be followed.
Selecting a Location (Freestanding Models)- Review the appliance clearance requirements bef or e ins talling the venting system (see page 6). Position the appliance far enough away from walls to allow adequate room for servicing. Choose the appliance location with the least amount of interference with the house fram ing, plumbing, wiring, etc.
Preferred Vent Configuration – For the best perform­ance, we recomm end a vent run design which runs verti­cally and terminates above the roofline. This design will allow natural draft to improve the flow of f lue gases and will aid in combustion and stove performance.
Type of Pipe – This stove requires type “PL” (pellet vent pipe, sometimes referred to as “L-Vent pellet vent”), which conforms to UL standard 641. Connect the pellet vent pipe or the “tee” to the flue collar using a minimum of three screws and seal as specified in “Pipe / Liner Joint Requirements” on this page. Do not use class B gas chim­ney or single wall chimney as a substitute.
Size of Pipe -These pellet appliances are approved for use with the following vent sizes: 3” / 75mm standard, or 4” / 100mm (see page 14 - for determining correct size vent). Use a 3” / 75mm to 4” / 100mm adapter (Cat. No. 14M81) or a 3” / 75mm to 4” / 100m m “tee” in order to run 4” / 100mm pipe.
Offsets - In every installation, a single or double clean-out “tee” is recommended f or every ninety-degree offset (this tee will help collect ash residue and will allow for routine cleaning without the need to disconnect sections of pipe).
Horizontal Runs - The maximum total horizontal run must not exceed 10 feet (3.1 meters).
Horizontal run of pipe requires 1/4” / 7 mm rise per foot. Pipe Clearances / Requirements – See pipe manuf ac-
turers instructions for installation of venting components and clearances. Follow pipe manufacturers installation precautions for passing pipe through a combustible wall or ceiling (i.e. use an approved thimble).
Notes: Pellet vent pipe requires 3” / 75mm clearance from out­side of pipe unless otherwise specified by v ent manufac­turer (all diameters: 3” / 75mm and 4” / 100mm).
A support bracket should be installed every 4’ (1.2m) of pellet vent pipe on the exterior wall of the hous e unless otherwise specified by vent manufacturer.
Pipe / Liner Joint Requirements - All pipe joints must be secured with a minimum of 3 screws. ALL horizontal joints must be sealed gas tight. Use RTV silicone with a rating of at least 570° F (969° C), or Interam to provide a complete seal at the flue collar and on all joints.
Connection to Masonry Chimney through a Wall
(Freestanding Models) - Be sure to verify the constr uc-
tion of a masonry chimney, as it may have combustible framing.
The use of single wall flex or rigid 24 gage stainless steel pipe as a liner is approved.
Connection to an Existing Class A Chimney (Free-
standing Models) - A chimney adapter can be used to
make the connection from 3” / 75m m or 4” / 100mm pellet vent pipe to existing UL chimney system. Verify with the pipe manufacturer that your pipe brands will interconnect. The use of single wall flex or rigid pipe (24 gage stainless steel) as a liner is approved.
Note: Offsets and horizontal runs accumulate fly ash and soot which reduces the exhaust flow and performance of the stove.
Total Offsets in venting system should not exceed 270° total in direction change.
Direct-Vent Installations (Horizontal): On all direct-vent installations (short, horizontal runs with no vertical pipe); care should be taken when choosing a location for termi­nating the vent. It is not recommended to directly vent the exhaust on the prevailing wind side of the house. It is rec­ommended that when an appliance is vented directly through a wall, a minimum of 8’ (2.5m) of vertical pipe should be installed to create som e natural draft. This will reduce the possibility of smoke or odor entering the dwelling during appliance shutdown or loss of power.
PAGE 12
Page 13
INSTALLTION
A
A
VENT TERMINATION
Do not terminate vent in an enclosed or semi-enclosed area such as: carports, garage, attic, c rawl space, under a deck, porch, narrow walkway, closely fenced area, or any location that can build up a concentration of fumes such as a stairwell, covered breezeway etc.
Vent surfaces can get hot enough to cause burns if touched. Adults should supervise children when they are in the area of a hot stove. Non-com bustible shielding or guards may be required.
Termination Cap: The termination of the outside chim­ney of the pellet stove shall be located in accordance with the following:
A. Higher than 3’ (.92m) above any forced air inlet (air
conditioner, etc.) located within 10’ (3m).
B. Not less than 4’ (1.2m) below, 4’ (1.2m) horizontally
from or 1’ (3.1m) above any gravity air inlet (door, window, etc.) which flue gases could re-enter the dwelling.
C. Not less than 2’ (.6m) from combustible materials
such as an adjacent buildings, fences, protruding parts of the structure, roof overhang, plants and shrubs, etc. and not less than 7’ (2.1m) above gr ade when located adjacent to the public sidewalks (ac­cess). The final termination of the exhaust system must be configured so that flue gases do not jeop­ardize the safety of people passing by, overheat combustible portions of nearby structures or enter the dwelling.
D. Not less than 3’ (.92m) below an eave (maximum
overhang of 3’ (.92m) or any construction that proj­ects more than 2” (51mm) from the plane of the wall.
E. The distance from the bottom of term ination to grade
is 12” (305mm) minimum. This is conditional upon plants and nature of grade surface: Be careful to choose a location for the vent term ination which does not expose people or shrubs to high heat from the exhaust gases. The exhaust gases are not hot enough to ignite grass, plants and shrubs located in the vicinity of the termination although they should be a minimum of 3’ (.92m) away. The grade s urface un­der the termination must not be a lawn.
F.
Since sparks may escape from the exhaust pipe of any stove, use caution when positioning the vent pipe. Refer to pipe manufacturer’s instructions when in­stalling and terminating the exhaust. The vent pipe should be horizontal and never run the pipe in a downward direction (recommend a ¼” (7mm) rise per foot horizontal).
Chimney Height Requirements
The vent termination height required is 12” minimum above the roof penetration point as illustrated below (Ref. National Standard, NFPA 7-4.1). Check with your local building official for additional requirements for your area.
REQUIRES A LISTED TERM­INATION CAP *
12” MIN
TERMINATION MUST BE
T LEAST 12” (305mm)
BOVE THE HIGHEST POINT WHERE IT PASS­ES THROUGH THE ROOF SURFACE.
Manufactured (Mobile) Home Chimney Height Requirements
The chimney must extend 3’ (.92m) above the level of roof penetration and a minim um of 2’ (.61m) higher than any roof surface within 10’ (3m) (see below). Check with your local building officials for additional require ments for your area.
TOP OF FLUE MUST BE 3’ HIGHER THAN
REQUIRES A LISTED TERMINATI
N
AP *
TOP OF FLUE MUST BE 2’ HIGHER THAN ANY PART OF ROOF WITHIN 10’ HORIZONTAL
To pass inspection in nearly any jurisdiction, the chimney must meet both safety and exhaust flow requirements. The (3’ by) 2’ by 10’ rule applies to both masonry and factory built chimneys.
* Ref. NFPA 7 – 4.1.2, Vents installed with a listed cap shall terminate in accordance with the terms of the cap’s listings.
Notes:
It is not recomm ended to terminate exhaust vent on the prevailing wind side of the house.
It is not recommended using a termination cap with a screen (fly ash can collect in a screen resulting in blockage).
PAGE 13
Page 14
INSTALLATION
DETERMINING SIZE OF PIPE TO INSTALL
To determine what diameter pipe to use in an installation (3” or 4”), firs t find the “ equivalent pipe length” using the f ollow­ing guidelines, then plot this figure and the altitude on the chart.
Fill out the installation chart, and calculate your total equivalent pipe length. After you have the total equivalent pipe length, use the Pipe Selection Chart below to determine if your installation requires 3” or 4” exhaust pipe
.
INSTALLATION CHART
Type of
Pipe
90o
Elbows /
Tee (A & G)
o
45
Elbows (C)
Horizontal
(B & F)
Vertical
(E)
# of Elbows
or Feet of
pipe
Equivalent
Feet
x 5 Ft. (1.5m)
x 3 Ft. (1m)
x 1 Ft. (.3m)
x.5 Ft.
(.15m)
Total
Equivalent
Feet
A- 90 Degree Elbow E- 8’ Vertical Pipe B- 1’ Horizontal Pipe F- 2’ Horizontal Pipe C- 45 Degree Elbow G- 90 Degree Tee D- Standoff Braces H- Wall Thimble
NOTE: All equivalent pipe styles shown to the right are standard for all freestanding models.
SAMPLE INSTALLATION CHART
Type of
Pipe
90o
Elbows /
Tee (A & G)
o
45
Elbows (C)
Horizontal
(B & F)
Vertical
(E)
# of Elbows
or Feet of
pipe
2 x 5 Ft. (1.5m) 10 (3m)
1 x 3 Ft. (1m) 3 (1m)
3 x 1 Ft. (.3m) 3 (1m)
8 x .5 Ft. (.15m) 4 (1.2m)
Equivalent
Feet
PIPE SELECTION CHART
Total
Equivalent
Feet
Total = 20
PAGE 14
Page 15
INSTALLATION
INSTALLING YOUR FREESTANDING PELLET STOVE
Standard Horizontal Exhaust Installation
1. Locate the proper position for the listed type “PL” wall
thimble. Avoid cutting wall studs when installing your pipe. Use a saber saw or keyhole saw to cut the proper diameter hole through the wall to acc ommo­date the wall thimble. Use extrem e caution to avoid cutting into power lines within the wall of the home. The hole size will depend on the brand of pellet vent that you are using. Install the wall thimble in the hole.
ALL INTERLOCKING PIPE CONNECTIONS WITH­IN THE ROOM MUST BE SEALED W IT H RTV AND SECURED WITH A MINIMUM OF 3 FASTENERS PER CONNECTION.
2. Position the stove approximately 12” (.3m) from the
wall on the floor pad. Push listed type “PL” pipe through wall thimble. Squeeze a bead of high tem­perature silicone (RTV) s ealer around the end of the machined portion of the 3” (76mm) pipe connector on the back of the stove. Firm ly push on a section of listed type “PL” pipe until inner pipe liner pushes into the bead of RTV sealer.
4. Install listed type “PL” 45 degree elbow with rodent screen or cap (optional) on outside end of pipe. The rodent screen should be no less than 1/2” (13mm) mesh and may clog with soot and ash if left unat­tended during the burn season.
NOTE: The end of the exhaust pipe must extend a minimum of 12” (.3m) from the outside of the build­ing.
5. If the installation includes a source of outside com­bustion air; cut a separate hole through the wall for the fresh air tube. This tube s hould be 1-5/8” (42mm) [min.] diameter, steel only. Connect outside air pipe to air inlet on stove. This tube must be terminated with a 90 degree elbow or hood.
NOTE: Combustion air may also be drawn from a vented crawl space under the home. All joints for c on­nector pipe are required to be fastened with at least three screws. If vented horizontally, joints shall be m ade gas-tight in a manner as specified on this page (see instruction #1). Install vent at clearances specified by the vent manufacturer.
3. Push the stove (with pipe attached) towards wall. Pipe will go through the wall thimble. Do not pos ition the back of the stove closer than 1” (25m m ) f rom the wall.
Note: Greater back clear ance will improve the serv­iceability of the stove.
PAGE 15
Page 16
INSTALLATION
Standard Horizontal Installation Configurations
Profile

30 FS*
Corner Through the Wall
Profile

20 FS *
Corner Through the Wall
Profile

20 FS and Profile
Parallel Through the Wall

30 FS
* If you vent to the furthest wall, the vent pipe must maintain a 3” clearance parallel to the other wall.
PAGE 16
Page 17
INSTALLATION
Standard Vertical Installation Configurations
Models: Profile

20 FS and Profile

30 FS
These freestanding models may be connected to an existing flue or by installing listed type “PL” vent pipe. If a liner is run all the way to the top of the existing chim­ney, the existing flue should be sealed with a steel plate. Start a vertical run with a Tee at the back of the stove. Other options are illustrated below. Note: See page 13
for Vent Termination Requirements
Preferred Instal lation – V erti cal V ent Through the Roof
This venting configuration allows for the best stove performance. The vertical pipe promotes natural draft and with the chimney inside the dwelling, the flue gases stay warm, thus rising at a consistent rate.
PAGE 17
Page 18
INSTALLATION
Standard Installation Configurations Into and Existing Fireplace – Model: Profile
IMPORTANT- Make sure the chimney and firebox are clean and free of soot and ashes before installation begins. Fail-
ure to do so may result in the transfer of soot into the room by way of the convection fan.

30 INS
Venting Into an Existing Chimney
The Profile
30 INS may be installed into a masonry or factory built fireplace as illustrated on this page. When installing into a masonry chimney, it is recommended that the exhaust vent be extended to the top of the chimney as shown on the following page. However, if the vent pipe does not extend to the top of the chimney, the starter pipe must extend a minimum of 18” above the damper. You must seal the dam per ar ea so that the air / exhaust in the chimney cannot communicate with the air in the fireplace firebox (this is a positive flue con­nection. See the following instructions for one method of sealing flue).
Direct Connection (Positive Flue Connection)
Installation into a Masonry Fireplace without a full reline – Profile
The Profile
30 INS
30 INS does not require a full reline when installing into a masonry fireplace ( however it is recom ­mended to ensure proper drafting of the appliance). As a minimum the vent connector from the insert must ex­tend a minimum of 18” above the damper and the damper area mus t be sealed to prevent dilution air from entering the chimney which will affect proper draf ting of appliance.
Note: Sealing the damper area so that the air / exhaust in the chimney cannot communicate with the air in the fireplace firebox is called a “Direct Connection” or a “Positive Flue Connection”. See the following instruc­tions for acceptable methods for sealing chimney throat.
Positive Flue Connection Methods
A qualified installer should evaluate the existing fire­place to determine the best method for achieving a positive flue connection between the flue extension (starter pipe) and the chimney. The most common method for achieving a positive f lue connection in ma­sonry fireplaces is to secure a seal- off plate in the fire­place throat using masonry screws. Other acceptable methods include packing noncombustible material around vent pipe or using a flue adapter. Whatever “seal off” method is us ed must effectively seal the area to prevent dilution air to enter the chimney.
PAGE 18
Page 19
INSTALLATION
INSTALLING PROFILE 30 INS (CONTINUED)
IMPORTANT- Make sure the chimney and firebox are clean and free of soot and ashes before installation begins. Fail-
ure to do so may result in the transfer of soot into the room by way of the convection fan.
VENT TERMINATION WHEN SINGLE WALL LINER IS USED.
A single wall liner is not designed for exposure to the ele­ments. A section of pellet vent pipe is required as illustr ated below.
PAGE 19
Page 20
CARE AND OPERATION
CONTROL BOARD OPERATION
Stove On / Off Button – This button will turn your
stove on or off while in Manual or Automatic m ode (s ee page 23 for details). The green on / of f light at the top of control board will indicate the on / off status.
Heat Output Button – The heat output button has three selection settings, Low, Medium and High. Pressing the button will scroll the red indicator lights from Low to High. The button controls the pellet f eed and combustion airflow simultaneously. The control board is preset to provide the optimum r atio of fuel and air at each setting. Settings can be changed at any time but will only take affect af ter the start-up cycle is complete. Each press of the Heat Button will increase the heat output, and will scroll to the lowest setting after reaching the maximum setting.
Blower – The blower button operates the convection fan. This will change the flow of hot air into the room. Three choices are available Low, Medium, and High. When the Blower Button is pr essed the yellow indicator light will scroll to Low, Medium, or High. NOTE: W hen running your stove on high heat output, the control board will not allow you to select the low blower speed. This is a safety precaution to protect against overheat­ing. Blower settings can be changed at any time, but will only take affect after the start-up cycle is complete.
Fault Mode – The control system automatically monitors the flame using a photoeye located near the pellet feed tube. If the stove runs out of pellets the control board automatically goes into a “fault” status. The control board will initiate the shut down cycle and safely shut down the stove leaving it in the “fault” mode. The on / off indic ator light near the top of the control board will flash rapidly when in this mode. After ref illing the hopper with pellets, press the Start Button. If a therm ostat is not being used the stove will go into the start-up cycle. If a thermostat is being used the stove will go into the start-up cycle if the thermostat is in the demand m ode. If the thermostat is in the stand-by mode when the fault is cleared, the stove will remain in the stand-by mode until it closes again.
illumination of an LED labeled “Calib.” Pressing the Cali­bration Button for the first time will initiate the fuel feed trim, where one red “Heat” LED will illuminate to indicate the cur­rent trim status (factory set at ‘0’). The f uel feed rate may now be increased by pressing the Heat Button and de­creased by pressing the Blower Button. Each increment from the ‘0’ position is +/- 5%, with a total trim r ange of +/­20%. To exit calibration mode without adjusting the com­bustion air (see Combustion Air Trim below), press the Calibration Button two times. The new fuel feed setting will remain in mem ory and can only be changed by repeating the above procedures.
* It is important to note that changing the fuel feed trim WILL affect the time of the initial fuel feed dump during start-up. The start-up f uel dump is factory set at 1 m inute and 50 seconds. Each increm ental change in the fuel feed trim changes the start-up time by +/- 6 seconds.
Combustion Air Trim – Pressing the Calibration Button for the second time will initiate the combustion air tr im, where one yellow “Blower” LED will illuminate to indicate the cur­rent trim status (f actory set at ‘0’). The c ombus tion air flow may be increased by pressing the Heat Button and de­creased by pressing the Blower Button. Each increment from the ‘0’ position is +/- 5%, with a total trim r ange of +/­20%. Press the Calibration Button for a third time to stor e the settings into memory and exit calibration mode. The new combustion air trim settings will rem ain in m e m ory and can only be changed by repeating the above procedures.
NOTE – It is recommended that the damper be used to fine-tune your stove to your particular fuel and installation configuration (see page 10).
Control Board
Calibration Mode – Located behind the swing down
door at the bottom of the control board is a button la­beled “Calibration.” Pressing the Calibration Button enters the control board into “Calibration Mode,” where adjustments of up to +/- 20% (increments of 5%) can be made to the fuel feed and the combustion blower.
Fuel Feed Trim – It is recommended that you contact your authorized Lennox Hearth Products dealer before adjusting the Fuel Feed Trim. The size and density of pellet fuels varies widely among pellet manufacturers and has an impact on the fuel feed rates of your pellet stove. Pressing the Calibration Button will enter the control board into calibration mode, indicated by the
PAGE 20
Page 21
CARE AND OPERATION
A
CONTROL BOARD CONTINUED…
Note: The control board is equipped with an inter­nal memory which will recall the last setting and mode the stove was in prior to loss of power. Be­cause we individually check each stove prior to packaging, one of the two scenarios will appear when you first plug in your stove.
1). The Green LED at the top of the control board will
illuminate and the blowers will be running. This is a standard cool down mode and will last no longer than ten minutes. This happens dur ing testing when the stove is turned off (which initiates cool down mode) and then is unplugged.
2). The Green LED at the top will illuminate and the red
and yellow LED’s will illuminate on the control board, indicating that the stove is in the run mode. This happens during testing if the stove is unplugged without first turning the control board off ( the control board remember s its last setting, which was the run
mode). If your stove follows that described in number 2 above, simply press the ON / OFF button once to turn the stove off, this will initiate the cool down mode. The stove can be restarted at any time during the cool down mode by pressing the ON / OFF button once.
Start-up Sequence of Events
1. Fault time delay is initiated (14 minutes 15 sec-
onds).
2. Fuel feed rate of 100% for 1 minute 50 seconds
(when trim left at fact ory setting of 0) auger trim set-
ting ranges from 1:26 to 2:14 depending on -4 to +4
respectively.
3. Combustion fan operation starts (medium range
voltage).
4. Convection fan operation starts (medium range
voltage).Power LED is activated (steady green).
6. Igniter operation activated (line voltage).
7. Photoeye looks for flame (flame dominance
scheme).
8. * If needed second & third fuel dum ps are available
at predetermined time deliveries (4 minutes & 6
minutes after initial). Flame Detection Sequence of Events - This is what
happens after flame has been detected.
! Happens within the Start-up Time Delay sequence. ! 0 to 1 minute no fuel feed. ! Flame settles. ! Bed of embers built. ! 1 minute mar k: Fuel Feed rate 20% for 4 minutes
15 seconds (1 second on / 4 seconds off).
! 2 minute mark: igniter turns OFF / convection
blower = panel setting.
! 5 minute 15 seconds mark: combus tion f an = panel
setting / LED indicator still active.Start-up Time
delay ends 14 minutes 15 seconds after pushing the start button!
PHOTOEYE
PN LABEL
LOCATION
POWER
SELECT
MAIN
H
RNESS
FUSE
Calibrating Fuel Feed & Combustion Voltage
Calibration is the function of internal software and should be done by a quali­fied technician.
Access to perform calibra­tion is behind the lower door located on the face of the control board. Use a penknife to pop open door. Voltage access ports f or all c ir­cuits are located here as well.
Calibration is the function of internal software and should be done by a qualified technician.
Access to perform calibration is behind the lower door lo­cated on the face of the control board. Us e a penknife to pop open door.
Voltage access ports for all circuits are located here as well.
Fuel Feed Trim Steps:
1. Push button “once” to access fuel feed calibration mode.
2. Identify the current calibration setting indicated by one RED LED bar and the word “AUGER” in red be­low heat control button.
3. Pus h the “HEAT” control button to adjust setting UP. Each push raises the RED LED bar and increases feed rate.
4. Push the “BLOW ER” control button to adjust s etting DOW N. Each push will drop the RED LED bar de­creasing feed rate.
5. Push the calibration button two more times to lock in selected setting.
PAGE 21
Page 22
CARE AND OPERATION
Combustion Voltage Trim Steps:
1. Push button “twice” for access voltage calibration mode.
2. Identify the current calibration setting indicated by one YELLOW LED bar.
3. Push the “HEAT” control button to adjust setting UP. Each push raises the YELLOW LED bar & increases voltage 5%.
4. Push the “BLOWER” control button to adjust setting DOWN . Each push lowers YELLOW LED bar decreasing voltage 5%.
5. Push the calibration button once to lock in selected results.
Fuel Delivery Rate
The feed rate button manages the fuel deliver y rate by controlling the amount of time the auger motor will run as follows:

Profile
Profile
Profile
20 FS
Feed Rate Setting
Low = 1 on/5.40 off 1.5 Lb.’s hr. 13,000 BTU/hr 37 Med.= 1 on/3.30 off 2.5 Lb.’s/hr. 21,000 BTU/hr 22 High = 1 on/1.75 off 3. 8 Lb. ’s/hr. 32,000 BTU/hr 15
Feed Rate Setting
Low = 1 on/4. 50 of f 1.7 Lb.’s/hr. 14,000 BTU/hr 48 Med.= 1 on/1.90 off 2.6 Lb.’s/hr. 22,000 BTU/hr 30 High = 1 on/1.15 off 4. 5 Lb. ’s/hr. 39,000 BTU/hr 18
Feed Rate Setting
Low = 1 on/4. 50 of f 1.7 Lb.’s/hr. 14,000 BTU/hr 30 Med.= 1 on/1.90 off 2.6 Lb.’s/hr. 22,000 BTU/hr 20 High = 1 on/1.15 off 4. 5 Lb. ’s/hr. 39,000 BTU/hr 12

30 FS

30 INS
Auger Motor ON / OFF Time (seconds)
Auger Motor ON / OFF Time (seconds)
Auger Motor ON / OFF Time (seconds)
* Lb.’s per hour fuel delivery
* Lb.’s per hour fuel delivery
* Lb.’s per hour fuel delivery
Approximate
BTU per hour fuel delivery
Approximate
BTU per hour fuel delivery
Approximate
BTU per hour fuel delivery
Burn Time (hours)
Burn Time (hours)
Burn Time (hours)
* Feed rates are approximations only. Actual feed rate will
vary depending on size, quality and length of fuel used and variations in line voltage.
Your pellet stove can be operated in either manual or automatic mode. The manual mode is used when operating without a thermostat. The automatic mode is used when utilizing a wall thermostat. When utilizing the thermostat capability the burn time can be extended dramatically depending on thermostat setting. Note: It is norm al for some ash to build up on the inner glass surf ace at the lower burn settings.
Initial Start-Up / Empty Hopper or Feed Tube:
During an initial start-up, or in the case where the hopper has run out of fuel, it will be necessary to prime the auger feed system. The control boar d is set to deliver fuel for approximately 2 1/2 minutes during start- up, which, with a fully primed auger tube, will provide the appropriate amount of fuel for ignition.
When f irst starting your pellet stove, it will be nec­essary to prime the auger tube. To prim e the auger tube you need to first fill the hopper with pellets, and press the ON button on the control board. W ait ap­proximately 2 1/2 minutes and turn the control board OFF and then back ON again. W ait an additional 2 1/2 minutes (if necessary) and continue this proces s until fuel begins to fall into the UltraGrate. Re­member, different brand fuels feed at different rates.
Once fuel starts to enter the UltraGrate, turn the stove OFF and then back ON. The auger tube should now be primed and the stove should deliver enough fuel for proper ignition. It may be necessary to follow these procedures in the event that the hopper runs completely out of fuel.
Estimated heat input based on fuel value of 8500 BTU per
lb. of fuel.
PAGE 22
Page 23
CARE AND OPERATION
Manual Operation:
Pressing the stove on / off button initiates the s tart-up cycle. The green on / off light, near the top of the con­trol board, will light up to indicate the “on” status. The fan speeds and pellet feeds are fixed during this time to provide appropriate ignition. The Fas t-Fire igniter sys­tem will light the pellets feeding to the UltraGrate, after about 3 minutes. The s tar t-up c ycle is in eff ect for approximately 2 minutes after f lame is detected in the UltraGrate. A photoeye, located near the pellet feed tube monitors the existence of flam e. After the start- up cycle your stove will be in the run mode. At this point the stove will operate in the heat output and blower set­tings selected. These settings can be selected either during or after the start-up cycle. Pressing the stove on / off button during the run mode will initiate the shut down cycle. The on / off indicator light will turn off. The pellets will stop feeding and the blowers will run at a fixed speed for approximately 10 minutes. At this point your stove is safely shut down and can ONLY be re­started by pressing the stove on / off button again.
Automatic Operation:
Your stove is capable of running in an automatic mode with the use of a wall thermostat. NOTE: For the thermo­stat to control the operation of the s tove, the “on” status must be active on the stove’s on / off button. T he thermo­stat will establish either a demand mode or a stand-by mode. The thermos tat s hould be set f or the desir ed room temperature. If the room temperature drops below the level on the thermostat the st ove will automatically begin the start-up cycle, as explained above in the Manual Op­eration section. Once the start-up cycle is completed the stove will operate in whatever heat and blower setting you have selected. For best operation under thermostat c on­trol, the Medium or High settings recom mended. When the desired room temperature is reached the stove will automatically go into the shut down cycle. The pellet feed will stop and the blowers will continue for a controlled time allowing safe shut down of your stove. All lights will remain on when the thermostat is open. The heat and blower settings can be changed at any time, but only take affect during the run mode. When the tem perature in the room drops to the level set at the thermostat, the stove will again begin the start-up cycle and resume automatic operation in the demand mode.
Lighting Procedure Without Igniter
Your pellet stove can be lit manually without using the automatic igniter by following the procedure below. If your stove is set up to run on a thermostat, the thermostat circ uit needs to be closed (as if permanently in the demand mode). The therm ostat wires should be removed from the rear of the stove and replaced with the jumper originally supplied with your stove. If a jumper is not available the thermostat should be set to the highest setting. This will keep the stove in the demand m ode. If your automatic igni­tion system should ever need troubleshooting, repair or replacement, please contact your authorized Lennox Hearth Products dealer.
1. Press the ON button on the control board.
2. Wait approximately 2 1/2 minutes while the pellets prime the grate (the pellets will stop f eeding automati­cally).
3. Place a sm all amount of an approved (non-volatile) fire starter on top of the pellets in the grate, (see your authorized Lennox Hearth Products dealer for appro­priate fire starting products). DO NOT USE FLAMMA­BLE LIQUIDS TO START YOUR STOVE!
4. Light the “fire starter” with a match and close the door.
5. The photoeye will detect that a flame is present and will begin feeding pellets in approximately 2 minutes.
6. The control board will continue to go through the nor­mal start-up cycle and the flam e should be well estab­lished within 10 minutes from the time the ON button was initially pressed. Remember – you are now in manual mode and heat settings should be selected to the desired room heat level.
Turning Off Your Stove
Press the stove on / off button to initiate the shut down cy­cle. The pellets will stop feeding and the blowers will con­tinue to run on a timed cycle. The stove will shut down safely upon completion of the shut down cycle.
NOTE: If the stove on / off button is pres sed while the thermostat is in the standby mode the stove will not restart until the thermostat closes.
PAGE 23
Page 24
CARE AND OPERATION
DAMPER OPERATION (All models)
The damper is a plate that helps control the am ount of airflow supplied for combus tion. W ith the dam per pushed all the way in the airflow is at its minimum. As the damper is pulled out, more air is allowed to flow.
It will be necessary to monitor the appearance of the flame during the first 4-8 bags of pellets. If your flame is smoky red / orange with evidence of soot at the top of the flame, you need more combustion air; pull the damper out one notch and re-evaluate the appearance of the flame. It may be necessary to continue this process, moving the damper one notch at a time until proper com ­bustion is attained (the flame s hould become yellow and begin to “dance”). If the flame is “s hor t” at the higher burn rates, or if the pellets are burning up in the grate before new pellets are fed into the fire, push the dam per in one notch and monitor the flame. Continue the process of moving the damper one notch at a time and evaluating the flame until proper flame appearance is achieved.
Once the damper has been properly set it should not need adjusting unless you are changing from a prem ium grade pellet to a standard or high ash pellet, in which case the damper m ay need to be pulled out to help pre­vent the accumulation of ash in the grate.
DAMPER ADJUSTMENT GUIDELINE
Lack of Combustion Air: By opening the damper, this
will increase combus tion air delivery. Symptoms of insuf­ficient combustion air inc lude; unburned fuel, lazy smoky or red / orange flame, excessive ash or s oot, excessive buildup on glass.
Contributing factors:
High Altitude – Lack of oxygen
Restrictive Venting (elbows, horizontal runs,
cold external chimneys, etc.).
Dirty / Poor Quality Fuel.
Note: Excessive amounts of fly ash built-up in the grate, clinkers in the grate or leak age of air (if the grate is not properly seated) will starve the fire for air. See Routine Maintenance, on page 26 for information on cleaning the stove.
Excessive Combustion Air: By closing the damper, this will reduce combustion air deliver y. Symptoms of excessive air include; fuel burns too quickly (results in smoking or smoldering pellets), white to yellow flame, etc. If the damper is open too much, the burning pellets will lift off the grate and fly up into the air much like popping corn does.
Contributing factor:
Venting system providing excessive draft.
Correct Combustion Air / Proper Burn Characteris­tics: W hen the damper is corr ectly set, the burning pel-
lets should move (wiggle) around slightly and the flame should be bright yellow.
AUTOMATIC SAFETY FEATURES Power Outage:
During a power outage, the stove will shut down safely. The stove will automatically restart when power is re­sumed. The solid state control board has an internal memory that will retain heat output and blower speed settings through voltage interruptions. A sm all amount of smoke may leak from the top of the window glass, the hopper and from the combustion air intak e, if the s tove is vented horizontally with no vertical pipe. This will not per­sist for more than 3 to 5 m inutes and will not be safety hazard. It may set off your smoke alarm.
Note: If the area in which you live is prone to frequent power outages, it is recomm ended that a minimum of 8 feet (2 ½ meters) of vertical vent pipe be included in a freestanding installation to induce a natural draft in the event of a power failure.
Overheating:
A high temperature switch will automatically shut down the stove if it overheats. Allow up to 45 minutes cooling time before re-lighting. Keep enough c onvection air going through stove to keep it cooling properly, this will ensure long life of the stove. If the overheating continues, contact your authorized Lennox Hearth Products dealer for more information.
PAGE 24
Page 25
CARE AND OPERATION
FUEL
Pellet Fuel Hopper - It is recommended to open the hopper
lid by grasping it on the side as shown in the following pic­ture.
Open Hopper Lid by Grasping the Side
Be very careful not to touch other hot areas on stove!
Clinkering - Silic a (or sand) in the f uel, along with other im­purities, can cause clinkering. A clinker is a hard mass of silica formed in the bur ning proces s. Clink ering is a f unction of the fuel, (not the stove), but adversely affects the per­formance of the stove by blocking off the air pass ages in the grate. Even P.F.I. approved pellet fuel may tend to clinker. A clinker can be rem oved fr om the UltraGr ate and plac ed in the ash pan with the use of the grate scraper / ash pan tool furnished with your stove. See Routine Maintenance (on page 26) for more information on cleaning.
Ash - The frequency of removal of the ash and maintenance performed on the stove is directly proportional to the ash content of the fuel and the operation duration of your pellet stove. Low ash fuel may allow longer intervals between cleaning, however, a stove burning high ash fuel may need to be cleaned as often as everyday.
PLEASE NOTE: Lennox Hearth Products has no control over the manufacturing of pellet fuel and will not be held responsible for poor stove performance or any damage caused by poor quality pellet fuels.
Fuel Feed Rates -
Different brands of pellets will feed at varying rates due to their size and density (length and diameter). This may require a slight adjustment in the damper control (see page 10) or the fuel feed trim to compen­sate (see page 20).
UltraGrate
Fuel Specifications - Using the UltraGrate burn
system, this appliance has been designed to burn wood residue pellets with up to 3% ash content. Agri­cultural pellets (i.e.… Corn, alfalfa etc.) are not per­mitted to be burned in the stove. Dirty fuel will ad­versely affect the performance of the stove.
Caution: The use of unapproved, dirty, wet and / or high salt content fuel will void the warranty!
Wood pellets manufactured to the pellet fuels institute (P.F.I.) certification standard are available in two grades, Standard and Premium. The primary differ­ence between the two is the ash content of the pellets.
The P.F.I., specification for standard gr ade & prem ium grade residential pellet fuel is as follows:
CHLORIDES (Salt): Less than 300 p.p.m.
BULK DENSITY: 40 lb. / Cu. Ft. minimum
MOISTURE CONTENT: 8% maximum
ASH CONTENT: < 3% maximum (standard
grade) < 1% maximum (premium grade)
FINES: 0.5% maximum through a 1/8” screen
BTU CONTENT: Minimum 8200 BTU per
pound.
Pellet Feed / Pellet Size - The pellet feed s ystem is designed to handle a wide range of pellet sizes up to a maximum of 5 / 16" diameter. Different pellets may feed at considerably different rates. You may notice a difference in the burn if you change pellet fuel sizes. The longer the pellet, the slower it will feed and vice versa. If the stove will not stay burning at the minimum fuel feed setting, those particular pellets may not be feeding fast enough. If this happens, reduce the amount of combustion air by adjusting the damper. See page 10 before adjusting the damper.
Long Burn Time - When operated c orrectly, this ap­pliance cannot be overfired. Continuous operation at a maximum burn can, however, shorten the life of the electrical components ( blowers , motors, and electronic controls), and is not recom mended. Typical approved operation would include running at the low to mid range setting with occasional running on the maximum setting during the coldest periods of the winter. The blower speed control should be turned to high when operating the stove on the high heat setting. A lower heat setting is recommended for overnight operation or when the room is vacated for long periods of time.
Note: See Fuel Delivery Rate on page 22 for burn times.
PAGE 25
Page 26
ROUTINE MAINTENANCE
Unplug and Ensure Stove is Cold Before Performing Any Maintenance Work
The following areas need to be inspected and cleaned as part of routine maintenance:
ROUTINE CLEANING
Note: Stove will need to be shut off and cooled enough to handle before routine cleaning is performed. Always disconnect power before doing any routine cleaning.
The following areas need to be inspected during Routine Cleaning:
UltraGrate (burn grate)
Ash Slide Plate (free standing model only)
Ash Pan
Heat Exchange Tubes
Photoeye Slot
Exhaust Passages and Vent Pipe
UltraGrate (Burn Grate for All Models)
The UltraGrate s hould be inspected periodically to as­sure that the air holes have not become clogged with ash or clinkers. T he UltraGrate can easily be cleaned with the grate scraper / ash pan tool, or it can be removed for cleaning. It is very important to monitor the ash build up under the UltraGrate, as ex cessive am ounts of ash will block combustion air from entering the grate, causing pellets to pile-up in the grate. The ash build-up under the grate is easily dumped into the ash pan by pulling out the ash slide weekly as shown below. The grate cleaning procedure is the same for all models.
UltraGrate
ASH PAN (Profile

20 FS and Profile

30 FS)
The ash pan will have to be emptied periodically, de­pending on amount of fuel consumed. The ash pan is located in the pedestal on the Profile
20 & Profile 30. It can be removed by turning the T-Bar latch fully counter­clockwise.
Ash Pan
* (Recommended Frequency of 2 days – 2 weeks)
ASH PAN (Profile
The Profile

30 INS has two ash pans, an upper and
30 INS)
lower. They should be emptied whenever necess ary. The upper ash pan is accessed by opening the door and sim ­ply lifting the ash pan out. The lower ash pan is removed by pulling straight out using the grate scraper tool. Be sure to dump ashes into a non-c ombus tible container. All ash removal and cleaning should be done while stove is cold.
Lower Ash Pan
* (Recommended Frequency of 1 day – 2 weeks)
* Inspect at minimum frequency stated until you establish a minimum frequency required for your installation (frequency
will vary depending upon fuel BTU value / ash content, usage, and misc. installation variables).
* (Recommended Frequency of 1 day – 1 week)
PAGE 26
Page 27
ROUTINE MAINTENANCE
Unplug and Ensure Stove is Cold Before Performing Any Maintenance Work
The following areas need to be inspected and cleaned as part of routine maintenance:
ASH SLIDE PLATE (Profile

20 FS and Profile

30 FS)
Ash that accumulates around the gr ate can be “dropped” into the ash pan without opening the firebox door. Simply pull open the ash release slide plate as shown in photo using the grate scraper tool provided. Remove the ash pan as shown. Note: Make sure to fully close the plates when finished. Failure to close the ash release slide plates completely may cause the fuel to burn poorly (due to reduced air flow through the grate), which may then cause pellets to “pile up” in the gr ate. Im portant: T he ash slides must be fully closed for firebox door to close.
Ash Slide Plate
Tube Scraper
* (Recommended Frequency of 1 day – 2 weeks)
HEAT EXCHANGER TUBES (All Models)
ONLY CLEAN HEAT EXCHANGER TUBES AFTER STOVE HAS COOLED DOWN.
1. Tube Scraper
After opening the firebox door, use the hole in the handle of the Grate Scraper Tool to “grab” onto the rod. Using the Grate Scraper Tool, pull the rod up and out towards the opening of the firebox. Continue pulling until the Tube Scraper reaches the top of the firebox. The r od is located on the outside, above the door. Pull the tube scraper out, then repeat 2–3 times to remove fly ash from the heat exchange tubes.
It may be easier to clean the tubes by first rem oving the heat exchanger baffle. Loosen the two screws holding the baffle in place (do not fully remove). The baff le contains keyhole slots allowing the screws to remain in plac e while removing the baffle. T he scraper can now be pulled in a more horizontal manner, which allows the scraper to move more freely.
* (Recommended Frequency of 2 days – 2 weeks)
2. Cleaning Brush
WARNING: DO NOT USE BRUSH ON HOT STOVE With tube scraper rod pulled out 2 – 3 inches, insert
brush behind tube scraper and remove ash build-up. Clean to the left & right side of heat exchanger, between tubes and the top of the firebox.
Clean Behind Tube Scraper
* Inspect at minimum frequency stated until you establish a minimum frequency required for your installation (frequency
will vary depending upon fuel BTU value / ash content, usage, and misc. installation variables).
* (Recommended Frequency of 2 weeks - 2 months)
PAGE 27
Page 28
ANNUAL MAINTENANCE
(To be preformed by a certified technician).
Unplug and Ensure Stove is Cold Before Performing Any Maintenance Work. Include routine maintenance with an-
nual maintenance. The following areas need to be inspected and cleaned as part of annual maintenance:
PHOTOEYE (All Models) WARNING: DO NOT USE BRUSH ON HOT STOVE
The photoeye uses a narrow slot in the side of the feed tube to view flame (left side Prof ile
30 FS and INS). This area should be cleaned periodi-
file
20 FS, right side Pro-
cally to prevent pellet debris build-up. Pellet debris build- up may cause the stove to go into “fault” m ode. Use the br ush provided (see additional Suggestion below) and thoroughly clean the entire sidewall of the feed tube on the side where photoeye slot is located.
Suggestion: Compressed air can also be used to remove pellet debris from photoeye slot (use only canned com­pressed air such as what is commonly sold at computer supply stores. DO NOT use an air compressor).
Clean Photoeye Slot
ASH CLEAN-OUT PORTS
Make sure stove is cold. Ash clean-out ports must be cleaned as part of routine maintenance.
Accessing Clean-out Ports
Profile

30 Series: Loosen screws (1 per clean- out) and lift plate out. Use an approved ash vacuum or brush to remove ash. After cleaning, replac e clean-out plates and tighten screws.
IMPORTANT: Clean-out cover plates must be in­stalled when operating unit.
Profile

30 Series
* (Recommended Frequency of 2 weeks - 2 months)
EXHAUST PASSAGES AND VENT PIPE (All Models)
Inspect frequently and clean when necessary. Fly ash will accumulate at all bends in the exhaust system. Note: Large amounts of fly ash build-up will create a lack of combustion air. Rem oving the clean out tee cap on verti­cal installations will allow an inspection of the ash build-up in the clean out tee and will help you to decide how fre­quently more extensive cleaning must be performed.
Clean-Out Tee
Rain Cap
* (Recommended Frequency of 1-2 months)
Clean-outs
* (Recommended Frequency of 1-2 months)
* Inspect at minimum frequency stated until you establish a minim um f requency required for your installation (frequency
will vary depending upon fuel BTU value / ash content, usage, and misc. installation variables).
PAGE 28
Page 29
ANNUAL MAINTENANCE
Unplug and Ensure Stove is Cold Before Performing Any Maintenance Work. Include routine maintenance with an-
nual maintenance. The following areas need to be inspected and cleaned as part of annual maintenance:
(To be preformed by a certified technician).
DOOR ROPE GASKET (All Models)
The condition of the rope gasket around the door and windows should be checked periodically and replaced or repaired if necessary. A one-inch strip of paper may be used to perform a test of the integrity of the door seal. Close the door on the paper in at least eight points (see illustration, “Door Rope Gask et”). It is norm al to f eel only a slight amount of fric tion. The door gasket does not need to be “tight” in all areas, since a small am ount of leakage is not hazardous or detrimental to the performance of your stove.
Door Rope Gasket
(check seal at points indicated)
(Recommended Frequency of 1 year)
Checking Door Seal
WINDOW WASH (Models with one piece glass) Periodically insert a small piece of cardboard ( a business card) between the window trim and the window. Slide the card back & forth a few times to clear any dust or fibers from the window wash gap. Open the door and repeat from the other side of the glass.
Window Wash
(Recommended Frequency of 1 year)
WINDOW WASH (Models with three piece glass)
Periodically remove five screws which secur e the window wash bracket to the door frame, using a 5/16” sock et. Lift out the widow wash bracket, and set aside. Using a small brush, sweep out all debris buildup from behind the win­dow wash bracket. After all debris has been rem oved re­attach the window wash bracket.
Remove Window Wash Bracket (5 screws)
CREOSOTE REMOVAL (All Models)
When wood is burned slowly, it produces tar and other organic vapors, which com bine with expelled moisture to form creosote. The creosote vapors condense in the relatively cool chimney flue of a slow-burning fire. As a result, creosote residue accumulates on the flue lining.
When ignited this creosote makes an extremely hot fire. The chimney connector and chim ney should be inspec ted at least once every two months during the heating s eason to determine if a creosote buildup has occurred.
If creosote has accumulated it s hould be removed to re­duce the risk of a chimney fire.
* Inspect at minimum frequency stated until you establish a minim um f requency required for your installation (frequency
will vary depending upon fuel BTU value / ash content, usage, and misc. installation variables).
Continued, next page.
PAGE 29
Page 30
ANNUAL MAINTENANCE
Unplug and Ensure Stove is Cold Before Performing Any Maintenance Work. Include routine maintenance with an-
nual maintenance. The following areas need to be inspected and cleaned as part of annual maintenance:
(To be preformed by a certified technician).
Sweep Away Debris from Behind Window Wash Bracket
(Recommended Frequency of 1 year)
SMALL AREA PAINT TOUCH-UP
The stove body is painted with a quality high-temperature stove paint. Use only model TSPK-B Stove Paint, Catalog # 70K99. Do not touch-up your stove with any other paint.
Using one small piece of 320 grit sand paper and lightly sand the blemish so that the edges are “feathered” or smooth to the touch between the painted and bare surfaces. Do not let the sand paper gum up with paint, as this will cause scratches on the metal surface. If there are any scratches, use 600 grit sandpaper instead. Mask off surfaces you do not want painted. Paint lightly over the bare surface first as this will ac t as an un­dercoat. Then paint over a larger area in smooth even strokes to blend.
Profile 30 FS – Opening Side Panels
Profile 20 FS – Using a ¼” nut driver remove the #8 T EK
screw located at the front top of the panel (s ee following picture). Reinstall screw to prevent panel from opening accidentally!
Profile 20 FS – Opening Side Panels
#8 TEK
REAR STOVE COMPARTMENT (All Models)
The rear stove compartment should be cleaned periodi­cally (a minimum of once a year). DISCONNECT ELEC­TRICAL CORD PRIOR TO CLEANING STOVE. Any household dust, pet hair or sawdust should be vacuum ed or wiped out of the rear compartment of the stove, room air blower, and combustion blower (paying special atten­tion to vacuuming out the intakes of both blowers). The electrical components should be wiped clean.
Opening Side Panels
Profile 30 FS - Using a 5/16” nut driver remove the screw
from underneath the side panel at the front edge. Rein­stall screw to prevent panel from opening accidentally!
* Inspect at minimum frequency stated until you establish a minim um f requency required for your installation (frequency
will vary depending upon fuel BTU value / ash content, usage, and misc. installation variables).
PAGE 30
MOTOR LUBRICATION
The blowers are permanently lubricated by the manuf ac­turer. Do not apply oil to any part of the blower, doing so may cause damage.
Page 31
SPECIFICATIONS
- Profile 20 FS
Approx. Sq. Ft Heat Capacity ~1500 - 1800 sq. Ft.
Flue Size 3” Rear Width, Overall 23” Depth, Overall 22 3/4”
Depth, Overall w / 3” tee 28 1/2” Height 28 5/8” Floor to Rear
Flue Center 11 1/4” Facing back of unit,
outside edge of left side to center of rear flue outlet center 6 1/2”
Floor to Rear Outside Air Inlet 12”
Facing back of Unit outside edge of right side to center of air inlet 6 3/4”
BACK VIEW
SIDE VIEW
Floor Protection + Front and Sides:6” Requirements Back: 1”
Standard Features Fastfire Self Igniter
Wall Thermostat (wire
included) Hopper Capacity 55 lbs. Burn time 15-37 hours Fuse, Control Board 5 Amp, 250 volt, 3AG *
Fuse, Igniter 6 Amp, 125 volt * Heat Input (BTU’s per hour) 13,000-32,000 BTU / hr
Overall Efficiency 75-81% Emissions 0.4 gr / hr (varies w/size
and type of fuel) EPA ex-
empt. Shipping Weight 215 lbs. Room Fan 150 CFM; .8 Amps,
2175 rpm Auger Motor 1 RPM; .4 Amps Draft Fan 95 CFM: 1.0 Amps,
2880 rpm Options Nickel or Gold Trim Kits
4” Quick Disconnect
Log Set
Note: Dimensions shown are approximations only (+/- ¼”)
~ Square footage heating capacities are approxima-
tions only. They will vary depending upon the level of insulation, climate, house design, ceiling height, am­bient outside temperatures and how the stove is op­erated.
+
Non-combustible floor protection must be used when
installed on carpet (see Floor Protection, page 5).
♦♦♦♦ Fuel delivery and burn times will vary depending
on size and type of fuel used. Estimated heat in­put based on fuel value of 8500 BTU per lb.
* Fuses are rated as fast blow.
PAGE 31
Page 32
SPECIFICATIONS
- Profile 30 FS
Approx. Sq. Ft Heat Capacity ~1800 - 2000 sq. Ft.
Flue Size 3” Rear Width, Overall 25 7/8” Depth, Overall 24 7/8”
Depth, Overall w / 3” tee 30 3/4” Height 31 3/8” Floor to Rear
Flue Center 16 7/8” Facing Back of Unit,
outside edge on right to center of rear flue outlet 5 1/8”
Floor to Rear Outside Air Inlet 10”
Facing Back of Unit outside edge on right to center of air inlet 12 1/2”
Floor Protection + Front and Side: 6” Requirements Back: 1”
BACK VIEW
SIDE VIEW
Standard Features Fastfire Self Igniter
Wall Thermostat
(wire included) Hopper Capacity 80 lbs. Burn time 18-48 hours Fuse, Control Board 5 Amp, 250 volt, 3AG *
Fuse, Igniter 6 Amp, 125 volt * Heat Input (Max.) 14,000-39,000 BTU / hr
Overall Efficiency 81% Emissions 1.9 gr / hr (varies w / size
and type of fuel) EPA ex-
empt Ship Weight 270 lbs.
Room Fan 150 CFM; .8 Amps,
2175 rpm Auger Motor 1 RPM; .4 Amps
Draft Fan 95 CFM: 1.0 Amps,
2880 rpm Options Nickel or Gold Trim Kits
4” Quick Disconnect
Log Set
Note: Dimensions shown are approximations only (+/- ¼”)
~ Square footage heating capacities are approximations
only. They will vary depending upon the level of insu­lation, climate, house design, ceiling height, ambient outside temperatures and how the stove is operated.
+
Non-combustible floor protection must be used when
installed on carpet (see Floor Protection, page 5).
♦♦♦♦ Fuel delivery and burn times will vary depending
on size and type of fuel used. Estimated heat input based on fuel value of 8500 BTU per lb.
* Fuses are rated as fast blow.
PAGE 32
Page 33
SPECIFICATIONS - Profile 30 INS
Approx. Sq. Ft Heat Capacity ~ 1800-2000 sq. Ft.
Flue Size 3” Rear Width, Overall front (w/o surround) 26”
Width, Overall back (w/o surround) 24 1/8” Depth, Overall (w/o surround) 26 1/4” Height, rear (w/o surround) 19 15/16”
Height, front (w/o surround) 23 5/8” Floor to Rear
Flue Center 9 1/4” Fireplace Face to Rear
Flue Outlet Center (3” tee) 13 1/4” Dimensions into Fireplace
Minimum Height 20 1/8” Minimum Width @ Front (extends back 1 ½”) 32” Minimum Width @ Back 24 5/8” Minimum Depth 17 3/4”
Facing Back of Unit, Right Outside Edge of Unit to Center of Rear Flue Outlet 5”
Floor to Rear Outside Air Inlet 2 1/8”
BACK VIEW
SIDE VIEW
Facing Back of Unit, Right Outside Edge of Unit to Center of Air Inlet 12 7/16”
Floor Protection Requirements Front: 6”
Standard Features Fastfire Self Igniter
Wall Thermostat (wire in-
cluded) Hopper Capacity 50 lbs. Burn time 10-45 hours Fuse, Control Board 5 Amp, 250 volt, 3AG *
Fuse, Igniter 6 Amp, 125 volt * Heat Input (Max.) 14,000-39,000 BTU / hr
Overall Efficiency 81% Emissions 1.9 gr / hr (varies w/size
and type of fuel) EPA ex-
empt. Ship Weight 230 lbs. Room Fan 150 CFM; .8 Amps, 2175
rpm Auger Motor 1 RPM; .4 Amps Draft Fan 95 CFM: 1.0 Amps, 2880
rpm
TOP VIEW
Note: Dimensions shown are approximations only (+/- ¼”) ~ Square footage heating capacities are approximations
only. They will vary depending upon the level of insula­tion, climate, house design, ceiling height, ambient out­side temperatures and how the stove is operated.
+
Non-combustible floor protection must be used when
installed on carpet (see Floor Protection, page 5).
Options Nickel or Gold Trim Kits
4” Quick Disconnect
Log Set
♦♦♦♦ Fuel delivery and burn times will vary depending on
size and type of fuel used. Estimated heat input based on fuel value of 8500 BTU per lb.
* Fuses are rated as fast blow.
PAGE 33
Page 34
COMPONENT DEFINITIONS
AIR WASH
To inhibit buildup of soot on the door glass, air is deliv­ered to the glass through an air wash s ystem located in the doorframe surrounding the glass.
AUGER
It transfers the fuel down the burner tube into the firepot.
AUGER MOTOR
Motor specifications are: .4 Amp, 1 rpm (revolutions per minute). It drives the auger to deliver fuel to firepot.
BLOWER, CONVECTION (ROOM AIR)
The blower specifications ar e: 150 CFM (cubic feet per minute), .8 Amp, 2178 rpm (revolutions per minute). The blowers function is to transfer the heat from the appliance to heat the room air.
BLOWER, COMBUSTION (DRAFT INDUCER)
The blower specifications are: 95 CFM (cubic feet per minute), 1.0 Amp, 2880 rpm (revolutions per minute). It has a radial impeller to deliver m ore air to the firepot. It pulls air into the firepot by creating a negative pressure. This is done by extracting the exhaust gases out of the firebox and pushing the exhaust downstream to the f lue exit.
DISC, CONVECTION HIGH LIMIT (L250-30F, N / C)
If the temperature of the convection air chamber reaches 250° F., the high limit auto res et will “trip” and stop the flow of electricity to the auger motor. It will not automatically reset until it has cooled below 220° F).
DOOR SWITCH (Profile

30 FS and Profile

30 INS)
If the door is opened during operation (on model Profile 30 FS and Profile 30 INS), this switch disconnects power to the auger motor resulting in the unit shutting down.
ULTRAGRATE (BURN GRATE)
This is where combustion occurs.
HOPPER
The hopper is where the pellets are stored.
HEAT OUTPUT BUTTON
This is the main power button, which controls power to the feed system auger motor and draft fan. It has 3 f eed rate settings, which controls the burn rate.
PHOTOEYE
The photoeye is designed to signal the control board to discontinue power to the auger motor) if it does not sense a flame in the firepot.
PRESSURE SWITCH
The pressure switch is a safety device used to shut off the feed system (auger motor ) if there is too muc h back pressure in venting system. Som e possible causes are as follows:
The venting system is obstructed. High altitude or other misc. environmental condi-
tions affecting exhaust flow.
Improper venting system.
DISC, INLET HIGH LIMIT (L250-30F, N / C)
If negative pressure in the dwelling (ie. An extremely tight house which may not supply adequate combustion and ventilation air) causes the exhaust to pull back fr om the combustion air inlet, the heat fr om the exhaust will result in heat activation of this switch (tr ips at 250° F will stop the flow of electricity to the auger motor. It will not automatically reset until it has cooled below 220° F).
PAGE 34
Page 35
WIRING DIAGRAM
PAGE 35
Page 36
TROUBLESHOOTING
Qualified Technicians Only
Unplug Appliance Before Performing Any Troubleshooting or Maintenance
PROBLEM CAUSE(S) SOLUTIONS
1. Fire burns with a lazy orange flame. Pellets build up in the grate and the window gets sooted up.
There is insufficient combustion air. Remove any clinkers or ash from the bottom of the grate that might
be obstructing the primary air holes. Change to a better grade of fuel if necessary. Check that the damper has been opened enough for the amount of
fuel feed. Check that the heat exchange tubes are not coated with ash. Clean internal exhaust ducts. Check gasket seal around the door. Use a thin strip of paper, 1 in.
wide. Open the door and close it on the paper strip. A slight friction should be felt when the paper strip is pulled. Repeat this process at various locations around the door gasket. Replace the door gasket if necessary.
Check for blockage in the air inlet tube or exhaust pipe. Clean as necessary.
Close ash slide plates. Have your authorized Lennox Hearth Products dealer check your
combustion blower.
2. Fire goes out or stove shuts down automatically
3. Pellets will not feed.
Stove has run out of fuel. Pellets are not feeding. The high limit temperature switch has
tripped.
There is too much combustion air for the amount of fuel.
The hopper is empty. The auger motor or circuit board may
be defective. The pressure switch tap or hose may be blocked.
Back pressure in venting tripping pressure switch.
Thermostat is in stand-by mode. Thermostat wires disconnect.
High limit switch may have been tripped.
Door switch not engaged, stopping pellet feed (Profile
30 FS and Profile
30 INS).
Refill hopper. See (Pellets will not feed) this page. Allow stove to cool for 1 hour and re-light. If the stove has been
operating at a medium to high burn rate and the convection fan has been turned down low then the fan should be turned up higher. If this problem persists (particularly at lower burn rates) then the high limit snap switch should be replaced by your authorized dealer.
Adjust the damper to reduce combustion air flow.
Refill hopper. Check to be sure that there is no blockage in the pressure tap or
hose. Have your authorized Lennox Hearth Products dealer diag­nose the problem and clean or replace any necessary parts.
If new installation check for excessive 90˚ bends, long horizontal runs or excessive vertical run of 3” pipe. Possibly change to 4” pipe. If older installation check for excessive ash accumulation in pipe or other obstructions. Clean out pipe.
Check to see if thermostat is set to low or if sun is shining directly on thermostat.
Re-install wires. Allow stove to cool. Increase convection blower setting.
Have dealer check operation to determine if adjustment or re-
placement is necessary.
Self-aligning bearings in auger motor may be mis-aligned.
4. Blowers will not
There is no power to the stove. operate when the start button is de-
There is no power to the control board. pressed.
Gently tap the auger motor. Check that the stove is plugged in to the wall outlet. Check to see if your circuit breaker has tripped. Check the wire connections on the high limit snap switch and con-
trol board.
PAGE 36
Page 37
TROUBLESHOOTING
Qualified Technicians Only
Unplug Appliance Before Performing Any Troubleshooting or Maintenance
PROBLEM CAUSE(S) SOLUTIONS
5. There is soot or fly ash in the house.
The window is being cleaned when the
stove is operating.
Turn down the convection fan or turn off stove before cleaning to prevent dispersion of ash and soot into the room.
There is leakage at the joints between
the combustion fan, connection or
exhaust pipe connections. This will be
evidenced by dust on the impeller of
the convection fan, and in the heat
exchanger area.
The vacuum cleaner is leaking.
6. Stove acts as if a fire is present when
Excessive sun light may be shining
directly into firebox from window. there is not a fire in the grate.
7. Stove will not
The igniter element may have failed. light.
There is not enough pellets in the
grate.
8. Fault Photoeye not detecting flame.
Stove has run out of fuel.
A disk has tripped / pressure switch.
Seal up any leaks in the exhaust system with room temperature vulcanizing silicone sealer (RTV).
DO NOT use a standard household vacuum or “shop vac” as the filters will leak the fine particles of ash. Clean the stove with an approved ash vacuum ONLY.
Block excessive sunlight. Call authorized Lennox Hearth Products dealer if problem persists.
Check igniter element fuse in rear stove compartment. Call your authorized Lennox Hearth Products dealer. See alternate manual lighting procedure
Prime the feed system (see Initial Start-Up, page 22). Clean feed tube slot. Check for debris (see Photoeye page 28).
Check connection at control board following yellow wires to all con­nectors.
Refill hopper. Blower intake, exhaust passages and / or venting system needs
cleaning (follow routine and annual maintenance procedures).
Door switch not engaged, stopping
pellet feed (Profile
30 FS and Profile
30 INS).
Have dealer check operation to determine if adjustment or re-
placement is necessary. If this does not correct the problem contact your local authorized
Lennox Hearth Products dealer.
PAGE 37
Page 38
REPLACEMENT PARTS LIST / DIAGRAMS
Door Parts & Body Components Item # Part No. / Cat. No. Description Stove Model
1 14650006 Door Assembly, Firebox (with 3 Piece Glass) Profile 20 FS 2 HO297 Door Assembly, Firebox, DK-P30
(with 3 Piece Glass)
15051547 Gasket, Door, ¾” Rope, (8 Ft.) Profile 20 FS
61051000 Gasket, Door, 1” Rope, (7 Ft.) Profile 30 FS & INS (units with 3 piece
61057202 Gasket Kit, Glass (10 Ft.) All H0257 Glass, Front Profile 20 FS H0258 Glass, Side (order 2 if set is needed) Profile 20 FS H0254 Glass, Front Profile 30 FS & INS (units with 3 pc. glass)
H0255 Glass, Side (order 2 if set is needed) Profile 30 FS & INS (units with 3 pc. glass) 3 17250095 Handle Assembly, Door Profile 20 FS 4 17150095 Handle Assembly, Door Profile 30 FS & INS 5 14650047 Hinge Bracket Profile 20 FS 6 14750021 Hinge Bracket Profile 30 FS & INS 7 14650003 Panel, Left Side Profile 20 FS 8 14650004 Panel, Right Side Profile 20 FS 9 14750070 Panel, Left Side Profile 30 FS 10 14750075 Panel, Right Side Profile 30 FS 11 14650048 Panel, Rear Profile 20 FS 12 14750150 Panel, Rear Profile 30 FS 13 14750340 Panel, Left Side Profile 30 INS 14 14750345 Panel, Right Side Profile 30 INS 15 14750300 Panel, Top Profile 30 INS 16 14650012 Panel, Top Profile 20 FS 16 14750060 Panel, Top Profile 30 FS 17 14750186 Pedestal Assembly Profile 30 FS
12051409 Knob, Control Panel Door (6 per package
w/studs)
Includes gasket.
Profile 30 FS & INS
Profile
30 FS & INS (units with 1 piece
glass)
glass)
Profile 30 INS
Electrical Parts Item # Part # Description Stove Model
18 12046300 Auger Motor All 19 16053941 Control Board Profile 20 FS 19 16052112 Control Board Profile 30 FS & INS 20 12147705 Disc, High Limit, 250 DG (L250-30F,60T21) Set of 3 All 21 12140213 Igniter Probe, 400 W, 4.8 A All 22 14650043 Photoeye Assembly Profile 20 FS 23 14750127 Photoeye Assembly Profile 30 FS & INS 24 12058820 Power Cord, 8 feet All 25 16050205 Thermostat All 26 16050001 Pressure Switch All 27 12050815 Wiring Harness All
PAGE 38
Page 39
REPLACEMENT PARTS LIST / DIAGRAMS
18150150 Fuse , C on tro l B o ard , 5 Amp , 250 volt, Fast blow, 12pk. All 12055908 Fuse, Igniter, 6 Amp, 125 volt, Fast blow, 12pk. All
28 13050002 Switch, Door (set of 3) Profile 30 Series
Firebox Parts Item # Part # Description Stove Model
29 13640028 Clips, Brick Profile 20 FS 30 11750011 Clips, Brick Profile 30 FS & INS 31 14650011 Firebrick Set Profile 20 FS 32 14750015 Firebrick Set Profile 30 FS & INS 33 12051263 UltraGrate All
Auger System Components Item # Part # Description Stove Model
34 12051001 Bumper, Auger (Set of 5) All 35 12041300 Collar & Screw Set, Auger (Set of 3) All 36 17250241 Flange, Auger All 37 11756300 Shaft, Auger All
Misc. Item # Part # Description Stove Model
38 12050004 Brush, Cleaning All 39 61050003 Gasket, Auger Flange, 5pc. All 40 61050005 Gasket, Combustion Fan, 5pc. All 41 61057203 Gasket, Convection Fan, 5pc. All 42 61050016 Gasket, Quick Disconnect 5pc. All 43 12050011 Blower, Combustion All 44 12146109 * Blower, Convection, Hard Washer All 45 12055500 Tool, Grate Scraper All 46 12050093 Quick Disconnect 3” Vent Side All
* Includes gasket and four nuts.
1
2
PAGE 39
3
Page 40
REPLACEMENT PARTS DIAGRAMS
4
8
5
11
12
9
6
13
10
7
14
PAGE 40
Page 41
REPLACEMENT PARTS DIAGRAMS
15
16
19
20
24
25
17
18
21
26
22
27
23
PAGE 41
Page 42
REPLACEMENT PARTS DIAGRAMS
28
29
30
33
34
35
38
39
31
32
36
37
40
41
PAGE 42
Page 43
REPLACEMENT PARTS DIAGRAMS
42
43
44
45
46
PAGE 43
Page 44
OPTIONAL ACCESSORIES DIAGRAMS
Optional Accessories Item # Part # Model Description Stove Model
1 14M46 TKP2-G Trim Kit, Gold 1 14M47 TKP2-N Trim Kit, Nickel 1 14M49 TKP3-G Trim Kit, Gold 1 14M50 TKP3-N Trim Kit, Nickel 2 14M81 QDPC-4 Quick Disconnect Pipe Connector, 4” * All
70K99 TSPK-B Touch-up Spray Paint Kit, Black All 3 14M52 SKSP3 Surround Kit, Small, 28 ½” x 40 ¾”, Black 3 14M53 SKMP3 Surround Kit, Medium, 32” x 44”, Black 3 14M54 SKLP3 Surround Kit, Large, 36 x 48”, Black 4 14M55 STKSP3-B Surround Trim Kit, Small, 28 ½” x 40 ¾”, Brass 4 14M56 STKMP3-B Surround Trim Kit, Medium, 32” x 44”, Brass 4 14M57 STKLP3-B Surround Trim Kit, Large, 36 x 48”, Brass 5 H0244 DLS-P20 Decorative Log Set 6 H0245 DLS-P30 Decorative Log Set
1 2
Converts from standard 3” outlet to 4”
3
Profile 30 FS & INS
Profile Profile Profile Profile
Profile Profile Profile Profile Profile Profile Profile Profile
20 FS
20 FS
30 FS & INS
30 FS & INS
30 INS
30 INS
30 INS
30 INS
30 INS
30 INS
20 FS
30 Series
4
(1) Profile 20 FS & INS
5
6
4”
Panel and Trim Sizes Large:
36” (91.4cm) height 44” (121.9cm) width
Medium: 32” (81.3cm) height 44” (111.75cm) width
Small: 28 ½” (72.4cm) height 40 ¾” (103.5cm) width
PAGE 44
Page 45
PROFILE 20 PELLET STOVE SAFETY MODEL
Note that your stove’s serial number is printed on the safety label, which is located near the inside of the hopper. Your stove’s serial number is preceded by a “WH-”(Example WH-0000000).
PAGE 45
Page 46
PROFILE 30 PELLET STOVE SAFETY LABEL
Note that your stove’s serial number is printed on the safety label, which is located near the inside of the hopper. Your stove’s serial number is preceded by a “WH-”(Example WH-0000000).
PAGE 46
Page 47
OWNERSHIP RECORDS
Dealer’s Name: Dealer’s Address: City: State: Zip Code: Serial Number: Date of Purchase: Date Installed: Notes:
SERVICE AND MAINTENANCE LOG
Service Service Service Date Technician Description
PAGE 47
Page 48
1110 West Taft Avenue
Orange, CA 92865
Loading...