WHITE-RODGERS
Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INJURY AND/OR PROPERTY DAMAGE.
These room thermostats have been designed for controlling cooling equipment operating on line voltage with
heavy electrical loads. They are suitable for operation of
unit coolers, room coolers, etc., or any similar refrigeration application requiring a heavy duty room thermostat.
Models are available with various ranges for meeting the
needs of almost any application.
THESE CONTROLS MUST BE INSTALLED BY A
QUALIFIED INSTALLER.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical
codes and ordinances.
This control is a precision instrument, and should be
handled carefully. Rough handling or distorting components could cause the control to malfunction.
This control has been accurately calibrated at the factory.
Any attempt to calibrate this control will void the WhiteRodgers warranty.
The proper location of a heavy duty room thermostat is
very important to assure good performance. The following
general rules will help in determining the proper location:
1. Make sure that it is in a place where air circulates
around it freely. This is important.
2. Never install it on or near an outside wall.
3. Keep it away from windows or doors.
4. Don’t locate it too close to a strong light or any other
false source of heat such as direct sunlight, steam
lines, etc.
5. Mount it on a post or a partitioning wall, but make sure
that there are no pipes or duct work in that wall or
directly behind it.
6. If the electrical conduit leads into a cooler or a warmer
room, plug up the space around the wires in the conduit
with rock wool.
TYPE 151
ROOM THERMOSTAT
Cooling Service, External Dial
INSTALLATION INSTRUCTIONS
DESCRIPTION
W
H
I
T
E
-
R
S
O
R
D
E
G
90
70
80
50
60
40
PRECAUTIONS
To prevent electrical shock and/or equipment
damage, disconnect electric power to system, at
main fuse or circuit breaker box, until installation
is complete.
WARNING
Do not use on circuits exceeding specified voltages. Higher voltages will damage control and
could cause shock or fire hazard.
INSTALLATION
CONCRETE
PLASTER
JUNCTION BOX
THERMOSTAT
CONDUIT
INSIDE WALL
CONDUIT
ALONG WALL
WALL INSTALLATION
The mounting plate for this thermostat has two
5
holes 3
/16”apart for attaching the control on a
standard switch box.
Figure 1
WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO.
9797 REAVIS RD., ST. LOUIS, MO. 63123
(314) 577-1300, FAX (314) 577-1517
9999 HWY. 48, MARKHAM, ONT. L3P 3J3
(905) 475-4653, FAX (905) 475-4625
Printed in U.S.A.
PART NO. 37-1118B
Replaces 37-1118
9548
INSTALLATION CONT.
IMPORTANT
When control is located where ambient temperature is
below freezing, choose a control location far enough
away from doors and windows so that moisture will not
condense on control.
If the thermostat is used with unit coolers, the following
suggestions may help. (See Fig. 2).
1. Position “A” is good if it is sufficiently close to the unit
cooler so that the return air to the cooler flows over the
thermostat.
2. Position “B” is good if it is not necessary to make
frequent adjustments of the dial setting.
3. Position “C” is all right if it is sufficiently far from the
cooler that air flowing over the thermostat is not much
above the average room temperature.
4. In general, position “D” is not advisable because the
post may prevent air from circulating over the thermostat.
CEILING
POST
UNIT
B
D
C
RETURN AIR
FLOOR
Figure 2
PARTITION
WALL OR POST
DIRECTLY
BEHIND UNIT
A
WIRING
All wiring should be done in accordance with local and national electrical codes and ordinances.
If the manufacturer of the cooling equipment has supplied a wiring diagram, follow the manufacturer’s recommendations. The following diagrams show the general use of these controls.
TEMPERATURE
CONTROL
TO LINE SWITCH
AND POWER SUPPLY
HOT
GND
Circuit showing temperature control to open and
close refrigerant valve. Suction pressure control
starts and stops compressor through motor starter.
HIGH SIDE
PRESSURE CONTROL
(IF USED)
MOTOR
STARTER
Circuit showing temperature control controlling compressor directly.
TO LINE SWITCH
AND POWER SUPPLY
HIGH SIDE
PRESSURE
CONTROL
SUCTION
PRESSURE
CONTROL
TEMPERATURE
CONTROL
SOLENOID
REFRIGERANT
VALVE
SETTING THE DIAL
To set the dial, simply move it so that the indicating line on
the case points to the temperature at which the contacts
are to open as the temperature drops.
2