White Rodgers G9T, FG9 User Manual

USER’S INFORMATION, MAINTENANCE AND
EFFICIENCY RATING CERTIFIED
SERVICE MANUAL
MODELS: P*UR / G9T-UP / FG9-UP (Upflow)
CONTACT INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
TABLE OF CONTENTS
USER’S INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
INSTRUCTIONS FOR EXAMINING THE FURNACE
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
HOW YOUR GAS FURNACE WORKS . . . . . . . . . . . . . . . . . . . . . .3
START-UP AND SHUTDOWN INSTRUCTIONS . . . . . . . . . . . . . . .3
Read the Instructions Below Before Trying to Start the Furnace . . 3
Operating Instructions: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
To Turn Off the Appliance: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
FURNACE USER MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . .4
SERVICE AND MAINTENANCE MANUAL . . . . . . . . . . . . . . . . . . . . . 4
SAFETY SECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
FURNACE MAINTENANCE SECTION . . . . . . . . . . . . . . . . . . . . . . .4
Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Removing Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Blower Care . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
CONTACT INFORMATION
• Go to website at www.york.com click on “contact”, then click on “contact form” and follow the instructions.
• Contact us by mail:
York International
Consumer Relations
5005 York Drive
Norman, OK 73069
Motor Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Continuous Blower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Intermittent Blower - Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Heating Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Hot Surface Ignition System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
FURNACE CLEANING SECTION . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Burner Removal/Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Cleaning the Heat Exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Cleaning the Secondary Heat Exchanger . . . . . . . . . . . . . . . . . . .6
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
FURNACE CONTROL DIAGNOSTICS . . . . . . . . . . . . . . . . . . . . . . .7
REPLACEMENT PARTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
FIELD INSTALLED ACCESSORIES - NON-ELECTRICAL . . . . . .10
FIELD INSTALLED ACCESSORIES - ELECTRICAL . . . . . . . . . . .10
REPLACEMENT PART CONTACT INFORMATION . . . . . . . . . . . . .10
LIMITED WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
The manufacturer recommends that the user read all sec­tions of this manual and keep the manual for future refer­ence.
FIRE OR EXPLOSION HAZARD - Failure to follow safety
warnings exactly could result in serious injury, death, or prop­erty damage.
Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone (including cell phone) in your building.
Leave the building immediately.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire depart­ment.
Installation and service must be performed by a quali-
fied installer, service agency or the gas supplier.
SECTION I: USER’S INFORMATION
SAFETY
1. The furnace area must be kept clear and free of combustible mate­rials, gasoline and other flammable vapors and liquids.
2. Insulating materials may be combustible. The furnace must be kept free and clear of insulating materials. The furnace area must be examined when installed in an attic or other insulated space or when insulation is added to be sure that the insulation material has been kept away from the furnace.
3. The furnace needs air for combustion in order to operate properly and safely. Do not block or obstruct air openings on the furnace, air openings to the area where the furnace is installed, or spaces around the furnace.
4. Follow the instructions exactly as shown on the OPERATING INSTRUCTION LABEL or the Start-up and Shutdown Instructions on Page 3 of this manual when lighting the furnace or turning the furnace off.
5. Should the gas supply fail to shut off or if overheating occurs, shut off the gas valve to the furnace before shutting off the electrical supply.
6. Do not use this furnace if any part has been under water. A flood­damaged furnace is extremely dangerous. Attempts to use the fur­nace can result in fire or explosion. A qualified service agency should be contacted to inspect the furnace and replace all gas controls, control system parts, electrical parts that have been wet or the furnace if deemed necessary.
035-19592-001 Rev. C (0204)
035-19592-001 Rev. C (0204)
BURNER BOX
PRESSURE SWITCH
BLOWER
GAS VALVE
VENT PIPE
CONDENSATE DRAIN SYSTEM
INDUCER ASSEMBLY
INDUCER MOTOR
CONTROL BOARD
FIGURE 1: Component Locations
7. NEVER . . .Store flammable materials of any kind near your fur­nace. Gasoline, solvents, and other volatile liquids should be stored only in approved containers outside your home. These materials vaporize easily and are extremely dangerous.
8. NEVER . . .Store cleaning materials near your furnace. Materials such as bleaches, detergents, powdered cleansers, etc., can cause corrosion of the heat exchangers.
9. NEVER . . . Use the area around your furnace as a storage area for items which could block the normal flow of air. This flow of air is required for ventilation of the various furnace components.
INSTRUCTIONS FOR EXAMINING THE FURNACE INSTALLATION
It is the owner’s responsibility to ensure that an annual inspection of the entire heating portion of the unit is made by a qualified service agency.
1. Examine the heating exchanger, vent/combustion air piping, vent connectors and chimney to be sure they are clear and free of obstructions.
2. Examine the vent pipe making sure it is in firmly place, that it slopes slightly upward and is physically sound without holes and all of the connections are secure.
3. Examine the return-air duct connections to make sure they are physically sound, sealed to the furnace casing, and the ducts ter­minate outside the space containing the furnace.
4. Examine the furnace casing making sure the physical support is sound without sagging, cracks or gaps. Examine the furnace base making sure it is physically sound without cracks, gaps or sagging and has a good seal.
5. Examine the furnace casing for obvious signs of deterioration.
6. Examine the burner flames to make sure they are in good adjust­ment. Refer to the pictorial sketch shown in Figure 2 as a compari­son to the actual flame.
7. Examine the furnace as outlined above in steps “1 - 6” before each heating season. Use Figure 3 for visual reference.
COMBUSTION AIR INTAKE
BURNER FLAME
FIRE OR EXPLOSION HAZARD This furnace is designed and approved for use with Nat-
ural Gas and (LP) Propane Gas ONLY. DO NOT BURN ANY LIQUID FUEL OR SOLID FUEL IN THIS FURNACE.
Burning any unapproved fuel will result in damage to the furnace heat exchanger, which could result in Fire, Per­sonal Injury, and/or Property Damage.
EXAMINE HEA T EX CHANGER INTERNAL VENT COMBUSTION AIR PIPE. MUST REMOVE PANEL
5
EXAMINE ENTIRE FURNACE CASING SHOWN IN ALL DRAWINGS
3
EXAMINE RETURN-AIR DUCT CONNECTION
4
EXAMINE FURNACE CASING
TO EXAMINE.
FIGURE 2: Burner Flame Drawing
6
REMOVE PANEL TO EXAMINE BURNER FLAMES
MANIFOLD
2
EXAMINE EXTERNAL VENT PIPE
MAIN BURNER
4
EXAMINE FURNACE
CASING
INNER FLAME CONES
3
EXAMINE RETURN-AIR DUCT CONNECTION
(SIDE OR BOTTOM)
FIGURE 3: Furnace Examination Checkpoints
2 Unitary Products Group
035-19592-001 Rev. C (0204)
HOW YOUR GAS FURNACE WORKS
Your furnace is a very easy appliance to take for granted. Season after season, it sits there in your home, keeping you warm and comfortable. For this reason, you may never have given much thought to the way your furnace operates. In order to get the safest and most efficient oper­ation from your furnace, you should understand how your furnace does its job.
When you set your thermostat to provide more heat in your home, you are starting the heating cycle of the furnace. First, the inducer motor starts to purge the heat exchanger of any remaining gases. Next, the hot surface ignitor glows and after a warm-up period the gas valve opens and ignition occurs. A short time later, the blower starts and dis­tributes the warm air throughout the home. When the temperature set­ting on your thermostat is reached, the gas valve closes, the main burners are turned off, and the blower continues to run until the remain­ing warm air in the system is distributed. When the blower stops, the heating cycle has ended.
START-UP AND SHUTDOWN INSTRUCTIONS
Read the Instructions Below Before Trying to Start the Furnace
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury, and/or loss of life.
A. This appliance does not have a pilot. It is equipped with an ignition
device which automatically lights the burner. Do not try to light the burner by hand.
B. BEFORE OPERATING; smell all around the appliance area for
gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
C. Use only your hand to push the gas control switch to the “on” posi-
tion. Never use tools. If the switch will not operate by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water. Imme-
diately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control, which has been under water.
Operating Instructions:
1. STOP! Read the safety information above.
2. Set the thermostat to the lowest setting.
3. Turn off all electric power to the appliance.
4. Remove burner access panel.
5. Move gas control switch to the “OFF” position. Do not force.
6. Wait five (5) minutes to clear out any gas. If you then smell gas, STOP! Follow “B” in the safety information above. If you don’t smell gas, go to next step.
7. Move gas control switch to the “ON” position. Do not force.
8. Replace burner access panel.
9. Turn on all electric power to the appliance.
10. Set thermostat to the desired setting. Burner will light, which may take 30-60 seconds.
11. After three (3) trials for ignition, if the appliance will not operate fol­low the instructions, “TO TURN OFF THE APPLIANCE” and call your service technician or gas supplier.
To Turn Off the Appliance:
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be per­formed.
3. Remove burner access panel.
4. Move gas control switch to the “OFF” position.
5. Replace burner access panel.
Should overheating occur, or the gas valve fail to shut off, turn the external manual gas valve in the gas supply line to the furnace to the “off” position and let the furnace cool of f before shutting off the electrical power supply. Refer to Figure 5.
OUTLET PRESSURE PORT
INLET
WRENCH BOSS
INLET PRESSURE PORT
ON/OFF SWITCH
FIGURE 4: Gas Valve - White Rodgers
EXTERNAL MANUAL SHUTOFF VALVE
TO GAS SUPPLY
GROUND JOINT UNION MAY BE INSTALLED
DROP
INSIDE OR OUTSIDE UNIT.
LEG
FIGURE 5: Gas Piping NOTE: The spring-loaded safety cut-off switch, mounted under the
blower deck will automatically cut off the electrical power supply to the furnace when the blower panel is removed. As a safety precaution, all electrical power and the gas supply to the furnace should be turned off before servicing.
OUTLET
MAIN REGULATOR ADJUSTMENT
TO GAS SUPPLY
Unitary Products Group 3
035-19592-001 Rev. C (0204)
FURNACE USER MAINTENANCE
Before proceeding, be sure the area is well ventilated. Turn the thermostat OFF. If the blower is running, wait until it stops automatically. Turn OFF the gas and electrical power supplies to the furnace. Check all metal parts and surfaces to be sure they have cooled to room temperature before you begin.
Every time the filters are changed the following items should be visually inspected:
• Check combustion air and vent pipe for blockage or leakage.
• Check all components to be sure they are in good condition and that there are no obvious signs of deterioration.
• Check the drain lines to make sure there are no cracks or leaks.
• Check for dirt or lint on any surfaces or on components. Do not try to clean any of the surfaces or components. Cleaning of the fur­nace and its components must be done by a qualified service pro­fessional.
If, during the inspection of your furnace, you find any of the following conditions:
• Excessive amounts of dust and lint on components.
• Damaged or deteriorated components or surfaces.
• Leaks or blockage in the vent pipe passages.
• Water on any surface inside or outside of the furnace.
Do not operate the furnace, call a certified dealer / servicing contractor to check and / or clean your furnace, or for more information if you have questions about the operation of your furnace.
If all components appear to be in good operating condition, replace the front panels. Turn ON the gas and electrical power supplies to the fur­nace, and set thermostat to the desired temperature.
SECTION II: SERVICE AND MAINTENANCE MANUAL
2. The furnace vent and combustion air intake passageways. Should it be necessary to service the vent/air intake system, the manufac­turer recommends this service be conducted by a qualified service agency. The operation of this appliance requires the reassembly and resealing of the vent/air intake system.
3. The furnace burners, ignitor and flame sensor.
4. The condensate collection and disposal system. If any disassem­bly of components containing flue or vent gases is required, a qualified service agency must perform the service.
Air Filters
The filters should be checked every 3 months. On new construction, check the filters every week for the first four weeks and every three weeks after that, especially if the indoor fan is running continuously. When replacing the filter(s), refer to Table 1 to be sure you install the right size filter for your furnace. Dirty filters greatly restrict the flow of air and may cause damage to the moving parts of the furnace. If the filters become clogged the heat exchangers and blower motor could overheat resulting in a potentially dangerous situation.
Never operate your furnace without a suitable air filter.
Removing Filters
Internally Mounted Air Filters
Most upflow furnaces have their filters located on the side or bottom of the furnace in a filter wire retainer located inside the blower compart­ment. To check filters located in the blower compartment:
1. Remove the upper furnace door by lifting up. Pull out bottom of door and lower from furnace.
2. Remove the blower compartment panel by lifting up.
3. The filters will be located on the bottom or the one of the sides. To remove bottom-mounted or side mounted filter (s) on all furnaces, push the looped end of the filter retainer rod in, and then move away from the filter.
4. Reverse the procedure to reinstall filters.
POSITION WIRE RETAI N ER (IF PROVIDED) UNDER FLANGE
SAFETY SECTION
The following safety rules must be followed when servicing the furnace.
ELECTRIC SHOCK, FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in
dangerous operation, serious injury, death or property damage.
Improper servicing could result in dangerous operation, serious injury, and death or property damage.
• Before servicing, disconnect all electrical power to the fur­nace.
• When servicing controls, label all wires prior to discon­necting. Reconnect wires correctly.
• Verify proper operation after servicing.
FURNACE MAINTENANCE SECTION
The furnace should be cleaned and adjusted by a certified dealer or qualified service contractor once a year or before the start of every heating season. The following items must be cleaned and serviced or replaced if there are signs of deterioration.
1. The vent terminal screen (if applicable).
CLIPS
RIGHT SIDE INSTALLATION SHOWN
FIGURE 6: Upflow Internal Filter Retainer Externally Mounted Air Filters
Some installations may have the air filter in a rack attached to the cas­ing of the furnace or placed in the return air duct. You can gain access to the filter by pulling on the door or unscrewing the retaining screw, then slide the filter(s) out of its channel. Replace throw away filter(s) with the same size new filter(s). Throw away filter(s) may be replaced with cleanable filter(s) at this time. Cleanable filter(s) may be cleaned as described in the manufacturer instructions or as described below and then re-installed.
To replace the filter after cleaning you must do the following:
1. Slide filter into place.
2. Snap the door on or place the door in position and tighten the retaining screws, if provided.
3. Make sure the door is secure to the end of the filter rack.
IF FILTER PROVIDED
FURNACE FRONT
4 Unitary Products Group
035-19592-001 Rev. C (0204)
TABLE 1:
Filter Sizes
Input / Output
BTU/H (kW)
CFM (cm/m)
Cabinet
Size
Side (in) Side (mm) Bottom (in) Bottom (mm)
40/37 (11.71/10.84) 1000 (28.32) 14-1/2” (A) 16 x 25 406 x 635 14 x 25 356 x 635 60/55/ (17.57/16.10) 1000 (28.32) 17-1/2” (B) 16 x 25 406 x 635 16 x 25 406 x 635 80/75/ (23.42/21.96) 1200 (33.98) 17-1/2” (B) 16 x 25 406 x 635 16 x 25 406 x 635 80/75/ (23.42/21.96) 1600 (45.31) 21” (C) 16 x 25 406 x 635 20 x 25 508 x 635
100/95 (29.28/27.82) 1400 (39.64) 21” (C) 16 x 25 406 x 635 20 x 25 508 x 635
100/95 (29.28/27.82) 2000 (56.63) 21” (C) (2) 16 x 25 (2) 406 x 635 20 x 25 508 x 635 120/112/ (35.14/32.80) 2000 (56.63) 24-1/2” (D) (2) 16 x 25 (2) 406 x 635 22 x 25 559 x 635 140/130/ (40.99/38.06) 2000 (56.63) 24-1/2” (D) (2) 16 x 25 (2) 406 x 635 22 x 25 559 x 635
How to Clean your Filter
High-velocity filters may be cleaned with a vacuum cleaner or washed with a garden hose. Be sure to shake off excess water and allow filter to completely dry before re-installing the filter.
Blower Care
Even with good filters properly in place, blower wheels and motors will become dust laden after long months of operation. The entire blower assembly should be inspected annually. If the motor and wheel are heavily coated with dust, they can be brushed and cleaned with a vac­uum cleaner. If the blower cannot be properly cleaned without removing it from the furnace, then this service must be performed by a qualified service agency.
Intermittent Blower - Cooling
Cooling/heating thermostats have a fan switch that has an ON and AUTO position. In the AUTO position the thermostat circuit is completed between terminals R and G when there is a call for cooling. The motor will operate on the speed tap wire that is connected to the cooling termi­nal on the control board. The fan off setting is fixed at 60 seconds for SEER enhancement.
Heating Cycle
When the thermostat switch is set on HEAT and the fan is set on AUTO, and there is a call for heat, a circuit is completed between terminals R and W of the thermostat. When the proper amount of combustion air is being provided, the pressure switch will close, the ignition control pro­vides a 17-second warm-up period, the gas valve then opens, the gas starts to flow, ignition occurs and the flame sensor begins its sensing function. The blower motor will energize 30 seconds after the gas valve
Make sure you DO NOT move the clip on weight on the indoor fan wheel when cleaning the wheel. This weight is used to balance the wheel. Moving the weight will cause the fan wheel to vibrate.
Motor Lubrication
The motors in these furnaces are permanently lubricated, and do not require periodic oiling.
SEQUENCE OF OPERATION
The following describes the sequence of operation of the furnace. Refer
opens, if a flame is detected. Normal furnace operation will continue until the thermostat circuit between R and W is opened, which causes the ignition system and gas valve to de-energize and the burner flames to be extinguished. The vent motor will operate for 15 seconds and the blower motor will operate for the amount of time set by the fan-off delay jumper located on the control board. See Figure 7. The heating cycle is complete, and ready for the start of the next heating cycle.
RED-LOW SPEED
BLU-MEDIUM SPEED
BLK-HIGH SPEED
MOTOR LEADS
to Figure 1 for component location.
120
180
BLK
BLU
RED
60
COOL
HEAT PARK PARK
LINE XM
90
FAN OFF ADJUSTMENT
SWITCHES
Continuous Blower
Cooling/heating thermostats have a fan switch that has an ON and AUTO position. In the ON position the thermostat circuit is completed between terminals R and G. The motor will operate on the speed tap wire that is connected to the cooling terminal on the control board. To obtain a constant air circulation at lower flow rate, change the high­speed wire to either the medium speed wire or the low speed wire.
FIGURE 7: Typical Heat/Cool Speed Tap Connections
Unitary Products Group 5
035-19592-001 Rev. C (0204)
If the flame is not detected within 2 seconds of the gas valve opening, the gas valve is shut off and a retry operation begins. If the flame is lost for 2 seconds during the 10-second stabilization period, the gas valve is shut off and a retry operation begins. During a retry operation, the vent motor starts a 15 second inter-purge and the ignitor warm-up time is extended to 27 seconds. If the flame is established for more than 10 seconds after ignition during a retry, the control will clear the ignition attempt (retry) counter. If three retries occur during a call for heat, the furnace will shut down for one hour. If at the end of the one hour shut down there is a call for heat, the furnace will initiate a normal start cycle. If the problem has not been corrected the furnace will again lockout after three retries.
A momentary loss of gas supply, flame blowout, or a faulty flame probe circuit will result in a disruption in the flame and be sensed within 1.0 seconds. The gas valve will de-energize and the control will begin a recycle operation. A normal ignition sequence will begin after a 15 sec­ond inter-purge. If during the five recycles the gas supply does not return, or the fault condition is not corrected the ignition control will lock­out for 60 minutes.
During burner operation, a momentary loss of power for 50 milliseconds or longer will de-energize the gas valve. When the power is restored, the gas valve will remain de-energized and the ignition sequence will immediately restart.
Hot Surface Ignition System
HOT SURFACE IGNITION SYSTEM Do not attempt to light this furnace by hand (with a match or any other means). There may be a potential shock hazard from the components of the hot surface ignition system. The furnace can only be lit automatically by its hot surface ignition system.
FURNACE CLEANING SECTION
NOTE: The cleaning operations listed below must be performed only by
a qualified service agency.
Burner Removal/Cleaning
The main burners should be checked periodically for dirt accumulation. If cleaning is required, follow this procedure:
1. Turn off the electrical power to the unit.
2. Turn off the gas supply at the external manual shut-off valve and loosen the ground union joint.
3. Remove the upper access panel and remove the burner box cover.
4. Disconnect wires from flame sensor, rollout switch and HSI igniter. Remove igniter carefully, as it is easily broken.
5. Remove the screws that hold the burner box assembly to the vest panel and remove the assembly.
6. Remove burners from the burner assembly.
7. Burners may be cleaned by rinsing in hot water.
8. Reassemble the burners in the reverse order.
Cleaning the Heat Exchanger
1. Turn off the electrical power to the unit.
2. Turn off the gas supply at the external manual shut-off valve and loosen the ground union joint.
3. Remove the upper access panel and remove the burner box cover.
4. Disconnect wires from flame sensor, rollout switch and HSI igniter. Remove igniter carefully, as it is easily broken.
5. Remove the screws that hold the burner box assembly to the vest panel and remove the assembly.
6. Remove burners from the burner assembly.
7. Remove the upper cover plate at the top of the furnace. Remove the internal baffle.
8. The upper portion of the heat exchanger is now exposed.
9. With a long flexible wire brush, clean inside each tube at both the top and bottom. The brush must pass around the rear heat exchanger tubes and then vacuum loose the scale and dirt from each tube.
10. Clean - vacuum all burners.
11. Replace all components in reverse order. Reconnect all wiring.
12. Restore electrical power and gas supply to the furnace.
13. Check furnace operation.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and danger­ous operation. Verify proper operation after servicing.
Cleaning the Secondary Heat Exchanger
1. Follow steps 1 - 8 under cleaning the Heat Exchanger.
2. Remove the vent piping from the vent blower housing. Disconnect the drain lines from the vent blower housing and from the conden­sate drain pan. Remove the vent blower housing blower and the condensate pan. The turbulators can then be gently removed from the secondary heat exchanger.
3. Using a stiff wire brush, remove the loose scale or soot from each tube.
4. Vacuum the secondary heat exchanger.
5. Finish the cleaning procedure by following steps 11 thru 13 under cleaning the Heat Exchanger.
TROUBLESHOOTING
The following visual checks should be made before troubleshooting:
1. Check to see that the power to the furnace and the ignition control module is ON.
2. The manual shut-off valves in the gas line to the furnace must be open.
3. Make sure all wiring connections are secure.
4. Review the sequence of operation. Start the system by setting the thermostat above the room temperature. Observe the system’s response. Then use the troubleshooting section in this manual to check the system’s operation.
FURNACE CONTROL DIAGNOSTICS
The furnace has built-in, self-diagnostic capability. If a system problem occurs, a blinking red LED shows a fault code. It is located behind a clear view port in the blower compartment door. DO NOT remove the furnace blower compartment panel OR turn off furnace power, as either action will clear the control’s memory of the fault.
The control continuously monitors its own operation and the operation of the system. If a failure occurs, the LED will indicate the failure code. If the failure is internal to the control, the light will stay on continuously. In this case, the entire control should be replaced, as the control is not field repairable.
Flash sequence codes 1 through 11 are as follows: LED will turn “on” for one second and “off” for one second. This pattern will be repeated the number of times equal to the code. For example, six “on” flashes equals a number 6 fault code. All flash code sequences are broken by a 2 sec­ond “off” period.
6 Unitary Products Group
035-19592-001 Rev. C (0204)
Never bypass pressure switch to allow furnace opera­tion. To do so will allow furnace to operate under poten­tially hazardous conditions.
Do not try to repair controls. Replace defective controls with UPG Source 1 Parts.
Never adjust pressure switch to allow furnace operation.
CONTINUOUS FLASH: This indicates that flame was sensed when there was not a call for heat. With this fault code the control will turn on both the inducer motor and supply air blower. A gas valve that leaks through or is slow closing would typically cause this fault.
2 FLASHES: This indicates that the normally open pressure switch contacts are stuck in the closed position. The control confirms these contacts are open at the beginning of each heat cycle. This would indi­cate a faulty pressure switch or miswiring.
3 FLASHES: This indicates the normally open pressure switch contact did not close at the beginning of the heat cycle. This could be caused by a number of problems faulty inducer, blocked vent pipe, broken pres­sure switch hose or faulty pressure switch.
4 FLASHES: This indicates that a primary or auxiliary limit switch has opened its normally closed contacts. With this fault code the control will operate the supply air blower and inducer. This condition may be caused by: dirty filter, improperly sized duct system, incorrect blower speed setting, incorrect firing rate or faulty blower motor.
5 FLASHES: This fault is indicated if the normally closed contacts in the rollout switch opens. The rollout control is manually reset. If it has opened, check for proper combustion air, proper inducer operation, and primary heat exchanger failure or burner problem. Be sure to reset the switch after correcting the failure condition.
6 FLASHES: This indicates that after the unit was operating, the pres­sure switch opened 4 times during the call for heat. If the main blower is in a “Delay on” mode it will complete it, and any subsequent delay off period. The vent motor continues to operate until the pressure switch re-closes or a call for heat is removed.
7 FLASHES: This fault code indicates that the flame could not be established. This no-light condition occurred 3 times (2 retries) during the call for heat before locking out. Low gas pressure, faulty gas valve, faulty hot surface ignitor or burner problem may cause this.
8 FLASHES: This fault is indicated if the flame is lost 5 times (4 recy­cles) during the heating cycle. This could be caused by low gas pres­sure or faulty gas valve.
9 FLASHES: Indicates reversed line voltage polarity. Both heating and cooling operations will be affected. Check polarity at furnace and branch.
11 FLASHES: This fault will be indicated if the rollout jumper wire con­nection soldered into the board is broken. If this fault occurs the control will have to be replaced. This fault may also occur in installations where an improper ground is present. Prior to replacing control, verify that unit is properly grounded.
STEADY ON: This fault occurs if the gas valve is energized when there is no call for heat. If this happens the vent motor is energized and will remain energized for 5 seconds or until the fault clears itself at which point the vent motor de-energizes. This failure is counted as a recycle. Check the gas valve and control for proper operation.
60-MINUTE AUTOMATIC RESET FROM LOCKOUT: This control includes a “watchdog” type circuit that will reset from a lockout condition after 60 minutes. Operational faults 1,6,7,8 and Steady On will be reset. This provides protection to an unoccupied structure if a temporary con­dition exists causing a furnace malfunction. An example would be a low incoming gas supply pressure preventing unit operation. When the gas pressure is restored, at some point the “watchdog” would restart the unit and provide heat for the house.
NOTE: If a flame is detected the control flashes the LED for 1/8 of a
second and then enters a flame stabilization period.
IGNITION CONTROL (P/N 031-01972-001)
Normal flame sense current is approximately
3.7 microamps DC (µa)
Low flame signal control lockout point is
0.9 microamps DC (µa)
Thermostat Satisfied
0
OFF
15 Sec. Post Purge
OFF
OFF
60, 90, 120, 180 SEC. Selectable Fan Off Delay
OFF
OFF
OFF
OFF
(Seconds)
THERMOSTAT
INDUCER
IGNITOR
MAIN VALVE
HUMIDIFIER
ELECTRONIC AIR CLEANER
CIRCULATING BLOWER
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Thermostat Calling for Heat
0
2
ON
ON
ON
17 22
ON
Fan on Delay 30 Seconds
OFF
52
ON
OFF
ON
OFF
ON
OFF
FIGURE 8: Furnace Control Event Schedule
Unitary Products Group 7
035-19592-001 Rev. C (0204)
SECTION III: REPLACEMENT PARTS LIST
47
34
31
48
29
33
8
32
27
10
36
38
37
26 44
CGRWY
30
HUM
EAC
XFMR
LINE
CIR
HUM
EAC
XFMR
LINE
PARK
PARK
HEAT
COOL
63
13
45
23
5
24
9
6
20
28
58
43
62
4
2
59
14
17 18
12
11
56 60
22
21
1
16
49
50
7
3
25
52
51
15
8, 61
19
29
53
35
40, 42
27
24
46
9
13
9
OFF
ON
6
8 Unitary Products Group
035-19592-001 Rev. C (0204)
ITEM DESCRIPTION
MOTOR
1MOTOR,DIRECT DRIVE BLOWER 2 MOTOR,VENTOR ASS’Y
ELECTRICAL
CAPACITOR (7.5MFD/370V)
3
CAPACITOR (10 MFD/370V) 4 CAPACITOR, VENTOR (4MFD/370V) 5 CONTROL, HIGH LIMIT 6CONTROL,FLAME ROLL OUT 7 CONTROL,FURNACE
7A FUSE
8IGNITER 9 SENSOR, FLAME
10 SWITCH, AIR PRESSURE [LP]
11 SWITCH, DOOR 12 TRANSFORMER 13 VALVE, GAS
AIR MOVING
14 CUTOFF,BLOWER 15 HOUSING, BLOWER 16 WHEEL, BLOWER
FABRICATED PARTS
17 BAFFLE, AIR (LH Recoup.Coil) 18 BAFFLE, AIR (RH Recoup.Coil) 19 BURNER, MAIN GAS 20 COIL,
SECONDARY HEAT EXCHANGER
21 DECK, BLOWER (Rear) 22 DECK, FRONT 23 HEAT EXCHANGER ASS’Y 24 MANIFOLD, GAS 25 PAN, BASE 26 PAN, CONDENSATE 27 PANEL, BURNER BOX (Bottom) 28 PANEL, BURNER BOX (Front) 29 WRAPPER, BURNER BOX 30 CHANNEL, TOE PLATE
(Primary)
ITEM DESCRIPTION
31 COVER, HEAT EXCHANGER 32 PANEL, FRONT (Blower) 33 PANEL, FRONT (Burner) 34 PANEL, TOP 35 SUPPORT, BURNER 36 WRAPPER, CABINET 37 PANEL, VESTIBULE (Lower) 38 PLUG, WINDOW, CLEAR - .875”
MISCELLANEOUS
39*
CLIP, FILTER RETAINER(2Req’d)P3U,G9T
40 COLLAR, AIR INTAKE (Burner Box) 41 FILTER, AIR
FILTER SIZE - Refer to Table 1 42 GASKET, AIR INTAKE 43 GASKET,
COMBUSTION BLOWER
44 GASKET, CONDENSATE PAN 45 GASKET,
BURN BOX TO VEST PANEL
46 GROMMET, MANIFOLD SEAL 47 PLUG, WINDOW,CLEAR - 1.5” 48 HANDLE, DOOR 49 ISOLATOR, TUBE (3 Req’d.) 50 ISOLATOR, WASHER (3 Req’d.) 51 ISOLATOR,SLEEVE (3 Req’d.) 52 MOUNT, MOTOR 53 ORIFICE, BURNER
(Natural #45)
54
55* RETAINER, FILTER
56 TRAP, CONDENSATE
57* WIRING DIAGRAM
58 TUBE, DRAIN RAIN GUTTER 59 TUBE,
CONDENSATE DRAIN
60 TUBE, DRAIN CONDENSATE TRAP 61 BRACKET, IGNITOR 62 TUBE, DRAIN
CONDENSATE PAN
63 PIPE EXHAUST VENT
NOTE: *Not Shown
New replacement parts shown in bold face type at the first printing of parts list dated 11/02. Major components and suggested stocking items are shown with shaded item number.
Unitary Products Group 9
035-19592-001 Rev. C (0204)
FIELD INSTALLED ACCESSORIES ­NON-ELECTRICAL
MODEL NO. DESCRIPTION USED WITH
1NP0347 1NP0349 PROPANE (LP) 140 MBH
1CT0302 CONCENTRIC INTAKE/VENT 2” 1CT0303 CONCENTRIC INTAKE/VENT 3”
1PS0306
1PS0307
1PS0308
1PS0309
1PS0310
1BR0314 1BR0317 17-1/2” CABINETS
1BR0321 21” CABINETS 1BR0324 24-1/2” CABINETS
1NK0301
PROPANE (LP) CONVERSION
KIT ALL MODELS EXCEPT 140 MBH
HIGH ALTITUDE PRESSURE SWITCH KIT
(Does Not Include Orifices)
HIGH ALTITUDE PRESSURE SWITCH KIT
(Does Not Include Orifices)
HIGH ALTITUDE PRESSURE SWITCH KIT
(Does Not Include Orifices)
HIGH ALTITUDE PRESSURE SWITCH KIT
(Does Not Include Orifices)
HIGH ALTITUDE PRESSURE SWITCH KIT
(Does Not Include Orifices)
EXTERNAL BOTTOM FILTER
RACK 14-1/2” CABINETS
CONDENSATE NEUTRALIZER
KIT ALL MODELS
FIELD INSTALLED ACCESSORIES ­ELECTRICAL
MODEL NO. DESCRIPTION USED WITH
THERMOSTAT- One-stage heat/cool.
2TH07700124-
2TH13700424
2TB17700424
2ET07700224
6TH13701024
6TH07700124
2CT03700124 TWINNING CONTROL ALL MODELS
Manual changeover, integral sub-base.
System Switch: Cool-Off-Heat.
Fan Switch: Auto-On.
ALL P3U MODELS
THERMOSTAT- One-stage heat.
Deluxe 24V with heat only sub-base
does not include fan switch.
NOTE: For one-stage cool or
one-stage heat/cool, must be used
with sub-base 2TB17700424.
SUBBASE (24V) - One-stage heat/cool. Man-
ual changeover, integral sub-base.
System Switch: Cool-Off-Heat.
Fan Switch: Auto-On.
THERMOSTAT- One-stage heat/cool.
Programmable changeover, with sub-base.
System Switch: Cool-Off-Heat.
Fan Switch: Auto-On.
THERMOSTAT- Heating, One-stage heat, No
Fan Switch.
ALL G9T, FG9 MODELS
THERMOSTAT- Heating/Cooling,
One-stage heat/cool.
Manual changeover.
REPLACEMENT PART CONTACT INFORMATION
This is a generic parts list. To request a complete parts list, refer to the contact information below:
• Visit our website at www.source1parts.com for the following information:
1. Search for a part or browse the catalog.
2. Find a dealer or distributor.
3. Customer Service contact information. a. Click on the “Brand Links” button
b. Click on the “Customer Service” button
• You can contact us by mail. Just send a written request to:
York International
Consumer Relations
5005 York Drive
Norman, OK 73069
10 Unitary Products Group
035-19592-001 Rev. C (0204)
SECTION IV: WIRING DIAGRAM
FIGURE 9: Wiring Diagram
Unitary Products Group 11
Limited Warranty
UPG warrants this product to be free from defects in factory workmanship and material under normal use and service and will, at its option, repair or replace any parts that prove to have such d efects according to the terms outlined on t he reverse side of this warranty. This warranty covers onl y the equipment described by the Product Model Number and Serial Number listed on the Warranty Registration Card. UPG warrants the primary heat exchangers in the product to be free from defects in factory workmanship and material under normal use and service and will at its option, repair or furnish a replaceme nt heat exchanger, either new or reconditioned, that meets the intended fit, use and function of the original heat exchanger for any heat exchanger furnished by UPG which proves to have such defects within the duration of warranty coverage. Alternatively, UPG may, at its option, extend a replacement all owance to be applied toward th e purchase of a new furnace or packag ed unit marketed by UPG. The exact amount of the allowance will be determined at the discretion of UPG, based upon current market conditions, but in no case shall this allowance exceed thirty (30) percent of the original consumer pu rchase pr ice o f the fu rnace, exclu ding suc h items as du ctwork, w iring, piping and ins tallation costs. U PG shall have no responsibility hereunder for installation, shipping, handling or other charges except as specifically provided herein. For your benefit and protection, return the Warranty Registration Card to UPG promptly after installation. This will initiate the warranty period and all ow us to contact you, should it beco me necessary. In the abse n ce of a rec orded Warranty Registration Card, the warranty period will begin upon product shipment from UPG. This warranty extends only to the original consumer purchaser and is non-transferable. For this warranty to apply, the product must be installed accordin g to UPG recommendations and specifica tions , and in acc ordance with all l ocal, state, an d natio nal codes; and the pr oduct mus t not be removed f rom its plac e of original installation. The warranty period for repair or replacement parts provided hereunder shall not extend beyond the warranty period stated on the reverse
side of this warranty.
HEAT EXCHANGER
FURNACE TYPE
Original Owner Subsequent Owner
P*UR / G9T-UP
90%
FG9-UP
UPG strongly recommends regular periodic preventative maintenance on this equipment. The person most familiar with the equipment in your HVAC system is a UPG dealer. The UPG dealer can ensure your maintenance program meets the conditions of the "UPG Warranty", maximize the efficiency of the equipment, and service your unit within the mandated guidelines with regard to unlawful discharge of refrigerants into the atmosphere. This warranty applies only to products installed in the United States and Canada.
Lifetime 20 10 5
15 N/A 10 1
Non-Residential
Applications
EXCLUSIONS
This warranty does not cover any:
1. Shipping, labor, or material charges.
2. Damages resulting from transportation, installation, or servicing.
3. Damages resu lting from accide nt, abuse, fire, flood, alterati on, or acts of God (tamperi ng, altering, d efacing or removin g the product serial number will serve to void this warranty).
4. Damages resulting from use of the product in a corrosive atmosphere.
5. Damages res ulting from inadequacy or interruption of electrica l service or fuel supply, improper voltage conditions, blown fuses, or other like damages.
6. Cleaning or replacement of filters.
7. Damages resulting from failure to properly and regularly clean air and/or water side of condenser and evaporator.
8. Damages resulting from: (I) freezing of condenser water or condensate; (II) inadequate or interrupted water supply; (III) use of corrosive water; (IV) fouling or restriction of the water circuit by foreign material or like causes.
9. Damages resulting from operation with inadequate supply of air or water.
10. Damages resulting from use of components or accessories not approved by UPG (ve n t damp er s, etc.).
11. Increase in fuel or electric cost.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABIL­ITY AND FITNESS FOR A PARTICULAR PURPOSE.
SOME STATES DO NOT ALLOW THE DISCLAIMER OF IMPLIED WARRANTY, SO THAT THE ABOVE DISCLAIMER MAY NOT APPLY TO YOU. SOME STATES ALLOW ONLY A PARTIAL LIMITATION ON IMPLIED WARRANTIES TO LIMIT THE DURATION OF IMPLIED WARRANTIES TO THE DURA-
TION OF THE EXPRESS WARRANTY. IN SUCH STATES, THE DURATION OF IMPLIED WARRANTIES IS HEREBY EXPRESSLY LIMITED TO THE DURA­TION OF THE EXPRESS WARRANTY ON THE FACE HEREOF.
IN NO EVENT, WHETHER AS A RESULT OF BREACH OF WARRANTY OR CONTRACT, TORT (INCLUDING NEGLIGENCE) STRICT LIABILITY OR OTH­ERWISE, SHALL UPG BE LIABLE FOR SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, INCLUDING BUT NOT LIMITED TO LOSS OF USE OF THE EQUIPMENT OR ASSOCIATED EQUIPMENT, LOST REVENUES OR PROFITS, COST OF SUBSTITUTE EQUIPMENT OR COST OF FUEL OR ELEC­TRICITY. THE ABOVE LIMITATIONS SHALL INURE TO THE BENEFIT OF UPG'S SUPPLIERS AND SUBCONTRACTORS. THE ABOVE LIMITATION ON CONSEQUENTIAL DAMAGES SHALL NOT APPLY TO INJURIES TO PERSONS IN THE CASE OF CONSUMER GOODS.
SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITA TION OF LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGES, OR FOR STRICT LIABILITY IN TORT, SO THAT THE ABOVE EXCLUSIONS AND LIMITATIONS MAY NOT APPLY TO YOU.
UPG DOES NOT ASSUME, OR AUTHORIZE ANY OTHER PERSON TO ASSUME FOR UPG, ANY OTHER LIABILITY FOR THE SALE OF THIS PRODUCT . THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS. YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE. For Owner's Information:
PARTSResidential Applications
PRODUCT MODEL. NO. ____________________ INSTALLATION DATE ______________________________ UNIT SERIAL NO. _________________________ INSTALLING DEALER ______________________________
Subject to change without notice. Printed in U.S.A. 035-19592-001 Rev. C (0204) Copyright © by York International Corp. 2004. All rights reserved. Supersedes: 035-19592-001 Rev. B (1203)
Unitary 5005 Norman Products York OK Group Drive 73069
Loading...