White-rodgers F145-1328, F145-1378 User Manual

Page 1
F145-1328/F145-1378
!
!
Indoor Remote Sensor/Outdoor Remote Sensor
INSTALLATION INSTRUCTIONS
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.
F145-1328
INDOOR REMOTE SENSOR
OUTDOOR REMOTE SENSOR
F145-1378
Outdoor Probe
Interior Mounting Base
SPECIFICATIONS
Operating Range: (based on thermostat range)
F145-1328 Indoor Model: 40 to 99°F F145-1378 Outdoor Model: -40 to 140°F
Operating Humidity Range: 0 to 90% RH
(non-condensing)
Maximum Distance from Thermostat: 300 feet Recommended Wire: 18 or 20 gauge,
3-conductor shielded cable
Color: Classic White Dimension: 2 1/8" x 3 1/2" x 3/4"
Outdoor Remote includes 12 ft. of outdoor
probe lead
CONTENTS
Specications ................................................ 1
Installation .................................................... 2
Remote Sensor Terminal Cross Reference ...... 2
Wiring F145-1328 (Single Stage) .....................3
Wiring F145-1328, F145-1378 (Mul-Stage) ... 3
Wiring 1F97-1277 (Blue Touchscreen) .............4
Wiring 1F95-1277 (Blue Touchscreen) ............ 4
Conguration .................................................5
Remote Sensor Calculated Priority Average .....5
Maximum Sensing Locaons
Per Thermostat (Chart) ..................................6
Troubleshoong ...............................................7
For applications where the wire run is short (100 ft. or less) shielded cable may not be required provided the wires are not routed parallel to or across other wires carrying electrical power. To reduce electrical interference or inductance from other electrical wir­ing or devices use shielded cable and keep Remote Sensor wire runs separate from thermostat wiring. Remote sensors cannot be used with systems where power interruptions are part of normal system op­eration. Compatible with all White-Rodgers remote sensing thermostats.
To prevent electrical shock and/or equipment damage, disconnect electric power to system at main fuse or circuit breaker box until instal­lation is complete.
WARNING
Do not use on circuits exceeding specied
voltage. Higher voltage will damage control
and could cause shock or re hazard.
Do not short out terminals on gas valve or prima­ry control to test. Short or incorrect wiring will damage thermostat and could cause personal injury and/or property damage.
www.white-rodgers.com
www.emersonclimate.com
PART NO. 37-6606C
Replaces 37-6606B
1319
Page 2
INSTALLATION
Mounting Surface
Spacer
!
INDOOR SENSOR
SELECT SENSOR LOCATION
Proper location insures that the remote sensor will provide a comfortable home or building tempera­ture. Observe the following general rules when selecting a location:
1. The remote sensor can be located a maximum of 300 feet from the thermostat.
2. Locate sensor about 5 . above the room oor level.
3. Install sensor on a partitioning wall, not on an outside wall.
4. Never expose sensor to direct light from lamps,
sun, replaces or any temperature radiating
equipment.
5. Avoid locations close to windows, adjoining outside walls, or doors that lead outside.
6. Avoid locations close to air registers or in the direct path of air from them.
7. Make sure there are no pipes or duct work in that part of the wall chosen for the sensor location.
8. Never locate sensor in a room that is normally warmer or cooler than the rest of the home (such as the kitchen) or building.
9. Avoid locations with poor air circulation, such as behind doors or in alcoves.
10. In the home, the living or dining room is normally a good location, provided there is no cooking range or refrigerator on opposite side of wall.
OUTDOOR SENSOR
SELECT SENSOR LOCATION
Proper location insures that the remote sensor will provide a correct outdoor temperature reading. Observe the following general rules when selecting a location:
1. The interior mounting base can be located a maximum of 300 feet from the thermostat.
2. Install the interior mounting base within 12 . of the intended outdoor probe location.
3. Never install the outdoor probe where it will be exposed to direct light from lamps, sun, re­places or any temperature radiating equipment.
4. Make sure there are no pipes or ductwork in the wall chosen for the base location.
5. Outdoor temperature measurement requires installing the probe outdoors. Good probe loca­tions would be under a bay window or overhang, out of direct sunlight. Direct sun exposure will
aect sensed temperature. Install probe with
spacer to obtain a more accurate temperature.
6. Although connected to the probe wire for out­door temperature sensing, the interior mount­ing base must be placed indoors. Therefore, the interior mounting base must be installed near the perimeter of the building, so that the probe wire can be run through to the outside of the structure and placed in the selected (shaded) location. The outdoor probe wire is 12 feet long (and should not be cut or spliced), so plan the placement of both the probe and interior mounting base accordingly. Any excess wire may be coiled or bundled. The probe should be
connected to E2 as shown in gure 2.
REMOTE SENSOR TERMINAL CROSS REFERENCE
Old/New Remote Terminal Designations
Model Number Terminal Designation
*F145-1049, *F145-1170
F145-1328, F145-1378
*Models no longer available
S1 S2 S3
+ S -
Sensor
Positive
Sensor Return
Signal
Sensor
Negative
Do not allow the 3-conductor wire to be pinched between the sensor and the wall.
Check wire connections before applying power. Improper connections will lead to permanent damage to the sensor.
When shielded cable is used, cable shield must be connected to "-" or S3 on the THERMOSTAT ONLY.
2
Page 3
WIRING DIAGRAMS
RCEW2W1Y2Y1B OG
PH DSASBSCOTL
W3A1E2
P
SA SB SC OT
+ Te rminals
- Te rminals
Outdoor Probe
To +
+ SE2
To ­To SB
To +
+
S
E2
To -
To SC
To +
Note: When using shielded cable, connect shield of 18 or 20 gauge 3 connector cable to - or S3 on thermostat subbase.
Remote Sensor
Thermostat Subbase
Figure 1 – Single Stage Thermostat Remote Sensor Wiring (F145-1328)
Note: When using shielded cable, connect shield
of 18 or 20 gauge 3 connector cable to - or S3 on thermostat subbase.
Remote Outdoor Sensor Base
Thermostat Subbase
Remote Indoor Sensor A
+ SE2
To ­To SA
Figure 2 – Staging Thermostat Multi-Stage or Heat Pump Indoor/Outdoor
Remote Indoor Sensor B Remote Indoor Sensor C
Remote Sensor Wiring (F145-1328/F145-1378)
3
To +
To OT
To -
+ SE2–
Page 4
WIRING DIAGRAMS
+
S
E2
To + or To S1 To S or To S2 To - or To S3
To -
Outdoor Probe
To -
Outdoor Probe
Thermostat Subbase
Remote Sensor
Note: When using shielded cable, connect shield
of 18 or 20 gauge 3 connector cable to - or S3 on thermostat subbase.
Remote Sensor
+ SE2–
If connecting
outdoor service
Figure 3 – Single Stage (1F97-1277) Touchscreen Thermostat Indoor/Outdoor
Thermostat Subbase
If connecting
outdoor service
To +
To OT
Remote Sensor Wiring (F145-1328/F145-1378)
Note: When using shielded cable, connect shield
of 18 or 20 gauge 3 connector cable to - or S3 on thermostat subbase.
Remote Outdoor Sensor
+ SE2–
To +
To OT
Remote Sensor
Figure 4 – Staging Multi-Stage or Heat Pump Touchscreen Thermostat (1F95-1277) Indoor/Outdoor
Remote Sensor Wiring (F145-1328/F145-1378)
4
Page 5
CONFIGURATION
Comfort-Set II
Single Stage Models: Verify jumper wire W-22 on
the back of the thermostat (not the subbase) has been clipped.
Multi-Stage and Heat Pump Models: Verify jumper wire W-18 on the back of the thermostat (not the subbase) has been clipped.
Comfort-Set III/Comfort-Set
90/90 Series
Single Stage Models(excluding touchscreen): Veri-
fy jumper wire W-922 on the back of the thermostat (not the subbase) has been clipped. You must also enable the remote sensor option in the Installation
Instructions, Conguration Menu.
Multi-Stage/Heat Pump and Touchscreen Models:
When installing a remote sensor you must enable the remote sensor option in the Installation Instructions, Installer Menu.
REMOTE SENSOR CALCULATED PRIORITY AVERAGE
Consult Maximum Sensing Locations Per Thermostat chart on page 6 to determine how many sensors a thermostat will accept.
Tables 1-3 show how priority (LO, AVG, HI) eects the room temperature calculation. The example below table three shows the calculation of each remote sensor and how it uses them to arrive at room tempera­ture average.
Table 1: Remote Sensor A congured as a LO priority sensor
Remote Sensor
SA LO
Table 2: Remote Sensor A congured as a LO priority sensor
Remote Sensor
SB AVERAGE
Table 3: Remote Sensor A congured as a LO priority sensor
Remote Sensor
Sc HI
The example below lists three sensors each with a dierent priority and room temperature. All three sensors
are combined in the calculation to display the average temperature. The priority multiplier shown in the tables above causes a sensor with low priority to carry less weight in the calculated average. A sensor with a HI priority setting contributes more to the calculated average. Assume that the building in which the
thermostat is located has three indoor remote sensors (SA, SB, SC) that have dierent room temperatures
(70, 75, 80). The calculated average will be displayed as the room temperature shown in the example below.
Sensor Priority
Sensor Priority
Sensor Priority
Priority Multiplier
1 70°F (Sensor Temp.) 1 x 70 = 70 (Priority Multiplier x Room Temp.)
Priority Multiplier
2 75°F (Sensor Temp.) 2 x 75 = 150 (Priority Multiplier x Room Temp.)
Priority Multiplier
4 80°F (Sensor Temp.) 4 x 80 = 320 (Priority Multiplier x Room Temp.)
Room Temperature Averaging Calculation
Room Tempera­ture
Room Temperature Averaging Calculation
Averaging Calculation
Example: Remote Sensors A, B, and C congured as a LO, AVG, and HI priority sensors
Remote Sensor
SA LO
SB AVERAGE
SC HI
Sensor Priority
Priority Multiplier
1 70°F (Sensor Temp.) 1 x 70 = 70 (Priority Multiplier x Room Temp.)
2 75°F (Sensor Temp.) 2 x 75 = 150 (Priority Multiplier x Room Temp.)
4 80°F (Sensor Temp.) 4 x 80 = 320 (Priority Multiplier x Room Temp.)
Room Temperature Averaging Calculation
Avg. Calc. (540)/Sum Priority Mult. (7)
540/7 = 77°F (Calculated Displayed Temp.)
5
Page 6
REMOTE SENSOR TROUBLESHOOTING GUIDE
MAXIMUM SENSING LOCATIONS PER THERMOSTAT
1*
Remote
Sensor
Priority Assignment (LO/AVG/HI)
- -
Allows
Outdoor
Remote
Sensor
Thermostat
Model
Number
1F90-371 1
Total
(Max.)
Indoor Sensing Locations
Thermostat
Onboard
Sensor
OFF* With
Remote
Sensor
Sensor Set Up
Clip Jumper W922 and Enable Sensor in Menu
Clip Jumper W922 and Enable Sensor in Menu
Clip Jumper W922 and Enable Sensor in Menu
Clip Jumper W922 and Enable Sensor in Menu
2
2
OFF* With
ON or OFF +
OFF* With
OFF* With
ON or OFF +
ON or OFF +
ON or OFF +
ON or OFF +
ON or OFF +
ON or OFF +
1*
1*
1*
1*
Up to 3
Up to 3
1
Up to 3
Up to 3
Up to 3
1F96-344 1
Single
1F97-1277
Stage
(Blue)
1F97-371 1
1F97-391 1
1F93-380 4
1F94-371 4
1F95-1277
Staging
*Using a remote sensor on this model requires the onboard thermostat sensor to be o.
**Allows a sensor priority of LO, AVG., or HI to be assigned to the onboard thermostat sensor in addition to remote sensors ***Accepts one remote sensor, Indoor or Outdoor.
(Blue)
1F95-371 4
1F95-377 4
1F95-391 4
- -
Yes Yes** Enable Sensor in Menu
- -
- -
Yes** Ye s Enable Sensor in Menu
Yes** Ye s Enable Sensor in Menu
Yes Yes** * Enable Sensor in Menu
Yes** Ye s Enable Sensor in Menu
Yes** Ye s Enable Sensor in Menu
Yes** Ye s Enable Sensor in Menu
6
Page 7
TROUBLESHOOTING
To function correctly and read temperature accurately, the thermostat must have constant 24-volt pow­er. If the thermostat temperature is steadily dropping, reading low, or reads 08° when a remote sensor is installed, it can be traced to one of the three following conditions.
Condition Test Comments
1. Loss of 24-volt power.
2. A broken wire on S1, S2 and S3 or (+, SA, -) from the thermostat to the remote.
3. A shorted or damaged remote sensor.
On models with batteries, remove the batteries and re-install ther­mostat. If the display is blank, check heating and cooling system to determine why 24-volt power is absent.
Disconnect sensor wires at ther­mostat. Attach a short piece (2') of three-wire shielded cable to S1, S2 and S3 or (+, SA, -) on the subbase. Bring the remote sensor to the thermostat location and attach S1, S2 and S3 or (+, S, -) respectively. Reattach thermostat. If the temperature begins to climb (slowly), it is reading correctly. If it reads correctly with the 2' length but improperly when attached to the wire run, it indicates a fault in the wire run.
Because it is an electronic sensor, there are no Ohm values to test. If correct conditions as listed in 1 & 2 above and the temperature stays at or near 08°, it indicates a shorted or damaged remote sensor.
For the sensor to read correctly, the 24-volt system power must be present. Some systems may require an isolation relay to provide constant power to the thermostat. Limit or safety devices in the equipment can also cause a power interruption.
Repair or replace the 3 wire shielded cable. Be sure the remote wire run is not parallel to line voltage wires that carry heavy inductive loads, or across
uorescent light ballasts that may
cause an inductance to be transmitted to the thermostat.
Replace remote sensor.
Note: Digital thermostats and remote sensors acclimate very slowly to temperature change. It may take an hour or more for the temperature to acclimate to the room temperature from a low temperature reading as outlined above. To expedite the room temperature display use the reset instructions listed in the installation instructions for the thermostat model you are working with. When reset, the thermostat will default to a room temperature of 70° and begin sensing room temperature. Be sure to recongure the installer menu for a remote sensor because the reset function may cancel remote sensing.
7
Page 8
White-Rodgers is a business of Emerson Electric Co.
The Emerson logo is a trademark and service mark of Emerson Electric Co.
www.white-rodgers.com
www.emersonclimate.com
Loading...