For applications where the wire run is short (100 ft.
or less) shielded cable may not be required provided
the wires are not routed parallel to or across other
wires carrying electrical power. To reduce electrical
interference or inductance from other electrical wiring or devices use shielded cable and keep Remote
Sensor wire runs separate from thermostat wiring.
Remote sensors cannot be used with systems where
power interruptions are part of normal system operation. Compatible with all White-Rodgers remote
sensing thermostats.
To prevent electrical shock and/or equipment
damage, disconnect electric power to system
at main fuse or circuit breaker box until installation is complete.
WARNING
Do not use on circuits exceeding specied
voltage. Higher voltage will damage control
and could cause shock or re hazard.
Do not short out terminals on gas valve or primary control to test. Short or incorrect wiring will
damage thermostat and could cause personal
injury and/or property damage.
www.white-rodgers.com
www.emersonclimate.com
PART NO. 37-6606C
Replaces 37-6606B
1319
Page 2
INSTALLATION
Mounting
Surface
Spacer
CAUTION
!
INDOOR SENSOR
SELECT SENSOR LOCATION
Proper location insures that the remote sensor will
provide a comfortable home or building temperature. Observe the following general rules when
selecting a location:
1. The remote sensor can be located a maximum
of 300 feet from the thermostat.
2. Locate sensor about 5 . above the room oor
level.
3. Install sensor on a partitioning wall, not on an
outside wall.
4. Never expose sensor to direct light from lamps,
sun, replaces or any temperature radiating
equipment.
5. Avoid locations close to windows, adjoining
outside walls, or doors that lead outside.
6. Avoid locations close to air registers or in the
direct path of air from them.
7. Make sure there are no pipes or duct work in that
part of the wall chosen for the sensor location.
8. Never locate sensor in a room that is normally
warmer or cooler than the rest of the home
(such as the kitchen) or building.
9. Avoid locations with poor air circulation, such
as behind doors or in alcoves.
10. In the home, the living or dining room is normally
a good location, provided there is no cooking
range or refrigerator on opposite side of wall.
OUTDOOR SENSOR
SELECT SENSOR LOCATION
Proper location insures that the remote sensor will
provide a correct outdoor temperature reading.
Observe the following general rules when selecting
a location:
1. The interior mounting base can be located a
maximum of 300 feet from the thermostat.
2. Install the interior mounting base within 12 .
of the intended outdoor probe location.
3. Never install the outdoor probe where it will be
exposed to direct light from lamps, sun, replaces or any temperature radiating equipment.
4. Make sure there are no pipes or ductwork in the
wall chosen for the base location.
5. Outdoor temperature measurement requires
installing the probe outdoors. Good probe locations would be under a bay window or overhang,
out of direct sunlight. Direct sun exposure will
aect sensed temperature. Install probe with
spacer to obtain a more accurate temperature.
6. Although connected to the probe wire for outdoor temperature sensing, the interior mounting base must be placed indoors. Therefore, the
interior mounting base must be installed near
the perimeter of the building, so that the probe
wire can be run through to the outside of the
structure and placed in the selected (shaded)
location. The outdoor probe wire is 12 feet
long (and should not be cut or spliced), so plan
the placement of both the probe and interior
mounting base accordingly. Any excess wire
may be coiled or bundled. The probe should be
connected to E2 as shown in gure 2.
REMOTE SENSOR TERMINAL CROSS REFERENCE
Old/New Remote Terminal Designations
Model NumberTerminal Designation
*F145-1049,
*F145-1170
F145-1328,
F145-1378
*Models no longer available
S1S2S3
+S-
Sensor
Positive
Sensor
Return
Signal
Sensor
Negative
Do not allow the 3-conductor wire to be pinched
between the sensor and the wall.
Check wire connections before applying power.
Improper connections will lead to permanent
damage to the sensor.
When shielded cable is used, cable shield
must be connected to "-" or S3 on the
THERMOSTAT ONLY.
2
Page 3
WIRING DIAGRAMS
RCEW2W1Y2Y1BOG
PH DSASBSCOTL
W3A1E2
P
SA SB SC OT
+ Te rminals
- Te rminals
Outdoor Probe
To +
+ SE2–
To To SB
To +
+
S
E2
–
To -
To SC
To +
Note: When using shielded cable, connect
shield of 18 or 20 gauge 3 connector cable
to - or S3 on thermostat subbase.
Remote Sensor
Thermostat Subbase
Figure 1 – Single Stage Thermostat Remote Sensor Wiring (F145-1328)
Note: When using shielded cable, connect shield
of 18 or 20 gauge 3 connector cable to - or S3 on
thermostat subbase.
Remote Outdoor Sensor Base
Thermostat Subbase
Remote Indoor Sensor A
+ SE2–
To To SA
Figure 2 – Staging Thermostat Multi-Stage or Heat Pump Indoor/Outdoor
Remote Indoor Sensor BRemote Indoor Sensor C
Remote Sensor Wiring (F145-1328/F145-1378)
3
To +
To OT
To -
+ SE2–
Page 4
WIRING DIAGRAMS
+
S
E2
–
To + or To S1
To S or To S2
To - or To S3
To -
Outdoor Probe
To -
Outdoor Probe
Thermostat Subbase
Remote Sensor
Note: When using shielded cable, connect shield
of 18 or 20 gauge 3 connector cable to - or S3 on
thermostat subbase.
Remote Sensor
+ SE2–
If connecting
outdoor service
Figure 3 – Single Stage (1F97-1277) Touchscreen Thermostat Indoor/Outdoor
Thermostat Subbase
If connecting
outdoor service
To +
To OT
Remote Sensor Wiring (F145-1328/F145-1378)
Note: When using shielded cable, connect shield
of 18 or 20 gauge 3 connector cable to - or S3 on
thermostat subbase.
the back of the thermostat (not the subbase) has
been clipped.
Multi-Stage and Heat Pump Models: Verify jumper
wire W-18 on the back of the thermostat (not the
subbase) has been clipped.
Comfort-Set III/Comfort-Set
90/90 Series
Single Stage Models(excluding touchscreen): Veri-
fy jumper wire W-922 on the back of the thermostat
(not the subbase) has been clipped. You must also
enable the remote sensor option in the Installation
Instructions, Conguration Menu.
Multi-Stage/Heat Pump and Touchscreen Models:
When installing a remote sensor you must enable the
remote sensor option in the Installation Instructions,
Installer Menu.
REMOTE SENSOR CALCULATED PRIORITY AVERAGE
Consult Maximum Sensing Locations Per Thermostat chart on page 6 to determine how many sensors a
thermostat will accept.
Tables 1-3 show how priority (LO, AVG, HI) eects the room temperature calculation. The example below
table three shows the calculation of each remote sensor and how it uses them to arrive at room temperature average.
Table 1: Remote Sensor A congured as a LO priority sensor
Remote
Sensor
SALO
Table 2: Remote Sensor A congured as a LO priority sensor
Remote
Sensor
SBAVERAGE
Table 3: Remote Sensor A congured as a LO priority sensor
Remote
Sensor
ScHI
The example below lists three sensors each with a dierent priority and room temperature. All three sensors
are combined in the calculation to display the average temperature. The priority multiplier shown in the
tables above causes a sensor with low priority to carry less weight in the calculated average. A sensor with
a HI priority setting contributes more to the calculated average. Assume that the building in which the
thermostat is located has three indoor remote sensors (SA, SB, SC) that have dierent room temperatures
(70, 75, 80). The calculated average will be displayed as the room temperature shown in the example below.
Sensor
Priority
Sensor
Priority
Sensor
Priority
Priority
Multiplier
170°F (Sensor Temp.) 1 x 70 = 70 (Priority Multiplier x Room Temp.)
Priority
Multiplier
275°F (Sensor Temp.) 2 x 75 = 150 (Priority Multiplier x Room Temp.)
Priority
Multiplier
480°F (Sensor Temp.) 4 x 80 = 320 (Priority Multiplier x Room Temp.)
Room Temperature Averaging Calculation
Room Temperature
Room Temperature Averaging Calculation
Averaging Calculation
Example: Remote Sensors A, B, and C congured as a LO, AVG, and HI priority sensors
Remote
Sensor
SALO
SBAVERAGE
SCHI
Sensor
Priority
Priority
Multiplier
170°F (Sensor Temp.) 1 x 70 = 70 (Priority Multiplier x Room Temp.)
275°F (Sensor Temp.) 2 x 75 = 150 (Priority Multiplier x Room Temp.)
480°F (Sensor Temp.) 4 x 80 = 320 (Priority Multiplier x Room Temp.)
Room Temperature Averaging Calculation
Avg. Calc. (540)/Sum Priority Mult. (7)
540/7 = 77°F (Calculated Displayed Temp.)
5
Page 6
REMOTE SENSOR TROUBLESHOOTING GUIDE
MAXIMUM SENSING LOCATIONS PER THERMOSTAT
1*
Remote
Sensor
Priority
Assignment
(LO/AVG/HI)
--
Allows
Outdoor
Remote
Sensor
Thermostat
Model
Number
1F90-3711
Total
(Max.)
Indoor Sensing Locations
Thermostat
Onboard
Sensor
OFF*With
Remote
Sensor
Sensor Set Up
Clip Jumper W922 and
Enable Sensor in Menu
Clip Jumper W922 and
Enable Sensor in Menu
Clip Jumper W922 and
Enable Sensor in Menu
Clip Jumper W922 and
Enable Sensor in Menu
2
2
OFF*With
ON or OFF+
OFF*With
OFF*With
ON or OFF+
ON or OFF+
ON or OFF+
ON or OFF+
ON or OFF+
ON or OFF+
1*
1*
1*
1*
Up to 3
Up to 3
1
Up to 3
Up to 3
Up to 3
1F96-3441
Single
1F97-1277
Stage
(Blue)
1F97-3711
1F97-3911
1F93-3804
1F94-3714
1F95-1277
Staging
*Using a remote sensor on this model requires the onboard thermostat sensor to be o.
**Allows a sensor priority of LO, AVG., or HI to be assigned to the onboard thermostat sensor in addition to remote sensors
***Accepts one remote sensor, Indoor or Outdoor.
(Blue)
1F95-3714
1F95-3774
1F95-3914
--
YesYes** Enable Sensor in Menu
--
--
Yes**Ye sEnable Sensor in Menu
Yes**Ye sEnable Sensor in Menu
YesYes** * Enable Sensor in Menu
Yes**Ye sEnable Sensor in Menu
Yes**Ye sEnable Sensor in Menu
Yes**Ye sEnable Sensor in Menu
6
Page 7
TROUBLESHOOTING
To function correctly and read temperature accurately, the thermostat must have constant 24-volt power. If the thermostat temperature is steadily dropping, reading low, or reads 08° when a remote sensor is
installed, it can be traced to one of the three following conditions.
ConditionTestComments
1. Loss of 24-volt
power.
2. A broken wire on
S1, S2 and S3 or
(+, SA, -) from the
thermostat to the
remote.
3. A shorted or
damaged remote
sensor.
On models with batteries, remove
the batteries and re-install thermostat. If the display is blank,
check heating and cooling system
to determine why 24-volt power is
absent.
Disconnect sensor wires at thermostat. Attach a short piece (2')
of three-wire shielded cable to
S1, S2 and S3 or (+, SA, -) on the
subbase. Bring the remote sensor
to the thermostat location and
attach S1, S2 and S3 or (+, S, -)
respectively. Reattach thermostat.
If the temperature begins to climb
(slowly), it is reading correctly. If it
reads correctly with the 2' length
but improperly when attached to
the wire run, it indicates a fault in
the wire run.
Because it is an electronic sensor,
there are no Ohm values to test. If
correct conditions as listed in 1 & 2
above and the temperature stays at
or near 08°, it indicates a shorted or
damaged remote sensor.
For the sensor to read correctly, the
24-volt system power must be present.
Some systems may require an isolation
relay to provide constant power to the
thermostat. Limit or safety devices in
the equipment can also cause a power
interruption.
Repair or replace the 3 wire shielded
cable. Be sure the remote wire run is
not parallel to line voltage wires that
carry heavy inductive loads, or across
uorescent light ballasts that may
cause an inductance to be transmitted
to the thermostat.
Replace remote sensor.
Note: Digital thermostats and remote sensors acclimate very slowly to temperature change. It may take
an hour or more for the temperature to acclimate to the room temperature from a low temperature
reading as outlined above. To expedite the room temperature display use the reset instructions listed in
the installation instructions for the thermostat model you are working with. When reset, the thermostat
will default to a room temperature of 70° and begin sensing room temperature. Be sure to recongure
the installer menu for a remote sensor because the reset function may cancel remote sensing.
7
Page 8
White-Rodgers is a business
of Emerson Electric Co.
The Emerson logo is a
trademark and service mark
of Emerson Electric Co.
www.white-rodgers.com
www.emersonclimate.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.