To prevent electrical shock and/or equipment damage,
disconnect electric power to system at main fuse or
circuit breaker box until installation is complete.
This product does not contain mercury. However, this product may replace a product that contains mercury.
Mercury and products containing mercury must not be
discarded in household trash. Do not touch any spilled
mercury. Wearing non-absorbent gloves, clean up any
spilled mercury and place in a sealed container. For proper
disposal of a product containing mercury or a sealed
container of spilled mercury, place it in a suitable shipping
container. Refer to www.white-rodgers.com for location to
send product containing mercury.
PART NO. 37-6975A
0832
Page 2
INSTALLATION
WARNING
!
Thermostat installation and all components of the
control system shall conform to Class II circuits per
the NEC code.
Remove Old Thermostat
Before removing wires from old thermostat, mark wires for
terminal identifi cation so the proper connections will be made
to the new thermostat.
Installing New Thermostat
1. Pull the thermostat body off the thermostat base. Forcing
or prying on the thermostat will cause damage to the unit.
2. Place base over hole in wall and mark mounting hole
locations on wall using base as a template.
3. Move base out of the way. Drill mounting holes. If you
are using existing mounting holes and the holes drilled
are too large and do not allow you to tighten base snug ly, use plastic screw anchors to secure the base.
4. Fasten base snugly to wall using mounting holes shown
in Figure 1 and two mounting screws. Leveling is for
appearance only and will not affect thermostat operation.
5. Connect wires to terminal block on base using appropriate
wiring schematic.
6. Push excess wire into wall and plug hole with a fi re re sistant material (such as fi berglass insulation) to prevent
drafts from affecting thermostat operation.
7. Carefully line the thermostat up with the base and snap
into place.
Battery Location
2 "AA" alkaline batteries are included in the thermostat at the
factory with a battery tag to prevent power drainage. Remove
the battery tag to engage the batteries.
To replace batteries, set system to OFF, remove thermostat
from wall and install the batteries in the rear along the top of
the thermostat (see Figure 1). For best results, use a premium brand "AA" alkaline battery such as Duracell
®
gizer
. If the home is going to be unoccupied for an extended
period (over 3 months) and
is displayed, the batteries
®
or Ener-
should be replaced before leaving.
Power Stealing Switches
The Power Stealing Switches (Fig. 1) should be left in the
"On" position for most systems. The information in the
following table details the thermostat power method and
switch options.
Thermostat Power MethodSwitch Position/Description
Battery Powered, no 24
Volt system power available.
Hardwired with Battery
Back-up, for 24 Volt systems
with common connection from
transformer to "C" terminal
on thermostat.
*Battery Powered with
Power Stealing Assist,
for 24 Volt systems with no
common connection from
transformer to "C" terminal on
thermostat.
Switches "On", thermostat
runs on batteries.
Switches "On", thermostat
runs on power directly from
transformer with battery backup.
Switches "On", thermostat
runs on batteries and
supplemental power drawn
through the heat or cool circuit.
*Power Stealing Assist is very reliable to increase battery life,
but on a small number of heating or cooling systems with high
impedance electronic modules you may observe one of the
following conditions:
1. The furnace draft inducer motor may run with no call for
heat.
2. The furnace fan may turn on with no call for heat or may
not turn off.
3. The furnace may not turn off when the call for heat ends.
4. The air conditioner may not turn off when the call for cool
ends.
If the Power Stealing Assist method is not compatible with
your system, place the Power Stealing Switches to "Off". This
cancels Power Stealing Assist, operates the thermostat on
batteries and corrects the condition.
Figure 1 – Thermostat Base Multi-Stage 1F97-0671
Mounting
Hole
Place Level
across Mounting Tabs
(for appearance only)
Place Level
across Mounting Tabs
(for appearance only)
Mounting
Hole
Rear view of thermostat
2 "AA" Batteries
Power Stealing
Switches
2
Page 3
WIRING CONNECTIONS
Refer to equipment manufacturers' instructions for specifi c
system wiring information. After wiring, see CONFIGURATION section for proper thermostat confi guration.
TERMINAL DESIGNATION DESCRIPTIONS
Terminal Designation Description
O/B ........................................... Changeover valve for heat pump energized constantly in cooling and off/heating
Y ............................................ Compressor Relay
G ............................................ Fan Relay
RC ............................................ Power for Cooling
RH ............................................ Power for Heating
C ............................................ Common wire from secondary side of cooling (Optional). Required for fault indication, continuous back-
light operation or remote temperature sensor operation
W ........................................... Heat Relay (Stage 1)
- ............................................ Common (DC) for wired remote temperature sensor
S ............................................ Frequency signal from remote temperature sensor
+ ............................................ Power (DC) to remote temperature sensor
L ............................................ Compressor diagnostic indicator for systems with diagnostic connection typically found on Heat pump
systems or with Copeland's Comfort Alert
Wiring diagrams shown are for typical systems and describe
the thermostat terminal functions.
WIRING DIAGRAMS
Figure 2 – Single Stage or Heat Pump with no Auxiliary Heat with Single Transformer
System
RCRHCY*W*GO/B6L
24 volt
Single Stage
24 volt
power for
cooling
24 volt
power for
heating
common
(optional for
system
operation,
required for
remote
sensor and
system status
indicator)
Call for cool
Call for heat
Blower/Circulator fan
energized on a call
for cool or Fan On
(also energized in
heating if configured
for Electric Heat)
*Jumper Y to W required for heat pump systems not compatible with heat pump systems that
require an auxiliary heat output.
Figure 3 – Single Stage System (No Heat Pump) with Two Transformers
System
RCRHCYW6L
24 volt
common
Heat mode-1st
24 volt
power for
heating
(optional
for system
operation,
required
for remote
sensor)
stage,
Cool mode-1st
stage,
(Compressor)
Call for heat
120VAC
HEATING
120VAC
CLASS II
TRANSFORMER
Single
Stage
NEUTRAL
24VAC
HOT
24 volt
power for
cooling
Installer
Configuration
Menu selects
“O” or “B” for
changeover
function. Set
to “O” terminal
energized in Cool
& Off mode. Set
to “B” terminal
energized in Heat
Blower/Circulator fan
energized on a call
for cool or Fan On
(also energized in
heating if configured
for Electric Heat)
G
Power closed
connection for
SPDT 3-wire
zone valve
energized in Cool
& Off mode. Set
System
Indicator for
sytems
with “L” terminal
connection
O
Installer
Configuration
Menu selects
“O” or “B” for
changeover
function. Set
to “O” terminal
to “B” terminal
energized in
Heat
status
NEUTRAL
24VAC
HOT
Power closed
connection for
SPDT 3-wire
zone valve
NEUTRAL
24VAC
HOT
CLASS II
TRANSFORMER
System
status
Indicator for
sytems
with “L” terminal
connection
CLASS II
TRANSFORMER
Single Stage Connections
Refer to equipment manufacturers'
instructions for specifi c system
wiring information.
This thermostat is designed to
operate a single-transformer or
two-transformer system.
This thermostat is confi gured for
120VAC
use with the following fossil fuel
systems:
SINGLE STAGE gas, oil or
electric.
After wiring, see INSTALLER
CONFIGURATION section for
proper thermostat confi guration.
NOTE: If continuous backlight or
hardwired power input are desired
but do not function in both HEAT
and COOL modes, cut the heating
transformer 24V wires and tape off.
Connect the neutral circuit disconnected from the heating transformer
to the neutral circuit of the cooling
transformer. Disconnect the wire to
120VAC
COOLING
the RH terminal and install a jumper
between RH and RC. Depending on
the system requirements, replace
the cooling transformer with a 75VA
class II transformer if needed.
System
Single Stage
3-wire
Zone Valve
application
Figure 4 – 3-Wire (SPDT) Heat Only Zone Valve Wiring
Jumper
W
Y
Opens
Valv e
(4)
G
Blower/Circulator
Fan Energized
24 Volt
(Hot)
Heat
(5)
RC
24 Volt
(Hot)
Cool
C
Constant
24 Volt
(Com-
mon)
RH
Closes
Valv e
(6)
6
NEUTRAL
24VAC
HOT
CLASS II
TRANSFORMER
120VAC
3
Page 4
5
6
THERMOSTAT QUICK REFERENCE
7
8
9
10
11
12
Home Screen Description
Figure 5 – Home Screen Display
Displays the power level of
the 2 “AA” batteries:
indicates good power level
indicates batteries at about
half power. “Change ” indicates
batteries are low and should be
replaced with 2 new premium brand
“AA” Alkaline batteries.
(See page 2 for more details)
Room
Temperature
Setting
Temperature
Figure 6 – Programming & Confi guration Items
11
3
1
5
12
Programming and Confi guration Items
"System On" indicates when heating or cooling stage
1
is energized.
2
The word "Hold" is displayed when the thermostat is
in the Hold mode. "Temp" is displayed whenthe thermostat is in a Temporary HOLD mode.
Displays "Change Filter" when the system has run for
3
the programmed fi lter time period as a reminder tochange or clean your fi lter.
4
Displays "Set" for setpoint when in Run Program mode.
Displays System Mode (Heat, Auto, Cool, Off)
or "Time" in menu mode.
Displays Fan mode (On, Auto) "Prog FAN On" or "Run Sched" in Menu mode.
System
Indicator
8
2
4
6
7
Displays "Run Schedule", "Schedule", or "Menu".Displays "Save" when Cool SavingsTM is working.
Displays "Hold" in programmable mode when not in
Hold mode. Displays Light Bulb in non-programmable
mode.
Initially displays "Auto Sched". If Auto Schedule hadbeen used or disabled, then it displays "Cool Savings"when in the Cool Mode. Displays "Copy" in Schedule
mode and "Fan" in Fan Schedule mode.
"Call For Service" indicates a diagnostic fault in the heating/cooling system, it does not indicate a fault in the
thermostat.
"Keypad Lockout" in Menu mode when selecting key- pad Lockout or in RUN when a keypad Lockout is active.
Fan
Indicator
9
10
4
Page 5
INSTALLER/CONFIGURATION MENU
Press and hold the Menu button for at least 5 seconds. The display will show item #1 in the table below. Press Menu to advance to the next menu item. Press
MENU
REF.
PRESS
BUTTON
1MENU(GAS)ELEGAS setting: furnace controls the blower
2MENUCS (3)0, 1, 2, 4, 5, 6Selects Cool Savings
3MENUE (On)OFFSelects Energy Management Recovery (EMR)
4MENUCR Heat (ME)SL, FAAdjustable Anticipation:
5MENUCR Cool (ME)SL, FAAdjustable Anticipation:
6MENUCL (OFF)CL OnCompressor Lockout Time
7MENU Cool Off, Heat AutoHeat Auto Cool Off,
8MENUdL (On)dL OFFSelects Display Light On or OFF
9MENU0
10MENU°F°CSelects Fahrenheit/Celsius Temperature Display
11MENU(On) bOFFMay select Beeper OFF to stop audible
12MENUP (7)3, 0Defaults 7-day programming (P7) but non-
13MENUPS (4)2Selects Program periods per day:
14MENUHeat AS (On)OFFAutomatic Schedule for heat mode
15MENUCool AS (On)OFFAutomatic Schedule for cool mode
16MENURemote (OFF)OnSelects Remote Sensor On/OFF
MENURemote
MENUIndoor Loc
17MENUdS (On)OffSelects Automatic Daylight Saving Time option
DISPLAYED
(FACTORY DE-
FAULT)
(current temperature)
(In)
(On)
or to change a menu item options.
INSTALLER/CONFIGURATION MENU
Press
select from listed op-
Heat Off with Fan icon,
Heat Off without Fan icon
Cool Off, Auto Off
1 HI, 2 HI, 3HI, 4 HI,
1 LO, 2 LO, 3 LO, 4 LO
or to
tions
ELE setting: thermostat controls the blower
Selects heating cycle rate for MS or SS in #1 only
Selects the cycle rate for cooling
with Automatic Changeover capability
Adjustable Ambient Temperature Display
programmable (0) or 5/1/1 programming (P3)
OutdoorSelects Remote Sensor to outdoor
OFFSelects Local Sensor (in thermostat) to OFF.
N/A if Remote is selected to Outdoor
COMMENTS
Value 1 (low) to 6 (high),
Value 0 disables feature
On or OFF.
System Mode Confi guration
key feedback
is available on most models.
4 = Morn, Day, Eve, Night
2 = Day, Night
NA is Remote Sensor OFF
18MENU(OFF)
Keypad Lockout
MENU(000)
Keypad Lockout
19MENUL Heat
(99)
20MENUL Cool
(45)
L, P, LimitSelects one of 3 Keypad Lockout confi gurations
L - Total Keypad Lockout
P - Partial Keypad Lockout
(Up and Keys still work)
Limit - Limited Temperature RANGE
1-999Selects personal lockout code. 000 is NOT A
VALID CODE.
L 62 to L 98Selects Limited HEAT Range Temperature
L 46 to L 82Selects Limited COOL Range Temperature
5
Page 6
INSTALLER/CONFIGURATION MENU
21MENUChange Filter (OFF)OnSelects Filter Change-out Indicator On or OFF.
MENUChange Filter (200 h)25-1975 hChange Filter time in 25 hour increments. This
menu only appears if On is selected in above.
22MENU(OFF)
Change UV Lamp
MENU(350)
Change UV Lamp
23MENUCool On (o)Heat On (b)Selects operation of the reversing valve terminal
24MENURUN SCHEDReturns to Normal Operation
OnSelects UV Lamp
Timer: On/OFF
25-1975Selects number of Days between changing UV
Lamp
(O/B) output as an O or B terminal
1) GAS or Electric (ELE) fan operation. If the heating system
requires the thermostat to energize the fan, select ELE.
Select GAS if the heating system energizes the fan on a
call for heat.
2) Select Cool Savings™ – Cool Savings allows you to
select a temperature offset (from 1-6 degrees). When
the compressor runs for long periods, the thermostat will
internally slowly/gradually adjust the room temperature
display lower, subtracting a maximum of the number of
degrees you select.
This energy saving feature is based on the principal that
long compressor run times lower indoor humidity and
make slightly higher temperature feel comfortable. Cool
Savings operates only when the compressor runs 20
minutes or longer, normally on the hottest summer days.
When Cool Savings is operating the thermostat will fl ash
"Cool Savings" to indicate it is slowly adjusting the display temperature lower.
To turn this feature on in the Cool mode press Cool
Savings. The display will show “Save” next to the set-
point temperature. When Cool Savings is making adjustments to the room temperature display “Save” will be
fl ashing and the displayed room temperature may vary
within the adjustment range you selected.
If "Save" is not displayed and this feature is OFF, no
change will occur when the cooling system is continuously
running during periods of high demand.
3) Energy Management Recovery: (this step is skipped if
confi gured to be non-programmable).
Energy Management Recovery (E) On enables the ther-
mostat to start heating or cooling early to make the building
temperature reach the program setpoint at the time you
specify. Heating will start 5 minutes early for every 1° of
temperature required to reach setpoint.
Example: E On is selected and your heating is pro-
grammed to 65° at night and 70° at 7 AM. If the building
temperature is 65°, the difference between 65° and 70° is
5°. Allowing 5 minutes per degree, the thermostat setpoint
will change to 70° at 6:35 AM. Cooling allows more time
per degree, because it takes longer to reach set temperature.
4 & 5) Cycle Rate Selection – The factory default setting for
Heat and Cool modes is medium cycle (ME). To change
cycle rate, press the
Cycle rate differentials for different settings are:
6) Select Compressor Lockout CL OFF or ON – Selecting
CL ON will cause the thermostat to wait 5 minutes between cooling cycles. This is intended to help protect the
compressor from short cycling. Some newer compressors
already have a time delay built in and do not require this
feature. Your compressor manufacturer can tell you if the
lockout feature is already present in their system. When
the thermostat compressor time delay occurs, it will fl ash
the setpoint for up to fi ve minutes.
7) System Mode Confi guration – This thermostat is confi g-
ured for Heat and Cool (SYSTEM switch with Cool Off
Heat) default. It can also be confi gured for Heat and Cool
with Auto changeover (Heat, Auto, Cool, Off), Heat only
with fan (Off Heat), Heat only without fan, Auto only
(Auto Off), and Cool only (Cool Off).
8) Select Backlight Display – The display backlight improves
display contrast in low lighting conditions. When the "C"
terminal is powered, selecting backlight CdL ON will keep
the light on continuously. Select backlight OFF will turn the
light on momentarily after any button is pressed. When the
"C" terminal is not powered, the light will be on momentarily
after any button is pressed no matter whether the backlight
is selected ON or OFF.
9) Select Temperature Display Adjustment 4 LO to 4 HI –
Allows you to adjust the room temperature display up to 4°
higher or lower. Your thermostat was accurately calibrated
at the factory, but you have the option to change the display temperature to match your previous thermostat. The
current or adjusted room temperature will be displayed.
10) Select F° or C° Readout – Changes the display readout
to Celsius or Fahrenheit as required.
11) Select Audio Prompting (Beeper) On or Off – Factory
default setting is on (b, On). If you wish to turn off the
beeper select OFF.
12) Program Options: Selects confi guration for 7 day (7) or
5/1/1 day (3) programming or non-programming (0) mode.
The default setting is 7, indicating 7 day programming.
The programs per week can be changed to 3 or 0 by
pressing the
non-programmable will eliminate the need for EMR, and
that step in the menu will be skipped.
13) Program Steps per day – This control can be confi gured
for 4 or 2 program steps per day. Default is "2 PS" and
can be toggled between 4 PS and 2 PS.
14 & 15) Select Automatic Schedule – 1F97 only, with just
one touch of the Auto Schedule key this feature allows
you to program a desired comfort temperature into all the
program periods along with a 6° set back for night periods
of both Heat and Cool programs. Factory default is "On"
for both. When Heat AS On and Cool AS On are activated while in Heat or Cool mode, select desired setpoint
or buttons. A selection of 0 days for
6
Page 7
INSTALLER/CONFIGURATION MENU
temperature and press Auto Schedule. This value will be
copied into all the morning, day and evening program
periods. The night program periods will have a 6°F set back.
16) Select Remote Temperature Sensor – This control
allows one wired remote temperature sensor (indoor,
F145-1328, or outdoor, F145-1378) be connected to it and
indicates the measured temperature in clock digits. This
menu enables you to select the remote sensor and also
confi gure it as indoor or outdoor temperature sensor. Factory default is off. Select Remote On and Remote in (for
indoor) or Outdoor Remote.
Local Temperature Sensor disable – This is applicable
only when indoor remote temperature sensor is enabled.
Factory default is Loc On. You can make it Loc Off if you
desire by using
remote temperature reading will be used for control
17) Select Daylight Saving Time Calculation – This feature
will allow the thermostat to calculate the DST automatically and apply it to the Real Time Clock display. Default
On. Use or touch keys to select the feature OFF.
18) Keypad Lockout – This step allows you to select the type
of lockout or limited range security required. If no lockout or limited range security is required, press MENU to
advance the menu.
Three security settings are available in this menu item.
Use the
Lockout selections are:
"Keypad Lockout and L"= Total Lockout. Total Lockout
locks all keys.
"Keypad Lockout and P" = Partial Lockout. Partial Lock-
out allows only the
your set temperature limits.
"Keypad Lockout and Limit" prevents changing the
temperature limits in the Confi guration Menu.
Press Menu after selecting the type of lockout.
"Keypad Lockout Combination Number Selection"
Display will read "000" "Keypad Lockout". Note: "000" is
not a valid combination choice.
Skip this step and continue through the remaining confi gu-
ration menu items if you require an Air Filter Change out
indicator or Humidifi er Pad Change out indicator by pressing the MENU button to advance.
Return to this point when you are ready to start your
selected lock-out and continue by:
Press
Pressing
out combination number.
. Display will read "001".
or buttons. Then, only the indoor
or buttons to select the lockout desired.
or buttons to operate within
or buttons to select your keypad lock-
Record the number you select for future use.
Press MENU or RunSched to exit the menu. The security
feature you select will start. The system button will remain
active for 10 seconds to allow setting Heat, Off, Cool or
Auto.
19) Limited Heat Range – This feature provides a maximum
setpoint temperature for heat. The default setting is 99°F. It
can be changed between 62°F and 98°F by pressing the
or button.
20) Limited Cool Range – This feature provide a minimum
setpoint temperature for cool. The default setting is 45°F. It
can be changed between 46°F and 82°F by pressing the
or button.
21) Select Filter Replacement Reminder and Set Run Time
Select the "Change Filter" reminder On or OFF. If selected On, press MENU to select the time period from 25
to 1975 hours in 25 hours increments. In a typical system,
200 hours (default) of run time is approximately 30 days.
After the selected time of blower operation, the thermostat
will display "Change Filter" as a reminder to change or
clean your air fi lter. When "Change Filter" is displayed,
press MENU or RUN SCHED button to clear the display
and restart the time to the next fi lter change.
22) Change UV Lamp – This feature allows the thermostat to
display the words "Change UV Lamp" (Call for Service
of UV bulb) after a set time of UV bulb operation. This is
a reminder to maintain your UV system at optimum level
of operation. When enabled the factory set interval for
"Change UV Lamp" to be displayed is 350 days of UV
bulb operation and can be adjusted in 25 day increments.
This should be adjusted with respect to the bulb's recommended maintenance schedule.
When "Change UV Lamp" is displayed, you can clear it
by pressing MENU.
23) Select Reversing Valve Output – The O/B option is
factory set at "O" position. This will accommodate the
majority of heat pump applications, which require the
changeover relay to be energized in COOL. If the thermostat you are replacing or the heat pump being installed
with this thermostat requires a "B" terminal, to energize
the changeover relay in HEAT, the O/B option should be
set at "B" position.
7
Page 8
OPERATING YOUR THERMOSTAT
Check Thermostat Operation
NOTE
To prevent static discharge problems, touch side of
thermostat to release static build-up before touching
any keys.
If at any time during testing your system does not operate
properly, contact a qualifi ed service person.
Fan Operation
If your system does not have a G terminal connection, skip to
Heating System.
1. Turn on power to system.
2. Press FAN button to select ON. The blower should begin
to operate.
3. Press FAN button to select AUTO. The blower should
stop immediately.
CAUTION
!
Do not allow the compressor to run unless the compressor oil heaters have been operational for 6 hours
and the system has not been operational for at least
5 minutes.
Heating System
1. Press SYSTEM button to select Heat. If the auxiliary
heating system has a standing pilot, be sure to light it.
2. Press to adjust thermostat setting to 1° above room
temperature. The heat pump system should begin to operate. The display should show “System On” (see Confi guration menu, item 11).
3. Press to adjust the thermostat below room temperature. The heating system should stop operating.
CAUTION
!
To prevent compressor and/or property damage, if the
outdoor temperature is below 50°F, DO NOT operate
the cooling system.
Cooling System
1. Press SYSTEM button to select Cool.
2. Press to adjust thermostat setting below room temperature. The blower should come on immediately on high
speed, followed by cold air circulation. The display should
show “System On”. If the setpoint temperature display is
fl ashing, the compressor lockout feature is operating (see
Confi guration menu, item 5).
3. Press to adjust the temperature setting above room
temperature. The cooling system should stop operating.
Choose the Fan Setting (Auto or On)
Fan Auto is the most commonly selected setting and runs the
fan only when the heating or cooling system is on.
Fan On selection runs the fan continuously for increased air
circulation or to allow additional air cleaning.
Fan ProgOn indicates that the fan is programmed to be on
for the entire period. The Prog Fan On can be overridden
to have the fan cycle with the system. Press the FAN button to change the fan to Auto. The fan programming will be
overridden until the next program period begins or until Run
Schedule is pressed.
Choose the System Setting
(Cool, Off, Heat, Auto)
Press the SYSTEM button to select:
Heat: Thermostat controls only the heating system.
Off: Heating and Cooling systems are off.
Cool: Thermostat controls only the cooling system.
Auto: Auto Changeover is used in areas where both heating
and cooling may be required on the same day. AUTO allows
the thermostat to automatically select heating or cooling
depending on the indoor temperature and the selected heat
and cool temperatures. When using AUTO, be sure to set the
Cooling temperatures more than 1° Fahrenheit higher than
the heating temperature.
Manual Operation for
Non-Programmable Mode
Press the SYSTEM button to select Heat or Cool and use
the buttons to adjust the temperature to your desired setting.
After selecting your desired settings you can also press the
SYSTEM button to select AUTO to allow the thermostat to
automatically change between Heat and Cool.
Manual Operation (Bypassing the Program)
Programmable Mode
Adjust the temperature wherever you like and then press
the HOLD button. This will override the program. The HOLD
feature bypasses the program and allows you to adjust the
temperature manually, as needed. Whatever temperature
you set in HOLD will be maintained 24 hours a day, until you
manually change the temperature or press Run Schedule to
cancel HOLD and resume the programmed schedule.
Program Override (Temporary Override)
Press buttons to adjust the temperature. This will override the
temperature setting for a two hour override period.
Example: If you turn up the heat during the morning program,
it will be automatically lowered later, when the temporary hold
period ends. To cancel the temporary setting at any time and
return to the program, press Run Schedule.
If the SYSTEM button is pressed to select AUTO the
thermostat will change to Heat or Cool, whichever ran last. If
it switches to heat, but you want cool, or it changes to cool,
but you want heat, press both buttons simultaneously to
change to the other mode.
8
Page 9
PROGRAMMING
Energy Saving Factory Pre-Program
The 1F97-0671 thermostat is programmed with the energy saving settings shown in the table below for all days of the week. If
this program suits your needs, simply set the thermostat clock and press the RunSched button.
The table below shows the factory set heating and cooling schedule for all days of the week.
* Wake Up
(Morn)
Heating
Program
Cooling
Program
* You can eliminate these two program periods in the confi guration menu (reference #15) if the building is occupied all day.
Day period will change to 6:00 AM and 70° and can be programmed as required.
6:00 AM70°F8:00 AM62°F5:00 PM70°F10:00 PM62°F
6:00 AM75°F8:00 AM83°F5:00 PM75°F10:00 PM78°F
Leave For Work
(Day)
* Return Home
(Eve)
Go To Bed
(Night)
Planning Your Program – Important
The Heating and Cooling Program schedules below allow you to pencil in your own program times and temperatures.
The 1F97-0671 comes confi gured for 7 day programming and can also be confi gured for 5+1+1 programming (see confi guration section).
Factory settings are listed on Monday, Saturday and Sunday. If you are re-programming a 5+1+1 day schedule, pencil in your
own times and temperatures directly below the factory times and temperatures.
If you are re-programming a 7 day schedule, fi ll in all lines with the times and temperatures you want.
Keep the following guidelines in mind when planning your program.
• In Heating, lower temperatures will save energy.
• In Cooling, higher temperatures will save energy.
• If you plan on using Auto Changeover, do not program the heating temperature higher than the cooling temperature.
Worksheet for Re-Programming 5+1+1 and 7 Day Program
1) Press Menu button to enter installer menu. Then press
Time once to indicate hour & AM or PM designation
in clock display.
2) Press and hold either the
reach the correct hour and AM or PM designation.
3) Press Time again to display minutes only in clock
display.
4) Press and hold either the
reach the correct minutes.
5) Press Time once again to display year.
6) Press and hold either the
reach the correct year.
7) Press Time once again to display month.
8) Press and hold either the
reach the correct month.
9) Press Time once again to display date of the month
along with day of the week at top row (which is auto matic).
10) Press and hold either the
reach the correct day of the month and day of the week
is automatically calculated and displayed at the top row.
11) Press Run Sched button once; now the display will show
the correct time and room temperature.
or button until you
or button until you
or button until you
or button until you
or button until you
Automatic Daylight Saving Calculation
The Real Time Clock will adjust automatically for daylight savings time, in the following manner:
Increment one hour at 2 AM on the second Sunday of March
and decrement one hour at 2 AM on the fi rst Sunday of November. (New DST effective 2007).
The daylight saving feature can be enabled or disabled in
installer confi guration menu. Default is DS ON (enabled).
After entering installer confi guration mode, momentarily
press MENU button until the display indicates dS (in actual
temperature digits) and on (default – in clock digits).
buttons will toggle display and operation from on to OFF.
or
Programming Tip: Copy Program
When programming your thermostat, you may copy the program from one day to another day or group of days using the
Copy key. In 7 day programming mode, a day can be copied
to another day or all six other days. In 5/1/1 day programming
mode the weekday (Mon – Fri) program can be copied into
Sat and Sun or either Sat or Sun.
To copy a program from one day to another:
1) In Set Schedule mode, enter the program for the day or
select the day you wish to copy by pressing Advance Day.
2) Press Copy. On the display, "Copy" will begin to fl ash. The
day of the week being copied will show.
3) Press Advance Day. The day being copied will be indi-
cated and the other days will be fl ashing.
4) If you wish to copy to all days skip to next step or press
Advance Day until the day you wish to copy to is fl ashing.
5) Press Copy. “Copy” will be on, the day you copied from
will disappear and the day(s) you copied to will be on.
6) If you wish to copy this same program into other days,
press Copy and repeat steps 2 through 5.
7) Press RunSched to return to normal operation.
Fill in the blank schedule on the previous page then:
Enter the Heating Program
1) Press SYSTEM button to select "Heat" in the system
switch area indicating the active mode being programmed.
2) Press the Menu button and then press Schedule.
3) The top of the display will show the day(s) being programmed. The fi rst period to be programmed will appear.
The set temperature will also be displayed and the time
will be fl ashing to indicate that the time can be changed.
4) Press
period. The time will change in 15 minute increments.
5) Press the System Time button to change to the tempera-
ture fl ashing.
6) Press
your selected temperature for the fi rst heating period.
7) After you have set the time and temperature for the fi rst
period, press Schedule to advance to the next program
period.
8) Repeat steps 4 through 7 until all of the program times
and temperatures are entered for all program periods for
that day.
9) Press Schedule button to change to the next day and
repeat steps 4 through 8 until all program days and periods are entered.
10)When programming is complete and all of the times and
temperatures match your desired heating schedule, press
RunSched. The thermostat will now run your program.
or buttons to adjust the start time for the
or buttons to change the temperature to
Enter the Cooling Program
1) Press the SYSTEM button until the Cool icon appears.
2) Follow Enter Heating Program instructions for entering
cooling times and temperatures.
Automatic Schedule
This feature provides a method to program every day with the
most popular time and temperature settings using one key.
For this feature to be available, the Auto Schedule options
(Installer/Confi guration menu item 14, AS Heat, or item 15,
AS Cool) must be selected On.
To use Auto Schedule, press RunSched to be sure you are in
normal operating mode. In SYSTEM Heat mode, use the keys
to select your “Comfort Temperature”. When your “Comfort
Temperature” is selected, press Auto Sched button. The
Auto Schedule key will disappear to indicate that the Auto
Schedule command has been accepted.
In Heat mode the thermostat will maintain your “Comfort Temperature” during the Morning, Day and Evening periods and
setback 6° for the Night. Morning period will begin at 6:30 AM
and Night period will begin at 10:30 PM.
To set the Auto Schedule temperature for Cool mode, press
SYSTEM to change the mode to Cool and repeat setting the
temperature. In Cool mode, the thermostat will maintain your
selected “Comfort Temperature” continuously.
The “Comfort Temperature” can be temporarily overridden
by changing the setpoint temperature using the
buttons. Once Auto Schedule has been set and the key has
disappeared, it can be reset in the Installer/ Confi guration
menu.
or
10
Page 11
PROGRAMMING
Entering Fan Program
The fan can be programmed to turn on at the beginning of a
period and remain on through the whole period. In RunSched
mode when the FAN switch indicates Prog Fan On the fan is
programmed to be on for the period.
1) Press System button to select either Heat or Cool.
2) Press Menu button and then press Fan button to the right
of the display.
3) The top of the display will show the day(s) being programmed. The fi rst period to be programmed will appear.
4) Press the Fan button to change from Auto to Prog.
5) Press the Fan button to the right of the display to change
to the next period.
6) Repeat steps 4 and 5 to program the fan for all periods of
the day.
7) Press Fan to advance to the next day of the week and
repeat steps 4 through 7 to program the fan for all days of
the week.
Wired Remote Temperature Sensing
One remote temperature sensor can be installed indoor or
outdoor and connected to the thermostat by a maximum
cable length of 100 meters (300 feet). Terminals +, S and - on
the terminal block allow connection of the remote sensor.
The thermostat must have 24 VAC Common connection to
terminal C for the remote sensor to operate. The remote sensor can be enabled or disabled in the Installer/Confi guration
menu, item 16.
When remote sensor, Remote, is selected Off (factory default), no remote sensor is enabled. When remote sensor is
selected On, the next step is to select the remote as indoor,
Remote In, or outdoor, Remote Outdoor. If the remote is selected as Remote In, an additional step will be to select if the
temperature shown on the display will be from the thermostat,
Loc On, or the remote sensor Loc Off.
In normal operation, when a remote sensor is enabled the
time digits of the display will alternate between the time and
the remote temperature for three seconds each. Above the
remote temperature will be Remote, for indoor sensor or
Outdoor Remote, for outdoor sensor. If the remote sensor is
an indoor sensor and the local display has been disabled, the
temperature displayed as the room temperature will be the
remote sensor temperature.
Sensing Range:
Outdoor temperature range is -40
Indoor temperature range is 32
o
F to 140oF
o
F to 99 oF
Weighing of Remote Reading:
The thermostat will weight or average the temperature of the
indoor remote sensor with the local sensor in the thermostat
for each program period. The averaging will be active only
when the local sensor and the indoor remote sensor are both
functional and enabled in the Installer/Confi guration menu.
When the thermostat is in the Set Schedule mode, the weight
of the indoor sensor will be shown in the current temperature
digits of the display. The weight will show as A2 (average and
default), H4 (high) or L1 (low). Pressing the or buttons at the same time will change the weight for the program
period. The weight of the thermostat sensor is fi xed.
In normal operation of the thermostat, the current temperature displayed will be the weighted average of the local
sensor and the remote sensor using the formula (local sensor
weight x local sensor temperature) + (remote sensor weight x
remote sensor temperature) / (local sensor weight + remote
sensor weight).
Example: Local sensor temperature is 80° and the remote
sensor is 70°.
If weight is selected H4, the averaged temperature of 72° will
be displayed.
(1 x 80) + (4 x 70) / 5 = 72°
If weight is selected A2, the average temperature of 73° will
be displayed.
(1 x 80) + (2 x 70) / 3 = 73.3°
If weight is selected L1, the average temperature of 75° will
be displayed.
(1 x 80) + (1 x 70) / 2 = 75°
The example shows that the weight selected would prioritize
the overall averaged temperature between the two sensors.
The high weight selection caused the remote sensor to have
a higher infl uence in the calculated temperature average than
the local sensor and the low weight selection caused the
remote sensor to have less infl uence.
11
Page 12
TROUBLESHOOTING
Reset Operation
Note: When thermostat is reset, installer confi guration menu settings and programming will reset to factory settings.
If a voltage spike or static discharge blanks out the display or causes erratic thermostat operation, you can reset the thermostat by removing the wires from terminals R and C (do not short them together) and removing batteries for 2 minutes. After
resetting the thermostat, replace the wires and batteries. If the thermostat has been reset and still does not function correctly
contact your heating/cooling service person or place of purchase.
Note: Be sure to review the installer confi guration menu settings.
To reset the programming, clock and confi guration settings, press the
thermostat should go blank and then all segments will be displayed momentarily.
1. The location of the thermostat and/or
the size of the Heating System may
be infl uencing the cycle rate.
, and SYSTEM button simultaneously. The
Replace fuse or reset breaker.
Turn switch to ON.
Replace door panel in proper position to engage safety
interlock or door switch.
Tighten connections.
Re-light pilot.
Many furnaces have safety devices that shut down when
a lock-out condition occurs. If the heat works intermittently
contact the furnace manufacturer or local HVAC service
person for assistance.
Diagnostic: Set SYSTEM Switch to HEAT and raise the
setpoint above room temperature. Within a few seconds
the thermostat should make a soft click sound. This sound
usually indicates the thermostat is operating properly. If
the thermostat does not click, try the reset operation listed
above. If the thermostat does not click after being reset
contact your heating and cooling service person or place
of purchase for a replacement. If the thermostat clicks,
contact the furnace manufacturer or a HVAC service
person to verify the heating is operating correctly.
Same as diagnostic for No Heat condition except set the
thermostat to COOL and lower the setpoint below the
room temperature. There may be up to a fi ve minute delay
before the thermostat clicks in Cooling.
Check each wire connection to verify they are not shorted
or touching together. No bare wire should stick out from
under terminal block. Try resetting the thermostat as described above. If the condition persists the manufacturer
of your system or service person can instruct you on how
to test the Heat/Cool system for correct operation. If the
system operates correctly, replace the thermostat.
The thermometer can be adjusted +/- 4 degrees. See
Temperature Display Adjustment in the Confi guration
Menu section.
Digital thermostats provide precise control and cycle
faster than older mechanical models. The system turns
on and off more frequently but runs for a shorter time
so there is no increase in energy use. If you would like
an increased cycle time, choose SL for slow cycle in the
Confi guration menu, step 7 (heat) or 8 (cool). If an acceptable cycle rate is not achieved, contact a local HVAC
service person for additional suggestions.
Press the menu button (button will disappear) and hold in
for 20 seconds. This unlocks the thermostat.
White-Rodgers is a division
of Emerson Electric Co.
The Emerson logo is a
trademark and service mark
of Emerson Electric Co.
HOMEOWNER HELP LINE: 1-800-284-2925
St. Louis, MissouriMarkham, Ontario
www.white-rodgers.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.