White Rodgers 1F95-391 User Manual

INSTALLATION
DESCRIPTION
WHITE-RODGERS 90 SERIES
1F95-391
MULTI-STAGE/HEAT PUMP INSTALLATION/CONFIGURATION
This White-Rodgers Digital Thermostat uses microcomputer technology to provide precise time, humidity, and temperature control. This thermostat offers the flexibility to design
SPECIFICATIONS
1F95-391: 7 Day programming; residen-
ELECTRICAL DATA
Electrical Rating:
20 to 30 VAC, 50/60 Hz with common
0.05 to 1.5 Amps per terminal
2.5 Amps maximum total load (all terminals combined). Hardwired only. C terminal is required.
PRECAUTIONS
WARNING
!
Do not short out terminals on gas valve or primary control to test. Short or incorrect wiring will damage thermostat and could cause personal injury and/or property damage.
Do not use on circuits exceeding specified voltage. Higher voltage will damage thermostat and could cause shock or fire hazard.
Thermostat installation and all compo­nents of the system shall conform to Class II circuits per the NEC code.
heating and cooling programs that fit building needs. This thermostat is adaptable to most 24 volt residential forced air multi-
Standard Systems:
Multi-stage gas, oil, electric.
Single-stage or two-stage compressor
heat pump.
THERMAL DATA
Setpoint Temperature Range:
45° to 99°F (7° to 37°C)
CAUTION
!
To prevent electrical shock and/or equipment damage, disconnect electric power to system at main fuse or circuit breaker box until installation is complete.
NOTE
Read all instructions thoroughly before beginning installation.
This thermostat is intended for use with a low voltage system. Do not use on a line voltage system.
stage or heat pump systems with electric or fossil fuel auxiliary.
Operating Ambient Temperature:
32° to 110°F (0° to 43°C)
Operating Humidity Range:
90% non-condensing max.
Shipping Temperature Range:
-4° to 149°F (-20° to 65°C)
Do not exceed ratings shown in the Specifi­cations section, above. If in doubt about the electrical ratings of your heating/cooling system, have it inspected by a qualified heating and air conditioning contractor or licensed electrician.
All wiring must conform to local and national electrical codes and ordinances.
This control is a precision instrument, and should be handled carefully. Rough handling or distorting components could cause the control to malfunction.
White-Rodgers is a division
of Emerson Electric Co.
www.white-rodgers.com
Part No. 37-6527B
Replaces 37-6527A
0443
INSTALLATION
ATTENTION!
This product does not contain mercury. However, this product may replace a unit which contains mercury.
Do not open mercury cells. If a cell becomes damaged, do not touch any spilled mercury. Wearing non-absorbent gloves, take up the spilled mercury with sand or other absorbent material and place into a container which can be sealed. If a cell becomes damaged, the unit should be discarded.
Mercury must not be discarded in household trash. When the unit this product is replacing is to be discarded, place in a suitable container and return to White-Rodgers at 2895 Harrison Street, Batesville, AR 72501 for proper disposal.
REMOVE OLD THERMOSTAT
Shut off electricity at main fuse or circuit breaker box until installation is complete AND the new thermostat is configured properly.
Remove the front cover of the old thermo­stat. With wires still attached, remove wall plate from the wall.
Identify each wire attached to the thermo­stat using one of the labels enclosed with the
new thermostat. Disconnect the wires from the old thermostat
one at a time. DO NOT let the wires fall back into the wall.
Install the new thermostat using the follow­ing procedures.
ATTACH BASE TO WALL
Remove packing material from the thermo­stat. Place fingers of one hand on the center top and bottom portion of the thermostat. Grasp the base in the other hand on top and bottom center and gently pull straight out. Forcing or prying on the thermostat will cause damage to the unit.
Place the base over the hole in the wall where the wires come out and mark mount­ing hole locations using the base as a template. Drill
3
16” pilot holes, and install
screw anchors in the wall. Run wires through hole in base and attach
base to wall (see fig. 1). Insert the wires into the terminals on the base
using the appropriate wiring diagram and tighten the terminal screws.
CONFIGURING AND PROGRAM­MING
The thermostat must be configured to operate properly with the system. See the CON­FIGURATION section of this manual.
This thermostat can be programmed for automatic temperature control. Refer to Operating Instructions for programming.
Mounting screws
1
Pull wires through this opening
2
Insert wires into terminal holes, then tighten screws
3
Screw anchors
4
Jumper connections for remote sensor power
5
(Do not remove)
Figure 1. Thermostat base and terminals
2
MULTI-STA GE TERMINAL OUTPUTS
Refer to equipment manufacturers’ instruc­tions for specific system wiring information.
You can configure the thermostat for use with either multi-stage electric heat systems or multi-stage gas systems. When configured for electric heat, the G terminal (blower/fan) will be energized on a call for heat, using the installer table (pgs. 5 & 6).
THERMOSTAT TERMINALS (Upper)
L SA SB SC OT
Malfunction Light Remote Sense A Remote Sense B Remote Sense C Outdoor Sensor
SYSTEM C R HM W2 DHM E/W1 Y2 Y1 B O G
Multi-Stage
24 Volt
(Common)
24 Volt
(Hot)
Energizes on a
call for heat if
Humidity setpoint is
above room
humidity.
This thermostat is designed to operate a single-transformer system. If you have a two­transformer system, cut and tape off one transformer. If transformer safety circuits are in only one of the systems, remove the transformer of the system with NO safety circuits. If required, replace remaining transformer with a 75VA Class II transformer. After disconnecting one transformer, the two commons must be jumpered together.
THERMOSTAT TERMINALS (Lower)
Heat mode
2nd stage
E2/P switch in the P position,
Energizes on a call for
Dehumidification.
E2/P switch in E2 position,
De-energizes on a
call for Dehumidification.
Heat mode
1st stage
Cool mode
2nd stage
Use the terminal output information below to help you wire the thermostat properly for your multi-stage system. After wiring, see CONFIGURATION section for proper thermostat configuration.
Cool mode
1st stage
Energized in Heat
and Off Mode
Energized in
Cool Mode
Blower/Fan
Energized on
call for Cool (and Heat if configured
to Electric Heat).
HEAT PUMP TERMINAL OUTPUTS
Refer to equipment manufacturers’ instruc­tions for specific system wiring information.
You can configure the thermostat for use with the following heat pump system types:
HEAT PUMP TYPE 1. Single-stage compressor system; gas or electric backup.
HEAT PUMP TYPE 2. Multi-stage or two­compressor system; gas or electric backup.
This thermostat is designed to operate a single-transformer system. If you have a two­transformer system, cut and tape off one transformer. If transformer safety circuits are in only one of the systems, remove the transformer of the system with NO safety circuits. If required, replace remaining transformer with a 75VA Class II transformer. After disconnecting one transformer, the two
Use the terminal output information below to help you wire the thermostat properly for your heat pump system type. After wiring, see CONFIGURATION section for proper thermostat configuration.
commons must be jumpered together.
THERMOSTAT TERMINALS (Upper)
L SA SB SC OT
Malfunction Light Remote Sense A Remote Sense B Remote Sense C Outdoor Sensor
THERMOSTAT TERMINALS (Lower)
SYSTEM C R HM W2 DHM E/W1 Y2 Y1 B O G
Single-stage compressor system; gas or electric backup
Heat Pump 1
Multi-stage or two compressor system; gas or electric backup
Heat Pump 2
24 Volt
(Common)
24 Volt
(Common)
24 Volt
(Hot)
24 Volt
(Hot)
Energizes on a
call for heat if
Humidity setpoint is
above room
humidity.
Energizes on a
call for heat if
Humidity setpoint is
above room
humidity.
Heat mode
3rd stage,
Emergency Mode
2nd stage
Emergency Mode
2nd stage
E2/P switch in P position,
Energizes on a call for
Dehumidification.
E2/P switch in E2 position,
De-energizes on a
call for Dehumidification.
E2/P switch in P position,
Energizes on a call for
Dehumidification.
E2/P switch in E2 position,
De-energizes on a
call for Dehumidification.
Heat mode 2nd stage,
Emergency Mode
1st stage
Heat mode
3rd stage,
Emergency Mode
1st stage
No Output
Heat and
Cool mode
2nd stage
(compressor 2)
Heat and
Cool mode
1st stage
(compressor 1)
Heat and
Cool mode
1st stage
(compressor 1)
Energized in Heat,
Off, Emergency
Mode
Energized in Heat,
Off, Emergency
Mode
Energized in
Cool Mode
Energized in
Cool Mode
Blower/Fan
Energized on
call for Heat and Cool
Blower/Fan
Energized on
call for Heat and Cool
3
CONFIGURATION
SWITCHES
RESET SWITCH
See the Troubleshooting section at the end of this document for more information about the function of this switch.
E2/P SWITCH (DHM) TERMINAL
S18
FUNCTION
The E2/P switch is located on the back of the thermostat body (see fig. 2). This switch controls how the DHM terminal will be energized.
1. In the P position (up) the DHM terminal will be energized on a call for dehumidification.
2. In the E2 position (down) the DHM terminal will always be energized except on a call for dehumidification. The switch must be in the E2 position on some electronically controlled variable speed blower systems.
DEHUMIDIFICATION WIRING WITHOUT AN ELECTRONICALLY CONTROLLED VARIABLE SPEED BLOWER SYSTEM FOR SINGLE STAGE COMPRESSOR SYSTEM ONLY
If you have a single stage compressor system see the diagram below. A relay (customer provided) should be installed as shown in Fig. 5 to switch the fan speed to the next lower speed on a call for dehumidification from the thermostat. The reduction in air flow allows the coil to remove more humidity from the air. The relay should be rated for blower motor load. Since this configuration reduces the air flow in cooling, the anti­freeze-up control (White-Rodgers CAFC) or equivalent is recommended. The CAFC prevents the air conditioning coil from freezing due to low air flow, dirty filters, low refrigerant pressure, etc. The CAFC snaps onto the suction line close to the evaporator coil as possible and breaks the compressor circuit when the suction line drops below 38°F and re-make the circuit at 46°F.
Reset switch
1
E2/P switch
2
Figure 2. Switch locations on back of thermostat body
P
E2
S19
1
2
NOTE: If you have a two stage compressor, the thermostat software will lengthen cycle times for the first stage of cool. The longer cycles will
improve dehumidification while cooling, allowing the DHM terminal not to be used on a two stage compressor system.
Selecting P - DHM Energizes on call for
Dehumidification
Selecting E2 - DHM Deenergizes on call for
Dehumidification
CRG
Y1
E2
DHM
P
N.C.
Customer supplied relay rated for blower motor load
N.O.
24VAC
TRANSFORMER
Cool Fan Speed
Furnace Control Module
MED. HIGH
Heat Fan Speed
HIGH
3-4 speed Blower
LOW
Motor
COMMON
HOT
120 VAC
NEUTRAL
Figure 3. Typical Wiring for Dehumidifier System
HM
Relay 90-290Q or equivalent
Humidifier
System
Figure 4. Typical Wiring for 120V Humidifier System
HOT
NEUTRAL
120 VAC
Typical Wiring for 120V Humidifier System
24 VAC
R
I
TRANSFORMER
HOT
NEUTRAL
120 VAC
HM
Humidifier
System
Typical Wiring for 24V Humidifier System
Figure 5. Typical Wiring for 24V Humidifier System
24 VAC
R
I
TRANSFORMER
HOT
NEUTRAL
4
120 VAC
Loading...
+ 8 hidden pages