White Rodgers 1F95-391 User Manual

Page 1
INSTALLATION
DESCRIPTION
WHITE-RODGERS 90 SERIES
1F95-391
MULTI-STAGE/HEAT PUMP INSTALLATION/CONFIGURATION
This White-Rodgers Digital Thermostat uses microcomputer technology to provide precise time, humidity, and temperature control. This thermostat offers the flexibility to design
SPECIFICATIONS
1F95-391: 7 Day programming; residen-
ELECTRICAL DATA
Electrical Rating:
20 to 30 VAC, 50/60 Hz with common
0.05 to 1.5 Amps per terminal
2.5 Amps maximum total load (all terminals combined). Hardwired only. C terminal is required.
PRECAUTIONS
WARNING
!
Do not short out terminals on gas valve or primary control to test. Short or incorrect wiring will damage thermostat and could cause personal injury and/or property damage.
Do not use on circuits exceeding specified voltage. Higher voltage will damage thermostat and could cause shock or fire hazard.
Thermostat installation and all compo­nents of the system shall conform to Class II circuits per the NEC code.
heating and cooling programs that fit building needs. This thermostat is adaptable to most 24 volt residential forced air multi-
Standard Systems:
Multi-stage gas, oil, electric.
Single-stage or two-stage compressor
heat pump.
THERMAL DATA
Setpoint Temperature Range:
45° to 99°F (7° to 37°C)
CAUTION
!
To prevent electrical shock and/or equipment damage, disconnect electric power to system at main fuse or circuit breaker box until installation is complete.
NOTE
Read all instructions thoroughly before beginning installation.
This thermostat is intended for use with a low voltage system. Do not use on a line voltage system.
stage or heat pump systems with electric or fossil fuel auxiliary.
Operating Ambient Temperature:
32° to 110°F (0° to 43°C)
Operating Humidity Range:
90% non-condensing max.
Shipping Temperature Range:
-4° to 149°F (-20° to 65°C)
Do not exceed ratings shown in the Specifi­cations section, above. If in doubt about the electrical ratings of your heating/cooling system, have it inspected by a qualified heating and air conditioning contractor or licensed electrician.
All wiring must conform to local and national electrical codes and ordinances.
This control is a precision instrument, and should be handled carefully. Rough handling or distorting components could cause the control to malfunction.
White-Rodgers is a division
of Emerson Electric Co.
www.white-rodgers.com
Part No. 37-6527B
Replaces 37-6527A
0443
Page 2
INSTALLATION
ATTENTION!
This product does not contain mercury. However, this product may replace a unit which contains mercury.
Do not open mercury cells. If a cell becomes damaged, do not touch any spilled mercury. Wearing non-absorbent gloves, take up the spilled mercury with sand or other absorbent material and place into a container which can be sealed. If a cell becomes damaged, the unit should be discarded.
Mercury must not be discarded in household trash. When the unit this product is replacing is to be discarded, place in a suitable container and return to White-Rodgers at 2895 Harrison Street, Batesville, AR 72501 for proper disposal.
REMOVE OLD THERMOSTAT
Shut off electricity at main fuse or circuit breaker box until installation is complete AND the new thermostat is configured properly.
Remove the front cover of the old thermo­stat. With wires still attached, remove wall plate from the wall.
Identify each wire attached to the thermo­stat using one of the labels enclosed with the
new thermostat. Disconnect the wires from the old thermostat
one at a time. DO NOT let the wires fall back into the wall.
Install the new thermostat using the follow­ing procedures.
ATTACH BASE TO WALL
Remove packing material from the thermo­stat. Place fingers of one hand on the center top and bottom portion of the thermostat. Grasp the base in the other hand on top and bottom center and gently pull straight out. Forcing or prying on the thermostat will cause damage to the unit.
Place the base over the hole in the wall where the wires come out and mark mount­ing hole locations using the base as a template. Drill
3
16” pilot holes, and install
screw anchors in the wall. Run wires through hole in base and attach
base to wall (see fig. 1). Insert the wires into the terminals on the base
using the appropriate wiring diagram and tighten the terminal screws.
CONFIGURING AND PROGRAM­MING
The thermostat must be configured to operate properly with the system. See the CON­FIGURATION section of this manual.
This thermostat can be programmed for automatic temperature control. Refer to Operating Instructions for programming.
Mounting screws
1
Pull wires through this opening
2
Insert wires into terminal holes, then tighten screws
3
Screw anchors
4
Jumper connections for remote sensor power
5
(Do not remove)
Figure 1. Thermostat base and terminals
2
Page 3
MULTI-STA GE TERMINAL OUTPUTS
Refer to equipment manufacturers’ instruc­tions for specific system wiring information.
You can configure the thermostat for use with either multi-stage electric heat systems or multi-stage gas systems. When configured for electric heat, the G terminal (blower/fan) will be energized on a call for heat, using the installer table (pgs. 5 & 6).
THERMOSTAT TERMINALS (Upper)
L SA SB SC OT
Malfunction Light Remote Sense A Remote Sense B Remote Sense C Outdoor Sensor
SYSTEM C R HM W2 DHM E/W1 Y2 Y1 B O G
Multi-Stage
24 Volt
(Common)
24 Volt
(Hot)
Energizes on a
call for heat if
Humidity setpoint is
above room
humidity.
This thermostat is designed to operate a single-transformer system. If you have a two­transformer system, cut and tape off one transformer. If transformer safety circuits are in only one of the systems, remove the transformer of the system with NO safety circuits. If required, replace remaining transformer with a 75VA Class II transformer. After disconnecting one transformer, the two commons must be jumpered together.
THERMOSTAT TERMINALS (Lower)
Heat mode
2nd stage
E2/P switch in the P position,
Energizes on a call for
Dehumidification.
E2/P switch in E2 position,
De-energizes on a
call for Dehumidification.
Heat mode
1st stage
Cool mode
2nd stage
Use the terminal output information below to help you wire the thermostat properly for your multi-stage system. After wiring, see CONFIGURATION section for proper thermostat configuration.
Cool mode
1st stage
Energized in Heat
and Off Mode
Energized in
Cool Mode
Blower/Fan
Energized on
call for Cool (and Heat if configured
to Electric Heat).
HEAT PUMP TERMINAL OUTPUTS
Refer to equipment manufacturers’ instruc­tions for specific system wiring information.
You can configure the thermostat for use with the following heat pump system types:
HEAT PUMP TYPE 1. Single-stage compressor system; gas or electric backup.
HEAT PUMP TYPE 2. Multi-stage or two­compressor system; gas or electric backup.
This thermostat is designed to operate a single-transformer system. If you have a two­transformer system, cut and tape off one transformer. If transformer safety circuits are in only one of the systems, remove the transformer of the system with NO safety circuits. If required, replace remaining transformer with a 75VA Class II transformer. After disconnecting one transformer, the two
Use the terminal output information below to help you wire the thermostat properly for your heat pump system type. After wiring, see CONFIGURATION section for proper thermostat configuration.
commons must be jumpered together.
THERMOSTAT TERMINALS (Upper)
L SA SB SC OT
Malfunction Light Remote Sense A Remote Sense B Remote Sense C Outdoor Sensor
THERMOSTAT TERMINALS (Lower)
SYSTEM C R HM W2 DHM E/W1 Y2 Y1 B O G
Single-stage compressor system; gas or electric backup
Heat Pump 1
Multi-stage or two compressor system; gas or electric backup
Heat Pump 2
24 Volt
(Common)
24 Volt
(Common)
24 Volt
(Hot)
24 Volt
(Hot)
Energizes on a
call for heat if
Humidity setpoint is
above room
humidity.
Energizes on a
call for heat if
Humidity setpoint is
above room
humidity.
Heat mode
3rd stage,
Emergency Mode
2nd stage
Emergency Mode
2nd stage
E2/P switch in P position,
Energizes on a call for
Dehumidification.
E2/P switch in E2 position,
De-energizes on a
call for Dehumidification.
E2/P switch in P position,
Energizes on a call for
Dehumidification.
E2/P switch in E2 position,
De-energizes on a
call for Dehumidification.
Heat mode 2nd stage,
Emergency Mode
1st stage
Heat mode
3rd stage,
Emergency Mode
1st stage
No Output
Heat and
Cool mode
2nd stage
(compressor 2)
Heat and
Cool mode
1st stage
(compressor 1)
Heat and
Cool mode
1st stage
(compressor 1)
Energized in Heat,
Off, Emergency
Mode
Energized in Heat,
Off, Emergency
Mode
Energized in
Cool Mode
Energized in
Cool Mode
Blower/Fan
Energized on
call for Heat and Cool
Blower/Fan
Energized on
call for Heat and Cool
3
Page 4
CONFIGURATION
SWITCHES
RESET SWITCH
See the Troubleshooting section at the end of this document for more information about the function of this switch.
E2/P SWITCH (DHM) TERMINAL
S18
FUNCTION
The E2/P switch is located on the back of the thermostat body (see fig. 2). This switch controls how the DHM terminal will be energized.
1. In the P position (up) the DHM terminal will be energized on a call for dehumidification.
2. In the E2 position (down) the DHM terminal will always be energized except on a call for dehumidification. The switch must be in the E2 position on some electronically controlled variable speed blower systems.
DEHUMIDIFICATION WIRING WITHOUT AN ELECTRONICALLY CONTROLLED VARIABLE SPEED BLOWER SYSTEM FOR SINGLE STAGE COMPRESSOR SYSTEM ONLY
If you have a single stage compressor system see the diagram below. A relay (customer provided) should be installed as shown in Fig. 5 to switch the fan speed to the next lower speed on a call for dehumidification from the thermostat. The reduction in air flow allows the coil to remove more humidity from the air. The relay should be rated for blower motor load. Since this configuration reduces the air flow in cooling, the anti­freeze-up control (White-Rodgers CAFC) or equivalent is recommended. The CAFC prevents the air conditioning coil from freezing due to low air flow, dirty filters, low refrigerant pressure, etc. The CAFC snaps onto the suction line close to the evaporator coil as possible and breaks the compressor circuit when the suction line drops below 38°F and re-make the circuit at 46°F.
Reset switch
1
E2/P switch
2
Figure 2. Switch locations on back of thermostat body
P
E2
S19
1
2
NOTE: If you have a two stage compressor, the thermostat software will lengthen cycle times for the first stage of cool. The longer cycles will
improve dehumidification while cooling, allowing the DHM terminal not to be used on a two stage compressor system.
Selecting P - DHM Energizes on call for
Dehumidification
Selecting E2 - DHM Deenergizes on call for
Dehumidification
CRG
Y1
E2
DHM
P
N.C.
Customer supplied relay rated for blower motor load
N.O.
24VAC
TRANSFORMER
Cool Fan Speed
Furnace Control Module
MED. HIGH
Heat Fan Speed
HIGH
3-4 speed Blower
LOW
Motor
COMMON
HOT
120 VAC
NEUTRAL
Figure 3. Typical Wiring for Dehumidifier System
HM
Relay 90-290Q or equivalent
Humidifier
System
Figure 4. Typical Wiring for 120V Humidifier System
HOT
NEUTRAL
120 VAC
Typical Wiring for 120V Humidifier System
24 VAC
R
I
TRANSFORMER
HOT
NEUTRAL
120 VAC
HM
Humidifier
System
Typical Wiring for 24V Humidifier System
Figure 5. Typical Wiring for 24V Humidifier System
24 VAC
R
I
TRANSFORMER
HOT
NEUTRAL
4
120 VAC
Page 5
INSTALLER CONFIGURATION
BEFORE TURNING POWER ON, please read the following instructions. Before operating the system, you must configure the thermostat to operate properly with your equipment.
The thermostat, as it comes from the factory, is configured to operate a standard multi-
stage electric forced hot air system with a single stage air conditioning compressor
and fan. In this configuration, the thermostat will turn on the fan immediately on a call for heat. If you are unsure whether your system requires the thermostat to control the fan, contact your furnace/air conditioning system manufacturer or a qualified heating/air conditioning service person.
Your new thermostat has an Installer table, which allows you to customize the thermostat to meet your requirements.
(The thermostat also has a User menu,
Keypad Lockout menu and a Service menu; these menus are explained further
in the Operating Instructions.) The menu settings can be changed at any time
to meet system or personal requirements.
ENTERING THE CONFIGURA TION MENUS
After properly wiring the thermostat, turn on power to the system. Momentarily press
RUN
PROGRAM
to make certain the
thermostat is in the run program mode, then press TIME
FWD
and TIME
BACK
at the
same time to enter the User Configuration menu. When the display changes to the first item in the configuration menu, release the
TIME
buttons. Then press and hold SET
DAY
SET
for approximately 3 seconds to
and
enter the Installer table. The display will change to show the first item on the Installer table (multi-stage/heat pump selection). Use the following text, along with the Installer table, to guide you through the selections.
Once in the table, you set each item to the proper selection using
press TIME
FWD
to change the display to
the next item or TIME
or , then
BACK
to return to the
previous item. To exit the table at any time, press PRO-
RUN
GRAM
.
MULTI-STAGE/HEAT PUMP MODE.
(Installer table step 1.) Use this item to select the system type (multi-stage or heat pump). IF YOU HAVE A HEAT PUMP SYSTEM, you must select HEAT PUMP here. This sets up proper default values for most heat pump systems. This selection also makes available some additional menu items that apply only to heat pump systems.
HEAT PUMP COMPRESSOR CONFIGURATION.
(Installer table step 2; this item is displayed only when heat pump was selected in step 1.) Use this item to select the number of heat pump compressors.
ELECTRIC HEAT FAN CONFIGURATION.
(Installer table step 3.) This item determines whether fan control will be through the thermostat or through the heating system. If you have an electric heat or other system that REQUIRES the thermostat to control the fan, set this item ON. This allows the thermostat to energize the fan immediately on a call for heat. If you are unsure if the system requires the thermostat to control the fan, contact the equipment manufacturer or a qualified heating and air conditioning service person. If your system controls fan operation (as with most fossil fuel systems), set this item to OFF. Note that with heat pump systems, the fan always cycles with the compressor.
SET CYCLE HEAT, COOL, AUX (ANTICIPATION).
(Installer table steps 4 through 6; step 6 is for heat pump only). These items allow the cycle times in heating, cooling and auxiliary (heat pump systems only) to be increased or decreased. The factory set values can be adjusted higher for longer cycles or lower for shorter cycles.
NOTE: Some manufacturers still instruct you to set the anticipator to the current draw of the equipment. That instruction applies only to mercury bulb or mechanical thermostats; it does not apply to this digital thermostat. As configured at the factory, this thermostat will maintain an accurate temperature. No further adjustment is necessary, although you can use these items to customize the performance of the thermostat to your requirements.
The adjustment range for HEATING is from 1 to 40 (9 to 40 for heat pump). The factory preset is 5 (13 for heat pump). The adjust­ment range for COOLING is from 9 to 40. The factory preset is 12 (13 for heat pump). The cooling will not go below 9 because compressors require a longer cycle. The adjustment range for AUXILIARY (heat pump only) is from 1 to 40. The factory preset is 6.
The chart on page 7 shows how this adjustment range affects thermostat perfor­mance.
PROGRAMMABLE COOL FAN-OFF AND FAN-ON DELAY.
(Installer table steps 7 and 8.) These items allow a selection of 0 to 127 seconds of fan­off delay after the thermostat has satisfied the call for cool, or a fan-on delay of 1 to 30 seconds on a call for cool (or heat pump compressor activation).
The fan-off delay allows the fan to continue running after the compressor has shut off. This distributes the cool air that would otherwise stay trapped in the air conditioning coils through the ducts. Ideally the timing would be set so the fan shuts off just as the cool air is exhausted. If this timing is set too long the fan may begin blowing warm air before it shuts off. Shortening the fan-off delay will prevent this.
A short delay to allow the A-coil to cool off (or warm up in heat pump) before the fan turns on may be preferred. This also allows the compressor and the fan to come on at slightly different times, which allows full power to the compressor on start up. Recommended setting for fan-on delay is 10 seconds or less.
PROGRAMMABLE HEAT FAN­OFF DELAY.
(Installer table step 9.) This item allows a selection of 0 to 127 seconds of fan-off delay after the thermostat has satisfied the call for heat if ELECT HEAT FAN (Step 3) is selected ON.
The fan-off delay allows the fan to continue running after the burner, heating element, etc. has shut off. This distributes the heat that would otherwise stay trapped in the ducts. Ideally the timing would be set so the fan shuts off just as the warm air is exhausted. If this timing is set too long the fan may begin blowing cool air before it shuts off. Shorten­ing the fan-off delay will prevent this.
PUMP (FOSSIL FUEL KIT ALTER­NATIVE STEPS 10 - 13).
(Installer table step 10; heat pump only) This item controls heat pump compressor operation with a fossil fuel auxiliary. This item may eliminate the need for a separate fossil fuel kit, although we recommend that you consult the heat pump system manufac­turer before using this feature instead of a kit. This item will allow the thermostat to turn the heat pump compressor off if the auxiliary is on for more than one minute, to prevent compressor head pressure from getting too high. To use this feature instead of a kit, select PUMP OFF.
5
Page 6
INSTALLER TABLE
y
NOTE: You must be in the User Configuration Menu to enter the Installer Table. Firmly press TIME
FWD
and TIME
BACK
at same time and release to enter the Configuration Menu.
Step Press Button(s) Displayed (Factory Default) Press UP or DOWN to select: COMMENTS
1 MLTI STG HEAT PUMP
2 HEAT PUMP
3 ELEC HEAT FAN
4 1 to 40 for multi-stage
5 9 to 40
6 SET CYCL AUX
7 COOL FAN DELA OFF
8
9 HEAT FAN DELA OFF
10 PUMP
11 COMP OFF DELA
12
13
Firmly Press
SET TIME and
SET DAY (hold
for approx. 3 seconds)
TIME FWD
(Heat Pump ONLY)
TIME FWD
TIME FWD
TIME FWD
TIME FWD
(Heat Pump ONLY)
TIME FWD
TIME FWD
TIME FWD
TIME FWD
(Heat Pump ONLY)
TIME FWD
(Heat Pump ONLY)
TIME FWD
(Heat Pump ONLY)
TIME FWD
(Heat Pump ONLY)
(1)
(ON)
SET CYCL (05)
for MLTI_STG, (13) for
HEAT PUMP 1, (24)
for HEAT PUMP 2
SET CYCL (24)
for MLTI_STG, (13) for
HEAT PUMP 1, (24)
for HEAT PUMP 2
(08)
(00)
(01)
(00)
(ON)
(60)
(Balance point temperature)
bPT (35°F)
(Balance point)
bP (05)
2
OFF
9 to 40 for heat pump
1 to 40
0 to 127 seconds
1 to 30 seconds
0 to 127 seconds
OFF
(0) to (99)
5°F to 50°F
(01) to (09)
Selects type of system. Selecting HEAT PUMP makes additional items for heat pump systems available.
1. One compressor on Y1.
2. Two compressor on Y1, Y2. Fan cycles with call for heat if ON. Fan always
cycles with pump stages. Selects HEAT anticipation adjustment.
Selects COOL anticipation adjustment
Selects AUXILIARY stage anticipation adjustment. (Heat Pump ONLY
)
Selects time delay for COOL fan OFF
Selects time delay for fan ON. Applies only to compressor stages for heat pump or COOL.
Selects time delay for fan ON only when ELECT HEAT FAN (Step 3) is ON
Fossil Fuel Kit Alternative option. Turns compressor OFF if Auxiliary is ON for longer than one minute. (Heat Pump 1 & 2)
Available if Pump (Step 10) is OFF. Selects the delay between de-energizing fossil fuel stage and restarting Heat Pump stage.
Available if Pump (Step 10) is OFF and OUTDOOR Sensor ON. Selects outdoor balance point temperature for Heat Pump.
Available if Pump (Step 10) is OFF and OUTDOOR Sensor OFF. The higher the number the sooner the auxilary stage energizes. The lower the number the longer period of time before auxiliary is energized
14 (Programmable Blower
15
16
TIME FWD
(Heat Pump ONLY)
TIME FWD
TIME FWD
Balance Point) bbP
(OFF)
COMP LOCK
(OFF)
HEAT-OFF COOL-AUTO
or HEAT-EMER-OFF-
COOL-AUTO
(for heat pumps)
10 to 99%
ON
HEAT-OFF-COOL or
HEAT-EMER-OFF-
COOL (for heat pumps)
Available if configured for HEAT PUMP. Adjustable from 99-10. Lowers the Blower speed if the Heat Pump duty cycle is above the selected value in percentage.
Selects compressor short-cycle protection.*
Allows selection of HEAT and COOL or HEAT, COOL and AUTO with SYSTEM button. (EMER appears in sequence after HEAT if HEAT PUMP is selected).
See
Page
5
5
5
5
.
.
5
5
5
5 FAN DELA ON
5
.
5
7
7
7
.
7
7
7
7
Program RUN
Returns to Normal Operation.
* Note: COMP LOCK OFF permanently defeats compressor lockout. You must turn this selection ON if you do not have a system that already provides compressor short-c
cle protection. Please see “Lockout Bypass Option” to temporarily override compressor lockout.
6
Page 7
COMPRESSOR OFF DELAY
Installer table, step 11 is available if the fossil fuel kit alternative option (PUMP OFF) is selected.
This item allows a selection of 0 to 99 seconds, which is the time that the compres­sor will continue to run after the point that the auxiliary heat is energized. Running the compressor after the Auxiliary has started prevents cool air from creating drafts prior to the heat exchanger reaching normal tempera­tures. The factory default value of 60 seconds is typical for most systems. Consult with your equipment’s manufacturer before increasing this time.
BALANCE POINT TEMPERATURE
Installer table step 12, bPT, is available only if the fossil fuel kit option is selected and the outdoor temperature sensor is used (see the user menu in the owner manual).
This item allows a selection of 5 to 50° F, which is the outdoor temperature below which the thermostat will not energize heat pump compressor stages. It will use Auxiliary heat stages (only) until the outdoor temperature raises 3° above the selected temperature and then allow compressor stages to operate. The factory default value of 35° F is typical for most systems.
BALANCE POINT
Installer table step 13, bP, is available only if the fossil fuel kit option is selected and the outdoor temperature sensor is not used. The Balance Point influences when second stage comes on. The factory default creates approximately 1° F between stages. Increas­ing the setting decreases the separation between stages. Decreasing the value increases stage separation. This adjustment allows a small change in the operation of your heat pump system versus your auxiliary system relative to the thermostat adjustment.
Pump Stage
Fossil Auxiliary Stage
Higher number Lower number
Decreasing Indoor temperature
PROGRAMMABLE BLOWER BALANCE POINT
Installer table step 14, bbP, is available only when configured for Heat Pump systems, and wired as shown in Fig. 3.
If the system is running a high percentage of the time due to cold weather conditions, the output vent air temperature may be cooler than normal thus creating a drafty room condition. This feature will reduce the draft by lowering the blower speed with the DHM terminal. The lower speed will make the air temperature slightly warmer and more comfortable.
Example: If you want the blower to go to a lower speed when the system is running greater than 50% of the time,then reduce the Blower Balance Point to 50%.
To turn this feature OFF, press
to 99
then press once more to display OFF.
COMPRESSOR LOCKOUT.
(Installer table step 15). This thermostat is capable of helping to protect the system against premature compressor failure by “locking out” the compressor for at least five minutes after each cycle. When the thermo­stat is in compressor lockout, the word COOL will flash on the display. With heat pump systems, the word HEAT will flash if the lockout occurs during a heat cycle. During this period, the compressor will not be energized.
Stage separation 1˚F at setting 05
Lockout Bypass Option
FOR QUALIFIED SERVICE TECH­NICIANS’ USE ONL Y . HOMEOWNERS SHOULD NOT USE THIS FEATURE DUE TO POSSIBIL­ITY OF EQUIPMENT OR PROP­ERTY DAMAGE, OR PERSONAL INJURY .
COMPRESSOR SHORT TERM CYCLE PROTECTION
If this thermostat has been configured to provide short-cycle protection, during the 5-minute lockout period the thermostat will lock out the compressor to allow head pressure to stabilize. To override this feature for one cycle while testing
thermostat operation, press SET and SET
DAY
buttons at the same time.
TIME
If the system has short-cycle protection, this item should not need to be enabled. How­ever, if your system does not have short- cycle protection, turn COMP LOCK ON. This will protect the compressor from short­cycling and potential premature compressor failure.
Note that COMP LOCK OFF permanently disables compressor lockout. If you need to temporarily disable compressor lockout, please see Lockout Bypass Option.
DISABLING AUTOMATIC CHANGEOVER MODE.
(Installer table step 16). This thermostat, as configured at the factory, provides automatic changeover, which allows the thermostat to switch between heating and cooling to maintain temperature. In this configuration, when you press the SYSTEM button, the thermostat will go through HEAT-OFF­COOL-AUTO modes (HEAT-EMER-OFF­COOL-AUTO for heat pumps). Select HEAT(-EMER)-OFF-COOL to disable the automatic changeover feature.
(Continued)
HEATING COOLING
Anticipation Value Cycle Length Differential Temperature Cycle Length Differential Temperature
Shorter 0.4–0.6°F (0.2–0.3°C) N/A1–8 N/A Longer Shorter9–20 0.6–1.0°F (0.3–0.6°C) 0.6–1.0°F (0.3–0.6°C)
Hydronic Longer21–40 1.0–1.6°F (0.6–0.9°C) 1.0–1.6°F (0.6–0.9°C)
These numbers are approximate and represent operation with a typical system. Actual temperature differentials and run times may vary widely based on your building and equipment, as well as outdoor temperature conditions.
7
Page 8
SERVICE REMINDER
The Service Button Menu allows you to view or program as many as 4 reminders that indicate when service is required.
1. Humidifiers = A programmable run time in hours to indicate on the LCD when the humidifier will need to be serviced.
2. Air Filters = A programmable run time in hours to indicate on the LCD when the filter will need to be serviced or replaced.
3. UV Lights = A programmable run time in days to indicate on the LCD when the Ultra-Violet Bulb will need to be replaced.
4. Service Timer = A programmable run time in days to indicate on the LCD when to call your service contractor.
To enter the Service Button Menu when no service reminders are on the display, press and release the SERVICE button. Press TIME
setting an item to ON, you can then use or to select the time interval. Press
FWD
to step through the menu items. To turn a menu item OFF or ON when selected, press or . If you are
RUN
to exit the menu and return to
normal operation. When a service reminder appears on the display, press the SERVICE button to remove it and reset the timer to begin the count
down to the next service interval.
Service Button Menu
Step Press Button(s) Displayed Press or to select: COMMENTS (Factory Default)
1
2
3
4 SET FLTR TIME
5
6
7
8
SERVICE
TIME
(If PAD TIME is ON)
TIME
TIME
(If FLTR TIME is ON)
TIME
TIME
(If UV TIME is ON)
TIME
TIME
(If SERV TIME is ON)
PRGM
FWD
FWD
FWD
FWD
FWD
FWD
FWD
RUN
P AD TIME
(OFF) Hrs
or
REM PAD TIME
No. of Hrs
SET PAD TIME
(100) Hrs
FL TR TIME
(OFF) /Hrs
or
REM FLTR TIME
No. of Hrs
(200) Hrs UV TIME
(OFF) Days
or
REM UV TIME
No. of Days
SET UV TIME
(375) Days
SERV TIME (OFF) Days
or
REM SERV TIME
No. of Days
SET SERV TIME
(175) Days
(ON)
or
(OFF)
25 to 1975
(ON)
or
(OFF)
25 to 1975
(ON)
or
(OFF)
25 to 1975
(ON)
or
(OFF)
25 to 1975
Set Humidifier Maintenance Reminder.
Selects time intervals in increments of 25 hours. The RUN time accumulates when the HM terminal is energized.
Set Air Filter Maintenance Reminder.
Selects time intervals in increments of 25 hours. The RUN time accumulates when the fan is operating.
Selects UV Light Maintenance Reminder.
Selects time intervals in increments of 25 days. The RUN time is the calendar time from when it is entered or reset.
Selects Routine Maintenance Service Call Reminder.
Selects time intervals in increments of 25 days. The RUN time is the calendar time from when it is entered or reset.
Returns to Normal Operation.
8
Page 9
CHECK THERMOSTAT OPERA TION
FAN OPERATION
If your system does not have a G terminal Connection, skip to HEAT/HUMIDITY section below.
1. Turn power on to the system.
2. Press PROGRAM
3. Press The fan should begin to operate.
4. Press displayed. The fan should stop operating, unless a call for heat or cool is active.
FAN
FAN
RUN
.
until FAN ON is displayed.
until FAN AUTO is
HEAT/HUMIDITY
1. Press the shown at the top of the display.
SYSTEM
button until HEAT is
2.Press the HUMIDITY % button, then the temperature to the maximum humidity setpoint and hold for 5 seconds until ON is displayed.
3.Press the PROGRAM
RUN
.
4.Press the HOLD button.
5.Press the temperature to raise the temperature setting 4°F above room temperature. The 1st stage
(LED Green) and then 2nd stage (LED Yellow) will be energized,
and also the HM terminal should energize for humidification. The lowercase letter h will appear to the
6.Press the HUMIDITY % button and
7. Press the PROGRAM
HEAT PUMP EMERGENCY HEAT MODE
1.Press the
2.Press the temperature
3. LED indicatior will glow red indicat-
4. Lower the termperature a few degrees
NOTE: If the red LED flashes and check system appears this signals that there is a malfunction in the Heating/ Cooling system not the thermostat. For suggestions contact your Heating/
Cooling manufacturer.
right of HOLD, indicating that the thermostat is calling for Humidification. If configured for Heat Pump 1, 2, or 3 the third stage of HEAT will be indi- cated by a Flashing Yellow light.
set your desired humidifier set point in % RH with the and .
RUN
to
accept the change.
SYSTEM
button to select the
EMER mode.
to
raise the setpoint temperature 2°F above the room temperature to call for heat.
ing the thermostat is calling for heat.
below room temperature and the red LED and the heat should turn off.
COOL/DEHUMIDIFY
1.Press the
SYSTEM
button until COOL is
shown at the top of the display.
2.Press the HUMIDITY % button, then
the temperature to the minimum humidity setpoint and hold for 5 seconds until ON displayed.
3. Press the PROGRAM
RUN
button.
4. Press the HOLD button.
5. Press the temperature to lower
the temperature setting 1°F below room temperature and the 1
st
stage of the COOLING system should begin to operate and the LED indicator will glow green for first stage. The lowercase letter d will appear to the right of HOLD, indicat­ing that the thermostat is calling for Dehumidification.
6.Press the temperature to lower
your setpoint 4°F below room temperature, the DHM terminal will energize causing the FAN to go to high speed.
7.Press the HUMIDITY % button and
set your desired dehumidification setpoint in % RH using the and
.
8.Press PROGRAM
RUN
to accept
the change.
TROUBLESHOOTING
RESET BUTTON
If the thermostat does not respond when keys are pressed, or the thermostat is not operating properly, you may use the reset button located on the back of the thermostat body (see fig. 2). Thermostat programming and configuration will not be affected by pressing the reset button. However, the clock will need to be reset.
RESETTING THERMOST A T CONFIGURATION AND PROGRAMMING
The thermostat can be reset back to default programs and configuration. Removing power from the thermostat will not reset it, because the default settings are maintained in permanent memory. Before resetting the thermostat, you may want to make note of the previously selected configuration and programming. You must reconfigure and
reprogram the thermostat after resetting it using this method.
TROUBLESHOOTING Symptom Possible Cause Corrective Action
Thermostat Does Not Follow Program 1. AM or PM set incorrectly in program. Check current clock and program settings including
2. AM or PM set incorrectly on clock. AM or PM designations for each time period. If a
3. Voltage spike or static discharge. voltage spike or a static discharge occurs use
Blank Display and/or Keypad Not Responding 1. Voltage spike or static discharge. Replace batteries and check heat/cool system
2. Battery change required. for proper operation. If a voltage spike occurs
To reset the thermostat, press and release
RUN
PROGRAM TIME
time. This will reset the thermostat to factory default programs and configuration. The display will momentarily go blank, then all segments on the display will momentarily be shown. The thermostat will then go into the HOLD mode and will maintain factory preset temperatures.
the reset operation listed above.
use the Reset Operation listed above.
BACK
, then press the
and buttons at the same
FAN
,
9
Page 10
TROUBLESHOOTING Symptom Possible Cause Corrective Action
No Heat/No Cool/No Fan 1. Blown fuse or tripped circuit breaker. Replace fuse or reset breaker. (Common Problems) 2. Furnace power switch to OFF. Turn switch to ON.
3. Furnace blower compartment door or Replace door panel in proper position to engage panel loose or not properly installed. safety interlock or door switch.
No Heat 1. Pilot light not lit. Re-light pilot.
2. System button not pressed to display Heat. Set SYSTEM button until HEAT is displayed and
raise temperature above room temperature.
3. Loose connection to thermostat or system. Verify thermostat and system wires are securely
attached.
4. Furnace Lock-Out Condition. Heat may also Many furnaces have safety devices that shut be intermittent. down when a lock-out condition occurs. If the
heat works intermittently contact the furnace manufacturer or local service person for assistance.
5. Heating system requires service or Diagonistic: Set SYSTEM button until HEAT is
displayed and raise setpoint above room temperature. Within a few seconds the thermostat should make a soft click sound. This sound usually indicates the thermostat is operating properly. If the thermostat does not click, try the reset operation listed on the previous page. If the thermostat does not click after being reset contact your heating and cooling service person or place of purchase for replacement. If the thermostat clicks, contact the furnace manufacturer or a service person to verify the heating is operation correctly.
No Cool 1. System button not pressed to display Cool. Set SYSTEM button until COOL is displayed and
raise temperature below room temperature.
2. Loose connection to thermostat or system. Verify thermostat and system wires are securely
attached.
3. Cooling system requires service or Same procedure as diagnostic for No Heat thermostat requires replacement. condition except press the SYSTEM button until
COOL is displayed and lower the setpoint below room temperature. There may be up to a five minute delay before the thermostat clicks in Cooling.
Heat, Cool or Fan Runs Constantly. 1. Possible short in wiring. Check each wire connection to verify they are not
2. Possible short in thermostat. shorted or touching together. No bare wire should
3. Possible short in Heat/Cool/Fan system. out from under terminal screws. Try resetting the
4. Fan button pressed to display FAN ON. thermostat as described on the previous page. If
the condition persists the manufacturer of your system or service person can instruct you on how to test the Heat/Cool system for correct operation. If the system operates correctly, replace the thermostat.
Furnace Cycles Too Fast or Too Slow 1.The location of the thermostat and/or the size Digital thermostats normally provide precise (narrow or wide temperature swing) of the Heating System equipment may be temperature control and may cycle faster than
influencing the cycle rate. some older mechanical models. A faster cycle
rate means the unit turns on on off more frequently but runs for a shorter time so there is no increase in energy use. If you would like to increase the cycle time, refer to page 6 under Installer Table for settings. If an acceptable cycle rate is not acheived by the adjustment in the Installer Table then you may want to contact a local heating and air conditioning service person for further suggestions.
Cooling Cycles Too Fast or Too Slow 1. The location of the thermostat and/or the size The cycle rate for cooling is fixed and can not be (narrow or wide temperature swing) of the Cooling System can influence the adjusted. Contact a local service person for
rate. suggestions.
10
Page 11
TROUBLESHOOTING Symptom Possible Cause Corrective Action
Thermostat Setting and Thermostat 1. Thermostat thermometer setting requires The thermometer can be adjusted +/- 5 degrees. Thermometer Disagree adjustment. See Temperature Display Adjustment in the
Operating Manual under Configuration.
Thermostat Display Shows CHCK PAD, 1. Thermostat service indicators. These indicators can be reset or modified in the CHNG FLTR, CALL SERV UV, CALL SERV service button menu (see pg. 8).
FAQs
Why does the system run with the setpoint and room temperature the same?
Why is the temperature change display so slow?
How do I temporarily Override the program and Hold Til Timing?
Aux. = Auxiliary Heat or the second stage of heat in the Heat mode. This is energized
In cooling, as the room temperature falls you will eventually reach the setpoint temperature. The system will continue to run until it reaches the low side of the temperature setting. As an example: If set to 78 degrees with the room temperature falling the thermostat will continue to call for cool as the temperature decreases in the following manner. 78.9, 78.8, 78.7, 78.6, 78.5, 78.4, 78.3, 78.2, at approximately 78.2 the thermostat will quit calling for cool. This is why it is not unusual for the room temperature and set temperature to read the same but the system continues to run. The amount of time it takes for the system to shut off is dependent on system sizing, thermostat location, etc. Note: The thermostat display only displays whole numbers. Internally the thermostat calculates decimals.
In heating as the room temperature increases the system will continue to run until the thermostat reaches the high side of the temperature setpoint.
Digitals are engineered to a specific response rate. Compared to a thermometer it will seem slow. When left to acclimate and control temperature it will provide precise temperature control on a properly sized system.
Any time your program is running and you would like to override it for a specific amount of time, press display will indicate HOLD, and the number of hours remaining in the hold period will be indicated with the word HRS. To adjust the length of time for the override, press TIME FWD or TIME BACK. The time you select will become the new number of hours for the Hold Til timing. Once your time is selected, let the thermostat rever t back to normal operation on its own to accept the change.
or until the temperature you want is displayed. The
What is the thermostat Click Test?
Many furnaces have safety devices that shut the system down when a lock-out condition occurs in the furnace. If the thermostat is turned off or the call for heat is cancelled (by lowering and then raising the set temperature) the furnace may start operating again. A diagnostic to see if the thermostat is operating when the room temperature is below the thermostat setting (in heat) is to lower the setting below the room temp. Within about 3 seconds the thermostat should make a soft click sound. This sound is the thermostat turning off the call for heat and usually indicates the thermostat is operating properly. If the thermostat does not click you would be suspicious of the thermostat and try resetting it by following its reset operation. If the thermostat does not click after being reset contact your heating and cooling service person or place of purchase for a replacement. If the thermostat clicks and the heat works intermittently contact the furnace manufacturer or local service person. They will want to observe the condition when it is not working.
You can raise and lower the temperature a few degrees above and below the room temperature and each time expect to hear the thermostat click on and off within a few seconds. If it clicks, it is operating properly.
11
Page 12
The Emerson logo is a trademark and a service mark of Emerson Electric Co.
Loading...