Installation Instructions
YRH2330X Series – |
for vented installations only |
IMPORTANT: Read and save these instructions
IMPORTANT
Installer: Leave Installation Instructions with the owner.
Owner: Keep Installation Instructions for future reference.
Save Installation Instructions for local electrical inspector’s use.
30" (76.2 cm) Custom Series Range Hood
www.whirlpool.com |
628011A/9763396 |
Before you start...
Your safety and the safety of others are very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety messages.
This is the safety alert symbol.
This symbol alerts you to potential hazards that can kill
or hurt you and others.
All safety messages will follow the safety alert symbol and either the word “DANGER” or “WARNING”. These words mean:
DANGER
You can be killed or seriously injured if you don’t immediately follow instructions.
WARNING
You can be killed or seriously injured if you don’t follow instructions.
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what can happen if the instructions are not followed.
Important: Observe all governing codes and ordinances.
Proper installation is your |
Check the location where the |
responsibility. Make sure you have |
range hood will be installed. The |
everything necessary for correct |
location should be away from |
installation. It is the responsibility of |
strong draft areas, such as windows, |
the installer to comply with the |
doors, and strong heating vents. |
clearances specified. |
|
WARNING — To reduce the risk of fire or electrical shock, do not use this fan with any solid-state speed control device.
WARNING — TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer. Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device such as a tag to the service panel
CAUTION: For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.
WARNING — TO REDUCE THE RISK OF A RANGE TOP GREASE FIRE:
Never leave surface units unattended at high settings. Boilovers cause smoking and greasy spillovers that may ignite. Heat oils slowly on low or medium settings.
Always turn hood ON when cooking at high heat or when
cooking flaming foods.
Clean ventilating fans frequently. Grease should not be allowed to accumulate on fan or filter.
Use proper pan size. Always use cookware appropriate for the size of the surface element.
WARNING — TO REDUCE THE RISK OF INJURY TO PERSONS IN THE EVENT OF A RANGE TOP GREASE FIRE, OBSERVE THE FOLLOWING:
SMOTHER FLAMES with a closefitting lid, cookie sheet, or metal tray, then turn off the burner. BE CAREFUL TO PREVENT BURNS. If the flames do not go out immediately, EVACUATE AND CALL THE FIRE DEPARTMENT.
NEVER PICK UP A FLAMING PAN — You may be burned.
DO NOT USE WATER, including wet dishcloths or towels — a violent steam explosion will result. Use an extinguisher ONLY if:
You know you have a Class ABC extinguisher, and you already know how to operate it.
The fire is small and contained in the area where it is started.
The fire department is being called.
You can fight the fire with your back to an exit.
Tools and materials needed for installation:
• compass or 7" |
• 1-1/4" |
(17.8 cm) |
( 3 .0 cm) |
circle template |
drill bit |
• pliers |
• pencil |
• level |
• ruler |
• Phillips |
• caulking gun |
screwdriver |
• saber saw |
• metal snips |
• keyhole saw |
• drill |
• duct tape |
Electrical requirements
Important: Observe all governing codes and ordinances.
It is the customer’s responsibility:
To contact a qualified electrical installer.
To assure that the electrical installation is adequate and in conformance with National Electrical Code, ANSI/NFPA 70 — latest edition* or Canadian Electrical Code, C22.1 and C22.2 No. 113-M1984 (or latest edition),** and all local codes and ordinances.
If codes permit and a separate ground wire is used, it is recommended that a qualified electrician determine that the ground path is adequate.
Do not ground to a gas pipe.
Check with a qualified electrician if you are not sure range hood is properly grounded.
Do not have a fuse in the neutral or ground circuit.
Copies of standards listed may be obtained from:
*National Fire Protection Association One Batterymarch Park
Quincy, Massachusetts 02269
**CSA International
8501 East Pleasant Valley Road Cleveland, Ohio 44131-5575
Page 2
Product
29-7/8" (75.9 cm)
dimensions
10" (25.4 cm)
5" (12.7 cm)
knockout for rectangular roof vent
2" (5.1 cm)
17-1/2"
(44.5 cm)
3/4"
(19.1. mm)
7-1/2"
(19.1 cm)
12" (30.5 cm)
1-1/2"
3-1/4" (3.8 cm)
(8.3 cm)
3/8"
(9.5 mm) 6"
(15.2 cm)
3-1/4" (8.3 cm)
rear of hood
knockout for rectangular back vent
wiring knockouts
YRH2330X series vent hoods can be used for vented installations only.
A.A 115-volt, 60-Hz, AC-only, fused electrical supply is required. The total ampere load used, including the range hood, must not exceed 90% of the rated capacity of the circuit. The ampere rating of the range hood is located on the model/serial number rating plate located on the side cover of the blower motor housing.
B.The range hood must be connected with copper wire only.
C.The range hood should be connected directly to the fused disconnect (or circuit breaker) box through flexible armored or nonmetallic sheathed copper cable. A U.L./CSA-listed strain relief must be provided at each end of the power supply cable. Wire sizes (COPPER WIRE ONLY) and connections must conform with the rating of the appliance as specified on the model/serial rating plate.
Wire sizes must conform to the requirements of the National Electrical Code ANSI/NFPA
70 — latest edition* or Canadian Electrical Code, C22.1 and C22.2 No. 113-M1984 (or latest edition),** and all local codes and ordinances.
WARNING — TO REDUCE THE |
safety standards such as those |
|
RISK OF FIRE, ELECTRIC SHOCK, |
published by the National Fire |
|
OR INJURY TO PERSONS, |
Protection Association |
|
OBSERVE THE FOLLOWING: |
(NFPA),and the American |
|
Installation work and electrical |
Society of Heating Refrigeration |
|
and Air Conditioning Engineers |
||
wiring must be done by qualified |
||
(ASHRAE), and the local code |
||
person(s) in accordance with all |
||
authorities. |
||
applicable Codes and |
||
When cutting or drilling into wall |
||
Standards, including fire related |
||
construction. Sufficient air is |
or ceiling, do not damage |
|
needed for proper combustion |
electrical wiring and other |
|
and exhausting of gases through |
hidden utilities. |
|
the flue (chimney) of fuel |
Ducted fans must always be |
|
burning equipment to prevent |
||
vented to the outdoors. |
||
back drafting. Follow the |
||
|
||
heating equipment |
WARNING — To reduce the risk |
|
manufacturer’s guideline and |
of fire, use only metal ductwork. |
|
|
|
Page 3
Venting requirements
Venting system must terminate to the outside.
Do not terminate the vent in an attic or other enclosed space.
Do not use four-inch laundry-type wall caps.
Do not use plastic vent.
Vent system needed for installation is not included. Backdraft damper supplied with product must be used. If roof or wall cap has a damper, do not use damper supplied with hood. Use metal vent only. Rigid metal vent is recommended.
Determine which outside venting method you need to use.
The length of the vent and number of elbows should be kept to a minimum to provide efficient performance. The size of the vent should be uniform. Do Not install two elbows together. Use duct tape to seal all joints in the vent system. Vent can terminate either through the roof or wall. Use caulking to seal exterior wall or roof opening around exhaust hood. For the most efficient and quiet operation, it is recommended that the range hood be vented vertically through the roof using 7" (17.8 cm) round vent.
Figures 1-4 show common venting methods and what types of materials are needed.
Vertical roof venting
roof cap
7" (17.8 cm) |
round |
through roof |
damper located |
as far from hood |
as possible |
66" |
(167.6 cm) |
Figure 1
3-1/4" x 10"
(8.3 x 25.4 cm) to 7" (17.8 cm) fitting required for some models
roof cap
3-1/4" x 10" |
(8.3 x 25.4 cm) |
through the roof |
66" |
(167.6 cm) |
Figure 2
3-1/4" x 10"
(8.3 x 25.4 cm) damper
Horizontal wall venting
3-1/4" x 10" |
(8.3 x 25.4 cm) |
through the wall |
wall cap |
66" |
(167.6 cm) |
Figure 3 |
roof cap
7" (17.8 cm) min.
diameter round wall cap vent
elbows
3-1/4" x 10"
(8.3 x 25.4 cm) to round vent transition
Figure 4
Recommended vent length
Use 3-1/4" x 10" (8.3 x 25.4 cm) or 7" (17.8 cm) vent with a maximum length of 26 feet (7.9 m) for vent system. For best performance, use no more than three 90° elbows. To calculate the length of system you need, add the equivalent feet for each vent piece used in the system. See the following examples.
3-1/4" x 10" (8.3 x 25.4 cm) vent system
3-1/4" x 10" |
|
|
|
|
|
||||||||
(8.3 x 25.4 cm) |
|
|
wall cap |
||||||||||
elbow |
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
6 ft. (1.8 m) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
||||
|
|
2 |
ft. (0.6 m) |
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Maximum length |
= 26 ft. (7.9 m) |
|||
1 - 90° elbow |
= |
5 |
ft. (1.5 m) |
|
8 ft. (2.4 m) straight = |
8 |
ft. (2.4 m) |
||
1 - wall cap |
= |
0 |
ft. (0 m) |
|
Length of 3-1/4" x |
|
|
|
|
|
|
|
|
|
10" (8.3 x 25.4 cm) |
|
|
|
|
system |
= 13 ft. (4 m) |
Recommended standard fittings
3-1/4" x 10"
(8.3 x 25.4 cm) 90° elbow = 5 ft. (1.5 m)
3-1/4" x 10"
(8.3 x 25.4 cm) flat elbow = 12 ft. (3.7 m)
3-1/4" x 10"
(8.3 x 25.4 cm)
wall cap = 0 ft. (0 m)
Page 4
7" (17.8 cm) vent system |
Now start... |
||||||||||||||||||||||
90° elbow |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
6 ft. (1.8 m) |
|
|
|
|
|
With range hood in kitchen. |
|||||||||||
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Slide cardboard or hardboard |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
under range before moving range |
|
|
|
|
|
|
|
|
2 ft. (0.6 m) |
|
|
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
wall cap |
across floor to prevent damaging |
|||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
floor covering. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Cover countertop, cooktop or set- |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
in range with a thick, protective |
|
3-1/4" x 10" |
|
|
|
|
|
|
|
|
|
|
|
|
covering to prevent damaging |
||||||||||
(8.3 x 25.4 cm) to |
|
|
|
|
|
|
|
|
|
|
|
|
countertop. |
|
|||||||||
7" (17.8 cm) transition |
|
|
|
|
|
|
|
|
|
|
|
||||||||||||
Maximum length |
= 26 ft. (7.9 m) |
1.Disconnect and move |
|||||||||||||||||||||
1 - transition |
|
|
|
= 4.5 ft. (1.4 m) |
freestanding range from cabinet |
||||||||||||||||||
2 - 90° elbows |
|
|
|
= 10 ft. (3.0 m) |
|||||||||||||||||||
|
|
|
opening to provide easier access |
||||||||||||||||||||
1 - wall cap |
|
|
|
= |
0 |
|
ft. (0 m) |
||||||||||||||||
|
|
|
|
to upper cabinet and rear wall. Put |
|||||||||||||||||||
8 ft. (2.4 m) straight = |
8 |
|
ft. (2.4 m) |
||||||||||||||||||||
|
a thick, protective covering over |
||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Length of 7" |
|
|
|
|
|
|
|
|
|
|
|
|
cooktop, set-in range or |
||||||||||
(17.8 cm) system |
= 22.5 ft. (6.9 m) |
countertop to protect from |
|||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
damage or dirt. |
|
Recommended standard |
2.Determine which venting |
||||||||||||||||||||||
fittings |
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
method (roof or wall venting) you |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
3-1/4" x 10" |
|
|
|
|
need to use. |
|
|||||||
|
|
|
|
|
|
|
|
|
|
(8.3 x 25.4 cm) to |
|
|
|||||||||||
|
|
|
|
|
|
|
|
|
|
7" (17.8 |
cm) = |
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
4.5 ft. (1.4 m) |
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
3-1/4" x 10" |
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
(8.3 x 25.4 cm) to |
|
|
|||||||||||
|
|
|
|
|
|
|
|
|
|
7" (17.8 cm) 90° elbow = |
|
|
|||||||||||
|
|
|
|
|
|
|
|
|
|
5 ft. (1.5 m) |
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
90° elbow = |
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
5 ft. (1.5 m) |
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
rectangular |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
vent |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
knockouts |
|
|
|
|
|
|
|
|
|
|
45° elbow = |
|
|
|
|
wiring |
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||
|
|
|
|
|
|
|
|
|
|
2.5 ft. (0.8 m) |
|
|
|
|
knockouts |
|
3.Remove knockout from the wiring opening (top or rear) to be
7" wall cap = 0 ft. (0 m) used.
For rectangular venting, remove only the 3-1/4" x 10" (8.3 x 25.4 cm) rectangular opening knockout for the venting method (roof or wall) you have selected.
terminal box cover
4.Remove terminal box cover from range hood.
WARNING
Excessive Weight Hazard
Use two or more people to move and install range hood.
Failure to do so can result in back or other injury.
keyhole slot
front
of hood
5.Lift the range hood into final position and center. Mark on the underside of cabinet the location of the four keyhole mounting slots. Set range hood aside on a protected surface.
centerline centerline
6. Determine and clearly mark a vertical centerline on the wall and cabinet in the area the vent opening will be made.
Page 5
7-1/2"
(19.1 cm) 2" (5.1 cm) from wall
(not cabinet frame)
centerline
7.
To wire through top, mark a line 7-1/2" (19.1 cm) from the right of the centerline on the underside of the cabinet. Mark the point on this line that is 2" (5.1 cm) from back wall. Drill a 1-1/4" (3.0 cm) diameter hole through the cabinet at this point.
3/4" (19.1 mm)
65-1/4" |
7-1/2" |
|
(19.1 cm) |
||
(165.7 cm) |
||
to floor |
|
centerline
To wire through rear, mark a line 7-1/2" (19.1 cm) from the right of the centerline on the wall. Mark the point on this line that is 65-1/4" (165.7 cm) from the floor [or 3/4" (19.1 mm) from underside of cabinet]. Drill a 1-1/4" (3.0 cm) diameter hole through wall at this point.
cabinet cutouts
*1-1/2"
(3.8 cm)
*5-1/2"
(14 cm)
5-1/4"
(13.3 cm)
*from wall, not cabinet frame
8.
To make a 4" x 10-1/2" (10.2 x 26.7 cm) rectangle on the underside of cabinet top and bottom:
a.Mark lines 1-1/2" (3.8 cm) and 5-1/2" (14 cm) from the back wall on the centerline of the underside of cabinet.
b.Mark lines 5-1/4" (13.3 cm) to the right and left of the centerline on the underside of cabinet.
c.Use saber and keyhole saws to cut a rectangular opening for vent.
d.Repeat steps a-c for the underside of the top of the cabinet.
If venting through the wall with 3-1/4" x 10" (8.3 x 25.4 cm) rectangular vent —
To make a 4" x 10-1/2" (10.2 x 26.7 cm) rectangle in the wall:
a.Measure 1/8" (3.2 mm) and 3-5/8" (9.2 cm) down from underside of cabinet and mark on the centerline on the back wall.
b.Mark lines 5-1/4" (13.3 cm) to the right and left of the centerline on the underside of cabinet.
c.Use saber and keyhole saws to cut a rectangular opening for vent.
To transition from a 3-1/4" x 10" (8.3 x 25.4 cm) rectangular vent to a 7" (17.8 cm) round vent and vent through the roof —
Start by making a 4" x 10-1/2" (10.2 x 26.7 cm) rectangle on the
*1-1/2"
(3.8 cm)
*5-1/2" (14 cm) 5-1/4" (13.3 cm)
*from wall, not cabinet frame
underside of cabinet bottom:
a.Mark lines 1-1/2" (3.8 cm) and 5-1/2" (13.3 cm) from the back wall on the centerline of the underside of cabinet.
b.Mark lines 5-1/4" (13.3 cm) to the right and left of the centerline on the underside of cabinet.
c.Use saber and keyhole saws to cut a rectangular opening for vent.
7-5/8"
7-1/8" (19.4 cm)
(18.1 cm)
R
*5" (12.7 cm) |
*1-1/2" |
|
(3.8 cm) |
||
*5-1/2" (14 cm) |
||
|
cabinet
cutouts * from wall, not cabinet frame
Now make a 7-1/8" x 7-5/8" (18.1 x 19.4 cm) slot on the underside of the cabinet tops.
d.Mark lines 5" (12.7 cm) and 5-1/2" (14 cm) from the back wall on the centerline on the underside of the top of cabinet.
e.Draw two 7-1/8" (18.1 cm) circles using the marks made in step d as center points.
f.Use saber and keyhole saws to cut a slotted (oval) opening to make installing 7" (17.8 cm) round vent easier.
Page 6