
INSTALLER: LEAVE THESE INSTRUCTIONS WITH THE HOMEOWNER.
HOMEOWNER: RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.
Wiring Diagrams are included in this package.
1 INSTALLATION
INSTRUCTIONS
FOR 24” GAS BUILT-IN WALL OVEN (Short Model1
Before you begin, read the following instructions completely and carefully. If followed, they
will simplify the installation job.
IMPORTANT: OBSERVE ALL GOVERNING
CODES AND ORDINANCES.
Input ratings shown on the rating plate [serial taglare for elevatrons
up to 2,OflCl feet. For elevatrons above 2,000 feet. ratings should be
reduced at a rate of 4% for each 1,000 feet above sea level.
INSTALLATION REQUIREMENTS
This lnstallatlon must conform with the American Natlonal Standard, Natlonal Fuel Gas Code ANSI 2223.1-l 980’ and local codes
and ordinances.
MOBILE HOME INSTALLATION REDUIREMENTS ARE
LISTED ON PAGE 4.
PROPER GAS SUPPLY
Thus unit IS manufactured for use with NATURAL GAS. It
can be converted for use on LP GAS. The rating plate located under the marn top has the information on the type
of gas this unit can be used with. When in doubt check
with your local gas supplier.
Provide a gas supply line to the unit location. We suggest
using a 74” rigid pipe, as smaller size pipe on long runs may
result In the gas supply not being sufficient. Pipe lolnt
compounds resistant to the action of LP gas must be
used.
The supply line should be equipped with a shutoff valve.
This valve should always be located
the range and should be in a locatron that allows ease of
opening and closing. Do not block access to the shutoff
valve.
If local codes permit, It is recommended that flexible
metal tubing design-certified by the American Gas Association, be used for connecting the appliance to the gas
supply line. (The gas valve connection will accept a 3%”
male pipe thread.1
If rigid pipe is used as a gas supply line, a combination of
pipe fittings must be used to obtain an In-line connection
to the unit.
6
The gas pressure regulator on this model is convertible
and must be used. This regulator can be used on either
NATURAL or LP gases. The pressure regulator has fixed
outlet pressure at NATURAL and LP settings and these
cannot be changed. The fixed outlet pressure on NATURAL gas setting is 4 Inches W.C. On the LP gas setting
the outlet pressure
IS
10 inches W.C.
in
the same room as
* Copies of the standard listed above may be obtalned from:
AMERICAN GAS ASSOCIATION
151 5 Wilson Boulevard
Arlington, Vlrgrnia 22209
1

INLET PRESSURE
The Inlet pressure to the regulator should be as follows
for both operation and checking regulator setting:
NATURAL GAS:
Minimum pressure
Maximum pressure
LP GAS:
MInImum pressure
Maximum pressure
LINE PRESSURE TESTING
a. Testing ABOVE
3/4
Pound Per Square Inch
(Gauge1
The appliance and its indlvldual shutoff valve must be
dlsconnected from the gas supply piping system durIng any pressure testing of that system at test pressures In excess of % psig.
b. Testing AT
l/2
Pound Per Square Inch (Gauge)
OR LOWER
The appliance must be Isolated from the gas supply
plplng system by closing its indlvldual manual shutoff
valve during pressure testing of the gas supply piping
system at test pressure equal to or less than l/z pslg.
5 inches W.C.
14 Inches W.C.
11 Inches WC.
14 Inches W.C.
ELECTRICAL REQUIREMENTS
A 1 15 Volt, 60 Hz. AC only, 15 Ampere fused electrical supply is required [time delay fuse or circuit breaker is recommended]. It is recommended that a separate circuit serving
only this appliance be provided. DO NOT use an extension
cord.
RECOMMENDED GROUNDING
METHOD
Electrical ground is required on this appliance.
DO NOT, UNDER ANY CIRCUMSTANCES, CUT OR
REMOVE THE POWER SUPPLY CORD GROUND
PRONG.
For your personal safety, this appliance must be grounded.
This appliance
a 3-prong grounding plug. To minimize possible shock hazard,
the cord must be plugged into a mating 3prong grounding
type wall receptacle, grounded In accordance with the Natlonal ElectrIcal Code, ANSI/NFPA NO. 70-1961 l * and
local codes and ordinances. If a mating receptacle is not
available, it
the customer to have a properly grounded 3-prong wall receptacle installed by a quaIlfled electrician. See Figure I.
IS
equipped with a power supply cord having
IS
the personal responsiblllty and obllgatlon of
To convert from NATURAL to LP gas.
a. Change pressure regulator setting from NATURAL
to LP [See To Convert Pressure Regulator.)
b. Screw the burner orlflces hoods down tight against
the orifice pins. DO NOT OVER TORQUE.
c. Remove the oven control knob and the porcelain panel
and turn the select-a-gas screw to the LP posItIon.
This screw Is locatedon theovencontrolfthermostatl.
The mid posItIon turns the oven pilot off.
d. Adjust the burner air shutter to the widest opening
that
will
burner
To convert the pressure regulator. Note: The type of gas
for which the regulator IS set
plug on the top of the regulator (either NAT or LPI.
To change the regulator setting:
Remove the aluminum hex nut [plug] with a wrench or
coin. Turn the hex nut or plug over and screw It back Into
the regulator. Caution: Do not over tighten.
If the unit IS to be used on a NATURAL gas, NAT should
be vlslble on the regulator plug. If the unit is to be used
on LP gas, LP should be visible on the regulator plug.
not cause the flame to lift or blow off of the
IS
stamped on the aluminum
3-PRONG
GROUNDING TYPE
‘WALL RECEPTACLE
3-PRONG
GROUNDING
PLUG
POWER SU
CORD
FIGURE 1
* * Copies of the standard listed above may be obtained from:
NATIONAL FIRE PROTECTION ASSOCIATION
470 Atlantic Avenue
Boston Massachusetts 02210
OBSERVE ALL GOVERNING CODES
AND ORDINANCES
2