VENTED KITCHEN RANGE HOOD
FOR 120 V. OPERATION
READ AND SAVE THESE INSTRUCTIONS
Before you begin,
completely and carefully. If followed, they will simplify
the installation job.
IMPORTANT: OBSERVE ALL GOVERNING CODES
SAVE THESE INSTRUCTIONS FOR THE LOCAL
ELECTRICAL INSPECTOR’S USE
This unit can be vented vertically through upper cabinets or
horrzontally through an outside wall A typrcal vertical rnstallatron IS
shown In Figure 1. A typical honzontal installation IS shown In Figure
2. For proper ventilation when used wrth an Indoor electric grill, see
page 4for guldelines for proper duct sizing.
installation of restrictive roof jacks can reduce air moving capacity
and provide inadequate ventilation for an indoor electric grill.
read the following instructions
AND ORDINANCES
Improper duct sizing or
KITCHEN
RANGE HOOD
MODEL
RH8300XLS
SERIES
MOTOR LIGHTS
FILTER
For most efficient smoke removal, the top of the hood should be
approximately 66 inches (167.6 cm) from the floor.
TOOLS AND MATERIALS REQUIRED
l
Drill, electnc or ratchet drive, with l-‘/d” wood bit (to
dnll an access hole in the cabinet or kitchen wall for the
electric power line.)
l
One common head screwdrrver (to secure hood
mounting screws to the cabinet and hood sheet metal
parts).
l
Plrers (for openrng knockouts).
l
Pencil,
l
Saber saw or keyhole saw for cutting the wall or cabinet
openings.
l
Caulking, metal snips, duct tape, ducts (with elbow and
transition, if necessary) and wall cap or roof cap, as
req u rred
ruler and level for marking cabinet locations.
1626-l 26 830869
Page 1
3-l 7-82
1. Make atemplateortransfer measurements shown in Fig. 3
to cabinets or wall.
2. Cut holes to accomodate ventilating duct allowing W’ (.6
cm) clearance on all four sides for back vent. Allow %” (1.9
cm) clearance toward front for vertical vent. Allow W’ (.6 cm)
on other three sides for top vent.
3. Cut appropriate hole for electrical wiring.
4. Run wire through wall or cabinets according to National
Electrical Code and Applicable local codes. (DO NOT turn
power on until installation is complete.)
5. Remove blower housing and filters for easier installation
See exhaust unit assembly illustration on back page.
6. Remove screw holding junction box cover.
7. Remove proper electrical knockout. See Figure 3.
8. Remove proper venting knockout. See Figure 3. NOTE: If
horizontal discharge is selected an additional knockout in
the blower cradle must be removed.
9. Attach the damper as shown in Figure 5 for vertical
discharge or Fig. 6 for horizontal discharge.
10. Lift the hood into position. Mark location of four mounting
holes.
11. Remove hood and start all four screws in center of
narrow neck of keyhole slot marked on cabinet bottom.
12. Lift the hood into position simultaneously feeding the
electrical wire through the knockout. Follow applicable local
codes and/or latest National Electrical Code for electrical
conector to be used at field wiring entrance.
13. Tighten screws to secure hood. Be sure screw head is in
narrow neck of keyhole slot.
14. Install proper duct work. See page 4
15. Complete electrical wiring in junction box according to
the National Electrical Code and applicable Local Codes
NOTE: This unit must be permanently grounded in
accordance with the National Electrical Code and applicable
L,ocal codes.
16. Replace junction box cover.
17. Replace blower. Note different blower positions in
Figure 5 for vertical venting and Figure 6 for horizontal
venting. See Page 3 for correct blower installation.
18. Replace blower cover, light frame assembly and filters.
-.
66”
66”
TRAIN CAP
I
3: x IO” RECTANGULAR
IF RAIN CAP HAS
A CAMPER, REMOVE
DAMPER BLADE
VERTICAL VENTING
IF RAIN CAP riAS
A DAMPER. REMOVE
DAMPER BLAOE
FROM HOOD.
I
NOTE: It has been found that a large part of the energy loss
of the average home is due to outside air infiltrating the
structure. Seal around ductwork where it passes through
outside walls or ceiling. Seal around electrical wiring also.
19. Be sure that damper which is supplied with this model is
properly installed. (See Figures 1 & 2).
FIGURE 3
L
WIRING 6NOCKCUT