Whirlpool GCGM2991MQ Installation Guide

IMPORTANT:
Part No, 8527902
Read and save
these instructions
IMPORTANT Installer: Leave Installation Instructions
with the owner.
future reference.
Save Installation Instructions for local
electrical inspector's use.
www.whirlpool.com LAUNDRY
COMMERCIAL
ELECTRONIC DRYER
ELECTRIC
120-volt, 60 Hz
120/240-volt, 60 Hz
COMMERCIAL
PRODUCTS
®
Before you start...
Your safety and the safety of others are very important.
We have provided many important
safety message inthis manual and on your appliance. Always read
and obey allsafety messages.
You can be killed or seriously
injured if you don't immediately
follow instructions.
This is the safety alert symbol.
This symbol alerts you to
potentialhazards that can kill
or hurt you and others.
All safety messages will follow the
safety alert symbol and either the word =DANGER" or "WARNING". These
words mean:
You can be killed or seriously
injured if you don't follow instructions.
All safety messages will tell you what the potential hazard is, tell you
how to reduce the chance of injury, and tell you what can happen if the
instructions are not followed.
WARNING:FOryoursefotythe
informationinthismanualmustbe
followedtominimizetheriskoffireor explosionortopreventproperty
damage,personalinjuryordeath.
Donottouchanyelecbicnl
switah;donotuseanyphonein yourbuilding.
Clearthe room,buildingornrseof
nil occupants.
Immndintalycallyourgassupplier
-- Donotstoreorusegasoline,
orotherflammablevaporsandliquids
inthevicinityofthis oranyother
appliance.
-- WHATTOgo IFYOUSMELLGAS:
Donottrytolightanyappliance.
fromnneighbor'sphone.Follow thegassupplier'sinstructions.
Ifyoucannotreachyourgas supplier,callthe firedepartment.
-- Installationandservicemustbe
donebynqualifiedinstaller, serviceagencyorthegassupplier.
It is your
responsibility to:
Observe allgoverningcodes and ordinances.
Check code requirements: Some codes
Explosion Hazard
Keep flammable materials and vapors, such as gasoline, away from dryer.
Place dryer at least 18 inches(45.8
cm) above the floor for a garage
installation.
Failureto do so can result in death, explosion, or fire.
tns aGASdt r:
Postthis warning in a prominent
location.
It isrecommended that the operator
post, in a prominent location,
instructions for the customer's use in the
event the customer smells gas, This
information should be obtained from
your local gas supplier,
Page 2
limit or do not permit installation of clothes dryers in garages, closets, mobile homes or sleeping quarters, Contact your local
building inspector,
Comply with the installation specifications and dimensions,
Consider spacing requirements for companion appliances,
Make sure you have everything necessary far proper installation,
Properly install dryer,
Contact a qualified installer to insure that the electrical and gas installations meet all
national and local codes and ordinances,
Exhaust to outdoors: Dryer must be exhausted outdoors,
Note: The dryer must not be installed in an area where itwill be exposed to water
and/or weather,
IMPORTANTSAFEW INSTRUC11ONS
WARNING -- To reduce the riskof fire, elecldc shock, or injury to persons when
using your appliance, follow basic precautions, including Ihe following:
1. Read all instructions before using the
appliance,
2. Do not dry articles that have been previously cleaned in, washed in,
soaked in, or spaffed with gasoline,
dry-cleaning solvents,or other
flammable or explosive substances, as they give off vapours that could ignite
or explode,
3. Do not allow children to play on or in
the appliance, Close supervision of
children is necessary when the appliance isused near children,
4. Before the appliance isremoved from
service or discarded, remove the door to the drying compartment,
5. Do nat reech into the appliance if the drum ismoving,
6. Do nat install or store this appliance
where itwill be exposed to the weather,
7. Do nat tamper with controls,
8. Do not repair or replace any part of
the appliance or attempt any servicing unless specifically
recommended in the user- maintenance instructions or in
published user-repair instructions that
you understand and have the skillsto
corry out,
9. Do not use fabric softeners or products
to eliminate static unless
recommended by the manufacturer of the fabric softener or product,
10. Do not use heat to dry articles containing foam rubber or similarly
textured rubber-like materials,
11. Clean lint screen before or after each load,
12. Keep area around the exhaust opening and adjacent surrounding
areas flee from the accumulation of lint, dust, and dirt,
13. 11neinteriorof the appliance and exhaust duct should be cleaned
periodically by qualified service personnel,
14. Do not place items exposed to cooking oils in your dryer, Items contaminated with cooking oiLsmay
conlTibute to a chemical reaction that could cause a load to catch fire,
SAVE THESEINSTRUCTIONS
Post this warning in a prominent
location.
FOR YOUR SAFEW
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliances.
Exhaust requirements
Fire Hazard
Use a heavy metal vent. Do not use a plastic vent.
Do not use a metal foil vent. Failure to do so can result in
death or fire,
Do not use non-metal flexible vent, metal vent that issmaller than four inches in diameter or exhaust hoods with
magnetic latches,
The dryer must be exhausted outdoors.
Do not exhaust dryer into a gas vent,
chimney, wall, ceiling, or concealed space of a building,
Do not install flexible vent in enclosed
walls, ceilings or floors,
If using an existing exhaust system, clean lint from entire length of exhaust system, Make sure exhaust hood is not plugged
with lint, The exhaust system should be inspected
and cleaned yearly,
Replace any plastic or metal foil exhaust
vent with rigid metal or flexible metal vent,
Use 4" (10,2 cm) vent clamps to
secure vent system,
exhaust airflow
better _ good _=I
a
Metal flexible vent must be fully
extended and supported when the dryer is in its final position, DO NOT
KINK OR CRUSH THEVENT, The metal
flexible vent must be completely open to allow adequate exhaust air
to flow.
Allow as much room as possible when using elbows or making turns, Bend vent gradually to avoid kinking,
Remove excess flexible vent to avoid sagging and kinking that may result in
reduced air flow, Exhaust outlet is located at the
center of the boftom dryer back, The exhaust vent can be routed up,
down, left, right, behind the dryer or straight out the back of the dryer,
Maximum length of exhaust system depends upon the type of vent used,
number of elbows and type of exhaust hood, The maximum length for both rigid and flexible vent is
shown in the chart,
EXHAUSTHOOD TYPE
r
(10.?.cnO
No.of
90°
turns
MAXIMUM LENGTHOF 4-1NCH (10.2 cm) DIAMEIER
0 64 FT.(19.5 m) 64 ET.(19.5 m) 58 FT.(17.7 m]
I 54 FT.(16.5 rn] 54 ET. [16.5 m) 48 FT.(14.6 m]
2 44 FT.(13.4 rn] 44 ET. [13.4 m) 38 FT.(II.6 m] 3 36 FT.(I0.7 m) 35 ET.(I0.7 m) 29 FT.(8.8 rn)
4 27 FT.(8.2 m) 27 FT.(8.2 m) 21 FT.(6.4 m)
MAXIMUM LENGTHOF 4-1NCH (I 0.2 cm] DIAMETER
O 36FT.(11.0 m) 36 FT.(11.0 m) 28 FT.(8.5 m)
I 31 FT.(9.4 m) 31FT. (gA n0 23 FT.(7.0 m) 2 Z'/FT.(8.2 m] 27 FT.(8.2 nO 19 FT.(5.8 m) 3 25 FT.(7.6 m] 28 FT.(7.6 n0 17 FT.(5.2 m)
4 23 FT.(7.0 m) 23 FT.(7.0 m) 18FT.(4.6 m)
FLEXIBLEMETALVENT
4
(10.2cnO
(lo.2cm)
RIGID METALVENT
For exhaust systems not covered by the exhaust length chart, see Whirlpool Service Manual, "Exhausting Whirlpool Dryers," Part No, 603197, available from your Whirlpool parts
distributor,
If dryer is installed in a confined area, such as a bedroom, bathroom or closet, it must be exhausted to the outside and provision made for
enough air for combustion and ventilation, (Check governing codes and ordinances,) See "Recessed area
and closet installation instructions" on
Page 12,
2-1/2"
Four-inch (I 0.2 cm) metal exhaust vent
isrequired, Plan installation to use the
fewest number of elbows and turns,
Page 3
An exhaust hood should cap the exhaust vent to prevent exhausted air from returning into the dryer, The
outlet of the hood must be at least
12 inches (30,5 cm) from the ground or anything else that may be in the path of the exhaust,
Four-inch outlet hood is preferred.
However, a 2-1/2-inch (6,4 cm) outlet exhaust hood may be used, A 2-1/2-inch (6,4 cm) outlet creates greater back pressure than other
hood types, For permanent
installation, a stationary exhaust system is required,
A main exhaust vent can be used for exhausting a group of dryers, Main
exhaust vent should be sized to
remove 200 CFM of air per dryer,
Large-capaci_/lint screens of proper design may be used in the main exhaust vent if checked and cleaned
frequently, The room where the dryers are located should have make-up air equal to or greater than the CFM of all the dryers in the room,
Back-draft Damper Kits, Part No,
3391910, are available from your
Whirlpool dealer and should be
installed in each dryer's exhaust vent
to prevent exhausted air from
returning into the dryers and to keep
the exhaust in balance within the
main exhaust vent, Unobstructed air
openings are required,
Each exhaust vent should enter the
main vent at an angle pointing in the
direction of the airflow, Vents entering
from the opposite side should be
staggered to reduce the exhausted
air from interfering with the other
vents,
The maximum angle of each vent
entering the main vent should be no
more than 30+,
Keep air openings free of dry
cleaning fluid fumes. Fumes create
acids which, when drown through the
dryer heating units, can damage
dryers and loads being dried.
A clean-out cover should be located
on the main exhaust vent for
periodically cleaning of the exhaust
system,
An exhaust hood should cap the outside end of the main vent to
prevent exhausted air from returning
to the dryers, If an exhaust hood cannot be used, the outside end of
the main vent should have a sweep elbow directed downward, Ifthe
main vent travels vertically through
the roof, rather than through the wall,
install 180 ° sweep elbow on the end of vent at least 2 feet (61 cm) above the highest part of the building, The opening wall or roof shall have a diameter 1/2 inch (1,3 cm) larger than
the exhaust vent diameter, The exhaust vent should be centered in
the opening,
exhaust
hood or _[ wall
m°'wP i ho"Ta'ven'
2ft. (61 cm) _.--_ _j/elbow min. above
highestpoint of
building main collector
Do Not install screening or cap over
end of vent,
main exhaust vent
wall
180°
_op
vent
Gasrequirements
Explosion Hazard
Use a new AGA or CSA
approved gas supply line.
Install a shut-off valve.
Securely tighten all gas connections.
If connected to LP, have a
qualified person make sure gas
pressure does not exceed t3" (33 cm) water column. Examples
of a qualified person include
licensed heating personnel,
authorized gas company
personnel, and authorized
service personnel.
Failure to do so can result in
death, explosion, or fire.
OBSERVEALLGOVERNING CODES AND ORDINANCES.
Am The installation must conform
with local codes, or in the absence of
local codes with the National Fuel
Gas Code, ANSI Z223,1/NFPA 54
installation codes,
B mThe design of this dryer has been certified by the CSA
International for use at altitudes up to 10,000 feet (3048 m) above sea level
at the B,T,U, rating indicated on the
model/serial plate, Burner input adjustments are not required when the dryer is operated up to this
elevation, When installed above 10,000 feet
(3048 m), a four percent (4%)
reduction of the burner B,T,U, rating shown on the model/serial plate is
required for each 1,000 foot (305 m)
increase in elevation, For assistance when converting to other gas types
and/or installing above 10,000 feet (3048 m) elevation, contact your
local service company,
Page 4
Cm Check that dryer is equipped
with the correct burner for the particular type of gas used, Burner
information can be found on the
serial/rating plate in the door well of the appliance, If this information does
not agree with the type of gas
available, see your dealer,
D mThis dryer is equipped for use
with NATURAL GAS, It is certified by CSA International for manufactured,
mixed and L,P, (propane and butane) gases with appropriate
conversion, No affempt shall be
made to convert the appliance from the gas specified on the serial/rating plate for use with a different gas without consulting the serving gas
supplier. Conversion must be done by
a qualified service technician. Gas conversion kit part numbers are listed on the gas valve burner base.
E mProvide a rigid gas supply line of
I/2-inch IPSpipe to the dryer
location, If the total length of the supply line is more than 20 feet (6,1 m), larger pipe will be needed,
For L,P, gas usage, 3/8-inch, approved copper tubing may be used, Pipe-joint compounds suitable for use with L,P, gas should be used,
shutoffvalve
_"open" position
gas supply
FmThe supply line shall be equipped
with a shutoff valve installed within 6 ft, (1,8 m) of dryer in accordance with
the National Fuel Gas Code, ANSI Z223,1 -- latest edition*, This valve
should be located in the same room as the dryer and should be in a
location that allows ease of opening and closing, Do Not block access to
the shutoff valve,
G mIf the dryer isinstalled in a confined area such as a bathroom or
closet, provision must be made for enough air for combustion and
ventilation, (Check governing codes and ordinances, or refer to the
section of this instruction covering
recessed and closet installations,)
H m If local codes and ordinances
permit, it isrecommended that new flexible metal tubing, design-certified by the AGA or CSA, be used for connecting the dryer to the gas supply line, (The gas feed pipe which extends through the lower rear of the dryer isprovided with 3/8-inch metal pipe thread,)
oom inat,o o 'pip fiftingsmust
be used to obtain an in-line connection to the dryer,
J m Make sure that lower edges of the cabinet, plus the back and
bottom sides of the dryer are free of obstructions to permit adequate clearance of air openings for
combustion air, See "Recessed area and closet installation instructions,"
page 12, for minimum spacing requirements,
Km For ease of installation,
operation and servicing (if ever needed) adequate space should be provided around the dryer,
Lm A 1/8-inch NPT plugged tapping,
accessible for gauge testing, must be installed immediately upstream of the gas supply connection to the dryer,
The dryer must be disconnected from the gas supply piping system during any pressure testing of the system at test pressures in excess of 1/2 psig,
The dryer must be isolated from the gas supply piping system by closing the equipment shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less
than 1/2 psi,
Electrical requirements
Electrical Shock Hazard
Plugintoa grounded 3-prongoutlet. Donot removegroundprong. Donot usean adapter.
Donot usean extensioncord. Failureto followthese insbucttons
can result indeath,fire, orelectrical shock.
A 12B-volt, 6O-Hz, AC-only, 15-or 2B-ampere fused electrical supply is
required, A time-delay fuse or circuit breaker is recommended,
It is recommended that a separate
circuit serving only this appliance be provided,
If codes permit and a separate ground
wire is used, it is recommended that a qualified electrician determine that the ground path is adequate.
Recommended ground method
The dryer, when installed, must be electrically grounded in accordance
with local codes, or in the absence of
local codes, with the National
Electrical Code, ANSI/NFPA 70*, GROUNDING INSTRUCTIONS: This appliance must be grounded, In the
event of malfunction or breakdown, grounding will reduce the risk of electric shock by providing a path of
least resistance for electric current, The power supply cord plug must be
plugged into an appropriate outlet that isproperly installed and grounded in accordance with all
local codes and ordinances, WARNING - Improper connection of
the equipment-grounding conductor can result in a risk of electric shock,
Check with a qualified electrician or serviceman if you are in doubt as to whether the appliance isproperly grounded, Do not modify the plug provided with the appliance - if it will
not fit the outlet, have a proper outlet
installed by a qualified electrician,
3-prong outlet
3-pron_l _ grouna ,_r_/'-_lj11_
°u.
power /
supply cord ground
Copies of the standards listed above may be obtained from:
* National Fire Protection Association
One Balterymarch Park Quincy, Massachuselts 02269
prong
Important: Observe all governing "_Oa"e
codes and ordinances.
5
Now Start...
With dryer in laundry area.
Excessive Weight Hazard
Usetwo or morepeopleto moveand installdryer.
Failureto do so canresultin back or otherinjury.
3-prong, ground-type outlet
gas supply line
gas shuloff valve
l mTake tape off front corners of
dryer, Open dryer and remove the
literature and parts packages, Wipe
the interior of the drum thoroughly with a damp cloth,
mTake two of the cardboard
corners from the carton and place them on the floor in back of the dryer,
Firmly grasp the body of the dryer
and gently lay it on its back on the cardboard corners,
mMove dryer close to final
position, Remove cardboard or hardboard from under dryer,
a Remove red cap from gas pipe,
Carefully move dryer into final position, Place level on top of the
dryer, first side to side; then front to
back, If the dryer is not level, adjust the legs of the dryer up or down until the dryer is level,
a Connect gas supply to dryer,
Use pipe-joint compound resistant to the action of L,P, gas for gas
connections, If flexible metal tubing is
used, be certain there are no kinks,
If necessary for service, open the toe
panel, use a putty knife to press on the toe panel lock located at the center top of the toe panel, Pull downward on the toe panel to open, Toe panel ishinged at the bottom,
mOpen the shutoff valve in the
gas supply line,
mUsea non-corrosive leak
detection fluid to check for leaks,
Bubbles around connections will
indicate a leak, If a leak appears, shut off gas valve controls and adjust
connections, Then check connections again, Close toe panel,
All connections must be wrench- tightened.
0 To exhaust dryer, see Exhaust
requirements, Pages 3-4, Connect
exhaust vent system to dryer exhaust outlet and exhaust hood using 4"
(10,2 cm) clamps, Use caulking to seal exterior wall opening around
exhaust hood,
1 Carefully move dryer into
final position, Place level on top of the dryer, first side to side; then front
to back, Ifthe dryer is not level, adjust the legs of the dryer up or down until the dryer is level,
1 2 Plug power supply cord into
grounded outlet,
I 3 Check dryer operation (some
accumulated time may be on the timer due to factory testing),
Pull timer-set button left, (Operating time will accumulate per number of depressions and type of timing cam used,) Push START/RESTARTbutton,
Using a full heat cycle (not the air cycle), let the dryer run for at least
five minutes, Note: Dryer door must be closed for
dryer to operate, When door is open, dryer stops, but timer continues to run, To restart dryer, close door and push
START/RESTARTbutton,
4. If the burner does not ignite
and you can feel no heat inside the dryer, shut off dryer for five minutes,
Check that all supply valve controls are in "ON" position and that the
electrical cord is plugged in, Repeat five-minute test,
5 If drying time is too long,
make sure lint screen is clean,
mWith one of the legs in hand,
check the ridges for a diamond
marking, That's how far the leg is
supposed to go into the hole,
mStaff to screw the leveling legs
into the holes by hand, (Use a small
amount of liquid detergent to
lubricate the screw threads so it is
easier to turn the legs,) Use a 1-inch wrench or socket wrench to finish
turning the legs until you reach the diamond mark,
Now stand the dryer up,
Slide dryer onto cardboard or
hardboard before moving across floor
to avoid damaging floor covering.
Page 6
Electrical
Now Start...
requirements
If codes permit and a separate ground wire is used, it is recommended that a qualified electrician determine that the ground path isadequate.
Important: Observe all governing
codes and ordinances.
A four-wire or three-wire, single- phase, 120/240-volt, 60-Hz, AC-only
electrical supply (or four-wire or three- wire, 120/208-volt, if specified on the
model/serial rating plate) is required on a separate, 30-ampere circuit,
fused on both sides of the line, A time- delay fuse or circuit breaker is
recommended,
Recommended ground method
It is the personal responsibilily and obligation of the customer to contact
a qualified electrician to assure that the electrical installation isadequate
and in conformance with the
National Electrical Code, ANSI/NFPA 70 -- latest edition*, and all local
codes and ordinances,
Copies of the standards listed above may be obtained from:
* National Fire Protection Association
One Baited/march Park Quincy, Massachuselfs 02269
Excessive Weight Hazard
Usetwo or more peopleto moveand installdryer.
Failureto do so canresultin backor
other injury.
With dryer in laundry area...
exhaust _n vent _ nect
30-amp
outlet
l mTake tape off front corners of
dryer, Open dryer and remove the
literature and parts packages, Wipe the interior of the drum thoroughly with a damp cloth,
mTake two of the cardboard
corners from the carton and place them on the floor in back of the dryer,
Firmly grasp the body of the dryer and gently lay it on its back on the
cardboard corners,
mWith one of the legs in hand,
check the ridges for a diamond
marking, That's how far the leg is supposed to go into the hole,
mStart to screw the leveling legs
into the holes by hand, (Use a small amount of liquid detergent to
lubricate the screw threads so it is easier to turn the legs,) Use a 1-inch
wrench or socket wrench to finish turning the legs until you reach the
diamond mark,
Now stand the dryer up,
Slide dryer onto cardboard or
hardboard before moving across floor to avoid damaging floor covering.
mMove dryer close to final
position, Remove cardboard or
hardboard from under dryer,
Page 7
6. Makee ectr ca connection, Power supply cord Direct wire
Use a new UL-approved power supply
Thisdryer is manufactured with the cabinet-ground conductor
connected to the NEUTRAL(center) of the widng harness at the terminal
block. If local codes do NOT permit this type of connection, use "Four-
wire connection" instructions.
For a grounded, cord-connected appliance --
GROUNDING INSTRUCTIONS: This appliance must be grounded, In
the event of malfunction or
breakdown, grounding will reduce the risk of electric shock by providing a path of least resistance for electric
current,
If using a power supply cord, the plug
must be plugged into an appropriate outlet that is properly installed and grounded in accordance with all
local codes and ordinances, WARNING - Improper connection of
the equipment-grounding conductor can result in a risk of electric shock,
Check with a qualified electrician or serviceman if you are in doubt as to whether the appliance isproperly grounded, Do not modify the plug provided with the appliance - if it will
not fit the outlet, have a proper outlet
installed by a qualified electrician,
For a permanently connected appliance --
GROUNDING INSTRUCTIONS: This appliance must be connected to
a grounded metal, permanent wiring system; or an equipment-grounding
conductor must be run with the circuit conductors and connected to
the equipment-grounding terminal or
lead on the appliance,
cord rated 24D-volt min., 30 amperes and marked for use with a clothes
dryer.
Fire Hazard
Use a new UL approved 30
ampere power supply cord.
Use a UL approved strain relief. Disconnect power before making
electrical connections. Connect neutral wire (white or
center wire) to center terminal
(silver).
Ground wire (green or bare wire)
must be connected to green
ground connector. Connect remaining 2 supply
wires to remaining 2 terminals
(gold).
Securely tighten all electrical connections.
Failure to do so can result in
death, fire, or electrical shock.
I. Disconnect the power supply.
external ground
_/,_ductor screw
tab r._J _-i hold-
i/down
_ screw
2. Remove hold-down screw
and terminal block cover,
Fire Hazard
Use 10 gauge solid copper wire. Use a UL approved strain relief. Disconnect power before making
electrical connections. Connect neutral wire (white or
center wire) to center terminal
(silver).
Ground wire (green or bare wire)
must be connected to green
ground connector. Connect remaining 2 supply
wires to remaining 2 terminals
(gold).
Securely tighten all electrical connections.
Failure to do so can result in
death, fire, or electrical shock.
strain _dryer relief //_._ \cabinet clamp I_._.L _
sections_ /
-- _ strain relief
,3. Assemble screws 3/4" U,L,-listed strain relief (U,L, marking on strain relief) into the hole below terminal block opening, Tighten strain relief screws just enough to hold the two clamp sections together, Install power supply cord/cable through the strain relief,
Page 8
Complete installation following instructions for your type of
connection:
Four-wire (recommended method)
Three-wire (if tour-wire isnot
available)
Loading...
+ 16 hidden pages