Whirlpool 19760268A User Manual

1
9760268A
HOTTE D'ASPIRATION POUR MONTAGE MURAL
36" (91,4 cm)
Instructions d’installation et Guide d’utilisation et d’entretien
36" (91.4 cm) WALL-MOUNT CANOPY RANGE HOOD
Installation Instructions and Use and Care Guide
Table of Contents/Table des matières.............................................................................2
FOR RESIDENTIAL USE ONLY.
IMPORTANT : LIRE ET CONSERVER CES INSTRUCTIONS.
POUR UTILISATION RÉSIDENTIELLE UNIQUEMENT.
IMPORTANT: Installer: Leave installation instructions with the homeowner. Homeowner: Keep installation instructions for future reference.
Save installation instructions for local inspector's use.
IMPORTANT : Installateur : Remettre les instructions d'installation au propriétaire. Propriétaire : Conserver les instructions d'installation pour consultation ultérieure.
Conserver les instructions d'installation pour consultation par l'inspecteur local.
2
RANGE HOOD SAFETY
TABLE OF CONTENTS
RANGE HOOD SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
INSTALLATION REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . .4
Tools and Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Location Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Venting Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Electrical Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
INSTALLATION INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . .6
Prepare Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Install Hood . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Install Vent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Make Electrical Connection . . . . . . . . . . . . . . . . . . . . . . . . . .8
Complete Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
RANGE HOOD USE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Check Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
RANGE HOOD CARE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
ASSISTANCE OR SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . .11
RANGE HOOD WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . .12
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
You can be killed or seriously injured if you don't immediately
You
can be killed or seriously injured if you don't
follow
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what can happen if the instructions are not followed.
Your safety and the safety of others are very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety messages.
This is the safety alert symbol.
This symbol alerts you to potential hazards that can kill or hurt you and others.
All safety messages will follow the safety alert symbol and either the word “DANGER” or “WARNING.”
These words mean:
follow instructions.
instructions.
DANGER
WARNING
TABLE DES MATIÈRES
SÉCURITÉ DE LA HOTTE DE CUISINIÈRE . . . . . . . . . . . . . .14
EXIGENCES D'INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . .16
Outillage et pièces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Exigences d'emplacement . . . . . . . . . . . . . . . . . . . . . . . . .16
Exigences concernant l'évacuation . . . . . . . . . . . . . . . . .17
Spécifications électriques . . . . . . . . . . . . . . . . . . . . . . . . .18
INSTRUCTIONS D'INSTALLATION . . . . . . . . . . . . . . . . . . . . .19
Préparation de l'emplacement . . . . . . . . . . . . . . . . . . . . . . .19
Installation de la hotte . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Installation du conduit d'évacuation . . . . . . . . . . . . . . . . . .20
Raccordement électrique . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Achever l'installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
UTILISATION DE LA HOTTE DE CUISINIÈRE . . . . . . . . . . . .22
Fonctionnement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
ENTRETIEN DE LA HOTTE DE CUISINIÈRE . . . . . . . . . . . . .22
Nettoyage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Accessoires . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
ASSISTANCE OU SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . .24
GARANTIE DE LA HOTTE DE CUISINIÈRE . . . . . . . . . . . . . .25
SCHÉMA DE CÂBLAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
3
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC
SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
Use this unit only in the manner intended by the
manufacturer. If you have questions, contact the manufacturer.
Before servicing or cleaning the unit, switch the power off at
the service panel disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
Installation work and electrical wiring must be done by
qualified person(s) in accordance with all applicable codes & standards, including fire-rated construction.
Sufficient air is needed for proper combustion and
exhausting of gases through the flue (chimney) of fuel burning equipment to prevent backdrafting. Follow the heating equipment manufacturer's guideline and safety standards such as those published by the National Fire Protection Association (NFPA), the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
When cutting or drilling into wall or ceiling; do not damage
electrical wiring and other utilities.
Ducted systems must always be vented outdoors. CAUTION: For general ventilating use only. Do not use
to exhaust hazardous or explosive materials and vapors.
CAUTION: To reduce risk of fire and to properly exhaust
air, be sure to duct air outside - do not vent exhaust air into spaces within walls ceilings, attics, crawl spaces, or garages.
WARNING: TO REDUCE THE RISK OF FIRE, USE ONLY
METAL DUCTWORK.
WARNING: TO REDUCE THE RISK OF A RANGE TOP
GREASE FIRE:
Never leave the surface units unattended at high settings.
Boilovers cause smoking and greasy spillovers that may ignite. Heat oils slowly on low or medium settings.
Always turn hood ON when cooking at high heat or when
flameing food (i.e. Crepes Suzette, Cherries Jubilee, Peppercorn Beef Flambé).
Clean ventilating fans frequently. Grease should not be
allowed to accumulate on fan or filter.
Use proper pan size. Always use cookware appropriate for
the size of the surface element.
WARNING: TO REDUCE THE RISK OF INJURY TO
PERSONS IN THE EVENT OF A RANGE TOP GREASE FIRE, OBSERVE THE FOLLOWING:
a
SMOTHER FLAMES with a close fitting lid, cookie sheet, or
other metal tray, then turn off the gas burner or electric element. BE CAREFUL TO PREVENT BURNS. If the flames do not go out immediately, EVACUATE AND CALL THE FIRE DEPARTMENT.
NEVER PICK UP A FLAMING PAN - you may be burned.
DO NOT USE WATER, including wet dishcloths or towels -
a violent steam explosion will result.
Use an extinguisher ONLY if:
– You know you have a class ABC extinguisher, and you
already know how to operate it.
– The fire is small and contained in the area where it
started.
– The fire department is being called.
– You can fight the fire with your back to an exit.
a
Based on "Kitchen Fire Safety Tips" published by NFPA.
WARNING: To reduce the risk of fire or electrical shock,
do not use this fan with any solid-state speed control device.
4
Product dimensions
Location Requirements
IMPORTANT: Observe all governing codes and ordinances. Canopy hood location should be away from strong draft areas,
such as windows, doors and strong heating vents. Cabinet opening dimensions that are shown must be used. Given
dimensions provide minimum clearance. Grounded electrical outlet is required. See “Electrical
Requirements” section. The canopy hood is factory set for venting through the roof or
wall. For non-vented (recirculating) installations see “Non-vented (recirculating) installations” in “Prepare Location” section.
All openings in ceiling and wall where canopy hood will be installed must be sealed.
Tools and Parts
Gather the required tools and parts before starting installation. Read and follow the safety instructions provided with any tools listed here.
Tools needed:
level
drill with 1¹⁄₄" (3 cm), ³⁄₈" (9.5 mm), ⁷⁄₆₄" (2.75 mm) and
¹⁄₈" (3 mm) drill bits
pencil
wire stripper or utility knife
measuring tape or ruler
pliers
caulking gun and weatherproof caulking compound
duct tape
jig saw or keyhole saw
flat blade screwdriver
metal snips
Phillips screwdriver
Parts needed:
1 x ¹⁄₂" conduit
1 wall or roof cap
metal vent system
charcoal filter – for non-vented (recirculating)
installations only
Parts supplied:
Remove parts from packages. Check that all parts were included.
hood canopy assembly with ventilator, light bulbs and
transition with back draft dampers installed
deflector for non-vented (recirculating) installations
Installation Instructions and Use & Care Guide
filter – installed in hood canopy
screws and drywall anchors
mounting template
2 piece vent cover
INSTALLATION REQUIREMENTS
11
⁵⁄₁₆
"
(28.7 cm)
13
³⁄₁₆
"
(33.5 cm)
36" (91.4 cm)
1" (2.5 cm) min.*
19" (48.3 cm) max.
26"
(66.0 cm)
min.
44"
(111.8 cm)
max.
19
¹¹⁄₁₆
"
(50.0 cm)
25"
(63.5 cm)
*IMPORTANT: For non-vented (recirculating) installations, minimum dimension is
6" (15.2 cm).
5
30" (76.2 cm) min.
bottom of canopy to
cooking surface
vent and power
supply cable entry
location
21"
(53.3 cm)
min.
12"
(30.5 cm)
12"
(30.5 cm)
side
cabinet
side
cabinet
10-1/2" (26.7 cm)
2" (50.1 mm)
min.
36" (91.4 cm)
minimum
centerline
Installation dimensions
Venting Requirements
Vent system must terminate to the outside. Do not terminate the vent system in an attic or other enclosed
area. Do not use 4" (10.2 cm) laundry-type wall caps. Use metal vent only. Rigid metal vent is recommended. Do not
use plastic or metal foil vent.
For the most efficient and quiet operation:
Use a straight run or as few elbows as possible.
Use no more than three 90° elbows.
Make sure there is a minimum of 24" (61 cm) of straight vent
between the elbows if more than one elbow is used.
Do not install two elbows together.
Use duct tape to seal all joints in the vent system.
Use caulking to seal exterior wall or roof opening around
the cap.
Cold weather installations
An additional backdraft damper should be installed to minimize backward cold air flow and a nonmetallic thermal break to minimize conduction of outside temperatures as part of the vent system. The damper should be on the cold air side of the thermal break.
The break should be as close as possible to where the vent system enters the heated portion of the house.
Make-up air
Local building codes may require the use of make-up air systems when using ventilation systems greater than specified CFM of air movement. The specified CFM varies from locale to locale. Consult your HVAC professional for specific requirements in your area.
Venting methods
This canopy hood is factory set for venting through the roof or wall.
An 8" (20.3 cm) round vent system is needed for installation (not included). The hood exhaust opening is 8" (20.3 cm) round.
Vent system can terminate either through the roof or wall. To vent through a wall, a 90° elbow is needed.
Rear discharge
A 90° elbow may be installed immediately above the hood.
For non-vented (recirculating) installations
Should it not be possible to vent cooking fumes and vapors to the outside, the hood can be used in the non-vented (recirculating) version, fitting an activated carbon filter and the deflector, fumes and vapors are recycled through the top grille.
Calculating Vent System Length
To calculate the length of the system you need, add the equivalent feet (meters) for each vent piece used in the system.
Maximum equivalent vent length is 50 feet (15.2 meters).
Roof venting
roof cap
wall cap
8"
(20.3 cm)
round vent
Wall venting Non-vented
(recirculating)
8"
(20.3 cm)
round vent
8"
(20.3 cm)
round vent
deflector
90° elbow
wall cap
1 — 90° elbow = 5 ft. (1.5 m) 8 ft. (2.4 m) straight = 8 ft. (2.4 m) 1 — wall cap = 0 ft. (0 m) system length = 13 ft. (3.9 m)
6 ft. (1.8 m)
2 ft.
(0.6 m)
Example vent
system
Vent piece 8" (20.3 cm) round
45° elbow 2.5 feet
(0.8 m)
90° elbow 5.0 feet
(1.5 m)
2. Select a flat surface for assembling the unit. Cover that
surface with a protective covering.
3. Determine and mark the centerline on the wall where the
canopy hood will be installed.
4. Select a mounting height, minimum 30" (76.2 cm), above the
cooking surface and mark reference line on the wall.
5. Tape template in place, aligning the template centerline and
bottom of template with hood bottom line and with the centerline marked on the wall.
6
INSTALLATION INSTRUCTIONS
Prepare Location
Do not cut a joist or stud unless absolutely necessary. If a joist or stud must be cut, then a supporting frame must be constructed.
Before making cutouts, make sure there is proper clearance within the ceiling or wall for exhaust vent.
Hood installation height above cooktop is the user's preference. The lower the hood above the cooktop, the more efficient the capturing of cooking odors, grease and smoke.
Check your ceiling height and the hood height maximum before you select your hood.
1. If possible, disconnect and move freestanding or slide-in range from cabinet opening to provide easier access to rear wall. Otherwise put a thick, protective covering over countertop, cooktop or range to protect from damage or dirt.
WARNING
Excessive Weight Hazard
Use two or more people to move and install range.
Failure to do so can result in back or other injury.
A
D
C
B
Electrical Requirements
IMPORTANT: The hood must be electrically grounded in accordance with local codes and ordinances, or in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, latest edition, or Canadian Electrical Code, CSA C22.1.
If codes permit and a separate ground wire is used, it is recommended that a qualified electrical installer determine that the ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch Park, Quincy, MA 02269
CSA International
8501 East Pleasant Valley Road
Cleveland, Ohio 44131-5575
A 120-volt, 60-Hz, AC-only, 15-amp, fused electrical circuit is required. A time-delay fuse or circuit breaker is also recommended. It is recommended that a separate circuit serving only this hood be provided.
Do not ground to a gas pipe.
Check with a qualified electrician if you are not sure range
hood is properly grounded.
Do not have a fuse in the neutral or ground circuit.
The range hood must be connected with copper wire only.
The range hood should be connected directly to the fused
disconnect (or circuit breaker) box through flexible armored cable or flexible metallic conduit.
Wire sizes must conform to the requirements of the National Electrical Code, ANSI/NFPA 70, latest edition, or CSA Standard C22.1-94, Canadian Electrical Code, Part 1 and C22.2 No. 0-M91, latest edition, and all local codes and ordinances.
A. Centerline B. Lower support bracket C. Mounting height reference D. Fastener locations
WARNING
Electrical Shock Hazard
Disconnect power before servicing.
Replace all parts and panels before operating.
Failure to do so can result in death or electrical shock.
7
6. Place the lower support bracket on the template aligning it
with the traced rectangle. Mark centers of 3 fastener locations through the template to the wall.
IMPORTANT: All screws must be installed into wood. Remove the template.
7. Drill ⁷⁄₆₄" (2.75 mm) pilot holes at two upper locations where
screws are being installed into wood.
8. Determine and make all necessary cuts in the wall for the vent
system. Install the vent system before installing the hood. See “Venting Requirements” section.
9. Determine the required height for the ¹⁄₂" conduit and drill a
1¹⁄₄" (3.2 cm) hole at this location.
10. Run the ¹⁄₂" conduit through the hole. Run wire through the ¹⁄₂"
conduit according to the National Electrical Code or CSA Standards and local codes and ordinances. There must be enough ¹⁄₂" conduit and wires from the fused disconnect (or circuit breaker) box to make the connection in the hood’s electrical terminal box.
11. Use caulk to seal all openings. NOTE: Do not turn on power until installation is complete.
12. Attach the lower support bracket to the wall at location
marked on the template.
Vent cover bracket assembly and installation
1. Assemble the 3 pieces of the vent cover bracket using 4 screws provided. The assembled bracket should be sized to fit inside the upper vent cover.
2. Install vent cover bracket to wall about ¹⁄₈" (3 mm) away from the ceiling with drywall anchors supplied.
A
B
A
B
Install Hood
1. Hang blower housing on the lower support bracket using the
2 mounting hooks on the rear of the blower housing.
2. Level the blower housing with leveling screws in mounting
hooks, using a level across bottom of blower housing.
3. Remove the filter and secure the blower housing with one
screw in the bottom hole located in the rear of the blower.
Install Vent
Vented installations only
1. Fit vent system over transition piece.
2. Seal connection with duct tape.
WARNING
Excessive Weight Hazard
Use two or more people to move and install range hood.
Failure to do so can result in back or other injury.
B
C
D
E
A
A
B
X
X
B
A
A. Lower support bracket B. Centerline on wall
A. Vent cover bracket assembly B. Upper vent cover
A. Vent cover bracket B. Centerline on wall
A. Lower support bracket B. Mounting hooks C Adjust side to side D. Adjust up and down E. Blower housing
A. Rear of blower housing B. Bottom screw hole
8
Make Electrical Connection
1. Disconnect power.
2. Remove terminal box cover.
3. Remove the knockout.
4. Install the UL- or CSA-listed conduit connector.
5. Run 3 wires, black, white and green (14 AWG) in ¹⁄₂" conduit
from service panel to terminal box.
6. Use twist-on connectors and connect black wires together.
7. Use twist-on connectors and connect white wires together.
C
A
B
A
B
Non-vented (recirculating) installation
1. Assemble the 3 parts of the deflector with 2 screws provided. The assembled deflector should be sized to fit the width of the vent cover bracket installed earlier.
2. Connect the deflector to the vent cover bracket using 4 screws provided.
3. Measure length of 8" (20.3 cm) vent needed to connect the transition to the deflector.
NOTE: Vent should fit up inside deflector 1" (2.5 cm) minimum.
4. Install vent between the transition and the deflector.
5. Seal all connections with duct tape.
WARNING
Electrical Shock Hazard
Disconnect power before servicing.
Replace all parts and panels before operating.
Failure to do so can result in death or electrical shock.
A
A
B
A. Vent cover bracket width B. Deflector
A. Vent cover bracket
A. Knockout B. Terminal box cover
A. Conduit B. Terminal box cover C. Conduit connector
9
Complete Installation
1. Check lights and blower operation. See “Use and Care Guide” section.
If hood does not operate:
Check that the circuit breaker is not tripped or house fuse
blown.
Disconnect power. Check that wiring is correct.
2. For non-vented (recirculating) installations, install the charcoal filter. See “Use and Care Guide” section.
3. Place the 2 L-brackets onto the glass hood.
4. Slide the glass hood on the blower housing.
5. Attach M4x35 screws to secure the glass hood.
6. Install vent cover by placing both vent covers on the hood.
7. Secure lower vent cover to hood with 2 screws, one on
either side.
8. Lift upper vent cover to the ceiling.
B
A
C
A
A
8. Use twist-on connectors and connect green or bare wire with yellow-green wire.
9. Replace terminal box cover.
10. Check all light bulbs to make sure they are secure in their
sockets.
11. Reconnect power.
WARNING
Electrical Shock Hazard
Electrically ground blower.
Connect ground wire to green and yellow ground wire in terminal box.
Failure to do so can result in death or electrical shock.
A. L-bracket
A. Screws
9. Secure upper vent cover to vent cover bracket with 2 screws,
one on either side.
A. Vent cover bracket B. Upper vent cover C. Lower vent cover
Loading...
+ 19 hidden pages