wheelock ZNH, ZNS-MCC, ZNS-MCCH, ZNS-MCWH, ZNS-MCW Service Manual

...
Page 1
Series ZRS Strobes, ZNS Horn Strobes and Series ZNH Horns
S
N
A
P
Series ZNS
Description:
The Wheelock Series Z notification appliances feature an easy snap on base that is designed to simplify the installation and testing of horns, strobes, and horn/strobes. The separate Series Z snap on base can be pre-wired so circuit wiring can be fully tested before the appliance is installed and before the walls are covered. Once all surrounding work is complete, the appliance can be simply installed by snaping it on the base. Shorting contacts in the base, which provide continuity for circuit testing, are permanently opened when the appliance is installed so any subsequent removal of the appliance will indicate a trouble condition on that circuit at the control panel when circuit supervision is enabled. The same base is used for all Series Z horns, strobes and horn/strobes to provide consistent installation and easy replacement of appliances if required. A locking screw is also included for the appliance to provide extra secure installation.
The Wheelock Series Z appliances incorporate the same dependable circuitry and high efficiency optics that are used in Wheelock RSS strobes, NS horn/strobes and NH horns and have the same high performance ratings. The Series Z appliances are compatible with all UL listed “Regulated” panels and all panels that are compatibility listed with Wheelock RSS, NS and NH appliances.
Series ZNH
Features:
Approvals include: UL Standard 1971, UL Standard 464, New York City (MEA), California State Fire Marshal (CSFM), Factory Mutual (FM) and Chicago (BFP). See approvals by model number in Specifications and Ordering Information
ADA/NFPA/UFC/ANSI and OSHA 29, Part 1910, 165 compliant
EZ Mount SNAP design, with separate base plate, provides ability to pre-wire the base and test the circuit wiring before the walls are covered
The base plate is protected by a disposable cover and the appliances can quickly snap onto the base after the walls are painted.
Patented EZ Mount Universal Mounting Plate (ZBASE) – uses single plate for ceiling and wall mount installations
Wall Mount models feature field selectable candela settings of 15/30/75/110cd and 135/185cd
Ceiling Mount models feature field selectable candela settings of 15/30/75/95cd and 115/177cd
Strobes can be synchronized using the Wheelock sync modules or power supplies with built-in sync protocol
12 and 24 VDC models with UL “Regulated Voltage” using filtered DC or unfiltered VRMS input voltage
Strobes produce 1 flash per second over the “Regulated Voltage” range (ZNS, ZRS models)
Selectable Continuous Horn or Temporal (Code-3) Tones with selectable 90 or 95 dBA setting (ZNH, ZNS models)
Selectable 12 or 24VDC in 1 appliance (ZNH model)
Series ZRS
Series ZRS
ZNS, ZNH and ZRS appliances go onto the base plate in a SNAP.
Page 2
NOTE: All CAUTIONS and WARNINGS are identified by the symbol . All warnings are printed in bold capital letters.
WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING
OR APPLYING THIS PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
General Notes:
Strobes are designed to flash at 1 flash per second minimum over their “Regulated Voltage Range”.
All candela ratings represent minimum effective strobe intensity based on UL Standard 1971.
Series ZNS Strobe products are listed under UL Standards 1971 and 464 for indoor use with a temperature range of 32°F to 120°F (0°C to 49°C) and maximum humidity of 93% (± 2%).
Series ZNH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only).
“Regulated Voltage Range” is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology “Listed Voltage Range”.
Table 1: Series ZNS Ratings Per UL Standard 1971
Regulated
Voltage
Range
VDC/FWR
Strobe Candela
(CD)
Model
Input
Voltage
VDC
ZNS-MCW 24 16.0 - 33.0 15/30/75/110
ZNS-MCWH 24 16.0 - 33.0 135/185
ZNS-MCC 24 16.0 - 33.0 15/30/75/95
ZNS-MCCH 24 16.0 - 33.0 115/177
Table 2: Series ZNS/ZNH Horn dBA Ratings
Reverberant dBA
Description Volume
Continuous
Horn
Code 3
Horn
High 83 87 89 95
Low 76 81 84 90
High 79 82 89 95
Low 72 76 84 90
@ 10ft per UL 464
12
VDC
24
VDC 12VDC24VDC
Anechoic dBA
@ 10 ft
Table 3: Series ZNS UL Max. Current*
Audible Wall Mount Strobe Models Ceiling Mount Strobe Models
Series ZNS/ZNH
24 VDC
ZNH-12/24
ZNS-MCW ZNS-MCWH ZNS-MCC ZNS-MCCH
15cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd
High (95) dBA
Low (90) dBA 0.018 0.066 0.101 0.177 0.232 0.306 0.429 0.071 0.114 0.201 0.261 0.306 0.429
16-33
VDC
Series ZNS/ZNH
12VDC
0.044 0.074 0.107 0.184 0.244 0.350 0.477 0.082 0.124 0.209 0.275 0.350 0.477
Audible
ZNH-12/24
High (89) dBA
Low (84) dBA 0.012
8-17.5
VDC
0.021
Table 4: Series ZRS UL Max. Current*
ZRS - Wall Mount ZRS - Ceiling Mount
ZRS 24VDC
MCW MCWH MCC MCCH
Models
15cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd
16-33 vdc 0.060 0.092 0.165 0.220 0.300 0.420 0.065 0.105 0.189 0.249 0.300 0.420
* UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions.
Page 3
NS
NH
EOLR
+
-
SM
F
A C P
STROBE
Audible
STROBE
+
-
Audible
Audible
NAC
Circuit
Strobe
NAC
Circuit
Wiring Diagrams
+
-
APPLIA NCE
+
-
F
SYNC
+
DUAL SY NC MODULE
A
C
P
S YN C
+
-
-
A UD IB LE
A UD IB LE
C IR CU IT O UT
+
+
O UT 1
IN 1
M IN US 1
+
O UT 2
+
IN 2
M IN US 2
S IG NA L
S IG NA L
C IR CU IT R ET UR N
+
-
+
-
APPLIA NCE
ZNS/ZNH APPLIANCE
#
ZNS AND ZNH APPLIANCES SYNCHRONIZED WITH SM MOD­ULE SINGLE CLASS “B” NAC CIRCUIT WITH AUDIBLE SILENCE FEATURE
SIGNAL
ZNS AND ZNH APPLIANCES SYNCHRONIZED WITH DSM MODULE DUAL CLASS “A” NAC CIRCUIT WITH NO AUDIBLE SILENCE FEATURE
NOTE: ZNS/ZNH must be set on Code-3 horn tone to achieve synchronized temporal (Code-3) tone. Refer to installation instruction (P83983, P83600 respectively).
#
For detail using SM or DSM Sync Module refer to Data Sheet S3000 or Installation Instructions P83 123 for SM and P83177 for DSM. For wiring information on the power supplies refer to Installation Instructions P84662 for PS-24-8MC.
SPECIFICATION & ORDERING INFORMATION
Sync w/ SM,
DSM or
PS-24-8MC
24
VDC
12
VDC
Mounting Options#
Model Number
Order
Code
Strobe
Candela
ZNS-MCW-FR 0304 15/30/75/110 X X - B, D, E, F X * X * *
ZNS-MCW-FW 0305 15/30/75/110 X X - B, D, E, F X * X * *
ZNS-MCWH-FR 0306 135/185 X X - B, D, E, F X * X * *
ZNS-MCWH-FW 0307 135/185 X X - B, D, E, F X * X * *
ZNH-R 0300 - X X X B, D, E, F X * X * *
ZNH-W 0301 - X X X B, D, E, F X * X * *
ZNS-MCC-FR 0310 15/30/75/95 X X - B, D, E, F X * X * *
ZNS-MCC-FW 0311 15/30/75/95 X X - B, D, E, F X * X * *
ZNS-MCCH-FR 0312 115/177 X X - B, D, E, F X * X * *
ZNS-MCCH-FW 0313 115/177 X X - B, D, E, F X * X * *
ZRS-MCW-FR 4085 15/30/75/110 X X - B, D, E, F X * X * *
ZRS-MCW-FW 0302 15/30/75/110 X X - B, D, E, F X * X * *
ZRS-MCWH-FR 5242 135/185 X X - B, D, E, F X * X * *
ZRS-MCWH-FW 0303 135/185 X X - B, D, E, F X * X * *
ZRS-MCC-FW 0309 15/30/75/95 X X - B, D, E, F X * X * *
ZRS-MCC-FR 0308 15/30/75/95 X X - B, D, E, F X * X * *
ZRS-MCCH-FR 5240 115/177 X X - B, D, E, F X * X * *
ZRS-MCCH-FW 0314 115/177 X X - B, D, E, F X * X * *
ZBASE 5268 Accessory - Includes base, dust cover, mounting screws and installation sheet
ZBB-R 6036 Backbox for indoor suface mounting of all SNAP models
ZBB-W 6045 Backbox for indoor suface mounting of all SNAP models
#The ZRS, ZNS and ZNH will mount to single-gang, double-gang, 4” octal, 4” square and 3-1/2” octal back boxes.
NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions.
Agency Approvals
UL MEA CSFM FM BFP
*Pending
Page 4
ARCHITECTS AND ENGINEERS SPECIFICATIONS
General
Audible/visual notification appliances shall be listed for indoor use and shall meet the requirements of FCC Part 15 Class B. These appliances shall be listed under UL Standard 1971, (Standard for Safety Signaling Devices for Hearing Impaired) and UL Standard 464 (Fire Protective Signaling). The appliances shall use a Patented Universal EZMount backplate that shall allow mounting to a single­gang, double-gang, 4-inch square, 4” octal, or a 3-1/2” octal backbox. Two wire appliance wiring shall be capable of directly connecting to the mounting back plate. Continuity checking of the entire NAC circuit prior to attaching any audible/visual notification appliances shall be allowed. A dust cover shall fit and protect the mounting plate. The dust cover shall be easily removed when the appliance is installed over the backplate. Removal of an appliance shall result in an alarm condition by the Fire Alarm Control Panel (FACP).
Strobes
Strobe appliances shall produce a minimum flash rate of 60 flashes per minute (1 flash per second) over the Regulated Voltage Range of 16 to 33 VDC and shall incorporate a Xenon flashtube enclosed in a rugged Lexan lens. The strobes shall be available with two or four field selectable settings in one unit and shall be rated, per UL 1971, for up to 185 cd for wall mounting and 177 cd for ceiling mounting. The strobes shall operate over an extended temperature range of 32°F to 120°F (0°C to 49°C) and be listed for maximum humidity of 95% RH. Strobe inputs shall be polarized for compatibility with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP).
Audibles and Audible/Strobe Combinations
Horns and horn/strobes shall be listed for Indoor use under UL Standard 464. The horns shall be able to produce a continuous output or a temporal code-3 output that can be synchronized. The horns shall have at least 2 sound level settings of 90 and 95 dBA.
Synchronization Modules
When synchronization of strobes or temporal Code-3 audibles is required, the appliances shall be compatible with the Wheelock Series SM and DSM Sync Modules or the Wheelock PS-24-8MC Power Supply with built-in, patented sync protocol. The strobes shall not drift out of synchronization at any time during operation. Audibles and strobes shall be able to be synchronized on a 2-wire circuit with the capability to silence the audible if required. If the sync module or power supply fails to operate (i.e., contacts remain closed), the strobes shall revert to a non-synchronized flashrate
273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com
WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
3 YEAR WARRANTY
Made in USA
Z1000 ZNS/ZNH ZRS 04/07
Loading...