Series ZRS Strobes, ZNS Horn Strobes and Series ZNH Horns
S
N
A
P
Series ZNS
Description:
The Wheelock Series Z notification appliances feature an easy snap
on base that is designed to simplify the installation and testing of
horns, strobes, and horn/strobes. The separate Series Z snap on
base can be pre-wired so circuit wiring can be fully tested before
the appliance is installed and before the walls are covered. Once
all surrounding work is complete, the appliance can be simply
installed by snaping it on the base. Shorting contacts in the base,
which provide continuity for circuit testing, are permanently opened
when the appliance is installed so any subsequent removal of the
appliance will indicate a trouble condition on that circuit at the control
panel when circuit supervision is enabled. The same base is used
for all Series Z horns, strobes and horn/strobes to provide consistent
installation and easy replacement of appliances if required. A locking
screw is also included for the appliance to provide extra secure
installation.
The Wheelock Series Z appliances incorporate the same dependable
circuitry and high efficiency optics that are used in Wheelock RSS
strobes, NS horn/strobes and NH horns and have the same high
performance ratings. The Series Z appliances are compatible with
all UL listed “Regulated” panels and all panels that are compatibility
listed with Wheelock RSS, NS and NH appliances.
Series ZNH
Features:
• Approvals include: UL Standard 1971, UL Standard 464,
New York City (MEA), California State Fire Marshal (CSFM),
Factory Mutual (FM) and Chicago (BFP). See approvals by
model number in Specifications and Ordering Information
• ADA/NFPA/UFC/ANSI and OSHA 29, Part 1910, 165
compliant
• EZ Mount SNAP design, with separate base plate, provides
ability to pre-wire the base and test the circuit wiring before
the walls are covered
• The base plate is protected by a disposable cover and the
appliances can quickly snap onto the base after the walls are
painted.
• Patented EZ Mount Universal Mounting Plate (ZBASE)
– uses single plate for ceiling and wall mount installations
• Wall Mount models feature field selectable candela settings
of 15/30/75/110cd and 135/185cd
• Ceiling Mount models feature field selectable candela
settings of 15/30/75/95cd and 115/177cd
• Strobes can be synchronized using the Wheelock sync
modules or power supplies with built-in sync protocol
• 12 and 24 VDC models with UL “Regulated Voltage” using
filtered DC or unfiltered VRMS input voltage
• Strobes produce 1 flash per second over the “Regulated
Voltage” range (ZNS, ZRS models)
• Selectable Continuous Horn or Temporal (Code-3) Tones with
selectable 90 or 95 dBA setting (ZNH, ZNS models)
• Selectable 12 or 24VDC in 1 appliance (ZNH model)
Series ZRS
Series ZRS
ZNS, ZNH and ZRS
appliances go onto the
base plate in a SNAP.
Page 2
NOTE: All CAUTIONS and WARNINGS are identified by the symbol . All warnings are printed in bold capital letters.
WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING
OR APPLYING THIS PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION
INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION,
INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND
SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
General Notes:
•Strobes are designed to flash at 1 flash per second minimum over their “Regulated Voltage Range”.
• All candela ratings represent minimum effective strobe intensity based on UL Standard 1971.
• Series ZNS Strobe products are listed under UL Standards 1971 and 464 for indoor use with a temperature range of 32°F to 120°F (0°C to
49°C) and maximum humidity of 93% (± 2%).
• Series ZNH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only).
• “Regulated Voltage Range” is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology
“Listed Voltage Range”.
Table 1: Series ZNS Ratings Per UL Standard 1971
Regulated
Voltage
Range
VDC/FWR
Strobe Candela
(CD)
Model
Input
Voltage
VDC
ZNS-MCW2416.0 - 33.015/30/75/110
ZNS-MCWH2416.0 - 33.0135/185
ZNS-MCC2416.0 - 33.015/30/75/95
ZNS-MCCH2416.0 - 33.0115/177
Table 2: Series ZNS/ZNH Horn dBA Ratings
Reverberant dBA
DescriptionVolume
Continuous
Horn
Code 3
Horn
High83878995
Low76818490
High79828995
Low72768490
@ 10ft per UL 464
12
VDC
24
VDC 12VDC24VDC
Anechoic dBA
@ 10 ft
Table 3: Series ZNS UL Max. Current*
AudibleWall Mount Strobe ModelsCeiling Mount Strobe Models
* UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes
the UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max current is usually
at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions.
Page 3
NS
NH
EOLR
+
-
SM
F
A
C
P
STROBE
Audible
STROBE
+
-
Audible
Audible
NAC
Circuit
Strobe
NAC
Circuit
Wiring Diagrams
+
-
APPLIA NCE
+
-
F
SYNC
+
DUAL SY NC MODULE
A
C
P
S YN C
+
-
-
A UD IB LE
A UD IB LE
C IR CU IT O UT
+
+
O UT 1
IN 1
M IN US 1
+
O UT 2
+
IN 2
M IN US 2
S IG NA L
S IG NA L
C IR CU IT R ET UR N
+
-
+
-
APPLIA NCE
ZNS/ZNH APPLIANCE
#
ZNS AND ZNH APPLIANCES SYNCHRONIZED WITH SM MODULE SINGLE CLASS “B” NAC CIRCUIT WITH AUDIBLE SILENCE
FEATURE
SIGNAL
ZNS AND ZNH APPLIANCES SYNCHRONIZED WITH DSM MODULE
DUAL CLASS “A” NAC CIRCUIT WITH NO AUDIBLE SILENCE FEATURE
NOTE: ZNS/ZNH must be set on Code-3 horn tone
to achieve synchronized temporal (Code-3) tone.
Refer to installation instruction (P83983, P83600
respectively).
#
For detail using SM or DSM Sync Module refer
to Data Sheet S3000 or Installation Instructions
P83 123 for SM and P83177 for DSM. For
wiring information on the power supplies refer to
Installation Instructions P84662 for PS-24-8MC.
SPECIFICATION & ORDERING INFORMATION
Sync w/ SM,
DSM or
PS-24-8MC
24
VDC
12
VDC
Mounting
Options#
Model Number
Order
Code
Strobe
Candela
ZNS-MCW-FR030415/30/75/110XX- B, D, E, FX*X**
ZNS-MCW-FW030515/30/75/110XX- B, D, E, FX*X**
ZNS-MCWH-FR0306135/185XX- B, D, E, FX*X**
ZNS-MCWH-FW0307135/185XX- B, D, E, FX*X**
ZNH-R0300-XXX B, D, E, FX*X**
ZNH-W0301-XXX B, D, E, FX*X**
ZNS-MCC-FR031015/30/75/95XX- B, D, E, FX*X**
ZNS-MCC-FW031115/30/75/95XX- B, D, E, FX*X**
ZNS-MCCH-FR0312115/177XX- B, D, E, FX*X**
ZNS-MCCH-FW0313115/177XX- B, D, E, FX*X**
ZRS-MCW-FR408515/30/75/110XX- B, D, E, FX*X**
ZRS-MCW-FW030215/30/75/110XX- B, D, E, FX*X**
ZRS-MCWH-FR5242135/185XX- B, D, E, FX*X**
ZRS-MCWH-FW0303135/185XX- B, D, E, FX*X**
ZRS-MCC-FW030915/30/75/95XX- B, D, E, FX*X**
ZRS-MCC-FR030815/30/75/95XX- B, D, E, FX*X**
ZRS-MCCH-FR 5240115/177XX- B, D, E, FX*X**
ZRS-MCCH-FW0314115/177XX- B, D, E, FX*X**
ZBASE5268 Accessory - Includes base, dust cover, mounting screws and installation sheet
ZBB-R6036 Backbox for indoor suface mounting of all SNAP models
ZBB-W6045 Backbox for indoor suface mounting of all SNAP models
#The ZRS, ZNS and ZNH will mount to single-gang, double-gang, 4” octal, 4” square and 3-1/2” octal back boxes.
NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance
with Wheelock Inc. standard terms and conditions.
Agency Approvals
UL MEA CSFM FM BFP
*Pending
Page 4
ARCHITECTS AND ENGINEERS SPECIFICATIONS
General
Audible/visual notification appliances shall be listed for indoor use and shall meet the requirements of FCC Part 15 Class B. These
appliances shall be listed under UL Standard 1971, (Standard for Safety Signaling Devices for Hearing Impaired) and UL Standard 464
(Fire Protective Signaling). The appliances shall use a Patented Universal EZMount backplate that shall allow mounting to a singlegang, double-gang, 4-inch square, 4” octal, or a 3-1/2” octal backbox. Two wire appliance wiring shall be capable of directly connecting
to the mounting back plate. Continuity checking of the entire NAC circuit prior to attaching any audible/visual notification appliances
shall be allowed. A dust cover shall fit and protect the mounting plate. The dust cover shall be easily removed when the appliance is
installed over the backplate. Removal of an appliance shall result in an alarm condition by the Fire Alarm Control Panel (FACP).
Strobes
Strobe appliances shall produce a minimum flash rate of 60 flashes per minute (1 flash per second) over the Regulated Voltage Range
of 16 to 33 VDC and shall incorporate a Xenon flashtube enclosed in a rugged Lexan lens. The strobes shall be available with two
or four field selectable settings in one unit and shall be rated, per UL 1971, for up to 185 cd for wall mounting and 177 cd for ceiling
mounting. The strobes shall operate over an extended temperature range of 32°F to 120°F (0°C to 49°C) and be listed for maximum
humidity of 95% RH. Strobe inputs shall be polarized for compatibility with standard reverse polarity supervision of circuit wiring by a
Fire Alarm Control Panel (FACP).
Audibles and Audible/Strobe Combinations
Horns and horn/strobes shall be listed for Indoor use under UL Standard 464. The horns shall be able to produce a continuous output
or a temporal code-3 output that can be synchronized. The horns shall have at least 2 sound level settings of 90 and 95 dBA.
Synchronization Modules
When synchronization of strobes or temporal Code-3 audibles is required, the appliances shall be compatible with the Wheelock Series
SM and DSM Sync Modules or the Wheelock PS-24-8MC Power Supply with built-in, patented sync protocol. The strobes shall not
drift out of synchronization at any time during operation. Audibles and strobes shall be able to be synchronized on a 2-wire circuit with
the capability to silence the audible if required. If the sync module or power supply fails to operate (i.e., contacts remain closed), the
strobes shall revert to a non-synchronized flashrate