wheelock RSSWP-2475, ASWP-24MCCH, ET70WP-24185W, AHWP, ASWP-2475 Service Manual

...
THE CITY OF NEW YORK
DEPARTMENT OF BUILDINGS
U
L
Weatherproof Appliances - Series AH Audibles, AS Audible Strobes, MT Multitone Strobes,
RSS Strobes and ET70 Speaker Strobes and Weatherproof Mounting Accessories
Description:
Designed for life safety, performance and reliability, Cooper Wheelock’s cost effective weatherpoof notification appliances include:
Weatherproof Appliances Series
Strobes RSSWP Horn Strobes ASWP Horns AH-24WP, AH-12WP Multitone Horn Strobes MTWP Multitone Horns MT Speaker Strobes ET70WP Speakers ET-1010
All strobe models are UL dual listed - meeting both UL1638 and UL1971 requirements. As dual listed appliances, these weatherproof strobes, horn strobes and speaker strobes are listed for outdoor applications under UL 1638 as well as under UL 1971, the Standard for Safety Signaling Devices for Hearing Impaired. With an extended temperature range of –31°F to 150°F (-40°C to 66°C), Wheelock weatherproof appliances meet or exceed UL outdoor test requirements for rain, humidity and corrosion resistance while providing multiple strobe intensity options, including the highest strobe ratings available for area coverage per NFPA 72 strobe spacing tables (up to 185 candela for wall mounting and 177 candela for ceiling mounting).
To enable weatherproof mounting, Cooper-Wheelock provides the industry’s widest choice of mounting options for surface or unique semi-flush installation. Models are available for surface mounting to Wheelock weatherproof backboxes on walls or ceilings. The optional WP-KIT allows the weatherproof backboxes (IOB, WPBB or WPSBB) to be mounted to a recessed electrical box for concealed conduit installation. For semi-flush installation, the WPA and WFPA kits allow a customer to mount the weatherproof appliances to a recessed electrical box without the need for an external weatherproof backbox. See the Backboxes, Plates and Gaskets Table on page three of this document for a summarization of these mounting options and the required accessories.
When used in conjunction with Wheelock PS-24-8MC Power Supplies or SM/DSM Sync Modules, the Wheelock weatherproof appliances can be synchronized to meet NFPA 72 synchronization requirements. The horn output of horn strobes can be independently controlled on 2-wire circuits using the Wheelock patented sync protocol. MTWP horn strobe models are 4-wire appliances; the strobes can be synchronized while the audible can be connected to a coded fire alarm system or can be set to produce any of eight selectable tones.
Features:
Approvals include: UL Standards 1971, 1638, 464 and 1480
California State Fire Marshal (CSFM) and New York City (MEA), Factory Mutual (FM) and Chicago (BFP) . See agency approvals by model number on page two of this document
Compliance with the following requirements: NFPA, UFC,
ANSI 117.1, OSHA Part 29, 1910.165, ADA
Weatherproof with extended temperature range of –40°F to
150°F (-40°C to 66°C)*
Dual Listed strobe models (UL 1638 and UL 1971)
Industry’s highest strobe candela options
Synchronization capability using Series SM, DSM Synch
Modules (MTWP and MT-12/24 audible is non-sync)
Models with field selectable tone, dBA and candela settings
Wall or ceiling mounting options
Surface of semi-flush mounting
IN/OUT wiring termination accepting two #12-18 AWG wires
at each terminal
*The series RSSWP, ASWP, MTWP and ET70WP have UL approval down to -40°F. The AH-24WP, MT-12/24 and the ET-1010 have been ULC tested and approved to
-40°F, but not submitted to UL. The AH-12WP has UL/ULC approval to -31°F.
E5946 S5391 S2652
151-92-E
7125-0785:131 (ASWP) 7125-0785:146 (ET70WP) 7125-0785:156 (MTWP) 7300-0785:154 (RSSWP)
NOTE: All CAUTIONS and WARNINGS are identified by the symbol . All warnings are printed in bold capital letters.
WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR
APPLYING THIS PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
General Notes:
Strobes are designed to flash at 1 flash per second minimum over their UL Listed Regulated Voltage Range.
All candela ratings represent minimum effective Strobe intensity based on UL Standards 1971 and 1638 as indicated in candela ratings table.
Wall Mount
RSSWP
ASWP
Strobe Order Code
RSSWP-2475W-FR Red 9013 RSSWP-2475W-FW White 3034 RSSWP-24MCWH-FR Red 5161 RSSWP-24MCWH-FW White 5165
Audible Strobe
ASWP-2475W-FR Red 9012 ASWP-24MCHW-FR Red 5137 ASWP-24MCWH-FW White 5140
Multi-tone Strobe
MTWP-2475W-FR Red 8420 MTWP-2475W-FW White 3112 MTWP-24MCWH-FR Red 5132 MTWP-24MCWH-FW White 5134
Speaker Strobe
ET70WP-2475W-FR Red 9077 ET70WP-2475W-FW White 3179 ET70WP-24185W-FR Red 4885 ET70WP-24185W-FW White 4891
MTWP
ET70WP
Ceiling Mount
RSSWP
ASWP
Strobe Order Code
RSSWP-2475C-FR Red 4338 RSSWP-2475C-FW White 4446 RSSWP-24MCCH-FR Red 5167 RSSWP-24MCCH-FW White 5187
Audible Strobe
ASWP-2475C-FR Red 4251 ASWP-2475C-FW White 4502 ASWP-24MCCH-FR Red 5149 ASWP-24MCCH-FW White 5157
Multi-tone Strobe
MTWP-2475C-FR Red 4457 MTWP-2475C-FW White 4478 MTWP-24MCCH-FR Red 5102 MTWP-24MCCH-FW White 5122
Speaker Strobe
ET70WP-2475C-FR Red 4452 ET70WP-2475C-FW White 4454 ET70WP-24177C-FR Red 4845
MTWP
ET70WP
ET70WP-24177C-FW White 4859
Candela Ratings
Series
UL 1971
@ 32º-
120ºF
UL 1638
@ 77°F
UL 1638 @ -40°F
RSS, ET70WP and
MTWP UL Max Current
(Strobe Only)
ASWP
High Med Low
2475 30 180 115 0.138 0.168 0.155 0.150
MCWH
MCCH
135 135 65 0.300 0.355 0.340 0.335
185 185 90 0.420 0.480 0.465 0.460
115 115 50 0.300 0.355 0.340 0.335
177 177 75 0.420 0.480 0.465 0.460
24185 185 185 90 0.420
24177 177 177 75 0.420
UL Max. Current
(Audible)
MTWP/MT
24 VDC
MT
12 VDC
dBA HI STD HI STD Horn 0.108 0.044 0.177 0.034 Bell 0.053 0.024 0.095 0.020 March Time 0.104 0.038 0.142 0.034 Code 3 Horn 0.091 0.035 0.142 0.034 Code 3 Tone 0.075 0.035 0.105 0.021 Slow Whoop 0.098 0.037 0.142 0.035 Siren 0.104 0.036 0.152 0.030 Hi/Lo 0.057 0.025 0.114 0.026
Wall or Ceiling Mount
MT
ET-1010
Audible Order Code
AH-24WP-R Red 7416 AH-12WP-R Red 7415
Horn
MT-12/24-R Red 5023
Speaker
ET-1010-R Red 3135 ET-1010-W White 3137
UL Max. Current
High (99) dBA 0.080 0.192 Med (95) dBA 0.043 0.108 Low (90) dBA 0.021 0.058
UL Reverberant dBA @ 10 Feet
Watts 1/8 1/4 1/2 1 2 4 8 ET-1010 77 80 83 86 87 92 94 ET70WP 78 81 84 87 90 93 95
Model Number Agency Approvals
Strobe UL MEA CSFM FM BFP
RSSWP-2475 X X X X * RSSWP-24MCWH X * * * * RSSWP-24MCCH X * * * *
Audible Strobe
ASWP-2475 X X X X X ASWP-MCWH X * * * * ASWP-MCCH X * * * *
Multitone Strobe
MTWP-2475 X X X X * MTWP-MCWH X * * * * MTWP-MCCH X * * * *
Horns/Audibles
AH-24WP X X X - X AH-12WP X X X - X MT-12/24 X X X X X
Speaker Strobe
ET70WP-2475 X X X * * ET70WP-185 X * * * * ET70WP-177 X * * * *
*Pending
AH
AH
24 VDC 12 VDC
FACP
NAC #1
NAC #2
Sync
Module
or
PS-12/24-8
Power
Supply
Strobe Circuit
Audible
Circuit
MTWP
DSM
+ OUT 2�
+OUT 1�
+ IN 1�
+ IN 2�
MINUS 1�
MINUS 2�
+
-
-
+
SYNC�
AUDIBLE�
STROBE�
NAC�
CIRCUIT�
OUT�
STROBE�
NAC� CIRCUIT� RETURN�
FACP
RSSWP�
RSS�
RSS�
RSS�
ASWP�
ASWP�
TO NEXT
APPLIANCE
OR EOLR
FROM PRECEDING APPLIANCE OR FACP
+
-
STROBE AUDIBLE
+
-
RED
BLACK
+
- -
+
+
-
+
-
+
-
FROM
PRECEDING
APPLIANCE OR
FACP
TO NEXT
APPLIANCE
OR EOLR
Mounting Accessories
Gasket Kit Order Code
WP-KIT 4486
Flush Plates
WFPA-R Red 4698 WFPA-W White 4701 WFP-R Red 4696 WFP-W White 4697
Backboxes
IOB-R Red 5046 IOB-W White 5047 WPSBB-R Red 9751
WPSBB-W White 3033 WPBB-R Red 9014 WPBB-W White 4692 WBB-R Red 2959 WBB-W White 2960
Wiring Diagrams
WFP
WFPA
IOB
Mounting Options:
RSSWP Strobes WPSBB WPSBB + WP-KIT WFP
ET70WP Speaker Strobes IOB IOB + WP-KIT WFP
ASWP Horn Strobes WPBB WPBB + WP-KIT WFPA
AHWP Horns WBB - WFP
ET-1010 Speakers WBB - WFP
MTWP Multitone Horn Strobes IOB IOB + WP-KIT WFP
Multitone Horn IOB IOB + WP-KIT WFP
WPSBB
WPBB
Backboxes, Plates, Gasket Kits
Surface Mount
Exposed Conduit Concealed Conduit
WBB
Flush
Mount
SERIES MTWP APPLIANCES SYNCHRONIZED STROBE OPERATION WITH CODED FACP
Note: Models are available in Red or White. Contact Customer Service for Order Code and Delivery. #Refer to Data Sheet S7000 for Mounting Options
NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions.
SERIES MTWP AUDIBLE APPLIANCE AND STROBE OPERATE IN UNISON. RED AND BLACK SHUNT-WIRES ARE SUPPLIED.
SERIES RSSWP, ASWP, AHWP, MTWP AND MT-12/24
APPLIANCES
Note: Strobe circuit requires constant voltage.
SERIES RSSWP/ASWP APPLIANCES SYNCHRONIZED W/ DSM MODULE SINGLE CLASS “A” NAC CIRCUIT
ARCHITECTS AND ENGINEERS SPECIFICATIONS
General
Weatherproof notification appliances shall be UL listed for outdoor use. Weatherproof Strobe appliances shall be listed under UL Standard 1638 (Standard for Visual Signaling Appliances) for Indoor/Outdoor use and UL Standard 1971 (Standard for Safety Signaling Devices for Hearing Impaired). The appliances shall be available for optional wall mounting or ceiling mounting to weatherproof backboxes using either exposed conduit or concealed conduit, or semi-flush mounting to a recessed electrical box in walls or ceilings using Wheelock mounting accessories.
Weatherproof Strobes
Weatherproof Strobe appliances shall produce a minimum flash rate of 60 flashes per minute over the UL Regulated Voltage Range of 16 to 33 VDC and shall incorporate a Xenon flashtube. The weatherproof strobes shall be available with UL 1971 candela ratings up to 185 cd for wall mounting and 177 cd for ceiling mounting. UL 1638 candela ratings up to 180 cd at 77°F shall be available. The strobes shall operate over an extended temperature range of –40°F to 150°F (-40°C to 66°C) and be listed for maximum humidity of 95% RH. Strobe inputs shall be polarized for compatibility with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP).
Weatherproof Audibles and Audible/Strobe Combinations Weatherproof horns and multitone audibles shall be listed for Indoor/Outdoor use under UL Standard 464. The horns shall be able to produce a continuous output or a temporal code-3 output that can be synchronized. T
Multitone audibles shall be able to produce 8 distinct tones selectable by dip switch and shall have at least 2 sound level settings. Multitone Audible/Strobe combinations shall have independent inputs for the audible and strobe. The strobes shall be able to be synchronized. The audibles shall be able to be coded when operated on a separate NAC.
Weatherproof Speakers and Speaker/Strobes
Weatherproof speakers and speaker/strobes shall be listed for Indoor/Outdoor use under UL Standard 1480. All speakers shall provide field selectable taps for 1/8W to 8W operation for either 25 VRMS or 70 VRMS audio systems and shall incorporate a sealed back construction for extra protection and improved audibility. Speakers without strobes shall be Wheelock Series ET-1010. They shall be listed to produce up to 94 dBA and shall incorporate a vandal resistant grille design. Speaker with strobes shall be Wheelock Series ET70WP. They shall be available for surface or semi-flush mounting to walls or ceilings and shall be listed to produce up to 93 dBA.
Synchronization Modules
When synchronization of strobes or temporal code-3 audibles is required, the appliances shall be compatible with the Wheelock Series SM and DSM Sync Modules or the Wheelock PS-24-8MC Power Supply with built-in, patented sync protocol. The strobes and audibles shall not drift out of synchronization at any time during operation.
Series ASWP audibles and strobes shall be able to be synchronized on a 2-wire circuit with the ability to silence the audible if required. The strobes on Series MT multitone audible/strobe appliances shall be able to be synchronized and shall be able to be operated on a separate circuit from the audibles while the audible circuit is connected to a coded or continuous NAC.
Weatherproof Mounting Accessories
Weatherproof mounting options shall include surface mounting or semi-flush mounting to walls or ceilings. Surface mounted appliances shall mount to Wheelock IOB, WBB, WPBB or WPSBB weatherproof backboxes using either exposed conduit or concealed conduit. For concealed conduit the weatherproof backbox shall be mounted to a recessed electrical box with Wheelock’s WP-KIT to provide a weatherproof seal for the electrical box. Semi-flush mounted appliances shall mount to a recessed electrical box using Wheelock WFP or WFPA flush plates to provide a weatherproof seal between the electrical box and the appliance.
273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com
WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
3 YEAR WARRANTY
Made in USA
S9004 WP 03/07