GENERAL:
Wheelock's VL, VL1 and VLP Visible Signals are designed with dual lamps for extra visibility and dependability. They are non-flashing incandescent
lamp signals that can be used as a visible signal only or combined with an audible signal. They can be used on a continuous or coded alarm system.
The VLPS, VLPH and VLPM are flashing xenon strobe signals that are designed to be combined with an audible signal or speaker. They are ideal for
adding strobe capability to an existing audible signal installation and they offer maximum reliability and efficiency for effective visible signaling in fire and
life safety applications. They flash once per second on continuous (non-coded) alarm systems.
SPECIFICATIONS:
VL,VL1, VLP, VLPS, VLPH Models
W in the model number indicates white lens; substitute R for red lens. The VLPM is available with a clear lens. NOTE: At 0 degrees C, minimum UL
candela ratings apply: 15cd (70,000) models = 13.75cd
WIRING DIAGRAM:
INSTALLATION INSTRUCTIONS
SERIES VL/VLP SIGNALS
MODEL
VL-24 Incandescent 24VDC 0.100 0.84cd B
VL1-24 Incandescent 24VDC 0.100 0.84cd A
VLP-24 Incandescent 24VDC 0.100 0.84cd C,D
VLPS-24 Strobe 18-31VDC 0.025 1.5cd C,D
VLPH-24 Strobe 18-31VDC 0.075 15.0cd C,D
VLPH-115 Strobe 115VAC 0.060 15.0cd C,D
VLPM-24 Strobe 24VDC 0.088 117.0cd E,F
SIGNAL
TYPE
VLP, VLPS, VLPH & VLPM - POSSIBLE COMBINATIONS
AUDIBLE SIGNAL
OR SPEAKER
HORNS 31T, 34T, EH-E
BELLS (4", 6", 10") 43T, 46T, 42PT, MB
ELECTRONIC SIGNALS AES-E *
SPEAKERS ET-1010, 806T, 807T
INPUT
RANGE
VOLTAGE
* See Application Note 9.
INPUT
CURREN
T(AMPS)
WHEELOCK
SERIES
CANDELA
PER
UL 1638
MOUNTING
OPTIONS
Figure 1.
VL and VL1 models have terminals with wire clamps, (2) wires - 12 AWG max. per position are allowed. Do not pigtail or wrap wires around screw. See
Figure 1. VLP, VLPS, VLPH and VLPM models have double leads for in-out wiring (See Application Note 2).
Copyright 1986, 1989, 1990, 1991, 1992, 1993 Wheelock, Inc. All rights reserved.
P81415 N
Sheet 1 of 4
CANDELA AT VARIOUS ANGLES
PER UL 1638
MODEL VOLTAGE RATED
CANDELA A1 A2 A3 A4 A5 A6/A7
18-31VDC (24VDC) 0.84cd 0.84 0.92 0.66 0.87 0.41 0.03
18-31VDC (24VDC) 1.5cd 1.5 1.7 1.2 1.6 0.7 0.1
115VAC 1.5cd 1.5 1.5 1.3 1.3 0.7 0.1
18-31VDC (24VDC) 15.0cd 15.0 18.8 13.7 15.6 7.4 0.9
115VAC 15.0cd 15.0 18.0 14.6 17.7 8.4 0.8
18-31VDC (24VDC) 117.0cd 117.0 15.2 16.4 6.0 7.0 1.2
MOUNTING OPTIONS:
Figure 2. Figure 3.
* Shown With Optional 6" Bell
(See Table For Other Possible Signal Combinations)
P81415 N
Sheet 2 of 4