wheelock MIZ-24S Service Manual

FIRE ALARM SYSTEMS
Description:
Wheelock Series MIZ piezoelectric Mini Horns are compact electronic alarm appliances that are listed under CAN/ULC-525-99 for Audible Signal Appliances. The Series MIZ offer field selectable settings for Temporal (Code 3) or Continuous Horn along with an attractive appearance and dependable performance. The Series MIZ offers high sound output along with low current draw and is ideal for alarm signaling in individual rooms, apartments, hotels, motels and offices. Color choices of red or off-white will blend with any décor .
Applications:
Individual Rooms
Apartments
Hotels
Motels
Offices
Wiring Diagrams (for all models)
FROM PRECEDING APPLIANCE OR FACP
+
-
TO NEXT
+
APPLIANCE
-
OR EOLR
Helping People Take Action
SERIES MIZ MINI HORN
TEMPORAL (CODE 3) OR
CONTINUOUS TONE
SERIES MIZ
Features:
• Approvals include: CAN/ULC-S525-99 for Audible Signal Appliances
• Field selectable settings for Temporal (Code 3) or Continuous Horn.
• Designed to meet or exceed NFP A/ANSI standards.
• Convenient mounting to any standard single-gang box.
• No additional trimplate required for flush mounting
• Fast installation with In/Out screw terminals using #12 to #18 AWG.
• High sound output/low current draw/low temperature compensation.
• A vailable in red or off-white color .
INC.
SM
-
+
Specifications and Ordering Information
ledoM
R-S42-ZIM5848deR-snoitpOnroHsuounitnoCrolaropmeT,nroH-iniMtloV
redrO
edoC
noitpircseD
42B
W-S42-ZIM4848etihW-snoitpOnroHsuounitnoCrolaropmeT,nroH-iniMtloV42B
*Refer to Data Sheet S7000 for Mounting Options.
General Notes:
Mini Horn models are Listed for indoor use with a temperature range of 0º C to 49º C (32º F to 120º F) and maximum humidity of 93% RH ±2%.
Rated Input voltage (either filtered DC or unfiltered full-wave-rectified FWR): 16-33 VDC (for 24 VDC MIZ-TC)
MIZ-TC audible appliances are not designed to be used on coded systems in which the applied voltage is cycled on and off. Not designed to be used with Sync Modules (SM or DSM).
Copyright 2005 Wheelock Inc. All rights reserved.
gnitnuoM *snoitpO
22
Architects and Engineers Specifications
The notification appliance shall be a Wheelock Series MIZ audible appliance or approved equal. The MIZ Notification Appliance shall be electronic and shall have field selectable settings for Temporal (Code 3) or Continuous horn. The sound pressure measurement on Temporal (Code 3) setting shall be 87 dBA minimum at 24VDC. The sound pressure measurement on Continuous Horn setting shall be 87 dBA minimum at 24 VDC. Operating voltage shall be 24 VDC using filtered power or unfiltered power supply (full-wave­rectified). All models shall have provision for standard reverse polarity type supervision and IN/OUT wiring using terminals that accept #12 to #18 AWG wiring. The appliances shall be mounted indoors and mount on standard electrical backboxes requiring no additional trimplates or adapters.
segnaRdnasledoMdetsiLCLU:1elbaT
detaR
detalugeR
ledoM
CLU
egarevA
tnerruC
egatloV
CLU/NAC
suounitnoC3edoC
rePABdciohcenA
tf01@99-525S-
CDSMRABdABd
0.02420.720.4848
S42-ZIM
0.42520.830.7878
0.13620.340.0998
NOTE: All CAUTIONS and W ARNINGS are identified by the symbol . All warnings are printed in bold capit al letters. W ARNING: PLEASE READ THESE SPECIFICA TIONS AND ASSOCIA TED INST ALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION,INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. W ARNING: CONT ACT WHEELOCK FOR THE CURRENT “INSTALLA TION INSTRUCTIONS” (P83963) AND “GENERAL INFORMATION” SHEET (P82380) ON THESE PRODUCTS. THESE DOCUMENTS UNDERGO PERIODIC CHANGES. IT IS IMPORTANT THAT YOU HAVE CURRENT INFORMATION ON THESE PRODUCTS. THESE MATERIALS CONTAIN IMPORTANT INFORMATION THAT SHOULD BE READ PRIOR TO SPECIFYING OR INSTALLING THESE PRODUCTS, INCLUDING:
• TOTAL CURRENT REQUIRED BY ALL APPLIANCES CONNECTED TO SYSTEM SECONDARY POWER SOURCES.
• FUSE RATINGS ON NOTIFICATION APPLIANCE CIRCUITS TO HANDLE PEAK CURRENTS FROM ALL APPLIANCES ON THOSE CIRCUITS.
• THE VOLTAGE APPLIED T O THESE PRODUCTS MUST BE WITHIN THEIR RATED VOL TAGE RANGE.
• FAILURE TO COMPLY WITH THE INSTALLATION INSTRUCTIONS OR GENERAL INFORMATION SHEETS COULD RESULT IN IMPROPER INSTALLATION, APPLICATION, AND/OR OPERA TION OF THESE PRODUCTS IN AN EMERGENCY SITUA TION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
• CONDUCTOR SIZE (AWG), LENGTH AND AMPACITY SHOULD BE TAKEN INTO CONSIDERATION PRIOR TO DESIGN AND INSTALLATION OF THESE PRODUCTS, P ARTICULARLY IN RETROFIT INSTALLA TIONS.
Wheelock products must be used within their published specifications and must be PROPERL Y specified, applied, inst alled, operated, maintained and operationally tested in accordance with their installation instructions at the time of installation and at least twice a year or more often and in accordance with local, state and federal codes, regulations and laws. Specification, application, installation, operation, maintenance and testing must be performed by qualified personnel for proper operation in accordance with all of the latest National Fire Protection Association (NFP A), Underwriters’ Laboratories (UL), National Electrical Code (NEC), Occupational Safety and Health Administration (OSHA), local, state, county , province, district, federal and other applicable building and fire standards, guidelines, regulations, laws and codes including, but not limited to, all appendices and amendments and the requirements of the local authority having jurisdiction (AHJ).
NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions.
WE SUPPORT AND ENCOURAGE NICET CERTIFICATION
MADE IN THE USA
NATIONAL SALES OFFICE
800-631-2148
Canada 800-397-5777
E-Mail: Info@wheelockinc.com
http://www.wheelockinc.com
273 BRANCHPORT AVENUE • LONG BRANCH, NJ 07740 • TEL: 732-222-6880 • FAX: 732-222-2588
23
3 YEAR WARRANTY
Distributed By:
S1700C 05/05
Loading...