GENERAL:
Series MB Motor Bells are UL Listed for Fire Protective Service with the exception of the 6VDC Motor Bell which is UL approved for general signaling use. The Motor Bell Series incorporates a high torque permanent magnet motor to provide high output with minimum current draw. Integral MOV suppression is provided to minimize RFI and turn-off transients. In-out wiring terminals and a built-in trim plate, for semi-flush mounting, are provided for easy installation. The Motor Bell Series is available in 6VDC with a 6" bell shell and 12VDC or 24VDC with either a 6" or 10" bell shell.
NOTE: All CAUTIONS and WARNINGS are identified by the symbol . All warnings are printed in bold capital letters.
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
SPECIFICATIONS:
Table 1: UL Listed Models and Ratings
Model Gong Size
MB-G6-6 6" 4.2-7.8 0.130 0.160 75 82 85 A,B,C,D MB-G6-12 6" 8.0-17.5 0.090 0.110 79 85 88 A,B,C,D MB-G10-12 10" 8.0-17.5 0.090 0.110 82 88 91 A,B,C,D MB-G6-24 6" 16.0-33.0 0.040 0.056 82 85 88 A,B,C,D MB-G10-24 10" 16.0-33.0 0.040 0.056 82 88 91 A,B,C,D
Voltage Range (VDC/VRMS)
Maximum RMS Current Draw Reverberant dBA Per UL 464 Mounting
DC FWR Min Nom Max Options
WARNING: FOR UL APPLICATIONS THESE APPLIANCES WERE TESTED TO THE OPERATING VOLTAGE LIMITS OF 16-33 VOLTS FOR 24V MODELS, 8-17.5V FOR 12V MODELS, OR 4.2-7.8V FOR 6V MODELS USING FILTERED (DC) OR UNFILTERED FULL-WAVE-RECTIFIED (FWR). DO NOT APPLY 80% AND 110% OF THESE VOLTAGE VALUES FOR SYSTEM OPERATION.
WARNING: MAKE SURE THAT THE TOTAL RMS CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES, NAC CIRCUITS, SM, DSM SYNC MODULES OR WHEELOCKS POWER SUPPLIES DO NOT EXCEED THE POWER SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
When calculating the total currents: Use Table 1 to determine the highest value of “RMS Current” for an individual bell (across the expected operating voltage range of the bell), then multiply these values by the total number of bells; be sure to add the currents for any other appliances, including audible signaling appliances, powered by the same source and include any required safety factors.
If the peak current exceeds the power supplies’ peak capacity, the output voltage provided by the power supplies may drop below the listed voltage range of the appliances connected to the supply and the voltage may not recover in some types of power supplies. For example, an auxiliary power supply that lacks filtering at its output stage (either via lack of capacitance and/or lack of battery backup across the output) may exhibit this characteristic.
Copyright 2004 Wheelock, Inc. All rights reserved.
P81960 J
Sheet 1 of 4
WIRING DIAGRAM:
Figure 1:
-
+
FROM PRECEDING SIGNAL OR FIRE ALARM CONTROL PANEL (FACP)
MOUNTING INFORMATION:
Mounting Options Are Shown In The Following Diagrams:
1. Unscrew the center bolt to remove the bell shell. (See Mounting Procedures Note 2 .)
2. Connect wiring as shown in wiring diagram. Note polarity indicated on back cover of housing.
3. Mount housing with screws provided. (Note "TOP" arrow.)
4. Replace bell shell and secure with center bolt. Be sure shell is properly aligned with housing.
Figure 2: Bell Shell Mounting
+
-
+
TO NEXT BELL OR END OF LINE RESISTOR (EOLR)
-
BELL HOUSING
BELL SHELL
GUIDE PIN
CENTER BOLT
ALIGN PIN HOLE WITH GUIDE PIN