Wheelock MB Specification

FIRE ALARM SYSTEMS
Description
Wheelock’s Series MB Motor Bells provide a better engineered
motor bell for fire and life safety alarm systems. The Wheelock Series MB Bells include higher dBA, low current draw, built-in trimplate for semi-flush mounting, low frequency aluminum shells, and low RFI noise. The motor for Series MB Bells is a durable, high torque permanent magnet motor selected for its high performance and long life.
Helping People Take Action
SERIES MB MOTOR BELLS
INC.
SM
These DC vibrating Series MB Motor Bells are offered in 6” and 10” shell sizes in both 12 and 24 VDC models.
Series RSSP Sync/Non-Sync strobe plates are used in conjunction with the Series MB Motor Bell when combination appliances are required. The Series RSSP retrofit plates are available with either Multi-Candela or single candela strobes and easily mount to a 4” square or Wheelock SBL-2 backbox.
The Series RSSP retrofit plates may be synchronized when installed with the Wheelock Series SM, DSM, Sync Modules. Wheelock’s synchronized strobes offer an easy way to comply with recommendations concerning photo-sensitive epilepsy.
Features
Approvals include: CAN/ULC-S525-99
High sound output with low current draw
Low frequency aluminum shells for better audibility through walls, doors and other structures
6” and 10” shell sizes in 12 or 24 VDC models
Integral RFI suppression to minimize included noise on the NAC circuit
Mounting options for surface, semi-flush, outdoor, and concealed conduit installation
Built-in trimplate makes semi-flush mounting simpler and less expensive.
Screw terminals permit fast in-out field wiring of #12 to 18 AWG wire.
Polarized for DC supervision of NAC circuits.
Operates on filtered or unfiltered DC.
For combined audible (bell) and visual signaling, convenient strobe plate assemblies are available with Multi-Candela or Single candela strobes
SERIES MB
RSSP STROBE PLA TE with SBL-2
RSSP STROBE PLA TE
Ordering Information
rebmuNledoMedoCredrOeziSllehS
R-21-6G-BM2493”621250.0 S-21-6G-BM1224”621250.0 R-42-6G-BM1493”642820.0 S-42-6G-BM2224”642820.0
R-21-01G-BM4493”0121250.0 S-21-01G-BM3224”0121250.0 R-42-01G-BM3493”0142820.0 S-42-01G-BM4224”0142820.0
Copyright 2004 Wheelock, Inc. All rights reserved.
egatloVtupnI
)CDV(
tnerruCtupnI.tF01@ABd
29Z,
gnitnuoM
snoitpO
NOTE:
1. Typical dBA at 10 feet
is measured in an
S,R,N,K,J,E,D
anechoic chamber.
30
Architects and Engineers Specifications
The audible signal appliances shall be Wheelock Series MB vibrating Motor Bells or approved equal. They shall be ULC Listed for Fire Protective Service. Shells shall be aluminum in 6” or 10” diameter. Sound output at 10 feet shall be 92 dBA @ 10 feet. The bells shall incorporate a permanent magnet motor and provide the necessary suppression to minimize RFI. They shall include a built-in trimplate for semi-flush mounting to standard 4” square backboxes, or surface mounting to Wheelock’s indoor BB backbox or outdoor WBB backbox.
rebmuNledoMedoCredrO
F-WCM42-PSSR204942011/57/03/51041./901./360./140.Z,E,D
R
egatloVlanimoN
)CDV(
alednaCebortS
tnerruCegarevA*
CDVdetsilta)SPMA(
Note: For more information on the Series RSSP-24MCW-FR, see data sheet S0410C or Installation Instructions P83911.
SELUDOMCNYS
rebmuNledoM
#
R-42/21-MS
##
R-42/21-MSD
redrO
edoC
963642820.W
473642530.W
egatloVtupnI
)CDV(
tnerruCegarevA CDV42@)SPMA(
*Average Current per actual Wheelock Production Testing at listed VDC. For Rated Average and Peak current across ULC regulated voltage range for
gnitnuoM
both Filtered DC and Unfiltered VRMS, see Installation Instructions
**snoitpO
** Refer to Data Sheet S7000 for Mounting Options #SM Sync Module is rated for 3.0 amperes @ 24 VDC. ##DSM Sync Module is rated for 3.0 amperes per circuit. The maximum number of interconnected DSM modules is twenty (20). Refer to Data Sheet S3000C or Installation Instructions P83123 for SM and P83177 for DSM.
Wiring
Fig. 1 Bell Models
+-
FROM
PRECEDING
APPLIANCE
OR FACP
{}
TO NEXT
APPLIANCE
OR END-OF-LINE
RESISTOR
(EOLR )
gnitnuoM**
snoitpO
Wheelock products must be used within their published specification and must be properly specified, applied , installed, operated, maintained and operationally tested in accordance with their installation instruction at the time of installation and at least twice a year or more often and in accordance with local, state, and federal codes, regulations and laws. Specification, application, installation, operation, maintenance and testing must be performed by qualified personnel for proper operation in accordance with all of the latest National Fire Protection Association (NFPA), Underwriters’ Laboratories (UL & ULC), local, state, county, province, district, federal and other applicable building and fire standards, guidelines, regulations, laws and codes including, but not limited to all appendices and amendments an the requirements of local authority having jurisdiction (AHJ).
Due to continuous development of our products, specifications and offering are subject to change without notice in accordance with Wheelock, Inc. standard terms and conditions.
WARNING: PLEASE READ THESE SPECIFICA TIONS AND ASSOCIA TED INST ALLA TION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPL YING THIS PRODUCT . FAILURE T O COMPL Y WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR W ARNINGS COULD RESULT IN IMPROPER APPLICA TION, INST ALLA TION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUA TION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJUR Y OR DEA TH TO YOU AND/OR OTHERS.
WE SUPPORT AND ENCOURAGE NICET CERTIFICATION
31
ASSEMBLED IN THE USA
NATIONAL SALES OFFICE
800-631-2148
Canada 800-397-5777
E-Mail: Info@wheelockinc.com
http://www.wheelockinc.com
273 BRANCHPORT AVENUE LONG BRANCH, NJ 07740 TEL: 732-222-6880 FAX: 732-222-2588
3 YEAR WARRANTY
Distributed By:
S1500C 02/05