wheelock HS4-24185W-FR, HS4-24185W-FW INSTALLATION INSTRUCTIONS

273 Branchport Avenue Long Branch, NJ 07740 Thank you for using our products. (800) 631-2148 www.wheelockinc.com
INSTALLATION INSTRUCTIONS
SERIES HS4 HIGH INTENSITY
FOUR WIRE APPLIANCES
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
GENERAL:
Wheelock’s Series HS4 High Intensity Horn Strobes can provide a non-synchronized strobe appliance when connected directly to a Fire Alarm Control Panel (FACP), or provide a synchronized strobe appliance when used in conjunction with a Sync Module (SM), Dual Sync Module (DSM) or
Wheelock’s Power Supplies. The HS4 allows for independent operation of the strobe circuit and the horn circuit. It is the
ideal choice for retrofit applications as well as new installations. The HS4 Appliances are UL Listed under Standard 1971 for Signaling Devices for the Hearing Impaired and UL Standard 464 for Audible Signal Appliances. It is listed for indoor use only
and
can be mounted to double-gang, 4” backbox, 100mm European backbox or SHBB surface backbox (See Mounting Options). The
strobes use a Xenon flashtube with solid state circuitry enclosed in a rugged Lexan lens to provide maximum visibility and reliability for effective visible signaling.
The horn portion of the HS4 Appliances can be field set to provide either Continuous Horn or Code 3 Horn. They can provide a continuous horn when connected directly to the Fire Alarm Control Panel (FACP), or synchronized code 3 horn when used in conjunction with the Sync Module (SM), Dual Sync Module (DSM) or Wheelock’s Power Supplies. HS4 appliances can be field set to provide either High (HI) dBA, Medium (MED) dBA or Low (LO) dBA sound output. The audible portion of the HS4 appliances can be used on coded systems in which the applied voltage is cycled on and off.
The HS4 is designed for use with either filtered DC or unfiltered Full-Wave-Rectified (FWR) input voltage. All inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP).
: “Lexan” is a registered trademark of General Electric Corporation.
NOTE
: All
NOTE
WARNING: THE STROBE APPLIANCE IS A "FIRE ALARM DEVICE - DO NOT PAINT."
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, CANDELA SETTING, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
SPECIFICATIONS:
CAUTIONS
and
WARNINGS
Model
HS4-24150C 24 16.0-33.0 150 Ceiling A,B,C,D HS4-24185W 24 16.0-33.0 185 Wall A,B,C,D
Model
16.0VDC 0.014 0.018 0.020 0.033 0.035 0.067
24.0VDC 0.017 0.024 0.026 0.052 0.055 0.098
HS4-24185W 33.0VDC 0.021 0.027 0.035 0.068 0.069 0.110
HS4-24150C 16.0VRMS ------ 0.016 ------ 0.028 ------ 0.052
24.0VRMS ------ 0.031 ------ 0.043 ------ 0.075
33.0VRMS ------ 0.041 ------ 0.050 ------ 0.094
Description
Low 80 83 86
Continuous Horn Medium 85 88 91
High 88 91 93 Low 75 79 82
Code 3 Horn Medium 80 84 86
High 84 87 89
are identified by the symbol . All warnings are printed in bold capital letters.
Table 1: Ratings Per UL
Regulated
Voltage
VDC/VRMS
Regulated
Voltage
Voltage Range Limit
Per UL 1971 VDC/VRMS
Table 2: Rated Current Draw with Horn Only
Lo Med Hi
MEAN RMS MEAN RMS MEAN RMS
Table 3: dBA Sound Output for 24VDC Models
Volume
16.0VDC 24VDC 33.0VDC
Strobe
Candela
(cd)
Reverberant Per UL 464
Mounting
Options
P84425 D
Sheet 1 of 7
Copyright 2003 Wheelock, Inc. All rights reserved.
P84425 D
Sheet 2 of 7
NOTE: THE MAXIMUM WIRE IMPEDANCE BETWEEN STROBES SHALL NOT EXCEED 35 OHMS. THE MAXIMUM NUMBER OR STROBES ON A SINGLE NOTIFICATION APPLIANCE CIRCUIT SHALL NOT EXCEED 47.
NOTES
:
1. Regulated Voltage: 24VDC HS4 appliances are UL Listed to operate over a voltage range from 16.0VDC to 33.0VDC using
filtered DC or unfiltered FWR input voltage.
2. Anechoic dBA is measured on-axis in a non-reflective (free field) test room using fast meter response. For peak dBA (measured
with peak meter response), add 5dBA to anechoic values shown in Table 3. Reverberant dBA is a minimum UL rating based on sound power measurements in a reverberant test room.
3. Indoor operating temperature: +32°F to +120°F (0°C to +49°C) @ 85% RH.
4. Strobe flash rate over voltage range: 1.010 –1.045 without sync module, 1.000-1.020 with sync module
WARNING: FOR UL APPLICATIONS THESE APPLIANCES WERE TESTED TO THE OPERATING VOLTAGE LIMITS OF 16-33 VOLTS USING FILTERED (DC) OR UNFILTERED FULL-WAVE-RECTIFIED (FWR). DO NOT APPLY 80% AND 110% OF THESE VOLTAGE VALUES FOR SYSTEM OPERATION.
WARNING: CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY BATTERY AND SUBTRACT THE VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO DETERMINE THE APPPLIED VOLTAGE TO THE STROBES.
Table 4: Current Ratings (AMPS)
Rated Average Current
150cd 185cd
16.0VDC 0.506 0.570
24.0VDC 0.308 0.350
33.0VDC 0.227 0.250
16.0VRMS 0.773 0.865
24.0VRMS 0.469 0.540
33.0VRMS 0.398 0.415 Rated Peak Current *
Voltage 150cd 185cd
16.0VDC 0.768 0.850
24.0VDC 0.648 0.700
33.0VDC 0.800 0.900
16.0VRMS 2.400 2.500
24.0VRMS 1.800 2.100
* The time duration for the peak current is 1 millisecond.
NOTE: Inrush current is less than rated peak current.
33.0VRMS 1.800 2.000
When calculating the total average and peak currents: Use Table 3 to determine the highest value of “Rated Average Current” for an individual strobe (across the expected operating voltage range of the strobe), and use Table 3 to determine the highest value of “Rated Peak Current” of an individual strobe (across the expected voltage range of the strobe), then multiply these values by the total number of strobes; be sure to add the currents for any other appliances, including audible signaling appliances, powered by the same source and include any required safety factors.
If the peak current exceeds the power supplies’ peak/inrush capacity, the output voltage provided by the power supplies may drop below the listed voltage range of the appliances connected to the supply and the voltage may not recover in some types of power supplies. For example, an auxiliary power supply that lacks filtering at its output stage (either via lack of capacitance and/or lack of battery backup across the output) may exhibit this characteristic.
WARNING: MAKE SURE THAT THE TOTAL AVERAGE CURRENT AND TOTAL PEAK CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES, SIGNALING CIRCUITS, SM, DSM SYNC MODULES AND WHEELOCK’S POWER SUPPLIES DO NOT EXCEED THE POWER SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
P84425 D
Sheet 3 of 7
LIGHT DISTRIBUTION PER UL 1971:
Table 5: Horizontal and Vertical Plane
150C 185W
Angle
(in
deg.)
UL
Horizontal
Plane
Typ.
Min.
150C
Vertical
Plane
UL
Min.
Typ. 177C
Horizontal
Plane
UL
Min.
Typ. 150W
Vertical
Plane
UL
Min.
Typ. 177W
0 150.0 212 150.0 214 185.0 237 185.0 242 5 135.0 198 135.0 207 166.5 218 166.5 239
10 135.0 172 135.0 203 166.5 195 166.5 231 15 135.0 168 135.0 200 166.5 195 166.5 228 20 135.0 167 135.0 196 166.5 190 166.5 228 25 135.0 169 135.0 194 166.5 193 166.5 224 30 112.5 162 112.5 187 138.8 183 166.5 218
35 112.5 163 112.5 182 138.8 185 120.3 210 40 112.5 152 112.5 172 138.8 175 85.1 200 45 112.5 134 112.5 160 138.8 155 62.9 184 50 82.5 102 82.5 137 101.8 121 50.0 155 55 67.5 93 67.5 130 83.3 109 40.7 152 60 60.0 93 60.0 109 74.0 103 33.3 123 65 52.5 84 52.5 88 64.8 93 29.6 97 70 52.5 79 52.5 70 64.8 88 27.8 78 75 45.0 72 45.0 65 55.5 82 24.1 70 80 45.0 67 45.0 48 55.5 77 22.2 54 85 37.5 72 37.5 43 46.3 81 22.2 49 90 37.5 55 37.5 38 46.3 64 22.2 49
WARNING: THE HS4 APPLIANCES MUST BE FIELD SET TO THE DESIRED TONE AND dBA SOUND OUTPUT LEVEL BEFORE THEY ARE INSTALLED. THIS IS DONE BY PROPERLY INSERTING JUMPER PLUGS IN ACCORDANCE WITH THESE INSTRUCTIONS. INCORRECT SETTINGS WILL RESULT IN IMPROPER PERFORMANCE, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
SOUND OUTPUT (SPL) SETTINGS:
NOTE: The Code 3 Horn incorporates the temporal pattern (1/2 second on, 1/2 second off, 1/2 second on, 1/2 second off, 1/2 second
on, 1-1/2 off and repeat) specified by ANSI/NFPA for standard emergency evacuation signaling. The Code 3 Horn should be used only for fire evacuation signaling and not for any other purpose.
Figure 1: Showing Location of Jumper Plugs
TOP
P83511 ( )
C1
AH
B
R
J3
+ STR -
R5
J2
J1
C O
H
D
M
E
L
TB1
+ AUD -
3
Factory setting is on Medium dB and Code 3.
J2
J1
C O
H
D
M
E
L
3
P84425 D
Sheet 4 of 7
Figure 2: Jumper Plug Settings for High, Medium, Low dB,
E
Code 3 Horn and Continuous Horn Setting.
J2 J2 J2
J1
C O D E
CONTINUOUS
* HORN SETTING
H M
L
HIGH
HORN
SETTING
H M
L
MEDIUM
HORN
SETTING
H M
L
LOW
HORN
SETTING
J1
C O D E 3 3
CODE 3
HORN
SETTING
(Use needle nose pliers to pull and properly insert the jumper plug.)
No jumper plug is needed for continuous horn setting. However, it is recommended that the jumper plug be retained in the unit for future use (if needed) as shown in Figure 2.
NOTE: The HS4 must be set for Code 3 horn when used with the sync module. Refer to Sync Module Installation Instruction sheets SM (P83123), DSM (P83177) and Wheelock’s Power Supplies for additional information. If the HS4 audible is connected to a coded system in accordance with Fig 3 the continuous horn setting must be used.
WIRING INFORMATION:
Figure 3: Audible signal and strobe operate independently.
FROM FIRE ALARM
CONTROL PANEL (FACP),
PRECEDING APPLIANCE
OR SYNC MODULE
TO NEXT APPLIANCE
OR END OF LINE
RESISTOR (EOLR).
+ STR -
+
-
+
-
TB1
Figure 3A: Audible signal and strobe operate in unison. Red and black shunt wires are supplied.
TB1
CAUTION:
PRECEDING APPLIANCE
S
trobes are not designed to be used on coded systems in which the applied voltage is cycled on and off. The
FROM FACP,
OR SYNC MODULE
RED SHUNT WIRE
+ STR -
+
-
installation shown in figure 3A is NOT compatible with a coded system.
Figure 5.
1) HS4 Appliances have in-out wiring terminals that accepts two #12 to #18 American Wire Gauge (AWG) wires at each screw terminal. Strip leads 3/8” inches for connection to screw terminals.
2) Break all in-out wire runs on supervised circuit supervision as shown in Figure 5. The polarity shown in the wiring diagrams is for the operation of the appliances. The polarity is reversed by the FACP during supervision.
+ AUD -
+ AUD -
BLACK SHUNT WIRE
FROM FACP OR
-
PRECEDING APPLIANC
+
TO NEXT APPLIANCE
-
+
OR EOLR.
TO NEXT APPLIANCE
-
+
OR EOLR
P84425 D
Sheet 5 of 7
MOUNTING OPTIONS:
CAUTION: The following figures show the maximum number of field wires (conductors) that can enter the backbox used with
each mounting option. If these limits are exceeded, there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could damage the product.
Although the limits shown for each mounting option comply with the National Electrical Code (NEC), Wheelock recommends use of the largest backbox option shown and the use of approved stranded field wires, whenever possible, to provide additional wiring room for easy installation and minimum stress on the product from wiring.
Figure A
FLUSH (4" BOX)
4" SQ. X 2-1/8" DEEP BACKBOX
(2) #8-32x1"
SCREWS
(4) SCREW COVERS
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG #12
8 488
Figure C
SURFACE MOUNTING
BACKBOX (IOB)
Figure B
FLUSH (2-GANG BOX)
2-GANG x 3-1/2" DEEP BACKBOX
(4) #6-32x1"
SCREWS
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG #12
8 888
Figure D
CONCEALED CONDUIT MOUNTIN G
BACKBOX (IOB)
(4) SCREW COVERS
EXISTING BOX IN WALL
(2) WOOD
SCREWS
MOUNTING PROCEDURES:
(4) #8-18x1"
SCREWS
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG #12
8 888
(4) SCREW COVERS
MAXIMUM NUMBER OF CONDUCTORS AWG #18 AWG #16 AWG #14 AWG #12
8 888
(4) #8-18x1"
(4) SCREW COVERS
SCREWS
Use this mounting procedure to position the field wires in the backbox so that they use minimum space and produce minimum stress on the product. This is especially important for stiff, heavy gauge wires and wires with thick insulation or sheathing.
1. Connect field wires to the HS4 terminal block (polarity must be observed).
2. Bend the field wires up 90° at the connection to the terminal block.
3. Carefully push the field wires into the backbox by hand.
4. Carefully press the HS4 to the backbox, verifying that the HS4 is seated and aligned correctly.
5. Screw the HS4 to the backbox using the screws supplied. Refer to Mounting Options for screw size.
MOUNTING NOTES:
CAUTION: Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and
conduit, especially if sheathed multiconductor cable or 3/4" conduit fittings are used.
1. Conduit entrances to the backbox should be selected to provide sufficient wiring clearance for the installed product.
2. When terminating field wires, do not use more lead length than required. Excess lead length could result in insufficient wiring space for the signaling appliance.
3. Do not pass additional wires (used for other than the signaling appliance) through the backbox. Such additional wires could result in insufficient wiring space for the signaling appliance.
P84425 D
Sheet 6 of 7
CAUTION: If these appliances are operated within 15 inches of a person's ear, they can produce a sound pressure level that exceeds the maximum 120dBA permitted by ADA and OSHA rules. Exposure to such sound levels can result in damage to a person's hearing.
These appliances can produce a distinctive three pulse Temporal Pattern Fire Alarm Evacuation Signal (for total evacuation) in accordance with NFPA 72, 1999 Edition.
WARNING: WHEN INSTALLING STROBES IN AN OPEN OFFICE OR OTHER AREAS CONTAINING PARTITIONS OR OTHER VIEWING OBSTRUCTIONS, SPECIAL ATTENTION SHOULD BE GIVEN TO THE LOCATION OF THE STROBES SO THAT THEIR OPERATING EFFECT CAN BE SEEN BY ALL INTENDED VIEWERS, WITH THE INTENSITY, NUMBER, AND TYPE OF STROBES BEING SUFFICIENT TO MAKE SURE THAT THE INTENDED VIEWER IS ALERTED BY PROPER ILLUMINATION, REGARDLESS OF THE VIEWER'S ORIENTATION. FAILURE TO DO SO COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
HS4 high intensity strobe models are Listed for use in sleeping or non-sleeping areas when installed in accordance with appropriate NFPA Standards and the Authority Having Jurisdiction.
WARNING: A SMALL POSSIBILITY EXISTS THAT THE USE OF MULTIPLE STROBES WITHIN A PERSON'S FIELD OF VIEW, UNDER CERTAIN CIRCUMSTANCES, MIGHT INDUCE A PHOTO-SENSITIVE RESPONSE IN PERSONS WITH EPILEPSY. STROBE REFLECTIONS IN A GLASS OR MIRRORED SURFACE MIGHT ALSO INDUCE SUCH A RESPONSE. TO MINIMIZE THIS POSSIBLE HAZARD, WHEELOCK STRONGLY RECOMMENDS THAT THE STROBES INSTALLED SHOULD NOT PRESENT A COMPOSITE FLASH RATE IN THE FIELD OF VIEW WHICH EXCEEDS FIVE (5) Hz AT THE OPERATING VOLTAGE OF THE STROBES. WHEELOCK ALSO STRONGLY RECOMMENDS THAT THE INTENSITY AND COMPOSITE FLASH RATE OF INSTALLED STROBES COMPLY WITH LEVELS ESTABLISHED BY APPLICABLE LAWS, STANDARDS, REGULATIONS, CODES AND GUIDELINES.
NOTE: NFPA 72/ANSI 117.1 conform to ADAAG Equivalent Facilitation Guidelines in using fewer, higher intensity strobes within
the same protected area.
CAUTION: Check the installation instructions of the manufacturers of other equipment used in the system for any guidelines or restrictions on wiring and/or locating Notification Appliance Circuits (NAC) and notification appliances. Some system communication circuits and/or audio circuits, for example, may require special precautions to assure electrical noise immunity (e.g. audio crosstalk).
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital appliance, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
1) Reorient or relocate the receiving antenna, 2) Increase the separation between the equipment and receiver, 3) Connect the equipment into an outlet on a circuit different from that to which the receiver is connected, and 4) Consult the dealer or an experienced radio/TV technician for help.
The Series HS4 products and these instructions are copyrighted by Wheelock and the Series HS4 products contain proprietary, confidential and trade secrets of Wheelock. No part of the Series HS4 products and these instructions may be photocopied, printed or reproduced in any form or modified, adapted, changed or enhanced, or converted to another programming language, or used to create updated, related or derivative works, without the prior written consent of Wheelock. No part of the Series HS4 products shall be decomposed, disassembled or reverse engineered.
ANY MATERIAL EXTRAPOLATED FROM THIS DOCUMENT OR FROM WHEELOCK MANUALS OR OTHER DOCUMENTS DESCRIBING THE PRODUCT FOR USE IN PROMOTIONAL OR ADVERTISING CLAIMS, OR FOR ANY OTHER USE, INCLUDING DESCRIPTION OF THE PRODUCT'S APPLICATION, OPERATION, INSTALLATION AND TESTING IS USED AT THE SOLE RISK OF THE USER AND WHEELOCK WILL NOT HAVE ANY LIABILITY FOR SUCH USE.
P84425 D
Sheet 7 of 7
IMPORTANT: READ SEPARATE "GENERAL INFORMATION" SHEET FOR INFORMATION ON THE PLACEMENT, LIMITATIONS, INSTALLATION, FINAL CHECKOUT, AND PERIODIC TESTING OF NOTIFICATION APPLIANCES.
P84425 D
Sheet 8 of 7
Limited Warranty
Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated, maintained and operationally tested in accordance with these instructions at the time of installation and at least twice a year or more often and in accordance with local, state and federal codes, regulations and laws. Specification, application, installation, operation, maintenance and testing must be performed by qualified personnel for proper operation in accordance with all of the latest National Fire Protection Association (NFPA), Underwriters' Laboratories (UL), National Electrical Code (NEC), Occupational Safety and Health Administration (OSHA), local, state, county, province, district, federal and other applicable building and fire standards, guidelines, regulations, laws and codes including, but not limited to, all appendices and amendments and the requirements of the local authority having jurisdiction (AHJ). Wheelock products when properly specified, applied, installed, operated, maintained and operationally tested as provided above are warranted against mechanical and electrical defects for a period of three years from date of manufacture (as determined by date code). Correction of defects by repair or replacement shall be at Wheelock's sole discretion and shall constitute fulfillment of all obligations under this warranty. THE FOREGOING LIMITED WARRANTY SHALL IMMEDIATELY TERMINATE IN THE EVENT ANY PART NOT FURNISHED BY WHEELOCK IS INSTALLED IN THE PRODUCT. THE FOREGOING LIMITED WARRANTY SPECIFICALLY EXCLUDES ANY SOFTWARE REQUIRED FOR THE OPERATION OF OR INCLUDED IN A PRODUCT. WHEELOCK MAKES NO REPRESENTATION OR WARRANTY OF ANY OTHER KIND, EXPRESS, IMPLIED OR STATUTORY WHETHER AS TO MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE OR ANY OTHER MATTER.
USERS ARE SOLELY RESPONSIBLE FOR DETERMINING WHETHER A PRODUCT IS SUITABLE FOR THE USER'S PURPOSES, OR WHETHER IT WILL ACHIEVE THE USER'S INTENDED RESULTS. THERE IS NO WARRANTY AGAINST DAMAGE RESULTING FROM MISAPPLICATION, IMPROPER SPECIFICATION, ABUSE, ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND WHEELOCK'S CONTROL.
SOME WHEELOCK PRODUCTS CONTAIN SOFTWARE. WITH RESPECT TO THOSE PRODUCTS, WHEELOCK DOES NOT WARRANTY THAT THE OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR-FREE OR THAT THE SOFTWARE WILL MEET ANY OTHER STANDARD OF PERFORMANCE, OR THAT THE FUNCTIONS OR PERFORMANCE OF THE SOFTWARE WILL MEET THE USER'S REQUIREMENTS. WHEELOCK SHALL NOT BE LIABLE FOR ANY DELAYS, BREAKDOWNS, INTERRUPTIONS, LOSS, DESTRUCTION, ALTERATION, OR OTHER PROBLEMS IN THE USE OF A PRODUCT ARISING OUT OF OR CAUSED BY THE SOFTWARE.
THE LIABILITY OF WHEELOCK ARISING OUT OF THE SUPPLYING OF A PRODUCT, OR ITS USE, WHETHER ON WARRANTIES, NEGLIGENCE, OR OTHERWISE, SHALL NOT IN ANY CASE EXCEED THE COST OF CORRECTING DEFECTS AS STATED IN THE LIMITED WARRANTY AND UPON EXPIRATION OF THE WARRANTY PERIOD ALL SUCH LIABILITY SHALL TERMINATE. WHEELOCK IS NOT LIABLE FOR LABOR COSTS INCURRED IN REMOVAL, REINSTALLATION OR REPAIR OF THE PRODUCT BY ANYONE OTHER THAN WHEELOCK OR FOR DAMAGE OF ANY TYPE WHATSOEVER, INCLUDING BUT NOT LIMITED TO, LOSS OF PROFIT OR INCIDENTAL OR CONSEQUENTIAL DAMAGES. THE FOREGOING SHALL CONSTITUTE THE SOLE REMEDY OF THE PURCHASER AND THE EXCLUSIVE LIABILITY OF WHEELOCK.
IN NO CASE WILL WHEELOCK'S LIABILITY EXCEED THE PURCHASE PRICE PAID FOR A PRODUCT.
Limitation of Liability
WHEELOCK'S LIABILITY ON ANY CLAIM OF ANY KIND, INCLUDING NEGLIGENCE AND BREACH OF WARRANTY, FOR ANY LOSS OR DAMAGE RESULTING FROM, ARISING OUT OF, OR CONNECTED WITH THIS CONTRACT, OR FROM THE MANUFACTURE, SALE, DELIVERY, RESALE, REPAIR OR USE OF ANY PRODUCT COVERED BY THIS ORDER SHALL BE LIMITED TO THE PRICE APPLICABLE TO THE PRODUCT OR PART THEREOF WHICH GIVES RISE TO THE CLAIM. WHEELOCK'S LIABILITY ON ANY CLAIM OF ANY KIND SHALL CEASE IMMEDIATELY UPON THE INSTALLATION IN THE PRODUCT OF ANY PART NOT FURNISHED BY WHEELOCK. IN NO EVENT SHALL WHEELOCK BE LIABLE FOR ANY CLAIM OF ANY KIND UNLESS IT IS PROVEN THAT OUR PRODUCT WAS A DIRECT CAUSE OF SUCH CLAIM. FURTHER, IN NO EVENT, INCLUDING IN THE CASE OF A CLAIM OF NEGLIGENCE, SHALL WHEELOCK BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES. SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE PRECEDING LIMITATION MAY NOT APPLY TO ALL PURCHASERS.
9/03
P84425 D
Sheet 9 of 7
Loading...