wheelock HS4-24185W-FR, HS4-24185W-FW INSTALLATION INSTRUCTIONS

273 Branchport Avenue Long Branch, NJ 07740 Thank you for using our products. (800) 631-2148 www.wheelockinc.com
INSTALLATION INSTRUCTIONS
SERIES HS4 HIGH INTENSITY
FOUR WIRE APPLIANCES
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
GENERAL:
Wheelock’s Series HS4 High Intensity Horn Strobes can provide a non-synchronized strobe appliance when connected directly to a Fire Alarm Control Panel (FACP), or provide a synchronized strobe appliance when used in conjunction with a Sync Module (SM), Dual Sync Module (DSM) or
Wheelock’s Power Supplies. The HS4 allows for independent operation of the strobe circuit and the horn circuit. It is the
ideal choice for retrofit applications as well as new installations. The HS4 Appliances are UL Listed under Standard 1971 for Signaling Devices for the Hearing Impaired and UL Standard 464 for Audible Signal Appliances. It is listed for indoor use only
and
can be mounted to double-gang, 4” backbox, 100mm European backbox or SHBB surface backbox (See Mounting Options). The
strobes use a Xenon flashtube with solid state circuitry enclosed in a rugged Lexan lens to provide maximum visibility and reliability for effective visible signaling.
The horn portion of the HS4 Appliances can be field set to provide either Continuous Horn or Code 3 Horn. They can provide a continuous horn when connected directly to the Fire Alarm Control Panel (FACP), or synchronized code 3 horn when used in conjunction with the Sync Module (SM), Dual Sync Module (DSM) or Wheelock’s Power Supplies. HS4 appliances can be field set to provide either High (HI) dBA, Medium (MED) dBA or Low (LO) dBA sound output. The audible portion of the HS4 appliances can be used on coded systems in which the applied voltage is cycled on and off.
The HS4 is designed for use with either filtered DC or unfiltered Full-Wave-Rectified (FWR) input voltage. All inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP).
: “Lexan” is a registered trademark of General Electric Corporation.
NOTE
: All
NOTE
WARNING: THE STROBE APPLIANCE IS A "FIRE ALARM DEVICE - DO NOT PAINT."
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, CANDELA SETTING, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
SPECIFICATIONS:
CAUTIONS
and
WARNINGS
Model
HS4-24150C 24 16.0-33.0 150 Ceiling A,B,C,D HS4-24185W 24 16.0-33.0 185 Wall A,B,C,D
Model
16.0VDC 0.014 0.018 0.020 0.033 0.035 0.067
24.0VDC 0.017 0.024 0.026 0.052 0.055 0.098
HS4-24185W 33.0VDC 0.021 0.027 0.035 0.068 0.069 0.110
HS4-24150C 16.0VRMS ------ 0.016 ------ 0.028 ------ 0.052
24.0VRMS ------ 0.031 ------ 0.043 ------ 0.075
33.0VRMS ------ 0.041 ------ 0.050 ------ 0.094
Description
Low 80 83 86
Continuous Horn Medium 85 88 91
High 88 91 93 Low 75 79 82
Code 3 Horn Medium 80 84 86
High 84 87 89
are identified by the symbol . All warnings are printed in bold capital letters.
Table 1: Ratings Per UL
Regulated
Voltage
VDC/VRMS
Regulated
Voltage
Voltage Range Limit
Per UL 1971 VDC/VRMS
Table 2: Rated Current Draw with Horn Only
Lo Med Hi
MEAN RMS MEAN RMS MEAN RMS
Table 3: dBA Sound Output for 24VDC Models
Volume
16.0VDC 24VDC 33.0VDC
Strobe
Candela
(cd)
Reverberant Per UL 464
Mounting
Options
P84425 D
Sheet 1 of 7
Copyright 2003 Wheelock, Inc. All rights reserved.
P84425 D
Sheet 2 of 7
NOTE: THE MAXIMUM WIRE IMPEDANCE BETWEEN STROBES SHALL NOT EXCEED 35 OHMS. THE MAXIMUM NUMBER OR STROBES ON A SINGLE NOTIFICATION APPLIANCE CIRCUIT SHALL NOT EXCEED 47.
NOTES
:
1. Regulated Voltage: 24VDC HS4 appliances are UL Listed to operate over a voltage range from 16.0VDC to 33.0VDC using
filtered DC or unfiltered FWR input voltage.
2. Anechoic dBA is measured on-axis in a non-reflective (free field) test room using fast meter response. For peak dBA (measured
with peak meter response), add 5dBA to anechoic values shown in Table 3. Reverberant dBA is a minimum UL rating based on sound power measurements in a reverberant test room.
3. Indoor operating temperature: +32°F to +120°F (0°C to +49°C) @ 85% RH.
4. Strobe flash rate over voltage range: 1.010 –1.045 without sync module, 1.000-1.020 with sync module
WARNING: FOR UL APPLICATIONS THESE APPLIANCES WERE TESTED TO THE OPERATING VOLTAGE LIMITS OF 16-33 VOLTS USING FILTERED (DC) OR UNFILTERED FULL-WAVE-RECTIFIED (FWR). DO NOT APPLY 80% AND 110% OF THESE VOLTAGE VALUES FOR SYSTEM OPERATION.
WARNING: CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY BATTERY AND SUBTRACT THE VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO DETERMINE THE APPPLIED VOLTAGE TO THE STROBES.
Table 4: Current Ratings (AMPS)
Rated Average Current
150cd 185cd
16.0VDC 0.506 0.570
24.0VDC 0.308 0.350
33.0VDC 0.227 0.250
16.0VRMS 0.773 0.865
24.0VRMS 0.469 0.540
33.0VRMS 0.398 0.415 Rated Peak Current *
Voltage 150cd 185cd
16.0VDC 0.768 0.850
24.0VDC 0.648 0.700
33.0VDC 0.800 0.900
16.0VRMS 2.400 2.500
24.0VRMS 1.800 2.100
* The time duration for the peak current is 1 millisecond.
NOTE: Inrush current is less than rated peak current.
33.0VRMS 1.800 2.000
When calculating the total average and peak currents: Use Table 3 to determine the highest value of “Rated Average Current” for an individual strobe (across the expected operating voltage range of the strobe), and use Table 3 to determine the highest value of “Rated Peak Current” of an individual strobe (across the expected voltage range of the strobe), then multiply these values by the total number of strobes; be sure to add the currents for any other appliances, including audible signaling appliances, powered by the same source and include any required safety factors.
If the peak current exceeds the power supplies’ peak/inrush capacity, the output voltage provided by the power supplies may drop below the listed voltage range of the appliances connected to the supply and the voltage may not recover in some types of power supplies. For example, an auxiliary power supply that lacks filtering at its output stage (either via lack of capacitance and/or lack of battery backup across the output) may exhibit this characteristic.
WARNING: MAKE SURE THAT THE TOTAL AVERAGE CURRENT AND TOTAL PEAK CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES, SIGNALING CIRCUITS, SM, DSM SYNC MODULES AND WHEELOCK’S POWER SUPPLIES DO NOT EXCEED THE POWER SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
P84425 D
Sheet 3 of 7
Loading...
+ 6 hidden pages