Wheelock’s Weatherproof Low Profile Speaker
Strobe, Series ET70WP appliances for wall and ceiling
mounting have an extended temperature range of
°
-31
F to 150°F (-35°C to 66°C) that will satisfy virtually
all outdoor and severe environment applications.
ACTION MESSAGE S
ADA
SYSTEMS
U
L
COMMUNICATIONS
®
HelpingPeopleTakeAction
SERIES ET70WP
WEATHERPROOF SPEAKER
STROBE
INC.
SM
The Wheelock Weatherproof Speaker Strobe is
designed for maximum performance, reliability, and
cost effectiveness while meeting or exceeding the
latest requirements of NFPA 72 (National Fire Alarm Code), UL Standard 1638 (Standard for Visual Signaling
Appliances), and UL Standard 1480 (Standard for
Speaker Appliances).
The strobe has a 75 candela intensity on axis at -31°F
(-35°C) and 180cd at 77°F (25°C) with low current
draw. For outdoor applications the ET70WP–2475WFR must be wall mounted to a Weatherproof Back Box
(IOB). The speakers are designed for multiple power
requirements with high dBA output at each power tap.
The low profi le model offers a choice of fi eld selectable
taps, 1/8W to 8W for either 25.0 VRMS or 70.0 VRMS
audio systems. The low profi le design incorporates
a high efficiency speaker for maximum output at
minimum power across a frequency range of 400 Hz
to 4000 Hz and features a sealed back construction
for extra protection and improved audibility. The low
profi le speaker strobes can provide non-synchronized
operation when directly connected to the Fire Alarm
Control Panel, or synchronized strobe operation when
used in conjunction with a Wheelock Sync Module
(SM), Dual Sync Module (DSM), or Wheelock Power
Supplies (PS-12/24-8CP and PS-12/24-8MP) with builtin patented sync protocol. The strobes use a Xenon
fl ashtube with solid state circuitry enclosed in a rugged
Lexan lens to provide maximum visibility and reliability
for effective visible signaling.
SERIES ET70WP
Mounted to IOB-R
FEATURES
• Approvals include: UL Standard 1638, UL Standard
1480, California State Fire Marshal (CSFM), and
New York City (MEA) Pending: Factory Mutual (FM)
and Chicago (BFP)
• Designed to meet or exceed NFPA/UFC/ANSI 117.1/
OSHA Part 29, 1910.165, and ADA requirements.
• UL Standard 1638 and UL Standard 464 listed
with extended temperature range of -31°F
to 150°F (-35°C to 66°C)
• 24 VDC with new UL “Regulated” Voltage Range: 16-33 VDC using fi ltered DC or unfi ltered FWR voltage
• Sync/Non-Sync strobe. Synchronize strobe with
Series SM, DSM Sync Modules or PS-12/24-8CP and PS-12/24-8MP Power Supplies with built-in patented sync protocol
• IN and OUT wiring termination that accepts two #12-18 AWG wires at each terminal
• Inputs are polarized for compatibility with industry standard reverse polarity supervison
Copyright 2004 Wheelock, Inc. All rights reserved.
Page 2
NOTE: All CAUTIONS and WARNINGS are identifi ed by the symbol All WARNINGS are printed in bold capital letters.
WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY
BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTUCTIONS,
CAUTIONS, OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION, AND/OR OPERATION OF THESE
PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR
DEATH TO YOU AND/OR OTHERS.
General Notes:
• Wheelock UL 1638 Strobes are designed to produce 30-62 fl ashes per minute over the Regulated Voltage Range. If used in an indoor application,
UL 1638 strobes must be operated at a minimum of 20 VDC to meet the NFPA-72 (1999) fl ash rate of 1 to 2 fl ashes pers second and ADA Guideline
fl ash rate of 1 to 3 fl ashes per second.
•Wheelock Weatherproof Appliances are designed to operate over an extended temperature range of -31°F to 150°F (-35°C to 66°C) and all candela
ratings represent minimum effective strobe intensity based on UL 1638. Maximum humidity of 93% RH ± 2%.
•“Regulated Voltage Range” is the newest terminology used by UL to identify the voltage range. Prior to this change, UL used the
terminology “Listed Voltage Range”.
Table 1: ULListed Model and Rating - Speaker
Model
Reverberant dBA @ 10 feet (UL 1480) Rated
Watts
Voltage
(VRMS)
1/81/41/212481/81/41/21248
Anechoic dBA @ 10 feet @ 1 kHz
Rated Watts
ET70WP-2475W25/707780838688919378818487909295
ET70WP-2475C25/707780838688919378818487909295
* RMS current ratings are per UL average RMS
Table 2: ULListed Model and Candela Strobe Rating
Rated Strobe Candela (cd)
Voltage*Rated Average Current
24.0 VDC0.094
@ 77°F (25°C)@ -31°F (-35°C)
180cd75cd
UL Max*0.138
method. UL max current rating is the maximum
RMS current within the listed voltage range
(16-33v for 24v units). For strobes the UL max
current is usually at the minimum listed voltage
(16v for 24v units). For audibles the max current
is usually at the maximum listed voltage (33v
for 24v units). For unfi ltered FWR ratings, see
installation instructions.
SERIES ETWP SPEAKER & STROBE OPERATE
INDEPENDENTLY (NON-SYNC OR SYNC)
FROM
PRECEDING
APPLIANCE
OR VOICE
EVACUATION
PANEL
FROM
PRECEDING
STROBE,
SYNC MODULE,
POWER SUPPLY
OR FACP
+
-
++
-
-
+
STROBE
+
-
SPEAKER
+
-
-
TO NEXT
APPLIANCE
OR EOLR
TO NEXT
STROBE OR
EOLR
SERIES ETWP SPEAKER STROBE APPLIANCES
SYNCHRONIZED W/DSM MODULE SINGLE
CLASS “A”
STROBE
NAC
CIRCUIT
OUT
FACP
STROBE
NAC
CIRCUIT
RETURN
DSM
SYNC
+OUT 1
+ IN 1
MINUS 1
+
-
MINUS 2
+ IN 2
+ OUT 2
+
-
ETETET
AUDIBLE
ETETET
SERIES ETWP SPEAKER STROBES SYNCHRONIZED
W/MULTIPLE DSM MODULES
DSM #1
Strobe NAC Cir.
F
A
Strobe NAC Cir.
C
P
Strobe NAC Cir.
DSM Interconnecting wiring shown. Maximum of
Sync
+
-
DSM #2
Sync
+
-
DSM #3
Sync
+
-
twenty (20)
ETET
ETET
ETET
SERIES ETWP SPEAKER STROBE APPLIANCES &
RSS STROBES SYNCHRONIZED W/PS-12/24-8CP and
PS-12/24-8MP
Series PS-12/24-8MP
C
F
A
OUTPUTS
1-4
4-CLASS
"B"
OR
2-CLASS
"A"
ET
ET
RSS
RSS
EOLR
P
ET
Series PS-12/24-8MP
RSS
Page 3
WARNING: CONTACT WHEELOCK FOR THE CURRENT “INSTALLATION INSTRUCTIONS” SHEET P84149 AND
“GENERAL INFORMATION” SHEET (P82380) ON THIS PRODUCTS. THESE DOCUMENTS UNDERGO PERIODIC
CHANGES. IT IS IMPORTANT THAT YOU HAVE CURRENT INFORMATION ON THESE
PRODUCTS. THESE MATERIALS CONTAIN IMPORTANT INFORMATION THAT SHOULD BE READ PRIOR
TO SPECIFYING OR INSTALLING THESE PRODUCTS, INCLUDING:
• TOTAL CURRENT REQUIRED BY ALL APPLIANCES CONNECTED TO SYSTEM SECONDARY POWER
SOURCES.
•FUSE RATINGS ON NOTIFICATION APPLIANCE CIRCUITS TO HANDLE PEAK CURRENTS FROM ALL
APPLIANCES ON THOSE CIRCUITS.
• ADDING, REPLACING OR CHANGING APPLIANCES WILL EFFECT CURRENT DRAW. RECALCULATE
CURRENT DRAW TO INSURE THAT THE TOTAL AVERAGE CURRENT AND TOTAL PEAK REQUIRED BY
ALL APPLIANCES DO NOT EXCEED THE RATED CAPACITY OF THE POWER SOURCE OR FUSES
• COMPOSITE FLASH RATE FROM MULTIPLE STROBES WITHIN A PERSON’S FIELD OF VIEW.
• THE VOLTAGE APPLIED TO THESE PRODUCTS MUST BE WITHIN THEIR “REGULATED VOLTAGE
RANGE”.
•USE STROBES ONLY ON CIRCUITS WITH CONTINUOUSLY APPLIED OPERATING VOLTAGE. DO NOT USE STROBES ON CODED OR INTERRUPTED CIRCUITS IN WHICH THE APPLIED VOLTAGE IS CYCLED ON AND OFF AS THE STROBE MAY NOT FLASH.
• FAILURE TO COMPLY WITH THE INSTALLATION INSTRUCTIONS OR GENERAL INFORMATION
SHEETS COULD RESULT IN IMPROPER INSTALLATION, APPLICATION, AND/OR OPERATION OF THESE
PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND
SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
•CONDUCTOR SIZE (AWG), LENGTH AND AMPACITY SHOULD BE TAKEN INTO CONSIDERATION PRIOR TO DESIGN AND INSTALLATION OF THESE PRODUCTS, PARTICULARLY IN RETROFIT
INSTALLATIONS.
SPECIFICATIONS AND ORDERING INFORMATION
Model
Speaker/Strobe
ET70WP-2475W-FR9077YesYes75cd*180cd77-9324M
ET70WP-2475C-FR4452YesYes75cd*180cd77-9324M
ET70WP-2475C-FW4454YesYes75cd*180cd77-9324M
Back BoxesU
IOB-R5046
Sync Modules and Power Supply
SM-12/24-R6369 NoYesN/AN/AN/A
DSM-12/24-R6374NoYesN/AN/AN/A
PS-12/24-8MP3046YesYesN/AN/AN/A
PS-12/24-8CP3047YesYesN/AN/AN/A
Order
Code
NonSync
SE WITH
ET70WP-2475W-FR
Sync w/ SM, DSM
or PS-12/24-8MP
N/AN/AN/AN/AN/A
Strobe cd
@ -31°F
(-35°C)
Strobe cd
@ 77°F
(25°C)
dBA
Input
Voltage
12 or 24
VDC
12 or 24
VDC
120/220
VAC
120/220
VAC
Outdoor
Mounting
Options*
W
W
N/A
N/A
*Per UL 1638 @ 78°F (75cd @ -31°F).
N/A = Not applicable
Page 4
ARCHITECTS AND ENGINEERS SPECIFICATIONS
WEATHERPROOF SERIES ET70WP
The Weatherproof Low Profi le Speaker Strobe shall be Wheelock Series ET70WP for wall and ceiling applications or
approved equal. The Series ET70WP shall meet and be listed for UL Standard 1638 (Standard for Visual Signaling
Appliances) for Indoor/Outdoor use, Fire Protective Service and UL Standard 1480 (Standard for Speaker Appliances.
The strobe portion of the ET70WP shall produce a fl ash rate of 30-62 fl ashes per minute over the Regulated Voltage
Range of 16 to 33 VDC and shall incorporate a Xenon fl ashtube enclosed in a rugged Lexan lens to provide maximum
visibility and reliability for effective visible signaling. The strobe shall be rated 180cd @ 77°F (25°C) and 75cd at -31°F
(-35°C) and shall operate over an extended temperature range at -31°F to 150°F (-35°C to 66°C) and be listed for
maximum humidity at 95% RH. For outdoor applications the ET70WP shall be wall mounted to a weatherproof back
box (IOB). The speakers shall be designed for multiple power requirements with a high dBA output at each power tap.
The low profi le model shall offer a choice of fi eld selectable taps, 1/8W to 8W for either 25.0 VRMS or 70.0 VRMS
audio systems. The low profi le design shall incorporate a high effi ciency speaker for maximum output at minimum
power across a frequency range of 400Hz to 4000Hz and features a sealed back construction for extra protection
and improved audibility. When synchronization of the strobe is required, the strobe portion of the appliance shall be
compatible with Wheelock’s SM, DSM sync modules or Wheelock’s PS-12/24-8CP and PS-12/24-8MP Power Supplies
with built-in Patented Sync Protocol. If the sync module or syncprotocol in the Power Supply shall fail to operate (i.e.,
contacts remain closed), the strobe shall revert to a non-synchronized fl ash rate.
Due to continuous development of our products, specifi cations and offerings are subject to change without notice in accordance
with Wheelock Inc. standard terms and conditions.