West Penn 971BK0500, 971BK1000, 971OR0500, 971OR1000, 971RD0500 Specsheet

...
Technical Data Sheet Fire Alarm Cables
PART NUMBER:
DESCRIPTION: 16/2 Solid bare copper conductors, unshielded with an overall jacket.
NEC RATING: FPL, NEC Article 760
APPLICATION: Indoor for: Power –Limited Fire Protective Circuits
2833 West Chestnut Street
Washington, PA 15301
Toll Free: (800) 245-4964
Fax: (724) 222-6420
www.westpenn-wpw.com
971
Construction Parameters:
Conductor 16 AWG Bare Copper Stranding Solid Insulation Material PVC Insulation Thickness 0.032” Nom. Number of Conductors 2 Shield None Drain None Jacket Material PVC Jacket Thickness 0.115''x.225” Nom. Overall Cable Diameter '' Nom. Approximate Cable Weight 26 Lbs/1M' Nom. Flame Rating NFPA- 262 Flame Test
Electrical & Environmental Properties:
Temperature Rating -10deg C to 60deg C Operating Voltage 300 V RMS Max.Capacitance Between Conductors @ 1 KHz pf/ft Nom. DC Resistance per Conductor @ 20deg C 4.1 Ohms/1M' Nom. Insulation Colors Red, Black Jacket Color Red RoHS Compliant --
Mechanical Properties:
Max. Recommended Pull Tension Min. Bend Radius (Install) 2.25”
Specification Issue Date: 7/06
This document is the property of West Penn Wire.
.
The information contained herein is considered Proprietary and not to be reproduced by any means Without written consent of West Penn Wire
Standard Lengths are 1000ft. The Jacket is sequentially footmarked. The information presented here is, to the best of our knowledge, is true and accurate. However, since conditions of use are beyond our control, all recommendations or suggestions are presented without guarantee or responsibility on our part. We disclaim all liability in connection with the use of information contained herein or otherwise.