Westermo ODW-710-F1 User Manual

Page 1
User Guide
6651-2201
ODW-710-F1
Fibre Optic Modem
Westermo Teleindustri AB
©
Industrial Converter
PROFIBUS DP to
Fibre Optic Link.
Point to Point applications
Page 2
Legal information
The contents of this document are provided “as is”. Except as required by applicable law, no warranties of any kind, either express or implied, including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose, are made in relation to the accuracy and reliability or contents of this document. Westermo reserves the right to revise this document or withdraw it at any time without prior notice.
Under no circumstances shall Westermo be responsible for any loss of data or income or any special, incidental, and consequential or indirect damages howsoever caused.
More information about Westermo can be found at the following Internet address:
http://www.westermo.com
2
6651-2201
Page 3
Safety
Before installation:
!
Read this manual completely and gather all information on the unit. Make sure that you understand it fully. Check that your application does not exceed the safe operating specifications for this unit. This unit should only be installed by qualified personnel. This unit should be built-in to an apparatus cabinet, or similar, where access is restricted to service personnel only. The power supply wiring must be sufficiently fused, and if necessary it must be possible to disconnect manually from the power supply. Ensure compliance to national installation regulations. Branch circuit protection (fuse) is required for this unit with rating not exceeding 20 A. Product should be connected to UL Listed power supplies rated 12 – 48 VDC, min 500 mA or 24 VAC, min 500 mA or reliably grounded DC SELV source*. This unit uses convection cooling. To avoid obstructing the airflow around the unit, follow the spacing recommendations (see Cooling section).
!
Before mounting, using or removing this unit:
Prevent access to hazardous voltages by disconnecting the unit from the power supply. Warning! Do not open a connected unit. Hazardous voltages may occur within
!
this unit when connected to a power supply.
Class 1 Laser Product
This unit is designed to meet the Class 1 Laser regulations. However, the user is warned not to look directly into fibre optical fibre port or any connected fibre.
Care recommendations
Follow the care recommendations below to maintain full operation of the unit and to fulfil the warranty obligations. This unit must not be operated with covers or lids removed. Do not attempt to disassemble the unit. There are no user serviceable parts inside. Do not drop, knock or shake the unit. Rough handling beyond the specification may cause damage to internal circuit boards. Do not use harsh chemicals, cleaning solvents or strong detergents to clean the unit. Do not paint the unit. Paint can clog the unit and prevent proper operation. Do not expose the unit to any kind of liquids (rain, beverages, etc). The unit is not waterproof. Keep the unit within the specified humidity levels. Do not use or store the unit in dusty, dirty areas. Connectors as well as other mechanical parts may be damaged. If the unit is not working properly, contact the place of purchase, nearest Westermo distributor office, or Westermo Tech support. Fibre connectors are supplied with plugs to avoid contamination inside the optical port. The plug should be fitted when no optical fibre is inserted in the connector, e.g. during storage, service or transportation.
* Applicable for ODW-710-F1 only
6651-2201
3
Page 4
Note. Fibre Optic Handling
Fibre optic equipment requires careful handling as the fibre components are very sensitive to dust and dirt. If the fibre is disconnected from the modem, the protective plug on the transmitter/receiver must be replaced. The protective plug must be kept on during transportation. The fibre optic cable must also be protected in the same way.
If this recommendation is not followed, it can jeopardise the warranty.
Cleaning of the optical connectors
In the event of contamination, the optical connectors should be cleaned by using forced nitrogen and some kind of cleaning stick.
Recommended cleaning fluids:
• Methyl-, ethyl-, isopropyl- or isobutyl-alcohol
• Hexane
• Naphtha
Maintenance
No maintenance is required, as long as the unit is used as intended within the specified conditions.
Agency approvals and standards compliance
Type Approval / Compliance
EMC EN 61000-6-1, Immunity residential environments
EN 61000-6-2, Immunity industrial environments
EN 61000-6-3, Emission residential environments
EN 61000-6-4, Emission industrial environments
EN 55022, Emission IT equipment, class A
EN 55024, Immunity IT equipment
FCC part 15 Class A
EN 50121-4, Railway signalling and telecommunications apparatus
IEC 62236-4, Railway signalling and telecommunications apparatus
DNV Standard for Certification no. 2.4***
Safety UL/CSA/IEC/EN 60950-1, IT equipment*
EN 60950-1, IT equipment**
ATEX** EN 60079-0 and EN 60079-15
* Applicable for ODW-710-F1 only ** Applicable for ODW-710-F1 Ex only *** Applicable only for article number 3651-0711
FCC Part 15.105 Notice:
EN 55022 Notice:
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interfer­ence to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
This is a class A product. In a domestic environment this product may cause radio inter­ference in which case the user may be required to take adequate measures.
4
6651-2201
Page 5
ATEX Information (Applicable for ODW-710-F1 EX only)
General
This unit is intended for use in Zone 2 hazardous location only.
Marking
II 3 G Ex nA IIC T4 Gc SPECIAL CONDITION
WARNING – DO NOT SEPARATE WHEN ENERGIZED
Indicate that this unit complies with relevant European standards that are harmonised with the 94/9/EC Directive (ATEX).
II
3
G
Ex Indicates that this unit is in conformity with relevant European Ex standard(s).
nA
IIC Gas group, a typical gas i hydrogen.
T4
Gc
SPECIAL
CONDITION
Equipment group II. This unit can be installed in all places with an explosive gas atmosphere other than mines susceptible to firedamp Equipment category 3. A category is the classification according to the required level of protection. This unit ensures the requisite level of protection during normal operation and is intended for use in areas in which explosive atmosphere caused by gases, vapours, mists, or dust mixtures are unlikely to occure or, if they do occure, are likely to do so only infrequently and for a short periode only. Indicates protection concerning explosive atmospheres caused by gases, vapours or mists (G).
Type of protection used. This unit is a non-sparking device "nA" which is constructed to minimize the risk of occurence of arcs or sparks capable of creating an ignition hazard during conditions of normal operation.
Temperature class T4 (T4 = 135°C). This unit is classified in accordance with its maximum surface temperature (external and internal). Equipment protection level Gc (EPL Gc). Equipment for explosive gas atmospheres, having a "enhanced" level of protec­tion, which is not a source of ignition in normal operation and which may have some additional protection to ensure that it remains inactive as an ignition source in the case of regular expected occurences. EPL Gc are analogous to the ATEX Categories (Category 3 G = EPL Gc). This unit has a special condition of use. The special condition for safe use contains safety related information that is necesarry for the correct installation and safe use.
6651-2201
5
Page 6
Ratings
Power (12 – 48) VDC; 300 mA
Ambient temperature –40ºC Ta +70ºC
Ingress protection (IP) IP21
Maximum surface temperatur 135ºC (temperature class T4)
Safety Control Drawing
Degree of protection IP 21 Ambient temperature –40°C to +70°C
Installation spacing
Direction relative this unit!
1234
Minimum 25 mm above / below Minimum 10 mm left / right
Position Descripton Input / Output values
1 In & out / Relay contact (NO)
2 In & out / Relay contact (C) 3 In & out / Relay contact (NC)
Galvanically isolated via mechanical relay. See user manual for proven transient protection.
Position Descripton Input / Output values
1 – / – 2 – / – 3 In/out / RxD/TxD-P 4 Out / CNTR-P 5 – / DGND 6 Out / VP 7 – / – 8 In/Out / RxD/TxD-N 9 Not connected
Uin = 60 VDC max
Iin = 500 mA max
U
= ± 5 Vpk
max
I
= ± 400 mA
max
Data rate: 9600 bit/s to 12 Mbit/s
Position Descripton Output values
Rx In / Receive port Tx Out / Transmit port
Position Descripton Intput values
1 In / Common
2 In / +Voltage A
3 In / +Voltage B
4 In / Common
See section Type tests and environmental conditions in this user manual for proven transient protection.
6
Uin = (10 – 60) VDC Iin = 400 mA max PIn = Max 4 W
Max 0 dBm
6651-2201
Page 7
SPECIAL CONDITION FOR SAFE USE
Ambient temperature:
This unit is designed for use in extreme ambient temperature conditions as follows: –40 ºC Ta +70 ºC
Installation in an apparatus cabinet:
This unit requires installation in an Ex certified apparatus cabinet suitable for the area of use and providing a degree of protection of at least IP54.
Resistance to impact:
This unit requires installation in an apparatus cabinet where adequate resistance to impact is provided by the apparatus cabinet. See "Installation in an apparatus cabinet" above for requirements on the external apparatus cabinet.
Resistance to light:
This unit requires installation in an apparatus cabinet where it is protected from light (for example daylight or light from luminaires). See "Installation in an apparatus cabinet" above for requirements on the external apparatus cabinet.
Secureness of plugs:
When this unit is installed in an explosive atmospheres, all connectors must be mechanically secured to prevent loosening.
Conductor temperature:
When this unit is installed in locations with high ambient temperature, special precautions shall be taken upon the choice of external conductors and the temperature rating of the conductor(s).
Directive 94/9/EC alongside with other directives:
Directive 2004/108/EC (EMC) applies and to assure a safe performance of this unit under the scope of Directive 94/9/EC, refer to the electromagnetic immunity level specified under "Type tests and environmental conditions" in this manual.
Standards and date of compliance
EN 60079-0 and EN 60079-15 2010-12-17
6651-2201
7
Page 8
Declaration of Conformity
Org.nr/
Registered office
Westermo Teleindustri AB
Declaration of conformity
The manufacturer Westermo Teleindustri AB
Herewith declares that the product(s)
Type of product Model Art no
Industrial fiberoptic repeaters/media converters
is in conformity with the following EC directive(s).
No Short name
2004/108/EC Electromagnetic Compatibility (EMC) 94/9/EC1 Equipment Explosive Atmospheres (ATEX)
References of standards applied for this EC declaration of conformity.
No Title Issue EN 61000-6-1 Electromagnetic compatibility – Immunity residential environments 2007
EN 61000-6-2 Electromagnetic compatibility – Immunity industrial environments 2005 EN 61000-6-3 Electromagnetic compatibility – Emission residential environments 2007 EN 61000-6-4 Electromagnetic compatibility – Emission for industrial
EN 55022 Information technology equipment - Emission 2006 + A1:2007 EN 55024 Information technology equipment - Immunity 1998 + A1:2001 +
EN 50121-4 Railway applications – Electromagnetic compatibility – Emission
EN 60079-0 Explosive atmospheres – Equipment – General requirements 2009 EN 60079-15 Electrical apparatus for explosive gas atmospheres –
The last two digits of the year in which the CE marking was affixed: 11
SE-640 40 Stora Sundby, Sweden
ODW-700 series 3651-07xx ODW-700EX series 3651-37xx
environments
and immunity of the signalling and telecommunications apparatus
Construction, test and marking of type of protection “n” electrical apparatus
2007
A2:2003 2006
2005
Pierre Öberg Technical Manager 15th June 2011
1
Applicable for ODW-700EX series only.
Postadress/Postal address
S-640 40 Stora Sundby 016-428000 016-428001 52 72 79-4 5671-5550 556361-2604 Eskilstuna
Sweden Int+46 16428000 Int+46 16428001
8
Tel.
Telefax
Postgiro
Bankgiro Corp. identity number
6651-2201
Page 9
Type tests and environmental conditions
Electromagnetic Compatibility
Phenomena Test Description Level
ESD EN 61000-4-2 Enclosure contact ± 6 kV
RF field AM modulated IEC 61000-4-3 Enclosure 10 V/m 80% AM (1 kHz), 80 – 800 MHz
RF field 900 MHz ENV 50204 Enclosure 20 V/m pulse modulated 200 Hz, 900 ± 5 MHz Fast transient EN 61000-4-4 Signal ports ± 2 kV
Surge EN 61000-4-5 Signal ports unbalanced ± 2 kV line to earth, ± 2 kV line to line
RF conducted EN 61000-4-6 Signal ports 10 V 80% AM (1 kHz), 0.15 – 80 MHz
Pulse Magnetic field EN 61000-4-9 Enclosure 300 A/m, 6.4 / 16 µs pulse Voltage dips
and interruption
Mains freq. 50 Hz EN 61000-4-16 Signal ports 100 V 50 Hz line to earth Mains freq. 50 Hz SS 436 15 03 Signal ports 250 V 50 Hz line to line Radiated emission EN 55022 Enclosure Class B
Conducted emission EN 55022 AC power ports Class B
Dielectric strength EN 60950 Signal port to all other
Environmental
Temperature Operating –40 to +70°C
Humidity Operating 5 to 95% relative humidity
Altitude Operating 2 000 m / 70 kPa Service life Operating 10 year Vibration IEC 60068-2-6 Operating 7.5 mm, 5 – 8 Hz
Shock IEC 60068-2-27 Operating 15 g, 11 ms
Packaging
Enclosure, ODW-710-F1 UL 94 PC / ABS Flammability class V-1 Enclosure,
ODW-710-F1 EX Dimension W x H x D 35 x 121 x 119 mm Weight 0.26 kg Degree of protection IP 21 Cooling IEC 529 Enclosure Convection Mounting Horizontal on 35 mm DIN-rail
EN 61000-4-11 AC power ports 10 & 5 000 ms, interruption
FCC part 15 Class A
FCC part 15 AC power ports Class B EN 55022 DC power ports Class A
Enclosure air ± 8 kV
20 V/m 80% AM (1 kHz), 800 – 1000 MHz 20 V/m 80% AM (1 kHz), 1400 – 2700 MHz
Power ports ± 2 kV
Signal ports balanced ± 2 kV line to earth, ± 1 kV line to line Power ports ± 2 kV line to earth, ± 2 kV line to line
Power ports 10 V 80% AM (1 kHz), 0.15 – 80 MHz
200 ms, 40% residual voltage 500 ms, 70% residual voltage
isolated ports Power port to other
isolated ports
Storage & Transport –40 to +70°C Maximum surface
temperature
Storage & Transport 5 to 95% relative humidity
Cabelec 6141
2 kVrms 50 Hz 1min
3 kVrms 50 Hz 1min 2 kVrms 50 Hz 1min (@ rated power < 60V)
135ºC (temperature class T4)
2 g, 8 – 500 Hz
6651-2201
9
Page 10
Functional description
r
POWER
+VA
+VB
COM
COM
STATUS
NO C
NC
Switches
O V
P
Internal Electronics
LED’s
O V
P
SFP Fibre transceive
O C P
PROFIBUS DP
RxD/TxD - P
RxD/TxD - N
SHIELD
CH 1
OVP Over Voltage Protection OCP Over Current Protection
Converter PROFIBUS DP – optical fibre
ODW-710-F1 is a fibre optic modem that converts between electrical PROFIBUS DP and a fibre optical link.
Data rate up to 12 Mbit/s
ODW-710-F1 converts PROFIBUS DP data using data rates from 9 600 bit/s up to 12 Mbit/s. Retiming of the PROFIBUS DP data ensures that the correct signal form is transmitted from the ODW-710-F1 converter.
Automatic data rate detection
The PROFIBUS data rate is set automatically as soon as the ODW-710-F1 receives a correct data frame, whether data is received from PROFIBUS DP or the fibre optic link. The detected data rate remains until a number of consecutive faulty received frames have been detected or no further frames are detected within the timeout period. The timeout period is set by switches, with the default setting of 31 faulty frames or 5 seconds with­out any received frames.
10
6651-2201
Page 11
Interface specifications
Power
Rated voltage ODW-710-F1: 12 to 48 VDC and 24 VAC
Operating voltage ODW-710-F1: 10 to 60 VDC and 20 to 30 VAC
Rated current 300 mA @ 12 VDC
Rated frequency ODW-710-F1: DC and 48 to 62 Hz
Inrush current I2t 0.2 A2s Startup current* 1.0 Apeak Polarity Reverse polarity protected Redundant power input Ye s Isolation to PROFIBUS DP and Status port Connection Detachable screw terminal Connector size 0.75 – 2.5 mm2 (AWG 18 – 13)
Shielded cable Not required
* External supply current capability for proper startup
Status
Port type Signal relay, changeover contacts Rated voltage Up to 48 VDC Operating voltage Up to 60 VDC Contact rating 500 mA @ 48 VDC Contact resistance < 50 mW Isolation to PROFIBUS DP and Power port Connection Detachable screw terminal Connector size 0.2 – 2.5 mm2 (AWG 24 – 13)
Shielded cable Not required
ODW-710-F1 Ex: 12 to 48 VDC
ODW-710-F1 Ex: 10 to 60 VDC
150 mA @ 24 VDC 75 mA @ 48 VDC
ODW-710-F1 Ex: DC
Connect the unit using at least 18 AWG (0.75 mm2) wiring
6651-2201
11
Page 12
PROFIBUS DP (RS-485)
Electrical specification EIA RS-485 / EN 50 170
Data rate 9 600 bit/s, 19.2, 93.75, 187.5, 500 kbit/s, 1.5, 3, 6 and 12 Mbit/s
Data format 8 data bits, even parity, 1 stop bit, 11 bits total
Protocol PROFIBUS DP / EN 50170
Data Rate detection Yes, compliant with EN 50 170
Retiming Ye s
Turn around time In accordance with EN 50 170
Transmission range 1200 m, depending on data rate and cable type (EIA RS-485)
Settings None, external termination and failsafe biasing
Protection Installation Fault Tolerant (up to ±60 V)
Isolation to Power and Status port
Connection 9-pin D-sub female
Shielded cable Not required
Conductive housing Isolated to all other circuits and housings
12
6651-2201
Page 13
Location of Interface ports, LED’s and DIP-switches
ODW-710-F1
LED Indicators(for details see page 15)
FX(Fibre)
(for details
see page 12–13)
DIP-switches accessible under lid (for details see page 16–17)
Status screw terminal
Position Description Product
Contact with C when fibre optical
1
links are in operation
2 Common C
Open (no contact with C)
3
when fibre optical links are not in operation
marking
NO
NC
PROFIBUS DP (RS-485) D-sub
Position Direction* Description
1
2
3 In/Out RxD/TxD-P
4 Out CNTR-P
5 DGND
6 Out VP
7
8 In/Out RxD/TxD-N
9
* Direction relative this unit
6651-2201
Power screw terminal
Position Direction* Description Product
marking
1 In Common voltage COM 2 In Voltage A +VA 3 In Voltage B +VB 4 In Common voltage COM
13
Page 14
LED Indicators
LED Status Description
PWR
Power
BA
Bus active
CH 2 Not used CH 1
Channel 1 link status
DPR
Receive PROFIBUS DP
FR
Receive fibre link
FL R
Failure link remote
FL L
Failure link local
* Only valid if used togheter with ODW-710-F2 units in a multidrop network. Note: During power up, all LED’s will turn on for about 1 second.
ON Power is on. OFF Power is off. ON Data rate has been identified and
data frames are being received on the electrical or optical interface.
OFF Data rate has not been identified.
ON Fibre link to other unit has been
established at CH 1.
Flashing Optical power detected but link to
other unit has not been established at CH 1.
OFF No optical power detected and
no link to other unit has been established at CH 1.
Flash Data received on the electrical
interface and transmitted out on the optical interface.
OFF No data received on the electrical
interface.
Flash Data received on the optical interface
and transmitted out on the electrical interface.
OFF No data received on the optical
interface.
ON Remote fibre link failure. A fibre link
is out of operation at any other unit than this one.*
Flashing Hardware error or invalid configura-
tion.
ON Local fibre link failure. A fibre link is
out of operation.
Flashing Hardware error or invalid configura-
tion.
14
6651-2201
Page 15
DIP-switch settings
Before setting DIP-switches:
!
Prevent damage to internal electronics from electrostatic discharges (ESD) by discharging your body to a grounding point (e.g. use of wrist strap).
S2S1
S2 DIP-switch
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
Multidrop mid unit or redundant ring member. N/A for ODW-710-F1
Multidrop end unit. E.g. the first or last unit in a multidrop network. Always "ON" for ODW-710-F1
Redundant ring focal point Only one focal point allowed in a ring. N/A for ODW-710-F1
65535 t
interruption in receiving
bit
frames, until inactive BA.
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
* See section “About the automatic data rate detection”
on page 23 for a more detailed description.
5 seconds interruption in receiving frames, until inactive BA
10 seconds interruption in receiving frames, until inactive BA
20 seconds interruption in receiving frames, until inactive BA
*
.
*
.
*
.
6651-2201
15
Page 16
S1 DIP-switch
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
S2 DIP-switch
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
Description
1 faulty frame before data rate seen as unidentified*. S1: No extended retry limit.
2 faulty frames before data rate seen as unidentified*. S1: No extended retry limit.
3 faulty frames before data rate seen as unidentified*. S1: No extended retry limit.
4 faulty frames before data rate seen as unidentified*. S1: No extended retry limit.
5 faulty frames before data rate seen as unidentified*. S1: No extended retry limit.
6 faulty frames before data rate seen as unidentified*. S1: No extended retry limit.
7 faulty frames before data rate seen as unidentified*. S1: No extended retry limit.
8 faulty frames before data rate seen as unidentified*. S1: No extended retry limit.
31 faulty frames before data rate seen as unidentified*. S1: Extended retry limit.
63 faulty frames before data rate seen as unidentified*. S1: Extended retry limit.
127 faulty frames before data rate seen as unidentified*. S1: Extended retry limit.
255 faulty frames before data rate seen as unidentified*. S1: Extended retry limit.
Set status port at local fibre link (FL L) error only. Only applicable if used togheter with ODW-710-F2 units in a multidrop network.
Factory default
* See section “About the automatic data rate detection” on page 22 for a more detailed description.
16
6651-2201
Page 17
Start up guide
Follow the steps below to get the unit up and running in a simple application.
PROFIBUS DP PROFIBUS DP
PROFIBUS DP master
POWER CH 1
COM +VA +VB COM
PROFIBUS DP slave
POWER CH 1
COM +VA +VB COMTX RX TX RX
Fibre Optic
… Use the factory DIP-switch settings. … Connect The fibre link between the both units. … Connect the power supply to both units.
The Fibre link should be in operation as indicated by the CH1 LED.
… Connect the PROFIBUS DP connectors between both ODW-710-F1 and PROFIBUS
units configured to be units in the PROFIBUS DP network. The PROFIBUS DP will be in operation and the data rate will be automatically detect­ed, as indicated by the BA LED.
… The point to point application is up and running.
Note: In an ODW-710-F1 fibre optic link there will be some additional processing
delays that do not exist in an electrical bus. It is possible that the PROFIBUS application must be adjusted to accommodate for this delay. See page 21 “Calculating system processing delay” for more information on how to determine the overall system delay time.
6651-2201
17
Page 18
LED indication under normal operation
RX1
TX1
ODW-710
PROFIBUS
Slave
ODW-710
PROFIBUS
Master (PLC)
TX1
RX1
Data from the PROFIBUS master is received at the ODW-710-F1 electrical port (as indi­cated by the DPR LED), data rate is automatically detected (as indicated by the BA LED), data bits are retimed according to the determined rate and sent out on the optical fibre at CH 1.
The ODW-710-F1 slave unit receives data at optical fibre CH 1 (as indicated by the FR LED), data rate is automatically detected (as indicated by the BA LED) and data is sent out on the electrical port.
Responses from the PROFIBUS slaves are processed in the same fashion and sent back to the PROFIBUS master in the opposite direction.
18
6651-2201
Page 19
LED indication during optical link failure
TX1
RX1
ODW-710 ODW-710
Master
FL L LED is on
CH 1 LED is off
PROFIBUS
Faulty
fibre
RX1
TX1
PROFIBUS
Slave
FL L LED is on
CH 1 LED is flashing
If one fiber in the optical fibre pair fails, all cummunication with will be lost and the FL R LED’s will turn on. The ODW-710-F1 that is still sensing optical power will indicate this by flashing the CH1 LED.
TX1
RX1
ODW-710 ODW-710
CH 1 LED is off
FL L LED is on
Faulty fibres
RX1
TX1
FL L LED is on
CH 1 LED is off
PROFIBUS
Master
PROFIBUS
Slave
If both fibers in the optical fibre pair fails, all cummunication with will be lost, the CH1 LED’s will turn off and the FL R LED’s will turn on.
6651-2201
19
Page 20
Calculating system processing delay
Data exchange between a PROFIBUS DP master and slave via ODW-710-F1 fibre optic link, will be delayed due to the length of the optical fibre and the signal processing within the ODW-710-F1. The signal processing delay is dependent on the data rate, and the fibre delay is dependent on the total length of the optical fibre. The additional time resulting from the optical fibre and ODW-710-F1 is the Overall system delay.
Delay @ 1.5 Mbit/s Delay @ 3 to 12 Mbit/s
Optical fibre length delay (typical) 5 µs/km 5 µs/km
Signal processing, electrical to fibre (max) 1 tbit + 1 µs 9 tbit + 1 µs
Signal processing, fibre to electrical (max) 0.3 µs 0.3 µs
Signal processing, fibre to fibre (max) 1.3 µs 1.3 µs
Note! tbit = 1 / Baud rate (Baud rate in bit/s)
Example
One PROFIBUS DP master and slave using a data rate of 12 Mbit/s. and a total fibre length of 40 km. A data frame sent from the master to a slave.
1. Fibre: The total optical fibre length delay. 40 x 5 µs = 200 µs
2. Converter electrical to fibre: Signal processing delay (ODW-710-F1 connected to PROFIBUS DP master). 9 tbit + 1 µs = 9 x 0.083 µs + 1 µs 1.1 µs
3. Converter fibre to electrical: Signal processing delay (ODW-710-F1 connected to addressed slave).
0.3 µs
4. The system delay is calculated by summing the delays in item 1 to 3 above:
200 µs + 1.1 µs + 0.3 µs = 201.4 µs
20
6651-2201
Page 21
About the interfaces
Power
The power terminal has two independent inputs, +VA and +VB, allowing redundant power input. The ODW-710-F1 power supply is galvanically isolated from all other inter­faces.
Optical fibre interfaces
ODW-710-F1 uses Small Form Factor Pluggable (SFP) transceivers. This means that a wide range of different fibre transceivers and connectors can be used (see page 12).
PROFIBUS DP interface
The PROFIBUS DP interface is a female 9-position D-sub. Pin assignments are compli­ance with the PROFIBUS standard EN 50 170.
Status port
The status port connects to an internal relay witch may be used to trigger an external alarm if a fault condition occurs. During normal operation pins 1 and 2 are in contact with each other, and pins 2 and 3 are isolated. During an optical link failure, or power failure, pins 1 and 2 are isolated, and pins 2 and 3 are in contact with each other.
Optical link failures can be classified in to two categories, local or remote, as indicated by the FL L and FL R LED’s. A local link failure is when an optical link is down at this par­ticular unit. A remote link failure is when an optical link is down at some other unit.
From the factory, the status port is set to trigger on both types of link failures. However, by setting DIP-switch S1:1 to the ON position, the status port will only trigger when a local link failure has occurred.
Note: Setting DIP-switch S1:1 ON is only applicate if using the ODW-710-F1 togheter with ODW-710-F2 in a multidrop network.
6651-2201
21
Page 22
About the automatic data rate detection
ODW-710-F1 automatically detects the data rate by monitoring incoming PROFIBUS data frames on both the electrical and optical interfaces. When the data rate has been estab­lished the BA LED will go active.
If no data frames are transmitted for a period of time the automatic data rate detection will restart and the BA LED will go inactive.
The idle time before the automatic data rate detection re-starts is set using DIP-switches S2:4 and S2:5. The factory default setting is 5 seconds.
The automatic data rate detection determines the actual data rate by listening for PROFIBUS Start Delimiters (SD1 – SD4) at the beginning of each data frame. If one or more Start Delimiters are lost the automatic data rate detection will re-start.
The number of lost Start Delimiters before the automatic data rate detection re-starts is set using DIP-switches S1:2 and S2:6 – S2: 8. The factory default setting is 31 faulty frames (31 lost Start Delimiters).
Note: Start Delimiters can be lost during an electrical or optical disturbance. For example a PROFIBUS slave unit is connected/disconnected or an optical fibre is
disconnected. It is advisable to start of by using the factory default settings and only manipulate them if a problem exists.
22
6651-2201
Page 23
Mounting
CLICK!
This unit should be mounted on 35 mm DIN-rail, which is horizontally mounted inside an apparatus cabinet, or similar.
Snap on mounting, see figure.
Cooling
This unit uses convection cooling. To avoid obstructing the air­flow around the unit, use the following spacing rules. Minimum spacing 25 mm (1.0 inch) above /below and 10 mm (0.4 inches) left /right the unit. Spacing is recommended for the use of unit in full operating temperature range and service life.
10 mm *
(0.4 inches)
25 mm
* Spacing (left/right) recommended for
full operating temperature range
Removal
Press down the black support at the top of the unit. See figure.
6651-2201
25 mm
23
Page 24
Westermo • SE-640 40 Stora Sundby, Sweden
Tel +46 16 42 80 00 Fax +46 16 42 80 01
Sales Units
Westermo Data Communications
E-mail: info@westermo.com
www.westermo.com
China sales.cn@westermo.com www.cn.westermo.com
France infos@westermo.fr www.westermo.fr
Germany info@westermo.de www.westermo.de
For complete contact information, please visit our website at www.westermo.com/contact
REV.G 6651-2201 2014-10 Westermo Teleindustri AB, Sweden – A Beijer Electronics Group Company