Linjedelare
Line split unit
Leitungsteiler
Modem Partage de ligne
INSTALLATIONSANVISNING
INSTALLATION MANUAL
INSTALLATIONS ANLEITUNG
MANUEL D'INSTALLATION
6110-2012
www.westermo.se
LA-01 AC
LA-01 DC
©
Westermo Teleindustri AB • 2002 • REV. A
Galvanic
Isolation
Transient
Protection
Balanced
Transmission
CE
Approved

6 6110-2012
Specifications
Transmission Asynchronous, full/half duplex or simplex
Interface Interface 1: EIA RS-232-C/ITU-T V.24
Interface 2: ±10 mA current loop
Interface 1 and 2 are selectable on each channel
Connection Channel 1, 2 and 3: 5-pos screw terminal
Transmission rate Data rates up to 38 400 bit/s
Indicators Power
Channel 1: RD, TD, DCD
Channel 2, 3: DCD
Isolation Galvanic isolation with opto-coupler (Interface 2)
and transformer (supply)
Interface 1: Only isolation against supply
Isolation voltage 1 500 V
Overvoltage protection Mains: Breakdown voltage 440 V at
230 V AC and 220 V at 115 V AC
Interface 2: Breakdown voltage transmitter 15 V,
receiver 7 V
Surge capacity 0.6 kW during 1 ms
Power supply Switchable 115/230 V 48–62 Hz +15/–10%
Fuse 100 mA fast 5x20 mm
Power consumption Max 7 VA at 230 V
Temperature range 5–50°C, ambient temperature
Humidity 0–95% RH, non-condensing
Dimension 161x139x53 mm (WxHxD)
Weight 0.6 kg
Mounting With rubber pads or screws.
Screws: Remove the two ”keyholes” on the bottom
of the case.

76110-2012
Factory setting
Settings
The LA-01 can through different settings
be adapted to a variety of running
conditions. To set the jumpers, open
the plastic case by placing and turning a
screw-driver between top and bottom at the rear of the case.
Warning! Do not open connected unit
J2 – J11 Selection of RS-232-C/V.24 or
J2 – J11 W1interface on channel 1, 2 and 3
J12/J13 Selection of V or Y function,
see block diagram
S1 Selection of power supply
115 V/230 V AC
J1 Connects protected ground
to signal ground.
CHANNEL 3 CHANNEL 2 CHANNEL 1
231
231
231
321321
321
321
1
2
3
3
2
1
3
2
1
3
2
1
1
2
3
J13
S1
J1
J6 J10 J7
J8J11
J12
J2 J3 J4
X4 X2 X1
115
230
RS-232-C/V.24 or W1,
channel 1
J3
J4
J2
RS-232-C/V.24 W1
J3
J4
J2
J3
J4
J2
RS-232-C/V.24 W1
J10
J11
J9
J13
J12
RS-232-C/V.24 or W1,
channel 2
J6
J7
J8
J5
J6
J7
J8
J5
J6
J7
J8
J5
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
RS-232-C/V.24 or W1,
channel 3
J10
J11
J9
RS-232-C/V.24 W1
J10
J11
J9
1
2
3
1
2
3
V or
Y function
J13
J12
V funktion Y funktion
J13
J12
1
2
3
1
2
3

8 6110-2012
Direction Pin configuration 10 mA balanced current loop W1
Channel 1 Channel 2 Channel 3 Description
Receiver 1 1 1
(R+)
Receiver 2 2 2
(R–)
Transmitter 3 3 3
(T+)
Transmitter 4 4 4
(T–)
555
Shield
*
* If shielded cable is used, connect the shield only at one end to avoid ground currents.
10 mA balanced current loop
Transmission range (10 mA balanced current loop)
Cable Transmission speed bit/s
42 pF/m 600 1 200 2 400 4 800 9 600 19 200 38 400
0.3 mm
2
18 000 m 12 000 m 8 000 m 5 000 m 2 500 m 1 000 m 500 m
LA-01 DC
Specifications
Switch settings
According to LA-01 AC
Power supply 12–36 V DC
Power consumption Max 3 W
Isolation 1000 V
Fuse F1 1.6 A fast 5x20 mm
All other specifications according to LA-01 AC
Connections
According to LA-01AC, except power supply
Connection no. Power supply
1 + Voltage
2 – Voltage
123
POWER
12-36VDC
CHANNEL 3
CHANNEL 2 CHANNEL 1
Direction RS232-C/V .24 ITU-T V .24 Description
Circuit no.
I 1 1 1 103 TD/Transmitted Data
O 2 2 2 104 RD/Received Data
O 4 4 4 – +12 V (Pull-up resistor)
– 5 5 5 102 SG/Signal Ground
I = Input, O = Output on LA-01
Connections
RS-232-C/V.24
Channel 1 Channel 2 Channel 3

1
2
3
4
5
6
7
•
•
•
25
1
2
3
4
5
DTE LA-01 channel 1
1
2
3
4
5
LA-01 channel 1
1
2
3
4
5
9 pos. PC
1
2
3
4
5
1
2
3
4
5
DCE LA-01 channel 1
Hints
LA-01 has three channels and they can be configured as RS-232/V.24 or as W1
connection. The LA-01 splits the line and repeats the signal in a multidrop system.
The maximum number of units in serial connection is 14 LA-01:s.
The drop channel (no 1) is configured as DCE (Data Communication Equipment).
Most printers, PC’s and terminals are set as DTE (Data Terminal Equipment).
Some recommendation of cable configurations are given below.
If any problems do occur on set up of the LA-01:s, the LED’s will be helpful.
• PWR: The unit has power.
• RD channel 1: Data received from channel 2 or 3
• TD channel 1: Data received from connected unit
• DCD channel 1: Indicates that W1 is connected to channel 1
• DCD channel 2: Indicates that W1 is connected to channel 2
• DCD channel 3: Indicates that W1 is connected to channel 3.

6110-2012 02.06 Mälartryck AB, Eskilstuna, Sweden
Block diagram
V-function
Channel 3
Channel 2
Channel 1
Channel 3Channel 2
Channel 1
OR
OR
OR
Y-function
OR
Westermo Teleindustri AB • SE-640 40 Stora Sundby, Sweden
Phone +46 16 42 80 00 Fax +46 16 42 80 01
E-mail:info@westermo.se • W estermo W eb site: www.w estermo.se
Westermo Teleindustr i AB have distributors in several
countries, contact us for further information.
Westermo Data Communications Ltd
Unit 14 Talisman Business Centre • Duncan Road
Park Gate, Southampton • SO31 7GA
Phone:+44(0)1489 580 585 • Fax.:+44(0)1489 580586
E-Mail:sales@westermo.co.uk • Web:www.westermo.co.uk
Westermo Data Communications GmbH
Goethestraße 67,68753 Waghäusel
Tel.:+49(0)7254-95400-0 • Fax.:+49(0)7254-95400-9
E-Mail:info@westermo.de • Web:www.westermo.de
Westermo Data Communications S.A.R.L.
9 Chemin de Chilly 91160 CHAMPLAN
Tél :+33 1 69 10 21 00 • Fax :+33 1 69 10 21 01
E-mail :infos@westermo.fr • Site WEB:www.westermo.fr
Subsidiaries