Safety
Before installation:
!
Read this manual completely and gather all information on the unit. Make sure that
you understand it fully. Check that your application does not exceed the safe operating specifications for this unit.
This unit should only be installed by qualified personnel.
This unit should be built-in to an apparatus cabinet, or similar, where access is
restricted to service personnel only.
The power supply wiring must be sufficiently fused, and if necessary it must be
possible to disconnect manually from the power supply. Ensure compliance to
national installation regulations.
This unit uses convection cooling. To avoid obstructing the airflow around the unit,
follow the spacing recommendations (see Cooling section).
Before mounting, using or removing this unit:
!
Prevent access to hazardous voltage by disconnecting the unit from power supply.
Warning! Do not open connected unit. Hazardous voltage may occur within this
unit when connected to power supply.
Care recommendations
Follow the care recommendations below to maintain full operation of unit and to fulfil
the warranty obligations.
This unit must not be operating with removed covers or lids.
Do not attempt to disassemble the unit. There are no user serviceable parts inside.
Do not drop, knock or shake the unit, rough handling above the specification may cause
damage to internal circuit boards.
Do not use harsh chemicals, cleaning solvents or strong detergents to clean the unit.
Do not paint the unit. Paint can clog the unit and prevent proper operation.
Do not expose the unit to any kind of liquids (rain, beverages, etc). The unit is not water-
proof. Keep the unit within the specified humidity levels.
Do not use or store the unit in dusty, dirty areas, connectors as well as other mechanical
part may be damaged.
If the unit is not working properly, contact the place of purchase, nearest Westermo dis-
tributor office or Westermo Tech support.
A readily accessible disconnect device shall be incorporated external to the equipment.
This unit may have hot surfaces when used in high ambient temperature.
WARNING – SUBSTITIUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR
DIVISION 2
WARNING – DO NOT OPEN WHEN ENERGIZED
WARNING – DO NOT DISCONNECT EQUIPMENT UNLESS AREA IS KNOWN TO
BE NONHAZARDOUS
Maintenance
No maintenance is required, as long as the unit is used as intended within the specified
conditions.
6642-22102
6642-22102
3
3
ATEX Information
General
This unit is intended to be used in Zone 2 hazardous location only.
Marking
II 3G EEx nA II T4
SPECIAL CONDITION
The Ex mark (Epsilon X mark) is a specific marking for explosive protection
equipment. The mark shows that this unit complies with the requirements of the
relevant European standards that are harmonised with the 94/9/EC Directive.
Equipment group II.
II
3G
EEx
nA
II
T4
SPECIAL
CONDITON
This unit can be installed in all places with an explosive gas atmosphere other
than mines susceptible to firedamp.
Category 3G.
A category is the classification according to the required level of protection.
This unit is intended for use in areas in which explosive atmosphere caused by
gases, vapours or mists are unlikely to occur or, if they do occur, are likely to do
so only infrequently and for a short period only.
Equipment in this category ensures the requisite level of protection during normal
operation.
The letter 'G' indicates the protection concerning explosive atmospheres caused
by gases, vapours or mists.
The marking of "EEx" shows that this unit is in conformity with European Ex
standard(s).
Type of protection applied to electrical equipment to avoid ignition of a surrounding explosive atmosphere.
This unit is a non-sparking device "nA" which is constructed to minimize the risk
of occurrence of arcs or sparks capable of creating an ignition hazard during conditions of normal operation.
Equipment group II.
This unit can be installed in all places with an explosive gas atmosphere other
than mines susceptible to firedamp.
Temperature class T4.
This unit is classified in accordance with its maximum surface temperature
(external and internal).
This unit have special condition for use.
The special conditon for use containes safety related information that is necesarry
for the correct installation and safe use.
4
6642-22102
Special condition for use
Ambient temperature:
This unit is designed for use in extreme ambient temperature conditions according to the
following: –40 ºC ≤ T
≤ +70 ºC
amb
Degree of protection by enclosure (IP):
This unit is intended for installation in an apparatus cabinet or similar providing adequate
protection against the entry of solid foreign objects or water capable of impairing safety.
The unit shall attain an equivalent degree of protection of IP54 by the installation in the
apparatus cabinet or similar.
Resistance to impact:
This unit is intended for installation in an apparatus cabinet or similar, where the apparatus cabinet provides the adequate resistance to impact.
Resistance to light:
This unit is intended for installation in an apparatus cabinet or similar where it is protected from light (for example daylight or light from luminaries).
Conductor temperature:
When this unit is installed in locations with high ambient temperature, special precautions
shall be taken upon the choice of external conductors and the temperature rating of the
conductor(s).
Directive 94/9/EC alongside with other directives:
Directive 2004/108/EC (EMC) applies and to assure a safe performance of this unit under
the scope of Directive 94/9/EC, refer to the electromagnetic immunity level specified
under Type tests and environmental conditions in this manual.
W-moEN 50121-4, Railway signalling and telecommunications
apparatus
SafetyW-moEN 60950-1, IT equipment
SHDSLNEMKOITU-T G.991.2
EXFM ApprovalsClass 1, Division 2
ATEXW-moEN 60079-0 and EN 60079-15
FCC Part 15.105 Notice:
This equipment has been tested and found to comply with the limits for a
Class B digital device, pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful interference
in a residential installation. This equipment generates, uses and can radiate
radio frequency energy and, if not installed and used in accordance with
the instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio
or television reception, which can be determined by turning the equipment
off and on, the user is encouraged to try to correct the interference by
one or more of the following measures:
… Reorient or relocate the receiving antenna
… Increase the separation between the equipment and receiver
… Connect the equipment into an outlet on a circuit different from that to
which the receiver is connected
… Consult the dealer or an experienced radio/TV technician for help.
6
6642-22102
Declaration of Conformity
Westermo Teleindustri AB
Declaration of conformity
The manufacturer
Herewith declares that the product(s)
Type of product Model Art no From serial no.
DIN-rail Wolverine series DDW-22x 3642-02xx 2000
is in conformity with the following EC directive(s).
RF field AM modulated IEC 61000-4-3Enclosure20 V/m 80% AM (1 kHz), 80 – 1000 MHz
10 V/m 80% AM (1 kHz), 1400 – 2100 MHz
5 V/m 80% AM (1 kHz), 2100 – 2500 MHz
1 V/m 80% AM (1 kHz), 2500 – 2700 MHz
Fast transientEN 61000-4-4Signal ports± 2 kV
Power ports± 2 kV
SurgeEN 61000-4-5Signal ports balanced± 2 kV line to earth, ± 1 kV line to line
Power ports± 2 kV line to earth, ± 2 kV line to line
RF conductedEN 61000-4-6Signal ports10 V 80% AM (1 kHz), 0.15 – 80 MHz
Power ports10 V 80% AM (1 kHz), 0.15 – 80 MHz
Power frequency magnetic field
Pulse magnetic fieldEN 61000-4-9Enclosure300 A/m
Mains freq. 50 HzEN 61000-4-16Signal ports100 V 50 Hz line to earth
Mains freq. 50 HzSS 436 15 03Signal ports250 V 50 Hz line to line
Voltage dips and inter-
ruption
Radiated
emission
Conducted emissionEN 55022DC power portsClass B
Dielectric strengthEN 60950Signal port to other
TemperatureOperating-40 to +70ºC
HumidityOperating5 to 95% relative humidity
AltitudeOperating2 000 m / 70 kPa
Reliability prediction
(MTBF)
VibrationIEC 60068-2-6Operating7.5 mm, 5 – 8 Hz 2 g, 8 – 500 Hz
ShockIEC 60068-2-27Operating15 g, 11 ms
EnclosureUL 94Aluminium/ZinkFlammability class V-0
Dimension W x H x D134 x 105 x 122 mm
Weight1.5 kg
Degree of protectionIEC 529EnclosureIP40
CoolingConvection
MountingHorizontal on 35 mm DIN-rail
EN 61000-4-8Enclosure300 A/m
EN 61000-4-29DC power ports10 & 100 ms, interruption
Storage & Transport-40 to +70ºC
Maximum surface temperatur 135 ºC (temperatur class T4)
Storage & Transport5 to 95% relative humidity
MIL-HDBK- 217F Operating700 000 hours @ 25°C
1500 Vrms 50 Hz 1 min
8
6642-22102
Description
The DDW-221 is an Industrial Ethernet SHDSL extender with support for redundancy.
The redundant protocol can be used ether on the SHDSL interface or on the built-in
Ethernet switch.
Our unique FRNT (Fast Recovery of Network Topology) technology is the fastest protocol on the market to re-configure a network in the event of any failure of a link or
hardware.
SHDSL represents the best of several symmetric DSL technologies. This unit provides the
ability to reuse existing twisted copper pair with data rates from 192 kbit/s to 5.7 Mbit/s
in both directions. The DDW-221 makes it possible to communicate over 10 km
(6.2 miles) on twisted pair cable.
The DDW-221 is a bridge not router and so is simple to install. All configuration is done
using a web interface.
The DIN rail mounted DDW-221 is designed for harsh environments and can be used
in industrial and railway applications. It can be powered from two separate supplies and
handle an operating voltage range of 16 – 60 VDC.
Redundant protocol (FRNT) on SHDSL or on the Ethernet switch …
192 kbit/s to 5.7 Mbit/s …
Over 10 km (6.2 miles) on twisted pair …
Daisy chain SHDSL applications …
Wide temperature range (–40 to +70°C) (–40 to 158°F) …
Total galvanic isolation & transient protection …
Industrial and Rail EMC approvals …
Redundant power and wide DC input range …
Configuration using web interface …
Integrated 4-port Ethernet switch with 10/100Base-TX …
Auto MDI/MDI-X …
Auto speed on SHDSL with reliable, normal or high-speed mode …
Comprehensive statistics …
• SHDSL
• Ethernet
SNMP support …
Extensive line protection with over-current / voltage suppression …
Diagram showing speed versus distance
DDW-221 @ 0.5 mm
Speed bit/sDistance metre / milesDistance metre / miles
19200010000 / 6.216450 / 4.00
10240007650 / 4.754850 / 3.01
12800007050 / 4.384700 / 2.92
23040005950 / 3.694150 / 2.58
33280004900 / 3.043700 / 2.30
45440004250 / 2.643150 / 1.95
56960003650 / 2.262800 / 1.73
Distance is tested without noise.
6642-22102
2
DDW-221 @ 0.4 mm
2
9
Interface specifications
Power
Rated voltage20 to 48 VDC
Operating voltage16 to 60 VDC
Rated current300 mA @ 20 VDC
150 mA @ 48 VDC
Rated frequencyDC
2
Inrush current, I
Startup current*400 mA
PolarityReverse polarity protected
Redundant power inputYes
Isolation toEthernet, SHDSL
ConnectionDetachable screw terminal
Connector size0.2 – 2.5 mm
Shielded cableNot required
* If external power supply is used it must meet specified inrush current.
SHDSL
t3.1 A2s
2
(AWG 24 – 12)
Electrical specificationITU-T G.991.2 Annex B
Data rate192 kbit/s to 5696 kbit/s
ProtocolEFM according to IEEE 802.3-2004
Transmission rangeAccording to ITU-T G.991.2 depending on the line quality
ProtectionOvercurrent / overvoltage protection circuit and varistor
Isolation toPower, Ethernet
ConnectionDetachable screw terminal
2
Connector size0.2 – 2.5 mm
(AWG 24 – 12)
Shielded cableNot required
Number of ports2
Ethernet TX
Electrical specificationIEEE std 802.3 2000 Edition
Data rate10 Mbit/s, 100 Mbit/s, manual or auto
DuplexFull or half
Transmission range100 m / 328 ft
Isolation toPower, SHDSL
ConnectionRJ-45
Shielded cableNot required, except when installed in Railway applications as
signalling and telecommunications apparatus and located close
to rails**
Number of ports4 ports marked as 1, 2, 3, 4
** To minimise the risk of interference, a shielded cable is recommended when the cable is located inside 3 m
* Direction relative this unit
** To minimise the risk of interference, a shielded cable is recommended when the cable is located inside 3 m
boundary to the rails and connected to this port. The cable shield should be properly connected (360°) to an
earthing point within 1 m from this port. This earthing point should have a low impedance connection to the conductive enclosure of the apparatus cabinet, or similar, where the unit is built-in. This conductive enclosure should
be connected to the earthing system of an installation and may be directly connected to the protective earth.
CAT 5 cable is recommended.
Unshielded (UTP) or shielded (STP) connectors
can be used.
6642-22102
11
LED indicators
LEDStatusDescription
PWROFFNo power
ON (green)Booting ready, unit ready
ON (red)Unit is booting
FRNTOFFFRNT disabled
ON (green)FRNT enabled and unit is ring
member, ring ok
Flashing (green)FRNT enabled and unit is focal point,
ring ok
Flashing (red)FRNT error and unit is focal point,
ring broken
ON (red)FRNT error according
to the following
1. If unit is ring member at least
one trunk port is down
2. If unit is focal point ring is not
intact
10/100BASE-TX
Port 1 – 4
Green LED
10/100BASE-TX
Port 1 – 4
Yellow LED
DSL
Port 1 – 2
OFFNo link
ON Link active
FlashingTraffic on link
OFFNo port alarm
ONPort alarm
OFFNo link
ON (green)Link established
ON (red)Unit is booting
Flashing (green)Link negotiation
Flashing (red))Downloading firmware to DSL chip
12
6642-22102
Daisy chain SHDSL connection
DDW-221
DDW-221
DDW-221
Connect DDW-120 to DDW-22x
In an SHDSL connection one unit shall be configured as CO (Central Office)
and one as CPE (Customer Premises Equipment). DDW-22x factory default is,
DSL1 configured as CPE and DSL2 configured as CO.
Redundant SHDSL connection
The DDW-221 are available with redundant ring technology. This eliminates
network failure caused by communication failures on the ring ports. In a ring
application one unit must be configured as focal point, all other units will be configured as members.
Connect DSL 1 to DSL 2 on the following units to obtain a chain of linked units.
DDW-221
DDW-221
DDW-221
DDW-221
6642-22102
13
Configuration
The unit can easily be configured via the onboard Web based configuration tool. Local
IP addresses can also be configured by using the Westermo IP Config too. From the IP
Config tool it is then possible to browse into the unit for further configuration.
IP Address
When delivered, the default IP address of the DDW-2XX is 192.168.2.200.
The default gateway is 192.168.2.200
If the default address of the unit is valid in the connected network it is possible to access
the unit directly from a web browser.
Change local IP address
The local address of DDW-2XX can be configured using the IP Configuration tool.
The IP Configuration program is available on the CD or for download from the
WESTERMO web page: http://www.westermo.com, (choose Downloads/Software/
Ethernet/Ethernet switches/)
Name: setup.exe
Install the software and start the application from a PC on the network connected to
where the DDW-2XX is installed. Make sure that the Default IP of the configuration software (see figure below) is in the same subnet as your PC.
Note! If you are not sure about the subnet – consult your network administrator.
Note! IP Config version must be 10.0.0 or higher.
By clicking the Scan for switches button the IP Configuration Software will detect the
Westermo switches on the network. The software will list all Westermo managed switches or routers connected to the network. Information as in figure 1 will appear for each
detected unit connected to the same network as your PC.
If you only want to change the IP address and the subnet mask, this
can be done within the IP config tool.
IP configuration
Access switch via web?
CancelOK
1. Click the listed DDW-2XX that you wish to re-configure.
2. A pop-up screen will show with the message “Access switch via web”.
Figure 2
Click Cancel, figure 2.
3. Enter the preferred IP address, Subnet mask and IP gateway address, figure 3.
Click Set-button to confirm the settings in the unit, figure 3.
Click the Scan for switches button again and the settings you configured will appear in
the list. Now you can access the DDW-2XX via the browser for further configuration
by clicking the unit with an IP address that fits your subnet. Figure 2 will appear and now
you click the OK button and a web browser will be opened and redirected to the DDW2XX unit login page, figure 5.
Selected Device
Click the Close button to get back to main view.
You will then be asked if you would like to quit.
DDW-221 configuration
192
IP adress:
Subnet mask:
MAC adress:
Host name:
Location:
IP gateway adress:
SetClose
IP configuration
You have set new parameters on the switch. The switch must be restarted in order for the new parameters to take effect (except IP address change). Type cancel to return to
selected dialog or OK if you still want to quit.
1682 200
255 2550
255
00 07 7C 80 4A 6C
Westermo
location
1921682 200
CancelOK
Click the OK button, figure 4, and you will be
back to the main view of the IP Configuration
program (see figure 1).
Figure 3
Figure 4
6642-22102
15
Westermo - location - Provided by Westermo
http://192.168.2.220/conf/p.cgi
File Edit View Favorites Tools Help
Westermo - location
Login
Username:
Password:
Log in via Web
You will be prompted with a Login screen where
the default settings for Username and Password are:
Username: admin
Password: westermo
Login
Done
Figure 5
The unit can be easily configured via the on-board Web based configuration tool.
The network interface and switch properties can be configured and stored.
The Web tool also has an extended integrated help function describing all
configuration options.
Note! Max 10 characters can be used in the login.
Note! For login the following characters are not valid.
The DDW-2XX supports Simple Network Management Protocol version 1 and 2c
(SNMPv1 and SNMPv2c). SNMP is an Internet standard protocol (IP) developed to
manage IP nodes (servers, workstations, routers, switches and hubs etc.) on an
Ethernet network.
SNMP enables network administrators and control engineers to manage network
performance, find and solve network problems, and plan for network growth.
The DDW-2XX MIB’s are divided into groups allowing the SNMP manager to poll
the SNMP agents for information.
16
6642-22102
Factory default
It is possible to set the unit to factory default settings by using two Ethernet cables and
connect to the unit.
To set the unit to factory default do the following:
1. Connect Ethernet cable from port 1 to port 4.
2. Connect Ethernet cable from port 2 to port 3.
3. Power up the unit.
4. Wait for the unit to start up. Control that the PWR led is flashing green.
The PWR flashing indicates that the unit will be set to factory default.
5. Remove the Ethernet cables, the unit will automatically start with factory
default settings.
Note! The Ethernet cables must be removed within 30 seconds from power up
or the unit will do a normal start up.
6642-22102
17
Mounting
This unit should be mounted on 35 mm DIN-rail, which is
horizontally mounted inside an apparatus cabinet or similar.
Snap on mounting, see figure.
35 mm DIN-rail shall be mounted with a maximum distance
of 70 mm between the mounting points.
This unit can also be wall-mounted, see figure.
POWER
CLICK!
PWR
FRNT
DSL 1DSL 2
10/100 BASE-TX
DSL 1
1
DSL 2
2
3
4
Cooling
This unit uses convection cooling. To avoid
obstructing the airflow around the unit,
use the following spacing rules. Minimum
spacing 25 mm (1.0 inch) above /below
the unit. Spacing is recommended for the
use of unit in full operating temperature
range and service life.
Removal
Press down the support at the back of the unit using
a screwdriver. See figure.
POWER
25 mm
PWR
FRNT
DSL 1DSL 2
10/100 BASE-TX
DSL 1
1
DSL 2
2
3
4
POWER
PWR
FRNT
DSL 1DSL 2
10/100 BASE-TX
DSL 1
1
DSL 2
2
3
4
25 mm
18
6642-22102