West 6100+, 4100+ Data sheet

6100+, 8100+ & 4100+ Temperature & Process Controllers
Jumperless Configuration
Auto Detected Hardware Process & Loop Alarms Modbus & ASCII Comms Auto or Manual Tuning Heat/Cool Operation Ramping Setpoint Remote/Dual Setpoint Options Available in 1/16, 1/8 & 1/4 DIN Formats
With their improved interface, technical functionality and field flexibility, the West 6100+, 8100+ and 4100+ give
you the best in comprehensive control for most temperature and process control loops.
Specification
Features
Control Types Full PID with Pre-tune, Self-tune, manual tuning, or On-Off control. Heat only or heat & cool Auto/Manual
Alarm 1 & 2 Types Process high, process low, SP deviation, band, logical OR / AND. Also 1 loop alarm for process control
Human Interface 4 button operation, dual 4 digit 10mm & 8mm high (6100+, 8100+) and 13mm & 10mm high (4100+)
PC Configuration Off-line configuration from PC serial port to dedicated config socket (comms option not required).
Selectable from front panel or via digital input, with bumpless transfer
setpoint
security. Process alarms have adjustable hysteresis.
LED displays, optional choice of colours (Red/Red, Red/Green, Green/Red or Green/Green), plus 5 LED indicators
Configuration Software for Windows 98 or higher. West Part Number: PS1-CON
Input
Thermocouple J, K, C, R, S, T, B, L, N & PtRh20%vsPtRh40%. RTD 3 Wire PT100, 50 per lead maximum (balanced) DC Linear 0 to 20mA, 4 to 20mA, 0 to 50mV, 10 to 50mV, 0 to 5V, 1 to 5V, 0 to 10V, 2 to 10V.
Impedance >10M for Thermocouple and mV ranges, 47K for V ranges and 5 for mA ranges Accuracy ±0.1% of input range ±1 LSD (T/C CJC better than 1°C) Sampling 4 per second, 14 bit resolution approximately Sensor Break Detection <2 seconds (except zero based DC ranges), control O/P’s turn off, high alarms activate for T/C and mV
Scaleable -1999 to 9999, with adjustable decimal point
ranges, low alarms activate for RTD, mA or V ranges
Outputs & Operations
Control & Alarm Relays Contacts SPDT 2 Amp resistive at 240V AC, >500,000 operations Control SSR Driver Outputs Triac Outputs 0.01 to 1 Amp AC, 20 to 280Vrms, 47 to 63Hz DC Linear Outputs 0 to 20mA, 4 to 20mA into 500 max, 0 to 10V, 2 to 10V, 0 to 5V into 500 min.
Transmitter Power Supply Output 24VDC (nominal) into 910 minimum to power external devices Communications 2 Wire RS485, 1200 to 19200 Baud, Modbus and ASCII protocol (selectable) Digital Input Selects between 2 setpoints or Auto/Manual control. Volt free or TTL input Remote Setpoint Input 0 to 20mA, 4 to 20mA, 0 to 5V, 1 to 5V, 0 to 10V or 2 to 10V. Scaleable -1999 to 9999. Local/Remote
Drive capability >10V DC in 500 minimum
Control outputs have 2% over/under drive applied. Accuracy ±0.25% at 250Ω (degrades linearly to 0.5% for increasing burden to specified limits)
setpoint selected from front panel
Ref – EC01/1/11/09
© West Control Solutions 2009
(app
45
Operating & Environmental
Temperature & RH
Power Supply
Front Panel Protection
Standards
Dimensions 6100+
48mm
8100+
48mm
96mm
4100+
96mm
0 to 55°C (-20 to 80°C storage), 20% to 95% RH non-condensing
100 to 240V 50/60Hz 7.5VA (optional 20 to 48V AC 7.5VA/22 to 65V DC 5 watts)
IEC IP66 (Behind panel protection is IP20)
CE, UL & ULC recognised
110mm 48mm
100mm
10mm
rox)
Cut out
100mm
96mm
92mm +0.5
x 45mm
+0.5 –0.0
92mm +0.5
Ref – EC01/1/11/09
© West Control Solutions 2009