West 6010 & 8010 Panel Indicator
Jumperles
s Configuration
Auto Detected Hardware
Up to 4 Alarm Outputs
Modbus & ASCII Comms
Min/max Value Hold
Tare (auto-zero) Function
Multi-point Scaling
PC configuration
The P6010 and P8010 have multi-point scaling, tare function and improved flexibility. They have a universal input
and are available with a red or green display. Plug-in modules allow up to four alarm relays (latching or non-
latching), PV retransmission or transmitter PSU.
Specification
Features
Output Configuration Up to 4 total. Max 3 single/1 dual relay, max 1 retransmit of PV, max 1 transmitter power supply
Alarms Up to 5. Process high low or logical OR (direct or reverse acting). With adjustable hysteresis
Viewable Values Process variable, maximum value, minimum value and alarm 1 elapsed time since reset
Human Interface 3 button operation, 4 digit 10mm (6010) or 13mm (8010) high red or green display, plus 3 alarm 1
PC Configuration Off-line configuration from PC serial port to dedicated config socket (comms option not required).
max and 1 min indicator
Configuration Software for Windows 98 or higher. West Part Number: PS1-CON
Input
Thermocouple J, K, C, R, S, T, B, L, N & PtRh20%vsPtRh40%.
RTD 3 Wire PT100, 50Ω per lead maximum (balanced)
DC Linear 0 to 20mA, 4 to 20mA, 0 to 50mV, 10 to 50mV, 0 to 5V, 1 to 5V, 0 to 10V, 2 to 10V.
Impedance >10MΩ for Thermocouple and mV ranges, 47KΩ for V ranges and 5Ω for mA ranges
Accuracy ±0.1% of input range ±1 LSD (T/C CJC better than 1°C)
Sampling 4 per second, 14 bit resolution approximately
Outpu
ts & Options
Single Alarm Relays Contacts SPDT 2 Amp resistive at 240V AC, >500,000 operations. Latching or non-latching
Dual Alarm Relay Two x SPST contacts with shared common. 2 Amp resistive at 240V AC, >200,000 operations.
SSR Driver Outputs
Triac Outputs 0.01 to 1 Amp AC, 20 to 280Vrms, 47 to 63Hz
DC Linear Retransmit Outputs 0 to 20mA, 4 to 20mA into 500Ω max, 0 to 10V, 2 to 10V, 0 to 5V into 500Ω min.
Transmitter Power Supply Output 24VDC (nominal) into 910Ω minimum to power external devices
Serial Communications 2 Wire RS485, 1200 to 19200 Baud, Modbus and ASCII protocol (selectable)
Digital Input External reset of latched relay, stored alarm 1 elapsed time, stored min/max PV values or initiate tare
Opera
ting & Environmental
Temperature & RH 0 to 55°C (-20 to 80°C storage), 20% to 95% RH non-condensing
Power Supply 100 to 240V 50/60Hz 7.5VA (optional 20 to 48V AC 7.5VA/22 to 65V DC 5 watts)
Front Panel Protection IEC IP66 (Behind panel protection is IP20)
Standards CE, UL & ULC recognised. Pollution Degree 2, Installation Category II
Scaleable -1999 to 9999, with adjustable decimal point
Latching or non-latching
Drive capability >10V DC in 500 minimum
Accuracy ±0.25% at 250Ω (degrades linearly to 0.5% for increasing burden to specified limits)
function. Volt free or TTL input
Ref
DS-Px010-1209-1-EN
© West Control Solutions 2009
Dimensions
6010
8010
48mm
96mm
10mm (approx)
110mm
48mm
10mm (approx)
100mm
48mm
Cut out
45mm +0.5
45mm +0.5
45mm +0.5
92mm +0.5
Wiring Connections
6010
Field Reconfiguration
Input
Jumper-free configuration for any type
(no extra parts required)
Option Slot 1 Part Number
Relay Output........................... PO1-C10
Linear mA/V DC Output .......... PO1-C21
SSR Driver Output .................. PO1-C50
Triac Output ............................ PO1-C80
Option Slot 2 Part Number
Relay Output........................... PO2-C10
Dual Relay Output ................. PO2-W09
Linear mA/V DC Output .......... PO2-C21
SSR Driver Output .................. PO2-C50
Triac Output ............................ PO2-C80
Option Slot 3 Part Number
Relay Output........................... PO2-C10
Linear mA/V DC Output .......... PO2-C21
SSR Driver Output .................. PO2-C50
24VDC Transmitter PSU........ PO2-W08
Option Slot A Part Number
Digital Input............................ PA1-W03
RS485 Comms ...................... PA1-W06
Ref
DS-Px010-1209-1-EN
© West Control Solutions 2009