Customer Service +1 800.390.6405 • Technical Support +1 800.866.6659
www.westinstruments.com • www.danaherindustrialcontrols.com
Process Automation Worldwide Brands: LFE
TM
• Partlow
TM
• PMA
TM
• Rustrak
TM
• West
TM
2300
™
Small Size – Big Capability
SPECIFICATIONS*
CONTROL ADJUSTMENTS
On/Off Hysteresis: 0.1% to 10.0% of Input
Span
Proportional Band: 0.5% to 999.9%
Manual Reset: 0% to 100%
Auto Reset: 1 sec to 99 minutes 59
seconds and OFF
Rate: 0 (OFF) to 9 mins. 59 sec
Cycle Time: 0.5 sec (SSR Drive only) 1, 2,
4, 8, 16, 32, 64, 128, 256, and 512
seconds
Control Algorithms: Direct/reverse acting
PID or ON/OFF
Automatic Tuning Types: Pre-Tune or EASY
TUNE
PERFORMANCE
Measurement Accuracy: ± 0.1% of span, ±
1 LSD at 20 deg C
Note: Reduced performance with
Type "B" thermocouple between
100-600C (212-1112F).
Ambient Temperature Error: 0.01% of span
/deg C change in ambient
Linearization Accuracy: (TC and RTD)
Better than ± 0.2 deg C any point, 0.1
deg C range (± 0.05 deg C typical).
Better than ± 0.5 deg C any point, any 1
deg C range
Cold Junction Compensation: Better than
± 0.7 deg C
Noise Rejection: Common mode: >120dB
at 50/60Hz giving negligible effect at up
to 264V 50/60Hz
Series Mode: >500% of span (at
50/60Hz) causes negligible effects.
Source Resistance: 1000 ohm maximum
(thermocouple)
Lead Resistance: 50 ohm per lead
maximum balanced (Pt100)
PHYSICAL DIMENSIONS
Dimensions: 1/32 DIN front panel, 100mm
(3.9") deep
Weight: 100 g. (3.53 oz.)
STANDARD FEATURES
Full PID capability
Single or dual outputs via relay or SSR
driver
Indicator only, indicator with alarm or full
contoller models available
One or two alarm outputs
Universal Input for thermocouple, RTD, DC
linear mA/mV
ENVIRONMENTAL CHARACTERISTICS
Operating Temperature: 0 to 55°C, 32 to
131°F
Storage Temperature: -20 to 80°C, -4 to
176°F
Humidity: 20 to 90% RH, non condensing
ELECTRICAL
Line Voltage: 90 to 264VAC, 50/60 Hz
standard; 12 to 24VAC 50/60Hz or 12 to
30VDC (optional)
Power Consumption: 4 Watts maximum
INPUTS
Thermocouple types: J, K, T, R, S, B, and N.
RTD: 100 ohm (.00385 Ohm/Ohm/C)
Millivolts: 0 to 50mVDC, 10 to 50mVDC
Milliamps: 0 to 20 or 4 to 20mADC,
OUTPUTS
Relay: SPDT, 2.0 A Resistive @ 120/240VAC
SSR Driver: >10V DC into 500Ω minimum
(50mA maximum)
DISPLAY
Digital Display: Four 7 segment LEDs,
0.39” high
Status Indicators: Individual LED indictors
for Control, Alarm, and Configuration
status
ALARM ADJUSTMENT
Process Alarm: ± Input Span
Deviation Alarm: -1999 to + Input Span
Deviation Band Alarm: 1 to Input Span
COMMUNICATIONS
Type: Serial asynchronous UART-to UART Link
Data Format: 1 start bit, selectable parity (odd,
even or none), 8 data bits, 1 stop bit.
Physical Layer: RS-485 (two wire)
Presentation Layer: Modbus RTU protocol
Maximum Number of Zones: 128
Baud Rate: Selectable in range 9600, 4800,
2400, 1200
Zone Address Range: 1 to 128
RATINGS/AGENCY APPROVALS
UL & cUL recognized (E67237), CE
WARRANTY
3 years
1/32 DIN Temperature Controller/Indicator
* Specifications are for base models with standard features
only unless otherwise noted. Specifications subject to
change without notice in accordance with our DBS policy
of continuous improvement. All product and brand names
are trademarks of their respective owners. All rights
reserved.
West™ brand and 2300™ are trademarks of Danaher Industrial Controls
Group. All rights reserved.
© 2005 DICG Corp.
West Brand 2300 Data Sheet (7/05)