Weil-McLain WMBC-1A User Manual

Page 1
LGB
Gas–fired boiler
Control Supplement
Flame Guardian WMBC-1A
RM7895C Controller Electronic Pilot System
IRI
Contents
II. Gas piping ...................... 5
III. Wiring ............................. 5
IV.Startup ......................... 10
V. Sequence of operation 11
VI.Parts list ....................... 12
Indicates presence of hazards that can cause severe personal injury, death or substantial property damage.
Indicates special instructions on installation, operation or maintenance that are important but not related to personal injury or property damage.
This Control Supplement must only be used by a qualified installer/service technician. Read these instructions completely before beginning the installation. Failure to follow these instructions can cause severe personal injury, death or substantial property damage.
Part Number 550-141-807/0298
Page 2
LGB
(Series 2) — Control Supplement
I Installation
1. For use with LGB-6 through 12 boilers.
2. LOCAL INSPECTOR MUST CERTIFY BOILER FOR IRI COMPLIANCE.
3. Assemble pilot burner and flame sensor to main burners with pilot brackets. See Figures 2 and 3. Install ground wiring as shown in Figures 2 and 3.
4. Reinstall burner assemblies. See Table 1 for pilot burner and flame sensor locations.
5. Assemble control panel to boiler. See Figure 1.
6. Install gas controls as shown in Figure 4, page 4.
7. IRI installations require manual reset controls. Weil-McLain recommends installing manual controls in addition to standard as required by local inspector. Refer to the LGB Boiler Manual, “Boiler Controls” sect ion.
a. Steam boilers require a manual reset Low Water Cutoff and manual reset Pressure Limit
Control.
b. Water boilers require a manual reset Low Water Cutoff and manual reset Temperature
Limit Control.
Table 1
Pilot burner and flame sensor
locations
Figure 1
Mount control panel to jacket
as shown
Boiler Model Flame Sensor * Pilot Burner *
LGB-6 29 LGB-7 211 LGB-8 213 LGB-9 215 LGB-10 216 LGB-11 216 LGB-12 216
* From left burner.
Panel
Front of Boiler
Drill (3) Holes in Front
Drill (7) 1/8“
Drill (7) 1/8“
Holes In Jacket
Holes In Jacket
to Mount
to Mount
Bracket
Bracket
Drill (4) Holes in SideDrill (4) Holes in Side
Part Number 550-141-807/02982
55BGL
Page 3
Flame Guardian WMBC-1A Electronic Pilot System – IRI
I Installation – continued
Figure 2
Q179 pilot burner assembly
Figure 3
Main flame sensor assembly
LGB-A56
Locating Slot
Burner Support Bar
Pilot Line Tubing
Locating Slot
Sensor
Igniter
Sensor Lead
Flame Sensor
Igniter Lead
Q179 Pilot Burner
Compression Union
10-32 x 5/16“
Machine Screws(2)
Ground Leadwire:
Connect to WMBC
Panel Terminal G2 (Ground Terminal)
Pilot Mounting
Bracket
10-32 x 1/4“
Machine Screws (2)
Main Burner
(with Pilot
Mounting
Bracket)
6-32 x 5/16“ Type ”F”
Self Tapping Screws(2)
10-32 x 5/16“
Machine Screws(2)
Ground Leadwire:
Connect to Main Flame
Proving Module
24 V (GND) terminal
Burner Support Bar
Flame Sensor
Mounting Bracket
Sensor Lead
LGB-A85
Main Burner
(with Pilot
Mounting
Bracket)
Part Number 550-141-807/0298 3
Page 4
LGB
(Series 2) — Control Supplement
I Installation – continued
Figure 4
IRI gas train schematic
Atmosphere
Vent to Outside
6
5
3
7
Boiler Jacket
2
Drip Leg Service Valve
1718
1
4
8
GAS PIPING DIAGRAM - LGB (Series 2)
1
Manual main shut-off gas valve
2
Low gas pressure switch
3
Pilot manual shut-off valve
4
Motorized gas valve w/ on/off actuator
5
Pilot gas pressure regulator
6
Normally open solenoid vent valve
7
Pilot solenoid gas valve
8
Test cock Second motorized gas valve w/ on/off actuator
9
18
11
9
IRI Gas Train
10
Manual leak checking gas valve
11
Regulating diaphragm gas valve (two stage)
12
High gas pressure switch
13
Main flame sensor
14
Main burner with main flame sensor bracket
15
Pilot burner
16
Main burner with pilot burner bracket Adapter, for N. O. vent valve
17
18
Pipe flanges
10
12
14
1613 15
Part Number 550-141-807/02984
Page 5
Flame Guardian WMBC-1A Electronic Pilot System – IRI
’20’30’40’50’75’
II Gas piping
1. Size gas piping considering: a. Diameter and length of gas supply piping. b. Number of fittings. c. Maximum gas consumption (including any possible future expansion). d. Allowable pressure drop from gas meter outlet to boiler. For pressure drops, see ANSI-Z223.1 – latest
edition.
2. Size natural gas piping from table below. Size piping to provide proper inlet pressure to gas valve when operating at rated input. a. Inlet gas pressure to manual main shutoff gas valve minimum 7” W.C. standard (5½” on special order) –
maximum 13” W.C.
b. If pressure to gas valve exceeds 13” W.C., install positive dead-end lockup gas pressure regulator up stream of
hand valve.
c. To obtain approximate cubic feet per hour, divide input (BTU/HR) by 1000.
3. Remove gas supply knockout disc from jacket panel.
4. Follow good piping practices.
5. Pipe joint compound (pipe dope) must be resistant to corrosive action of liquefied petroleum gases. Apply sparingly only to male threads of pipe joints.
6. Install drip leg at inlet of gas connection to boiler. Where local utility requires, extend drip leg to floor.
7. Install ground joint union when required for servicing.
8. Support piping by hangers, not by boiler or its accessories.
9. Purge all air from supply piping.
10. Check all connections for leaks.
Do not check for gas leaks with an open flame – BUBBLE TEST. Failure to use bubble test or test for leaks can cause severe personal injury, death or substantial property damage.
a. Close manual main shutoff valve during any pressure testing at less than 14.0 inches water column. b. Disconnect boiler and gas controls from gas supply piping during any pressure test greater than 14.0 inches
water column.
11. Set gas pressure switches as follows or to local inspector’s requirements: a. Low – 3.0” W.C. b. High – 14.0” W.C
Table 2
Natural gas
supply pipe
sizing
PIPE SIZE
1¼" 1,050 730 590 500 440 360 305 250 1½" 1,600 1,100 890 760 670 545 460 380
2½" 4,800 3,300 2,700 2,300 2,000 1,650 1,400 1,130
* Include measured length of gas supply piping and allowance in feet for number and size of fittings.
PIPE LENGTH, FEET (NATURAL GAS CAPACITIES, LISTED IN MBH) (Specific Gravity 0.60 @ Pressure Loss of 0.30" w.c.)
2" 3,050 2,100 1,650 1,450 1,270 1,020 870 710
3" 8,500 5,900 4,700 4,100 3,600 2,900 2,500 2,000 4" 17,500 12,000 9,700 8,300 7,400 6,000 5,100 4,100
III Wiring
For your safety, turn off electrical power supply before making any electrical connections to avoid possible electrical shock hazard.
1. All wiring must be installed in accordance with the requirements of the National Electrical Code and any additional national, state or local code requirements having jurisdiction. All wiring must be N.E.C. Class 1.
2. The boiler must be electrically grounded in accordance with the National Electrical Code, ANSI/NFPA No. 70­latest edition. Use 105 °C. thermoplastic wire, or equivalent, if any of the original wire must be replaced (except for pilot spark, sense and ground wires).
3. Supply wiring to the boiler must be No. 14 gauge or heavier. Install in conduit.
4. A separate electrical circuit with a fused disconnect switch (15 amp. recommended) should be used for the boiler.
10
100
150
Part Number 550-141-807/0298 5
Page 6
LGB
Figure 5 — WMBC-1A panel wiring schematic
(Series 2) — Control Supplement
Flame Guardian WMBC-1A Electronic Pilot System – IRI
Part Number 550-141-807/02986
Part Number 550-141-807/0298 7
Page 7
LGB
(Series 2) — Control Supplement
Figure 6 — WMBC-1A panel wiring diagram – factory wiring
Part Number 550-141-807/02988
Page 8
Flame Guardian WMBC-1A Electronic Pilot System – IRI
Figure 7 — WMBC-1A field wiring diagram
Part Number 550-141-807/0298 9
Page 9
LGB
Low Fire Adjustment
(Series 2) — Control Supplement
IV Start-up
Turn off electrical power supply and gas supply to boiler before making the following connections and adjustment. Failure to do so can cause severe personal injury, death or substantial property damage.
1. Disable high fire by disconnecting the blue wire in the two-stage gas valve.
2. Connect manometer to gas manifold (manometer must be capable of measuring 0” to 14” W.C.).
3. Turn on electrical power supply and gas supply to boiler.
4. Fire boiler, which will light off and remain on low fire.
5. While reading manometer, turn low fire adjustment screw clockwise (Figure 5) until pressure reading is 1.2” W.C.
6. Turn off boiler.
Turn off electrical power supply and gas supply to boiler before the following steps. Failure to do so can cause severe personal injury, death or substantial property damage.
7. Remove manometer from manifold and plug the tapping.
8. Reconnect the blue wire in the two-stage gas valve junction box.
9. Turn on electrical power supply and gas supply to boiler.
10. Follow operating instructions label on boiler to set boiler in operation.
Figure 8
Low fire adjustment
Part Number 550-141-807/029810
Page 10
Flame Guardian WMBC-1A Electronic Pilot System – IRI
V Sequence of operation
1. Operating control begins startup sequence: a. Limit control contacts are closed. b. Purge timer is energized.
2. Flame safeguard control pilot circuit energizes after 2.0 seconds. a. Pilot gas valve opens. b. Ignition transformer energizes. c. Yellow “pilot on” lamp lights. d. Pilot ignition spark begins. e. Pilot ignites. f. Pilot flame proves.
3. Flame safeguard control energizes main flame circuit: a. Blue “gas valve on” lamp lights. b. Gas control train energizes. c. Downstream gas valve opens to low-fire position. d. Main burners ignite, operate at low fire.
4. Ignition transformer de-energizes after 10-second trial for ignition.
5. Pilot de-energizes after 10-second trial for main flame. Yellow “pilot on” lamp goes out.
6. Main flame sensor proves main burner operation at low fire.
7. Flame safeguard control energizes downstream gas valve to high-fire (through firing rate control, when used):
a. Main burners operate at high fire. b. Main burners operate at low fire when water temperature or pressure reaches setting of
firing rate control, when used.
8. Boiler shuts down when operating control satisfied.
9. Flame safeguard control lockout circuit energized if pilot is not proved during start-up or if main flame is not proved during run sequence.
a. Flame safeguard control locks out on safety. b. Red “alarm” lamp, alarm relay, and alarm bell energize. Silencing switch can shut off
alarm bell. c. Alarm relay de-energizes purge timer. d. Press reset button on flame safeguard control to permit normal start-up after correcting
lockout condition. e. Normal start-up resumes after purge timer automatically resets (5 minute enforced
wait).
Part Number 550-141-807/0298 11
Page 11
LGB
p
(Series 2) — Control Supplement
VI Parts list – Table 3
Description Size Vendor/Part Number Weil-McLain Part Number
Primary Control Honeywell RM7895C1012 510-350-431 Prepurge Timing Card 2.0 Seconds Honeywell ST7800A1005 510-350-432 Flame Amplifier Honeywell R7847A1033 510-350-434 Electric Bulb 120V Sylv. 120MB/CHI Min. CM8-967 * Fuse 6 Amp. Bussman MTH-6 * Relay 120V DPDT Honeywell R4222D1013 510-311-012* Control Timer SSAC EDRM427 510-350-430
Gas Cock, ¼ M x ¼ F Conbraco 53-300-01 * Pilot Regulator, ¼ NPT Maxitrol RV20A * Pilot Solenoid ¼" Honeywell V4046C
Johnson Controls H91ABA Brass Union, 1/8 NPT x 1/4cc * Low Gas Pressure Switch Honeywell C645A1030 511-624-550* High Gas Pressure Switch Honeywell C645B1013 511-624-555* Gauge Cock ¼" Conbraco 41-560-05 511-210-415* Pilot Burner Honeywell Q179C1009 511-330-181* Pilot Bracket Weil-McLain 460-005-624 Main Flame Sensor Honeywell 392956 511-724-274 Main Flame Sensor Bracket Weil-McLain 423-300-420 Main Burner with Bracket Weil-McLain 512-200-055 Ignition Transformer Honeywell Q624A1014 511-802-014*
1" Essex 500 *
Hand Valve
Valve Body (small - u
Pipe Flanges (for Valve Body)
Actuator For Valve Body (On/Off) Honeywell V4055A 510-744-317 Solenoid Vent Valve
(Normally Open) Adapter for small valve body
(for vent valve)
Gas Valve with Regulator
to 2" Pipe Flanges)
1 ¼" Essex 600 * 1 ½" Conbraco 50-603 *
2" Conbraco 50-703 *
Honeywell V5097A 510-744-315
1" Honeywell 32000109-002 511-044-170 1 ¼" Honeywell 32000109-003 511-044-171 1 ½" Honeywell 32000109-004 511-044-172
2" Honeywell 32000109-005 511-044-173
¾" Honeywell V4295S 511-046-340
1" Honeywell V4295S 511-046-342
Honeywell 32002513 511-044-176
1" Honeywell V4944N1011 511-048-503 1 ¼" Honeywell V4944N1029 511-048-502 1 ½" Honeywell V4944N1037 511-048-501
2" Honeywell V4944N1045 511-048-500
* Listed part can be purchased at local supply house
511-044-040*
Weil-McLain
500 Blaine Street
Michigan City, IN 46360-2388
http://www.weil-mclain.com
Part Number 550-141-807/029812
Loading...