Weil-McLain WJB1, WJB2 User Manual

Page 1
®
88
Water & Steam Boilers – Series 2
Flame retention burners for
Gas, Light Oil, & Gas/Light Oil firing
Burner Specification
& Data Sheet
Models WJB1 & WJB2
Gas burner
Webster
Gas/light oil burner
W
E
B
H
Part Number 550-142-022/0509
L
C
A
D
Page 2
Webster – Model WJB
Boiler
Model
Number
88
Series 2
488R 6.9 996 0.68 WJB1G-03 WJB1O-03 WJB1C-03 RM7897A R7184A RM7897C A A A 1/3 1/3 1/3 See notes
488 7.0 1010 0.70 WJB1G-03 WJB1O-03 WJB1C-03 RM7897A R7184A RM7897C A A A 1/3 1/3 1/3 See notes
588 9.4 1357 0.60 WJB1G-05 WJB1O-05 WJB1C-05 RM7897A R7184A RM7897C LFS LFS LFS 1/2 1/2 1/2 See notes
688 11.8 1701 0.58 WJB1G-07 WJB1O-07 WJB1C-07 RM7897A R7184A RM7897C LFS LFS LFS 3/4 3/4 3/4 See notes
788 14.2 2046 0.65 WJB1G-07 WJB1O-07 WJB1C-07 RM7897A R7184A RM7897C LFS LFS LFS 3/4 3/4 3/4 See notes
888 16.6 2382 0.66 WJB2G-07 WJB2O-10 WJB2C-10 RM7897A RM7897A RM7897C LFS LFS LFS 3/4 1 1 See notes
988R 17.2 2482 0.54 WJB2G-10 WJB2O-10 WJB2C-10 RM7897A RM7897A RM7897C LFS LFS LFS 1 1 1 See notes
988 18.8 2737 0.63 WJB2G-10 WJB2O-10 WJB2C-10 RM7897C RM7897A RM7897C LFS LFS LFS 1 1 1 See notes
1088R 20.0 2887 0.68 WJB2G-10 WJB2O-15 WJB2C-15 RM7897C RM7897A RM7897C LFS LFS LFS 1 1 1/2 1 1/2 See notes
1088 21.5 3082 0.78 WJB2G-10 WJB2O-15 WJB2C-15 RM7897C RM7897A RM7897C LFS LFS LFS 1 1 1/2 1 1/2 See notes
1188 23.5 3428 0.78 WJB2G-15 WJB2O-15 WJB2C-15 RM7897C RM7897A RM7897C LFS LFS LFS 1 1/2 1 1/2 1 1/2 See notes
1288 26.0 3773 0.76 WJB2G-15 WJB2O-15 WJB2C-15 RM7897C RM7897A RM7897C LFS LFS LFS 1 1/2 1 1/2 1 1/2 See notes
1388 28.5 4119 0.77 WJB2G-20 WJB2O-15 WJB2C-20 RM7897C RM7897A RM7897C LFS LFS LFS 2 2 2 See notes
1488 31.0 4464 0.78 WJB2G-20 WJB2O-15 WJB2C-30 RM7897C RM7897A RM7897C LFS LFS LFS 2 2 3 See notes
1588 33.0 4809 0.73 WJB2G-20 WJB2O-30 WJB2C-20 RM7897C RM7897A RM7897C LFS LFS LFS 2 3 2 See notes
1688R 34.5 4979 0.68 WJB2G-30 WJB2O-30 WJB2C-30 RM7897C RM7897A RM7897C LFS LFS LFS 3 3 3 See notes
1688 35.5 5155 0.74 WJB2G-30 WJB2O-30 WJB2C-30 RM7897C RM7897C RM7897C LFS LFS LFS 3 3 3 See notes
1788 38.0 5494 0.82 WJB2G-30 WJB2O-30 WJB2C-30 RM7897C RM7897C RM7897C LFS LFS LFS 3 3 3 See notes
1888 40.5 5845 0.80 WJB2G-30 WJB2O-30 WJB3C-50 RM7840L RM7897C RM7840L MOD LFS MOD 3 3 5 See notes
Standard Voltage Notes: 1/3 HP blower motor through ¾ HP – 120V/60/3 phase, 1 HP blower motor – 240V/60/3 phase, 1-½ HP blower motor through 5 HP- 240V/60/3 phase
Burner Input
No. 2
Oil
GPH
Gas
MBH
Positive
Pressure in
Firebox In. W.C.
Standard Burner Model
Designation
Gas
Light
Oil
Gas/
Light Oil
Standard Combustion
Control
Gas
Light
Oil
Gas/
Light Oil
Standard Control
System
Gas/
Light
Gas
Oil
Light
Oil
Burner Motor
3450 RPM H.P.
Light
Oil
Gas/ Light
Gas H.P.
Standard
Voltage
Oil
Standard Gas Components and Sizes in Inches
Boiler Model
Number
488R 1-¼ Optional 1-¼ 1 n/a n/a 1-¼ 1 Optional
488 1-¼ Optional 1-¼ 1 n/a n/a 1-¼ 1 Optional 588 1-¼ Optional 1-¼ n/a 1-¼ n/a 1-¼ 1-¼ Optional 688 1-½ Optional 1 ½ n/a 1-½ n/a 1-½ 1-½ Optional 788 1-½ Optional 1 ½ n/a 2 n/a 2 2 Optional 888 1-½ Optional 1 ½ n/a 2 n/a 2 2 Optional
988R 1-½ Optional 1 ½ n/a 2 n/a 2 2 Optional
988 1-½ Standard 1 ½ n/a 2 n/a 2 2 Standard
1088R 1-½ Standard 1 ½ n/a 2 n/a 2 2 Standard
1088 2 Standard 2 n/a 2 n/a 2 2 Standard
1188 2 Standard 2 n/a 2 n/a 2 2 Standard 1288 2-½ Standard 2-½ n/a 2 n/a 2-½ 2 Standard 1388 2-½ Standard 2-½ n/a 2 n/a 2-½ 2 Standard 1488 2-½ Standard 2-½ n/a 2 n/a 2-½ 2 Standard 1588 2-½ Standard 2-½ n/a 2 n/a 2-½ 2 Standard
1688R 2-½ Standard 2-½ n/a 2 n/a 2-½ 2 Standard
1688 2-½ Standard 2-½ n/a 2 2” 2-½ 2 Standard 1788 2-½ Standard 2-½ n/a 2-½ 2-½ 2-½ 2-½ Standard 1888 2-½ Standard 2-½ n/a 2-½ 2-½ 2-½ 2-½ Standard
Notes
Manual
Hand Valve
Low Gas Pressure
Switch
Gas Pressure
Regulator
Burner capacities listed for elevations up to 2,000 feet. For higher elevations, consult local Weil-McLain distributor/agent or sales office.1.
Light Oil ratings based on No. 2 fuel oil with heating value of 140,000 Btu per gallon.2. Gas ratings based on natural gas with heating value of 1,000 Btu per cubic foot and specific gravity of 0.60. Gas burners for other gases are available. Consult local 3.
Weil-McLain distributor/agent or sales office. Boiler-burner unit to be adjusted to achieve +0.10 inches W.C. pressure at the flue collar, resulting in positive pressure in firebox as listed.4.
Diaphragm
Operating Gas Valve
Motorized Operating Gas Valve
Motorized Operat-
ing Gas Valve w/
Proof of Closure
Safety Gas
Valve
Manual
Checking
Gas Valve
High Gas
Pressure
Switch
Minimum gas pressures listed are subject to variations due to job conditions. Gas burners for other gas pressures are available. Consult local Weil-McLain distribu-5. tor/agent or sales office.
Gas orifice pressures shown are for initial start-up. Final pressures should be determined after checking actual gas flow and combustion readings.6.
Part Number 550-142-022/05092
Page 3
Burner Specification and Data Sheet
Gas Control Systems:7.
A (OO): On-off operation, low fire start, high fire run. Single-position air, adjustable opening gas valve. L (LFS): On-off operation, low fire start, high fire run. Two-position air controlled by damper arm on motorized gas valve. H (LHL): Low-high-low-off firing conditions. Two-position air controlled by damper arm on motorized gas valve. M (MOD): On-off operation, with proven low fire start and full modulating firing conditions with combustion air control. Proportional motor drives fuel metering valve and combustion air damper according to the firing conditions. Fixed damper pre-purge on 488-988R, open damper pre-purge on 988-1888.
Gas
Pressure
required at
Pressure
Boiler
drop thru
Model
Number
Standard Oil Pump Location: 488R through 1488 Gas / Oil – Integral to Burner, 1588 through 1888 Remote Pump 488R through 1688 Oil – Integral to Burner, 1788 and 1888 Remote Pump
gas train
Inches
W.C.
488R 2.3 2.4 5.5 14 1/4 1 1-1/4 1-5/16 1 1 4.00 Hago P 45º 300 100 22R220D 45
488 2.3 2.5 5.7 14 1/4 1-13/16 1-7/16 1-9/16 1-3/16 1 4.00 Hago P 45º 305 100 22R220D 45 588 3.7 2.8 7.0 28 1/2 13/16 1-7/8 1-7/8 1-3/16 1 5.50 Hago P 45º 290 100 22R220D 45 688 2.7 3.2 6.2 28 7/16 7/8 1-3/16 1-5/16 1 1 7.00 Hago P 45º 290 100 22R220D 45 788 2.9 2.8 5.1 28 1/2 1-3/8 1-13/16 1-7/8 1-1/2 2 4.25 Hago P 60º 280 100 22R221D 70 888 2.55 1.8 4.5 28 5/8 1-1/2 1 1-3/4 1-1/2 1 10.00 Hago P 45º 280 100 22R221D 70
988R 3.15 1.7 4.9 28 5/8 1-3/4 1-1/8 1-7/8 1-3/4 1 10.00 Hago P 45º 300 100 22R221D 70
988 3.8 1.8 5.8 28 1-3/16 1-5/16 1-1/4 1-1/2 1-3/16 1 11.00 Hago P 45º 290 100 22R221D 70
1088R 4.4 2.2 6.6 28 5/8 1-1/8 1-3/8 1-1/4 1-1/8 2 6.00 Hago P 45º 280 100 22R221D 70
1088 3.2 2.4 6.0 28 3/4 1-5/16 1-7/16 1-7/16 1-5/16 2 6.50 Hago P 45º 280 100 22R221D 70 1188 4.0 2.0 6.4 28 3/4 1-3/4 1-13/16 1-7/8 1-3/4 2 7.00 Hago P 45º 280 100 22R221D 70 1288 3.0 2.4 6.0 28 13/16 2-1/16 2-5/16 2-5/8 2-1/8 2 7.50 Hago P 45º 300 100 22R221D 70 1388 3.8 2.0 6.3 28 3/4 1-1/2 2-1/2 2-1/2 1 7/8 2 8.50 Hago P 60º 290 100 22R322D 105 1488 4.6 2.6 7.7 28 15/16 2-3/16 2-1/8 2-1/4 2 2 9.00 Hago P 60º 300 100 22R322D 105 1588 5.1 2.8 8.7 28 1 2-1/8 3-3/8 3-1/4 2-1/4 2 10.00 Hago P 60º 280 100 22R322D 105
1688R 4.6 2.9 9.2 28 1 1/16 2-1/2 1-7/8 2-1/4 1-1/2 2 10.00 Hago P 60º 300 100 22R623D 135
1688 6.1 3.1 9.8 28 1 2-5/8 2-1/4 2-1/2 2-1/8 2 10.50 Hago P 60º 295 100 22R623D 135 1788 5.25 4.5 9.1 28 9/16 2-1/4 3-1/4 3-1/4 3 2 11.00 Hago P
1888 5.7 6.0 10.4 28 1 3 1-3/4 1-7/8 1-7/8 3 8.0 Delevan 60º 300 65 SG0550 108
orice
pressure
Inches
Gas
W.C.
Gas Control
Inlet
Inches
W.C.
Min. Max.
Initial Damper
Setting Inches
(Oil)
Low
High Fire High Fire
Fire
Light Oil Control Systems:8.
LF (FALFS): On-off operation, fixed air, reduced fuel low fire start, high fire run. Single-position air, two-position oil.
L (LHO): On-off operation, low fire start, high fire run. Two-position air, two-position oil.
H (LHL): Low-high-low-off firing conditions. Two-position air, two-position oil.
M (MOD): On-off operation, with proven low fire start and full modulating firing conditions. Proportional motor drives fuel metering valve and combus-
tion air damper according to the firing conditions. Fixed damper pre-purge on 488-1088R, open damper pre-purge on 1088-1888.
Gas/Light Oil Control Systems:9.
A/LF (OO/FALFS): Combines gas and light oil characteristics listed above.
L/L (LHO/LHO): Combines gas and light oil characteristics listed above.
H/H (LHL/LHL): Combines gas and light oil characteristics listed above.
M/M (MOD/MOD): Combines gas and light oil characteristics listed above.
120/60/1 control circuit is used for all burners.10.
Control circuit transformer is available as an option.11.
Motor starter contact will be furnished for all units.12.
Combustion Controls:13.
a) R8184G combustion control uses cadmium cell for flame detector to monitor oil burner flame, also furnishes intermittent ignition.
b) RM7897 flame safeguard control uses ultraviolet electronic flame detector to monitor gas or oil burner flame and provides pre-purge programming. “A”
models provide intermittent pilot; “C” models provide interrupted pilot and RUN/TEST switch.
c) RM7840M, E110/EPD390 flame safeguard control monitors the oil or gas burner flame, provides pre-purge and post-purge programming. Timed low fire
start is provided by means of timing built into control. Control is used with UL on-off (low fire start) systems. Ultraviolet sensitive electronic flame detector is standard with infrared detector available.
d) RM7840L, E110/EPD170 flame safeguard control monitors the oil or gas burner flame, provides pre-purge and post-purge programming, provides switch-
ing necessary to allow firing rate motor to be driven to both low fire and high fire positions, prevents start-up if pre-ignition interlocks are open and has low fire start proving circuit. In the event pre-ignition interlock circuit or running interlock circuit does not “prove”, system will lock out on safety. Ultraviolet sensitive electronic flame detector is standard with infrared detector available.
Initial
Damper
Setting Inches
(Gas)
Initial Damper Setting Inches
(Gas/Light Oil)
High
(Gas)
Fire
High
Fire
(Oil)
Qty.
Oil Nozzle(s)
GPH @
100
PSIG
Brand
Fuel Unit
Low
Fire
Burner-Motor
Driven
3450 RPM
Type
Oil
Pressure
PSIG
Spray
High
Angle
Fire
60º 300 100 22R623D 135
Gear GPH
Part Number 550-142-022/0509 3
Page 4
Webster – Model WJB
Flame Safeguards Provided with Listed Control Systems by Code
GAS BURNERS
Boiler model
number
UL FM CSD-1 IRI
OO LHO LHL MOD OO LHO LHL MOD OO LHO LHL MOD OO LHO LHL MOD
488R-488
RM7897A RM7897A RM7897A RM7897A RM7897A RM7897A RM7897A RM7897A RM7897A RM7897A RM7897A RM7897A RM7897C RM7897C RM7897C RM7840L
588-988R
– – RM7897A RM7897A RM7897A – – RM7897A RM7897A RM7897A – – RM7897A RM7897A RM7897A – – RM7897C RM7897C RM7840L
988-1888
– – RM7897C RM7897C RM7840L – – RM7897C RM7897C RM7840L – – RM7897C RM7897C RM7840L – – RM7897C RM7897C RM7840L
LIGHT BURNERS
Boiler model
number
UL FM CSD-1 IRI
FALFS LHO LHL MOD FALFS LHO LHL MOD FALFS LHO LHL MOD FALFS LHO LHL MOD
488R
R8184G R8184G R8184G R8184G R8184G R8184G R8184G R8184G R8184G R8184G R8184G R8184G RM7897C RM7897C RM7897C RM7840L
488-588
R8184G R8184G R8184G R8184G R8184G R8184G R8184G R8184G RM7897A RM7897A RM7897A RM7895A RM7897C RM7897C RM7897C RM7840L
688-988R
– – R8184G R8184G R8184G R8184G R8184G R8184G R8184G – – RM7897A RM7897A RM7895A – – RM7897C RM7897C RM7840L
988-1088R
– – R8184G R8184G R8184G R8184G R8184G R8184G RM7840L – – RM7897A RM7897A RM7895A – – RM7897C RM7897C RM7840L
1088-1888
– – RM7896C RM7896C RM7840L – – RM7896C RM7896C RM7840L – – RM7897C RM7896C RM7840L – – RM7896C RM7896C RM7840L
GAS/LIGHT OIL BURNERS
Boiler model
number
UL FM CSD-1 IRI
OO/
FALFS
LHO LHL MOD
OO/
FALFS
LHO LHL MOD
OO/
FALFS
LHO LHL MOD
OO/
FALFS
LHO LHL MOD
488R-488
RM7897A RM7897A RM7897A RM7897A RM7897A RM7897A RM7897A RM7897A RM7897A RM7897A RM7897A RM7897A RM7897A RM7897A RM7897A RM7840L
588-988R
– – RM7897A RM7897A RM7897A – – RM7897A RM7897A RM7897A – – RM7897A RM7897A RM7897A – – RM7897A RM7897A RM7840L
988-1888
– – RM7897C RM7897C RM 7840L
– –
RM7896C RM7896C RM7840L – – RM7896C RM7896C RM7840L – – RM7896C RM7896C RM7840L
Notes
e) RM7800L, E110/EP170 flame safeguard control monitors the oil or gas burner flame with digital readout control system, provides pre-
purge and post-purge programming, provides switching necessary to allow firing rate motor to be driven to both low fire and high fire posi­tion, prevents start-up if pre-ignition interlocks are open and has low fire start proving circuit. In the event pre-ignition interlock circuit or running interlock circuit does not “prove”, system will lock out on safety. Ultraviolet sensitive electronic flame detector is standard with infrared detector available.
14. Airflow safety switch is standard for all gas and combination gas/light oil units.
15. Burners will be completely assembled and wired (except gas train) and factory test-fired.
16. Burners listed by Underwriters Laboratories, Inc., state of Connecticut, Fire Marshal state of Massachusetts, city of New York MEA, and others.
17. Special controls can be provided to meet other code requirements not listed. Consult your local Weil-McLain distributor/agent or sales office.
18. Electric gas pilot is standard equipment on all gas and combination gas/light oil units and on oil units 1688R-1888. Direct spark ignition is standard on light oil units 488R-1588. Direct spark ignition is optional on combination gas/ light oil units 488R-1588. Consult your local Weil-McLain distributor/agent or sales offices.
19. Available for Low NOx applications. Consult your local Weil-McLain distributor/agent or sales offices.
4