Weil-McLain WJB1, WJB2 User Manual

®
88
Water & Steam Boilers – Series 2
Flame retention burners for
Gas, Light Oil, & Gas/Light Oil firing
Burner Specification
& Data Sheet
Models WJB1 & WJB2
Gas burner
Webster
Gas/light oil burner
W
E
B
H
Part Number 550-142-022/0509
L
C
A
D
Webster – Model WJB
Boiler
Model
Number
88
Series 2
488R 6.9 996 0.68 WJB1G-03 WJB1O-03 WJB1C-03 RM7897A R7184A RM7897C A A A 1/3 1/3 1/3 See notes
488 7.0 1010 0.70 WJB1G-03 WJB1O-03 WJB1C-03 RM7897A R7184A RM7897C A A A 1/3 1/3 1/3 See notes
588 9.4 1357 0.60 WJB1G-05 WJB1O-05 WJB1C-05 RM7897A R7184A RM7897C LFS LFS LFS 1/2 1/2 1/2 See notes
688 11.8 1701 0.58 WJB1G-07 WJB1O-07 WJB1C-07 RM7897A R7184A RM7897C LFS LFS LFS 3/4 3/4 3/4 See notes
788 14.2 2046 0.65 WJB1G-07 WJB1O-07 WJB1C-07 RM7897A R7184A RM7897C LFS LFS LFS 3/4 3/4 3/4 See notes
888 16.6 2382 0.66 WJB2G-07 WJB2O-10 WJB2C-10 RM7897A RM7897A RM7897C LFS LFS LFS 3/4 1 1 See notes
988R 17.2 2482 0.54 WJB2G-10 WJB2O-10 WJB2C-10 RM7897A RM7897A RM7897C LFS LFS LFS 1 1 1 See notes
988 18.8 2737 0.63 WJB2G-10 WJB2O-10 WJB2C-10 RM7897C RM7897A RM7897C LFS LFS LFS 1 1 1 See notes
1088R 20.0 2887 0.68 WJB2G-10 WJB2O-15 WJB2C-15 RM7897C RM7897A RM7897C LFS LFS LFS 1 1 1/2 1 1/2 See notes
1088 21.5 3082 0.78 WJB2G-10 WJB2O-15 WJB2C-15 RM7897C RM7897A RM7897C LFS LFS LFS 1 1 1/2 1 1/2 See notes
1188 23.5 3428 0.78 WJB2G-15 WJB2O-15 WJB2C-15 RM7897C RM7897A RM7897C LFS LFS LFS 1 1/2 1 1/2 1 1/2 See notes
1288 26.0 3773 0.76 WJB2G-15 WJB2O-15 WJB2C-15 RM7897C RM7897A RM7897C LFS LFS LFS 1 1/2 1 1/2 1 1/2 See notes
1388 28.5 4119 0.77 WJB2G-20 WJB2O-15 WJB2C-20 RM7897C RM7897A RM7897C LFS LFS LFS 2 2 2 See notes
1488 31.0 4464 0.78 WJB2G-20 WJB2O-15 WJB2C-30 RM7897C RM7897A RM7897C LFS LFS LFS 2 2 3 See notes
1588 33.0 4809 0.73 WJB2G-20 WJB2O-30 WJB2C-20 RM7897C RM7897A RM7897C LFS LFS LFS 2 3 2 See notes
1688R 34.5 4979 0.68 WJB2G-30 WJB2O-30 WJB2C-30 RM7897C RM7897A RM7897C LFS LFS LFS 3 3 3 See notes
1688 35.5 5155 0.74 WJB2G-30 WJB2O-30 WJB2C-30 RM7897C RM7897C RM7897C LFS LFS LFS 3 3 3 See notes
1788 38.0 5494 0.82 WJB2G-30 WJB2O-30 WJB2C-30 RM7897C RM7897C RM7897C LFS LFS LFS 3 3 3 See notes
1888 40.5 5845 0.80 WJB2G-30 WJB2O-30 WJB3C-50 RM7840L RM7897C RM7840L MOD LFS MOD 3 3 5 See notes
Standard Voltage Notes: 1/3 HP blower motor through ¾ HP – 120V/60/3 phase, 1 HP blower motor – 240V/60/3 phase, 1-½ HP blower motor through 5 HP- 240V/60/3 phase
Burner Input
No. 2
Oil
GPH
Gas
MBH
Positive
Pressure in
Firebox In. W.C.
Standard Burner Model
Designation
Gas
Light
Oil
Gas/
Light Oil
Standard Combustion
Control
Gas
Light
Oil
Gas/
Light Oil
Standard Control
System
Gas/
Light
Gas
Oil
Light
Oil
Burner Motor
3450 RPM H.P.
Light
Oil
Gas/ Light
Gas H.P.
Standard
Voltage
Oil
Standard Gas Components and Sizes in Inches
Boiler Model
Number
488R 1-¼ Optional 1-¼ 1 n/a n/a 1-¼ 1 Optional
488 1-¼ Optional 1-¼ 1 n/a n/a 1-¼ 1 Optional 588 1-¼ Optional 1-¼ n/a 1-¼ n/a 1-¼ 1-¼ Optional 688 1-½ Optional 1 ½ n/a 1-½ n/a 1-½ 1-½ Optional 788 1-½ Optional 1 ½ n/a 2 n/a 2 2 Optional 888 1-½ Optional 1 ½ n/a 2 n/a 2 2 Optional
988R 1-½ Optional 1 ½ n/a 2 n/a 2 2 Optional
988 1-½ Standard 1 ½ n/a 2 n/a 2 2 Standard
1088R 1-½ Standard 1 ½ n/a 2 n/a 2 2 Standard
1088 2 Standard 2 n/a 2 n/a 2 2 Standard
1188 2 Standard 2 n/a 2 n/a 2 2 Standard 1288 2-½ Standard 2-½ n/a 2 n/a 2-½ 2 Standard 1388 2-½ Standard 2-½ n/a 2 n/a 2-½ 2 Standard 1488 2-½ Standard 2-½ n/a 2 n/a 2-½ 2 Standard 1588 2-½ Standard 2-½ n/a 2 n/a 2-½ 2 Standard
1688R 2-½ Standard 2-½ n/a 2 n/a 2-½ 2 Standard
1688 2-½ Standard 2-½ n/a 2 2” 2-½ 2 Standard 1788 2-½ Standard 2-½ n/a 2-½ 2-½ 2-½ 2-½ Standard 1888 2-½ Standard 2-½ n/a 2-½ 2-½ 2-½ 2-½ Standard
Notes
Manual
Hand Valve
Low Gas Pressure
Switch
Gas Pressure
Regulator
Burner capacities listed for elevations up to 2,000 feet. For higher elevations, consult local Weil-McLain distributor/agent or sales office.1.
Light Oil ratings based on No. 2 fuel oil with heating value of 140,000 Btu per gallon.2. Gas ratings based on natural gas with heating value of 1,000 Btu per cubic foot and specific gravity of 0.60. Gas burners for other gases are available. Consult local 3.
Weil-McLain distributor/agent or sales office. Boiler-burner unit to be adjusted to achieve +0.10 inches W.C. pressure at the flue collar, resulting in positive pressure in firebox as listed.4.
Diaphragm
Operating Gas Valve
Motorized Operating Gas Valve
Motorized Operat-
ing Gas Valve w/
Proof of Closure
Safety Gas
Valve
Manual
Checking
Gas Valve
High Gas
Pressure
Switch
Minimum gas pressures listed are subject to variations due to job conditions. Gas burners for other gas pressures are available. Consult local Weil-McLain distribu-5. tor/agent or sales office.
Gas orifice pressures shown are for initial start-up. Final pressures should be determined after checking actual gas flow and combustion readings.6.
Part Number 550-142-022/05092
Loading...
+ 2 hidden pages