This manual must only be used by a qualified heating installer/service technician.
Read all instructions, including this manual, the Ultra Control Supplement and the
Ultra Vent Supplement, before installing. P erfo rm steps in the order give n. Failur e
to comply could result in severe personal injury, death or substantial propert y
damage.
Part number 550-101-233/0903
GAS-FIREDWATERBOILER — Boiler Manual
GAS-FIREDWATERBOILER — Boiler Manual
PhPh
THEBOILER, WITH
PhDPhD
PhD technology
PhDPhD
PhD Technology, Precision hydronic Data, is an intelligent system that
delivers Precision hydronic heating and hot water needs while maximizing
efficiency by measuring the Data parameters of your heating system.
1. Cast aluminum heat exchanger
Ph
PhPh
DD
D
TECHNOLOGY – HOWITWORKS . . .
DD
12. Burner
Made with high-grade stainless steel construction, the burner
uses pre-mixed air and gas and provides a wide range of firing
rates.
13. Water outlet pipe (system supply)
2. Heat exchanger access cover
3. Blower
The advanced blower design and air inlet silencer (5a) on Ultra boilers
result in very quiet operation.
80 & 105 — Air enters the boiler enclosure through the air intake adapter
(18), flows through the enclosure, enters the air inlet silencer (5a), then
enters the blower . The blower pulls air through the silencer and pushes it
into the venturi (5), where it mixes with gas before ente ring the burner.
155, 230 & 310 — Air enters the boiler enclosure through the air intake
adapter (18), flows through the enclosure, enters the air inlet silencer
(5a), then enters the venturi (5). The blower pulls air and gas through the
venturi and pushes the mixture into the burner .
4. Gas valve
The gas valve senses the vacuum in the venturi caused by flowing air , and
allows gas to flow when power is applied. The manual gas valve (4a) allows
shutting off the gas supply for servicing or shutdown. Models 80 and 105
use a sensing line (4b) from the gas valve to the blower outlet so the gas
valve references the same pressure as the venturi inlet.
5. Venturi
When air flows through the venturi, it creates a vacuum. This vacuum
pulls gas from the gas valve. So gas will only flow if air is flowing. On 80
and 105 models, the gas air mixture enters the burner after the venturi.
On 155, 230 and 310 models, the gas/air mixture enters the blower
before passing on to the burner .
6. Flue gas sensor
This sensor monitors the flue gas exit temperature. The control module
will shut down the boiler if flue gas temperature gets too hot. This protects
the flue pipe and the heat exchanger from overheating.
7. Outlet water temperature sensor
This sensor monitors boiler outlet water temperature (system supply).
The control module adjusts boiler firing rate so the outlet temperature is
correct.
8. Return water temperature sensor
This sensor monitors return water temperature (system return). The
control module reduces or increases boiler input, depending on how
close the return water temperature is to the outlet water temperature.
9. Temperature and pressure gauge
10. Electronic display & buttons
The 4-digit electronic display is used to:
• Set space heating temperature.
• Show outlet water temperature (normal) or other operating conditions
(in Information mode).
• Show boiler status and shutdown or lockout codes for easy
troubleshooting.
The buttons allow changing display mode and reset after lockout. The
on/off Power switch (10a) turns power to the boiler controls on or off.
11. Flue pipe adapter
14. Water return pipe (system return)
15. Gas connection pipe
16.
17. Transformer
18. Air intake adapter
19. Electrical entrance cover plate
20. Boiler drain valve
21. Line voltage receptacle
22. P/T gauge temperature sensor well
23. Flue gas condensate drain connection
24. Front door
25. Ignition electrode
26. Flame inspection window
Control Module
The
thermostat, supply water sensor, return water sensor, flue gas
sensor and (if used): domestic hot water aquastat, outdoor
temperature sensor, and summer/w inter switch. The control
module automatically adjusts blower speed (and gas flow rate)
to match boiler output to space heating and/or DHW heating
demand. The control module is accessed by removing top front
cover (16a).
The transformer reduces line voltage from 120 vac to 24 vac,
providing 24 vac to the control module for the gas valve and
blower signal .
Remove the electrical cover plate to access the line voltage
terminal strip (19b) and the low voltage terminal strip (19a).
Attach line voltage conduits to the three holes at the left of the
line voltage terminal strip for power, CH pump and DHW
pump. Route low voltage wires through the opening to the right
of the low voltage terminal strip.
Use this connection to plug in line voltage meters or tools while
working on boiler. Do not exceed 10-amp load.
The remote sensor for the panel-mounted pressure/temperature
gauge inserts into the outlet water pipe here.
Connect condensate drain line to ½" PVC te e here. The
condensate trap (23a) and PVC fittings are field-installed.
The front door is sealed to the boiler assembly around its entire
perimeter. Two knurled-head screws (24a) secure the door in
place.
The burner flame is ignited by applying a high voltage to the
ignition electrode. This causes a spark (from electrode to ground).
The quartz glass window provides a view of the burner surface
and flame.
Control Module responds to signals from the room
2
Part number 550-101-233/0903
GAS-FIREDWATERBOILER — Boiler Manual
THEGAS-FIREDWATERBOILER, WITH
PhPh
Ph
PhPh
DD
D
TECHNOLOGY
DD
Part number 550-101-233/0903
3
Contents
How it works.................................................................................... 2–3
See Ultra Control Supplement for wiring and additional
startup and operating information.
Hazard definitions
The following defined terms are used throughout this manual to bring attention to the presence of hazards of various
risk levels or to important information concerning the life of the product.
Indicates presence of hazards that will cause severe personal injury, death or substantial property
damage.
Indicates presence of hazards that can cause severe personal injury, death or substantial property
damage.
Indicates presence of hazards that will or can cause minor personal injury or property damage.
Indicates special instructions on installation, operation or maintenance that are important but not
related to personal injury or property damage.
4
Part number 550-101-233/0903
GAS-FIREDWATERBOILER — Boiler Manual
Please read before proceeding
Installer— Read all instructions, including
this manual, the Ultra Control Supplement
and Ultra Vent Supplement, before
installing. Perfo rm steps in the order given.
User — This manual is for use only by a
qualified heating installer/service
technician. Refer to User’s Information
Manual for your reference.
User — Have this boiler serviced/
inspected by a qualified service technician,
at least annually .
Failure to comply with the above could
result in severe personal injur y, death or
substantial property damage.
The boiler contains ceramic fiber materials.
Use care when handling these materials per
instructions on page 29 of this manual.
Failure to comply could result in severe
personal injury.
When servicing boiler —
•T o avoid electric shock, disc onnect electrical supply before performing
maintenance.
•To avoid severe burns, allow boiler to cool before performing
maintenance.
Boiler operation —
•Do not block flow of combustion or ventilation air to boiler .
•Should overheating occur or gas supply fail to shut off, do not turn
off or disconnect electrical supply to circulator . I nstead, shut off the
gas supply at a location external to the appliance.
•Do not use this boiler if any part has been under water. Immediately
call a qualified service technician to inspect the boiler and to replace
any part of the control system and any gas control that has been
under water.
Failure to adhere to the guidelines on this page can result in
severe personal injury, death or substantial propert y
damage.
When calling or writing about the boiler—
Please have the boiler model number from
the boiler rating label and the CP number
from the boiler jack et. You may list the CP
number in the space provided on the
Installation and service certificate found on
page 27.
Consider piping and installation when
determining boiler location.
Any claims for damage or shortage in
shipment must be filed immediately
against the transportation company by the
consignee.
Commonwealth of Massachusetts
When the boiler is installed within the Commonwealth
of Massachusetts:
•This product must be installed by a licensed
plumber or gas fitter .
•If antifreeze is used, a reduced pressure back-flow
preventer device shall be used.
Boiler water —
•The Ultra heat exchanger is made of aluminum, and requires that
system pH always be between 7.0 and 8.5 and water chemistry be
checked. Chemical treatment ma y be necessary. See page 24 for details.
•Thoroughly flush the system (without boiler connected) to remove
sediment. The high-efficiency heat exchanger can be damaged by
build-up or corrosion due to sediment.
•Do not use petroleum-based cleaning or sealing compounds in boiler
system. Gaskets and seals in the system may be damaged. This can
result in substantial property damage.
•Do not use “home made cures” or “boiler patent medicines.” Serious
damage to boiler, personnel and/or pr operty may result.
•Continual fresh make-up water will reduce boiler life. Mineral buildup
in heat exchanger reduces heat tr ansfer, overheats the aluminum
heat exchanger , and causes failu re. Addition of oxygen carried in by
make-up water can cause internal corrosion. Leaks in boiler or piping
must be repaired at once to prev ent make-up water.
•Do not add cold water to hot boiler. Thermal shock can cause heat
exchanger to crack.
Freeze protection fluids —
NEVER use automotive or standard glycol antifreeze, even glycol made
for hydronic systems. Use only freeze-protection fluids recommended in
the Ultra Boiler Freeze Protection Supplement.
Follow all guidelines in the Ultra Boiler Freeze Protection Supplement.
Thoroughly clean and flush any replacement boiler system that has used
glycol before installing the new Ultra boiler .
Part number 550-101-233/0903
5
GAS-FIREDWATERBOILER — Boiler Manual
GAS-FIREDWATERBOILER — Boiler Manual
1
Prepare boiler location
Installations must comply with:Installations must comply with:
Installations must comply with:
Installations must comply with:Installations must comply with:
•Local, state, provincial, and national codes, laws,
regulations and ordinances.
•National Fuel Gas Code, ANSI Z223.1 – latest edition.
•Standard for Controls and Safety Devices for
Automatically Fired Boilers, ANSI/ASME CSD-1,
when required.
•National Electrical Code.
•For Canada only: B149.1 or B149.2 Installation Code,
CSA C22.1 Canadian Electrical Code Part 1 and any
local codes.
The Ultra boiler gas manifold and controls
met safe lighting and other performance
criteria when boiler underwent tests
specified in ANSI Z21.13 — latest edition.
Before locating the boiler, check:
1. Check for nearby connection to:
• System water piping
• Venting connections
• Gas supply piping
• Electrical power
2. Check area around boiler . Remov e any combustible
materials, gasoline and other flammable liquids.
Failure to keep boiler area clear and free of
combustible materials, gasoline and other
flammable liquids and vapors can result in
severe personal injury , death o r substantial
property damage.
Provide clearances:
Clearances from combustible materials
1. Hot water pipes — at least ½" from combustible
materials.
2. Vent pipe — at least 0.20" from combustible
materials.
3. See Figure 1 for other clearance minimums.
Clearances for service access
1. See Figure 1 for recommended service clearances. If
you do not provide minimum clearances shown, it
might not be possible to service the boiler without
removing it from the space.
Ultra boilers, except the Ultra-310, may be
wall mounted (using special wall mount
kit) or floor mounted. No clearance is
required at the rear of the unit, either for
service or for clearance to combustible
surfaces.
Figure 1Clearances required
3. The Ultra boiler must be installed so that gas control
system components are protected from dripping or
spraying water or rain during operation or service.
4. If new boiler will replace existing boiler, check for and
correct system problems, such as:
• System leaks causing oxygen corrosion or heat
exchanger cracks from hard water deposits.
• Incorrectly-sized expansion tank.
• Lack of freeze protection in boiler water causing system
and boiler to freeze and leak.
6
Part number 550-101-233/0903
1
GAS-FIREDWATERBOILER — Boiler Manual
Prepare boiler location
Flooring and foundation
Flooring
The Ultra boiler is approved for installation on
combustible flooring, but must never be installed on
carpeting.
Do not install boiler on carpeting even if
foundation is used. Fire can result, causing
severe personal injury , death or s ubstantial
property damage.
Foundation
Provide a solid foundation pad, at least 2 inches above
the floor, if any of the following is true:
• floor can become flooded.
• the floor is dirt, sand, gravel or other loose material.
• the boiler mounting area is severely uneven or sloped.
The minimum foundation size is:
• Ultra-80 to -230: 24 inches wide x 20 inches deep.
• Ultra-310: 24 inches wide x 23 inches deep
24 inches x 20 inches.Foundation may be of wood, brick
or concrete (minimum 2 inches thick) construction.
If flooding is possible, elevate boiler sufficiently to prevent
water from reaching boi ler .
(continued)
Ultra boiler in same space with other gas or
oil-fired appliances
1. Follow the National Fuel Gas Code (U. S.) or CSA
B149.1 and B149.2 (Canada) to size/verify size of the
combustion/ventilation air openings into the space.
The space must be provided with
combustion/ventilation air openings
correctly sized for all other appliances
located in the same space as the Ultra boiler .
Replace boiler jacket front door after
servicing. The boiler front door must be
securely fastened to the boiler to prevent
boiler from drawing air from inside the
boiler room. This is particularly important
if the boiler is located in the same room as
other appliances.
Failure to comply with the above warnings
could result in severe personal injury , death
or substantial property damage.
2. Size openings only on the basis of the other appliances
in the space. No additional air opening free area is
needed for the Ultra boiler because it takes its
combustion air from outside (direct vent installation).
Residential garage installation
Precautions
Take the following special precautions when installing
the boiler in a residential garage. If the boiler is located in
a residential garage, per ANSI Z223.1, paragraph 5.1.9:
•Mount the boiler with a minimum of 18 inches above
the floor of the garage to the bottom of the boiler to
ensure the burner and ignition devices will be no less
than 18 inches above the floor .
•Locate or protect the boiler so it cannot be damaged
by a moving vehicle.
Provide air openings to room:
Ultra boiler alone in boiler room
1. No air ventilation openings into boiler room are
needed when clearances around Ultra boiler are at
least equal to the SERVICE clearances shown in
Figure 1. For spaces that do NOT supply this
clearance, provide two openings as shown in Figure 1.
Each opening must provide 1 square inch free area
per 1,000 Btuh of boiler input.
Vent and air piping
The Ultra boiler requires a special vent system, designed
for pressurized venting. Ultra boilers are rated ANSI
Z21.13 Category IV (pressurized vent, likely to condense
in the vent).
Y ou must also install air piping from outside t o the boiler
air intake adapter . The resultant installation is categorized
as direct vent (sealed combustion). Note prevention of
combustion air contamination on page 8 when
considering vent/air termination.
V ent and air must t erminate near one another and may
be vented vertically through the roof or out a side wall.
Y ou ma y use any of the vent/air piping methods cov ered
in the Ultra Boiler Vent Supplement, included in the
envelope assembly. Do not attempt to install the Ultra
boiler using any other means.
Be sure to locate the boiler such that the vent and air
piping can be routed through the building and properly
terminated. The vent/air piping lengths, routing and
Part number 550-101-233/0903
7
1
GAS-FIREDWATERBOILER — Boiler Manual
GAS-FIREDWATERBOILER — Boiler Manual
Prepare boiler location
Prevent combustion air
contamination
Install air inlet piping for the Ultra boiler as described in
the Ultra Boiler Vent Supplement. Do not terminate vent/
air in locations that can allow contamination of
combustion air. Refer to Table 1 for products and areas
which may cause contaminat ed combustion air .
Y ou must pipe c ombustion air to the boiler
air intake. Ensure that the combustion air
will not contain any of the contaminants
below . Contaminat ed combustion air will
damage the boiler, resulting in possible
severe personal injury , death o r substantial
property damage. Do not pipe combustion
air near a swimming pool, for example.
Also avoid areas subject to exhaust fumes
from laundry facilities. These areas will
always contain contaminants.
Table 1 Corrosive contaminants and sources
(continued)
When removing a boiler from
existing common vent system:
Do not install the Ultra boiler into a
common vent with any other appliance.
This will cause flue gas spillage or appliance
malfunction, resulting in possible severe
personal injury, death or substantial
property damage.
Failure to follow all instructions can result
in flue gas spillage and carbon monoxide
emissions, causing severe personal injury
or death.
At the time of removal of an existing boiler, the fo llowing
steps shall be followed with each appliance remaining
connected to the common venting system placed in
operation, while the other appliances remaining connected
to the common venting system are not in operation.
a. Seal any unused openings in the common venting
system.
b. Visually inspect the venting system for proper size
and horizontal pitch and determine there is no
blockage or restriction, leakage, corrosion or other
deficiencies which could cause an unsafe condition.
c. Test vent system — Insofar as is practical, close all
building doors and windows and all doors between
the space in which the appliances remaining
connected to the common venting system are located
and other spaces of the building. Turn on clothes
dryers and any appliance not connected to the
common venting system. Turn on any exhaust fans,
such as range hoods and bathroom exhausts, so they
will operate at maximum speed. Do not operate a
summer exhaust fan. Close fireplace dampers.
d. Place in operation the appliance being inspected.
Follow the lighting instructions. Adjust thermostat
so appliance will operate continuously.
e. Test for spillage at draft hood relief opening after 5
minutes of main burner operation. Use the flame of
a match or candle, or smok e fro m a cigarette, cigar,
or pipe.
f. After it has been determined that each appliance
remaining connected to the common venting system
properly vents when tested as outlined herein, return
doors, windows, exhaust fans, fireplace dampers, and
any other gas-burning appliance to their previous
conditions of use.
Any improper operation of common venting system
should be corrected so the installation conforms with
the National Fuel Gas Code, ANSI Z223.1 — latest edition.
Correct by resizing to approach the minimum size as
determined using the appropriate tables in Part 11 of
that code. Canadian installations must comply with
B149.1 or B149.2 Installation Code.
8
Part number 550-101-233/0903
2
GAS-FIREDWATERBOILER — Boiler Manual
Prepare boiler
Remove boiler from crate
Cold weather handling — If boiler has been
stored in a very cold location (below 0°F) before
installation, handle with care until the plastic
components come to room temperature.
1. The Ultra boiler is generally easier to handle and maneuver
after removing from crate.
2. After removing outer shipping carton from boiler,
REMOVE jacket front door by loosening two knurledhead screws at lower front. Removing the door will prevent
possible damage to the door during handling.
3. To remov e boiler from pallet (after remo ving jacket front
door):
a. Remove the four lag screws securing shipping brackets.
b. Unscrew the two rear boiler legs and remove the
shipping brackets.
c. Replace legs.
d. Discard the cardboard protector insert on the rear of
the boiler.
Do not drop boiler or bump jacket on floor or
pallet. Damage to boiler can result.
Prepare for propane if operating
on propane — Ultra-80 & -105
Ultra-80: DO NOT apply the following
instructions to conversion of Ultra-80 boilers.
Follow the instructions provided with the
optional propane conversion kit. The propane
conversion kit is NOT included as standard
equipment for the Ultra-80.
Do not apply the following to conversion of a
boiler already installed and connected to gas
supply. For a boiler alr eady installed, you must
turn off gas supply, turn off power and allow
boiler to cool before proceeding. You must also
completely test the boiler after conversion to
verify performance as described under “Startup, ”
Section 6 of this manual. See separate natural
to propane conversion instructions for
conversion of an existing boiler.
Y ou m ust install the propane o rifice to fire the
Ultra boiler on propane. Verify when installing
that the orifice size marking matches boiler
size. Failure to comply could result in severe
personal injury, death or substantial property
damage.
Ultra-80-LP boilers are factory-equipped
to operate on propane gas.
Figure 2Installing propane orifice (Ultra-105)
1. With boiler on its back, remove jacket front door by
removing two knurled head screws at lower front. Then
lift door away fro m boiler.
2. Disconnect the gas valve electrical plug.
3. Remove the 4 screws securing gas valve inlet adapter to
valve.
4. Remove (3) TORX screws securing gas valve to venturi
(Figure 2).
5. Locate propane orifice disc from co nversion kit bag. Verify
that the stamping on the orifice disk matches the boiler
size. Place orifice in the black rubber grommet in the side
of the gas valve and secure in valve (Figure 2).
6. Reposition gas valve against venturi and replace (3) TORX
screws securing valve to venturi. Secure gas valve inlet
adapter to gas valve with 4 screws. Make sure the plastic
hose is connected from gas valve to inlet elbow.
Inspect the O-ring between the gas valve and
gas valve inlet adapter block whenever they are
disassembled. The O-ring must be in good
condition and must be installed. Failure to
comply will cause a gas leak, resulting in severe
personal injury or death.
7. DO NOT attempt to adjust gas valve outlet pressure.
8. Connect gas valve electrical plug to valve terminals.
9. After installation is complete, attach the propane
conversion label (in conversion kit bag) next to the boiler
rating plate.
10. Replace jacket front panel.
Part number 550-101-233/0903
9
2
GAS-FIREDWATERBOILER — Boiler Manual
Prepare boiler
Prepare for propane if operating
on propane — Ultra-155 to -230
Ultra-80: DO NOT apply the following
instructions to conversion of Ultra-80
boilers. Follow the instructions provided
with the optional propane conversion kit.
The propane conversion kit is NOT
included as standard equipment for the
Ultra-80.
Do not apply the following to conversion
of a boiler already installed and connected
to gas supply . For a boiler already installed,
you must turn off gas supply, tur n off
power and allow boiler to cool before
proceeding. You must also co mpletely test
the boiler after conversion to verify
performance as described under “Startup , ”
Section 6 of this manual. See separate
natural to propane conversion instructions
for conversion of an existing boiler .
Y ou must install the pr opane orifice to fire
the Ultra boiler on propane. Verify when
installing that the orifice size marking
matches boiler size. Failure to comply could
result in severe personal injury, death or
substantial property damage.
1. With boiler on its back, remove jacket front door by
removing two knurled head screws at lower front.
Then lift door away fr om boiler.
2. Disconnect the gas valve electrical plug.
3. Disconnect the gas line union below the gas valve.
4. Remove (3) TORX screws securing gas valve to venturi
(Figure 2a).
5. Locate propane orifice disc from conversion kit bag.
V erify that the stamping on the orifice disk mat ches
the boiler size. Place orifice in the black rubber
grommet in the side of the gas valve and secure in
valve (Figure 2).
6. Reposition gas valve against venturi and replace (3)
TORX screws securing valve to venturi. Reconnect
gas line union.
7. DO NOT attempt to adjust gas valve outlet pressure.
8. Connect gas valve electrical plug to valve terminals.
9. After installation is complete, attach the propane
conversion label (in conversion kit bag) next to the
boiler rating plate.
10. Replace jacket front panel.
(continued)
Figure 2a Installing propane orifice (Ultra-155
and Ultra-230)
Ultra-310 boilers cannot be equipped for
propane firing as of October, 2003.
Propane capability should be available in
2004.
Placing floor-mounted boilers
1. Set boiler in place and check level.
a. Adjust legs, if necessary to level boiler.
Placing wall-mounted boilers
1. Ultra-80, -105, -155 and -230 boilers can be wall
mounted. Use only the separately available Ultra
boiler wall mounting kit and instructions. See
W ARNING below .
The wall must be vertically plumb and
capable of carrying the weight o f the boiler.
The operating weights are:
Model Ultra-310 boilers are NOT designed
for wall mounting.
W all mount Ultra boilers only using W eilMcLain Ultra boiler wall-mounting kit and
accompanying instructions. This kit is not
supplied as standard equipment with the
boiler, and must be purchased separately .
Failure to comply with above could result
in severe personal injury, death or
substantial property damage.
10
Part number 550-101-233/0903
2
GAS-FIREDWATERBOILER — Boiler Manual
GAS-FIREDWATERBOILER — Boiler Manual
Prepare boiler
Perform hydrostatic pressure test
Pressure test boiler before permanently attaching water
or gas piping or electrical supply .
Prepare boiler for test
1. See Figure 3 for reference in following steps.
2. Remove supply line tee* and ¾” street elbow from
accessory bag. Pipe to boiler supply connection as
shown. Use pipe dop e sparing ly. (*1" x 1" x ¾" tee
with Ultra-80 to -230 or 1¼" x 1¼" x ¾" tee with
Ultra-310)
3. Temporarily plug the ¾" relief valve tapping in the
street elbow with a ¾" NPT pipe plug.
4. Connect a hose to boiler drain valve, the other end
connected to a fresh water supply. Make sure hose
can also be used to drain boiler after test.
5. Connect a nipple and shutoff valve to system supply
connection on the supply tee. This valve will be used
to bleed air during the fill. (V alv e and nipple are not
included with boiler .)
6. Connect a shutoff valve to system return connection.
(V alve is not includ ed with boiler.)
7. To avoid getting water on boiler, you may want to
pipe street elbows on top of shutoff valves and attach
catch-buckets beneath.
8. If convenient, install the boiler circulator and any
other piping compatible with Figure 3 that would
still allow bleeding air from shutoff valves. Follow
guidelines in this manual for piping components,
locations and sizing.
(continued)
Leaks must be repaired at once. Failure to
do so can damage boiler, resulting in
substantial property damage.
Do not use petroleum-based cleaning or
sealing compounds in boiler system.
Gaskets and seals in the system may be
damaged. This can result in substantial
property damage.
Drain and remove fittings
1. Disconnect fill water hose from water source.
2. Drain boiler through drain valve. Remove hose after
draining.
3. Remove nipples and valves unless they will remain
for use in the system piping.
4. Remove plug from relief valve street elbow. See
section 3 (page 12) to install relief valve.
Figure 3Hydrostatic test piping connections
Fill and pressure test
1. Open the shutoff valves you installed on supply and
return connections.
2. Slowly open boiler drain valve and fresh water supply
to fill boiler with water. The boiler will fill quickly
because of its low water content.
3. When water reaches shutoff valves, close boiler drain
valve.
4. Close shutoff valves.
5. Slowly reopen boiler drain valve until test pressure
on the pressure/temperature gauge reaches at least
45 psig, but no higher than 55 psig.
6. Hold at test pressure for 10 minutes.
7. Make sure constant gauge pressure has been
maintained throughout test. Check for leaks. Repair
if found.
Part number 550-101-233/0903
Do not leave boiler unattended. A cold
water fill could expand and cause excessive
pressure, resulting in severe personal injury ,
death or substantial property damage.
11
3
GAS-FIREDWATERBOILER — Boiler Manual
Install water piping
Install relief valve
1. Install relief valve in ¾" street elbow piped from boiler
supply piping tee (Figure 3, page 11). Pipe the relief
valve only as shown, in the location shown.
2. Connect discharge piping to safe disposal location,
following guidelines in the W ARNING below .
To avoid water damage or scalding due t o
relief valve operation:
•Discharge line must be connected to relief
valve outlet and run to a safe place of
disposal. Terminate the discharge line in a
manner that will prevent possibility of
severe burns or property damage should
the valve discharge.
•Discharge line must be as short as possible
and be the same size as the valve discharge
connection throughout its entire length.
•Discharge line must pitch downward from
the valve and terminate at least 6" above
the floor drain where any discharge will be
clearly visible.
•The discharge line shall terminate plain, not
threaded, with a material serviceable for
temperatures of 375 °F or greater.
• Do not pipe the discharge to any place
where freezing could occur.
•No shutoff valve shall be installed between
the relief valve and boiler , or in the discharge
line. Do not plug or place any obstruction
in the discharge line.
• Test the o peration of the valve after filling
and pressurizing system by lifting the lev er.
Make sure the valv e discharges freely . If the
valve fails to operate correctly, replace it
with a new relief valve.
•Failure to comply with the above guidelines
could result in failure of the relief valve to
operate, resulting in possibility of severe
personal injury, death or substantial
property damage.
Use two wrenches when tightening water
piping at boiler, using one wrench to
prevent the boiler return line or supply line
from turning. Failure to support the boiler
piping connections to prevent them from
turning could cause damage to boiler
components.
General piping information
Additional controls, when required
The Ultra control module uses
temperature sensors to provide both high
limit protection and modulating
temperature control. The control module
also provides low water protection by
sensing the temperature of the heat
exchanger . Some codes/jurisdictions may
require additional external controls for
high limit and/or low water cutoff
protection.
Additional limit control:
Following standard industry practices, if installation is
to comply with ASME or Canadian requirements, an
additional high temperature limit is needed. Consult local
requirements for other codes/standards to determine if
needed.
1. Install additional high temperature limit constructed
to prevent a temperature setting above 200°F in system
supply piping between boiler and isolation valve.
(Note that the Ultra control module operating limit
function shuts the boiler down at 190°F or Parameter
4, whichever is lower .)
2. See Ultra Control Supplement for wiring.
a. If limit control is to cause a boiler hard lockout (requiring
manual reset of Ultra control module), connect isolated
contact to field control wiring terminals 6 and 8 as
shown in wiring diagram.
b. Otherwise, connect isolated contact between
terminals 6 and 7 for a soft lockout (automatic reset).
c. If using a manual reset limit control or wiring in the
manual reset circuit, Parameter 4 should be no closer
than 20°F to the limit control setting (i.e., no higher
than 180°F for a 200°F limit setting, for example).
Separate low water cutoff:
A low water cutoff device is required when boiler is
installed above piping level or by certain state or local
codes or insurance companies. Consult local
requirements to determine.
1. If required, use a low water cutoff designed for water
installations. Electrode probe-type is recommended.
2. Purchase low water cutoff and install in tee in supply
piping above boiler .
3. See Ultra Control Supplement for wiring.
a. If limit control is to cause a boiler hard lockout (requiring
manual reset of Ultra control module), connect isolated
contact to field control wiring terminals 6 and 8 as
shown in wiring diagram.
b. Otherwise, connect isolated contact between
terminals 6 and 7 for a soft lockout (automatic reset).
Backflow preventer:
Use backflow check valve in cold water supply as required
by local codes.
12
Part number 550-101-233/0903
3
GAS-FIREDWATERBOILER — Boiler Manual
GAS-FIREDWATERBOILER — Boiler Manual
Install water piping
System water piping methods
All piping methods shown in this manual
use primary/secondary connection to the
boiler loop. These designs ensure proper
flow through the Ultra boiler , fo r the most
efficient and reliable operation of the boiler
and the heating system. For other piping
methods, consult your local Weil-McLain
representative or refer to separate Ultra
boiler piping guides.
Wall-mounted boilers — Piping can exit
bottom of boiler enclosure. See separate
wall-mounting instructions for details.
Expansion tank and make-up water
1. Ensure expansion tank size will handle boiler and
system water volume and temperature. Allow 3
gallons for boiler and its piping.
Undersized expansio n tanks cause system
water to be lost from relief valve and makeup water to be added through fill valve.
Eventual boiler failure can result due to
excessive make-up water addition.
(continued)
Figure 4Expansion tank piping
2. Tank must be located as shown in this manual, or
following recognized design methods. See tank
manufacturer’ s instructions for details.
3. Connect the expansion tank to the air separator only
if the separator is on the suction side of the circulator.
Always install the system fill connection at the same
point as the expansion tank connection to the system.
4. Most piping drawings in this manual show
diaphragm expansion tanks. See Figure 4 for piping
from air separator to expansion tank and make-up
water line using a closed-type expansion tank.
5. Most chilled water systems are piped using a closedtype tank, as shown in Figure 10, page 18.
Diaphragm (or bladder) expansion tank
1. (Figure 4) Always install an automatic air vent on
top of the air separator to remove residual air from
the system.
Closed-type expansion tank
1. See Figure 4, Alternate, for piping connections when
using a closed-type expansion tank.
2. Pitch any horizontal piping up towards tank 1 inch
per 5 feet of piping. Connect to tank with at least ¾"
piping to allow room for air to rise.
DO NOT install automatic air vents on
closed-type expansion tank systems. Air
must remain in the system and return to
the tank to provide its air cushion. An
automatic air vent would cause air to leave
system, resulting in water-logging the
expansion tank.
Circulators
The boiler circulator (Taco 007 for Ultra-80 and -105;
T aco 0011 for Ul tra-155, -230, and -310) is shipped loose.
Locate it either in the return or supply piping, as shown
in the appropriate piping diagram in this manual.
DO NOT use the boiler circulator in any
location other than the ones shown in this
manual. The boiler circulator is selected to
ensure adequate flow through the Ultra
boiler. Failure to comply could result in
unreliable performance and nuisance
shutdowns from insufficient flo w.
Sizing space heat system piping
1. See Figures 7 through 10, pages 15 – 18, for
recommended piping. In all diagrams, the space
heating system is isolated from the boiler loop by the
primary/secondary connection.
2. Size the piping and components in the space heating
system using recognized design methods.
Part number 550-101-233/0903
13
3
GAS-FIREDWATERBOILER — Boiler Manual
Install water piping
Sizing DHW system piping
When using the boiler for dedicated DHW
applications, use the circulator supplied with
the boiler (007 for Ultra-80/105; 0011 for
Ultra-155/230/310) to circulate to the water
heater except where higher flow rates may be
required for the heater used. Use the following
method to select a circulator for the water
heater on combined space heating/DHW
systems.
1. Figure 5 shows recommended DHW piping, as shown in
Figures 7 through 10, pages 15 – 18. All show direct
connection of the DHW piping to the boiler because the
boiler circulator shuts down during DHW operation.
2. Figure 6 shows the pump curves for suggested DHW
Figure 5DHW piping (see Table 2 f or approxi-
mate head losses)
(continued)
circulators (Taco 007, 0011, 0012, 0013, 0014, B&G PL-36 or equivalent). Use
these curves along with boiler pressure drop data fro m T able 2 to size the DHW
piping and circulator . Or you can use T able 2 for a quick-selection method.
3. Table 2 uses the available head from the circulat ors list ed to help you select the
right circulator.
a. See Figure 5.
b. H1 is the head loss across the boiler.
c. H2 is the head loss across the DHW piping.
d. H3: Table 2 subtracts H1 and H2 from the available head of the circulator. This
gives the maximum value for H3, head loss across the water heater.
4. Procedure to select a circulator using Table 2:
Step 1: From the water heater manufacturer’s data, find:
• Required boiler water flow rate, GPM, at 180°F.
• Pressure drop across the water heater at this flow rate, in feet water column.
Step 2: Find your boiler model in Table 2. Select a flow rate in column 1 just
larger than the required flow rate from step 1.
Step 3: The value in column H3 must be larger than the water heater pressure
drop from step 1.
Table 2Pipe sizing and head losses for DHW applications
(H1=boiler head loss; H2=piping head loss; H3=maximum
allowable head loss through water heater based on available head
of circulator chosen; i.e., Taco 007, 0011, 0012, 0013 or 0014, Bell
or Gossett PL-36)
Figure 6Pump curves for typical circulators
suggested for DHW loop
14
Part number 550-101-233/0903
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.