®
Series 2
Gas-Fired W ater Boilers
Boiler Manual
• Installation
• Startup
• Maintenance
• Parts
This manual must only be used by a qualified h eating installer/service technician. BEFORE ins talling, read
all instructions in this manual and all other information shipped with the boiler. Perf orm steps in the order
given. Failure to comply could result in severe personal injury, death or substantial property damage.
Part number 550-142-783/1012
GV90+ Series
2
oAs·FIRED
WATER
BOILER
-
Boiler
Manual
How
it
works
•••
1 Integrated boiler control
The
integrated
pressure switdl, i
to operate
for heat, the I
The JBC runs the biO'\\•
lets it warm up.
Aft
er
igniter warm· up, the I
flam
e.
The flam
fu
ll
cyde again.
hen
the room thermostat
W
wa
i.ts (or the
The
IBC indicator ligh.ts show nonnal sequence wh
problem occurs, the JBC
reason for the proble
While attempting to satisfy the heat demand,
temperature changes via the temperature sensors a
availab
le hot water w.
is needed, the sequence
heat
above is bypassed.
boiler
control (I BC) responds to signals from the room thermostat,
:n
let water sensor, boiler
the
circulators,
BC
star
ts
the
er
e
must
come
next
beat
call.
m..
tll
satisfy the demand, only running
wa
.ter temperature sensor and boiler limit circuit
gas
valve,
igniter and bl
sys
tem circulator and blower.
to
purge the boiler
DC
opens the
on
within 4 wconds
is
satisfied. the IBC turns off the boiler components
flashes
combinations
conti:nues..
gas
When
ower.
flue
passages, then turns on the igniter
vah-e,
or
of
lights which indica
the
control module m
DHW
2 Transformer
The
control transformer
reduces line
vottage
to
24
volts for the
3 Blower
The
blower pulls
m
ixturt into
4 Recuperator
The recupenttor
trading
additional beat &omthefluega
entering the boiler.
before
5 Water temperatu re sensor
The
wat~r
off
rhe
gas
circulator
6 System
The system circulator circulates water through the external
ra.te
ofthecirculator
entering t
7 Bypa
..
The
IBC
colder return "'a ter from the S)'Stem
th
e cast iron heat exchanger.
Whe
n
the
culatorand
it enters the cast iron sections, By balancing these
before
agai:n.st
condensation
Pump
mU$t re
i:n ai:
r and mixes
lhe
burner for coml
is
a stainless steel beat exchang
t~mptralur~
valv~
if
the
wlll conrinue to
it
with gas
xu:tio
n in
ws,
sensor
provides a signal
temprratur~
run
in the boiler goes
as long as there is a call for heat.)
circulator
i:s
he boil
er
.se<tion$.
controlled
by
Pump m
the
u.<
IBC,
n rema
circulator
operates the bypass circulator to
as needed
water
returning to the boiler
sy
stem circulator
in
the
main on boiler-
flow
cas
t iron heat exchanger e\'en if return
rates
do
Is
to
not rem
&om
side-
the-
er
that increases boaer e
Return waterpasws through the recuperator
depending on the temperatu
in
on
mi.x
hot water
to
prevent condensation
below IW F. the I
rai
se
the
return
m-e.
When a room thermostat caUs
rurns the igniter off,
the me will shut
en the lights are
nd
determines wheth
the
ci:
(if
used)
caJJs for heat. sequen
gas
th
e gas
valve.
and
down
on
steady. When a
te
the most
onitors
er
rculator. If additional
valve
and limit
The bla\\'et
boiler chamber.
fficiency
to
the
conrrol
(S)
boiler -
fro
BC
water temperature
flow
modu
abo~
its setring. (The
'Stem)
piping, The
re
do
not
remove.
m t
he
boil
er
of
regulate$
rate
the
s.
the IBC can protect
water
Is
flue gas
as low as
air
and
checks for
and
try
the
and
bkel
the
boiler
or
not t
he
ce
ci:rcuit.
forces
this
by ex·
le
to
turn
flow
of
the water
outlet with
es
bypass
ci:
up
to l40'"
6Cr
in
r·
f.
LEGEN
a
b R
c Combustion
y
d
D
Supply to
etu
3"'
FJ
ue outlet -3"'
rn from
P
VC
system>
connecti
1"'
system,
air
lnlet fit
on
PVC
NPT
I" NPT
ting -
conntc·
tion
e Gas
vaJve
regulated
- negati
gas
control
ve
pr~ss
urt
I Pressure/temperature gauge
g
FJueway
inspection port
CO\'tr
h Stnsor hose trap
Manual air
Relief
k Thermal
device
te:mptrature exceeds irs
m Condtnsate trap line
loose
n Condensate drain con
W'
PVC
F
vtnt
vaJ\ ·t
fuse-
a one·time fuse
that shuts boiler off
-sh
with boiler,
field
nection-
female
if
flue
strpo
int
ipped
installed
8
Air
pre
..
ure switch
The
ai:r
pressure switch signals
the blower.
the
IBC.te U
ing the control whether air is moving through
9 Return water temperature sensor
The
water tempera t
sectfons. The sensor sends this Information to the
to
adjust the cirrulator
exchanger.
UI'e
sensor monitors
fl
O\\'
rates
the
temperatu
to
provide at least 140'"
2
IBC
re
of
. The I
the water
P water
entering
BC
determines how m
to
the
boiler
the cast iron beat
uch
Thi
s boile r uses a negarive·
tgulattd
r
pressure
column
00
ha
n facto ry
t
gas valve, ser for
approximately -0.
.
NOT
set rhe
sett
Pan
outle
ing.
number 55
prtssurt
an outl
20"'
t
pr~ssurt
higher
0-
142-783/1012
-
et
water
GV90+
Series
2 GAS·FIRED WATER BOILER -
Boiler
Manual
GV90+
Series
2 Water Boiler
Part
num
ber 550-
14-2
-783/10 12
3
GV90+
Series
2
oAs·FIRED
Contents
How
it
works
.....
GV90
+ Water Boiler .
Pie
aM read belore
Pr
epa
re boilerlocat
Installations m
High altitude i:nstallatfons
Residential garage installation
Check orifice plate - replace
Install condensate uap. . .
Install h
required
Rotate t
Perform hydrostatic pressure
In
sta
ll water piping
General
Install reliefvah-e
Exp
ansion tank
Sys
tem water piping m
Orculators
Simplified pipe/cirrulator selection
Baseboard system piping - ORCULATOR
'ZOning
Baseboard system piping -
'ZOning
Radiator system piping
Single·
Ad;wt
Multi·
wne
Piping snow melt systems
snow
melt/space heating
Water
chiller systems . . . . . . . . . . .
u.<
igh
altitude
{onJy above
he
boiler into position
pipi:
ng informat
•..............
.................
(pri:m
arylseco
(d
irect connection)
wne
radiant h
b
alanci
ng
radiant heatiog system . . . .
Multiple boil er installat
Placing
mul
tiple
Conuolling multiple CV90+ boilers . . .
Piping multiple CV90+ boil
Multiple boil er water
Easy·Fit•
piping installation . . . . . . .
Ventin g & air-
When removing a boiler from an existing
common
Existing vent
Provi
Vent and
DIRECfVENTinstallations
DIRECT
Combust
Ma
RECT
Air manifold sizing . . . . . . . . . . . . 3 1
Commo
in
sta
ven
t system . . . . . . . . . . .
de
nifolded combustion
llati
tes
combustion air:
air termination options
EXHAUST
io
n air contamination: . . . . . 30
VENT multiple
nwe
alth of Mlls
ons
. . . . . .
Vent termination req uiremen
DIRECT VENT- Boiler room air
ope
nings . . . . . . . .
DIRECT VENT-
ve
ntfair plate. . . . . .
DIRECT VENTr
ate pipe
s. . . . . . . .
.
p~eding
ion
n
fonow
these codes:
..........
air press
S.SSO
........
ion
.............
eth
ods
ncf
ary) .......
..........
eati:
ng
vah<S
, , , , , , , , , , 19
or
;Systems.
boi~s
. . . . . . . . . .
piping
genKal ......
t procedure
..........
installations
air
boib
inslallations
Sidewa
Sidewa
...
.......
...
.......
if
necessary. 8
.........
ure switch wh
feet)
......
......
t
est
.....
........
.......
...
ZO
NE VAL
........
or
heat
pum
combinati
ions
ers.
on
. . . . 2 1
....
. . . . .
•...
........
.....
.......
.....
option
(or
Dl
. . . 3 1
saohusetts
......
ts
..
......
ll
with W-M
......
ll
with oepa·
......
VE
WATER
DIRECT VENT
.2
concentric .............
.3
DIRECT VENT
5
rate pi
pes
..............
BOILER
- Sidewa
- Vertical with
6
DIRECT VENT
6
conce
6
1
ntric
Concentric termination assem
(sidewa
9
en
Ve
nt
9
10
II
12
12
12
13
IS
IS
IS
16
16
18
p 19
20
and a
nections
DIRECTEXHAUST&DIRECTVENT .
Follow
termination instructions . . . . . 48
Installing vent a
DI
RECT
DIRECT EXHAU
ope
nings
Combustion
Siring
combu.<Jtio
Special constderations. . . . . . . . . . . 49
9V90+ boiler
tn room . . . . . . . . . . . . . . . . . . .
Air openings . . . . . . . . . . . . . . . .
CV90+ boiler
roon1 . . . . . . . . . . . . . . . . . . . .
DIRECT EXHAU
- Vertical with
.............
ll
or vertica
ir
pipi
..............
nd
EXHAUST
..............
ai:
r provision. . . . . . . . . 49
n air openings . . . . . 49
WITHOUT other appl
WITH other
DIRECT EXHAU
22
23
23
23
23
24
24
29
29
29
30
30
30
30
·
34
35
36
37
39
Gas piping
Connecting
Natural Cas . . . . . . . . . . . . . . . . .
Propane Cas . . . . . . . . . . . . . . . .
Wiri
ng
Field wiring. . . . . . . . . . . . . . . . .
Sta
rt-
Freeze
Clean system to
Water
Antifreeze . . . . . . . . . . . . . . . . . . S9
F
lll
and
Use
inhibit
Check/Ve
Check
Check
Verifygas/airorificeplate . . . . . . . . . 61
Check thermostat circuit(s) . . . . . . . . 61
In
spect/fiJI condensate syst
Final checks before starting boiler . . . . 62
Adjust
Aju.•
n boiler control
Bo
iler
st
art
To
If
boiler does
Ch
eck
Cas
vatve
re.tONLY
Final checklist
.............
gas
suppty pi ping. . . . . . .
...............
up
...............
protection (wh
remo\>e
chemistry . . . . . . . . . . . . . . S9
test wa.ter system . . . . . . . . . 60
or
supplied with boiler . . . . 60
ri
fy water chemistry. . . . . . . 60
imllit:or
boiler control srttinp . . . . . . . 62
c.oncm
for
gas
leaks. . . . . . . . . . . . . 61
Eco
nomy settings. . . . . . . . . . 62
the
boiler
nots
system
and
adjustment - attitude
.................
...............
-
Boiler
ll
with 3"
41
-·
43
3"
45
bly
l)
ng
........
and
boiler con-
47
48
48
air piping . . . . . . . 48
ONLY
. . . . . . . .
48
ST - Boiler room air
49
iances
50
50
appliances in
ST - Sidewa
ST -
Ve
rtical
ll
•..
..
50
51
53
54
S4
SS
SS
55
S6
59
en
u.W)
. . . . . . S9
sediment . . . . S9
tnr:
ion
an
rualy
. . . 60
em
. . . . . . 61
setti:nSJ>
. . . . . . . . 62
.............
tart correctly
boiler after start·up
.....
O\'ft'
62
62
..
62
S.SOO
63
64
Manual
Department of
IBC
(Sequence
Operating lnstrustions
Annual start·up a
nance schedule . . . . . . . . . . 68
Annual start-up . . . . . . . . . . 69
Address reported problems . . . . . . . . 69
Inspect boiler area . . . . . . . . . . . . . 69
Inspect boiler interior . . . . . . . . . . .
Inspect condensate drain syst
Inspect
Inspect gas piping . . . . . . . . . . . . .
Inspect
Check water syst
Inspect expansion tank . . . . . . . . . .
Inspect
Inspect
Inspect boil
Inspect igniter . . . . . . . . . . . . . . .
Inspect t
Inspect
Inspect
Inspect blower mot
Inspect oiled·beari:ng circulaton . . . . .
Inspect supply temperature sensor . . . .
Inspect boiler relief
To
comple1< Annual
startup
Review
Se
rvi
ce
Cleaning boil
To remove the blower assembty . . . . . 73
To
dea
n heating surfaces . . . . . . . . . 73
To
dea
n
To
replace blower assembly
Inspecting and
Tro~eshooting
VERIFY
SERV
ICING
Before troubleshooting . . . . . . . . . .
Check the following . . . . . . . . . . . .
Checking the air pressure
Ig
niter
....................
Gas
Valve
Blower
Thermal
Return temperature sensor . . . . . . . .
Suppty temperature sensor . . . . . . . .
IBC
(integrated boiler control) . . . . . .
IBC
indKat
IBCin<iiolt«
Installation a
ce
rtificate . . . . . .
Replacement
Dimensions
Handling ceramic fiber
glaoo
mat
NOTES ..............
Energy
of
eon-.>liance
operations)
..........
.......
nd general maint
e:n
l . . . . .
all
pipi
ng
for
leaks . . . . . . . .
the
water system. . . . . . . . . .
e:n
l chemist
air
openings . . . . . . . . . . . .
ven
t system and air piping . . . .
er
heati
ng
e:nlpe:ral'Ute
additional
gauge5
and
with
conuok
. . . . . . . . . . . . . . .
or
checks . . . . . . . . . . . . n
owner.
& maintenan
er
heati
the
burner
deaning
ry
. . . . . .
surfaces
mi.xi:
. . . . . . . . . . .
valve
Slan·up,
. . . . . .
ng system . . .
and
cutotfs
. . . . . . . . . n
perform
. . . . . . . . . . . . n
ce
. . . . . . 73
ng
surf:lces
. . . . . . . . . . . . 74
. . . . . 73
........
the recuperator 74
..........
PROPER
Housi
fuse
OPERATION
.................
. . . . . . . . . . . . . . . . . .
ng
. . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
or Lights - lockout modes. .
l
iglu>-non·~m<><l<!
nd
service
parts
and
ratings. 1
AFTER
switch
. . . . . 76
. . . . 91
and
fiber-
erials. 106
. . .
.
65
66
67
e-
69
69
69
69
69
69
70
70
70
70
70
71
71
71
71
71
71
74
76
76
76
76
77
77
77
77
78
78
79
79
.
79
90
02
107
4
Pan
number
SS0-142· 783/1012
GV90+
Series
2
OAS·FtRED
WATER BOILER -
Boiler
Manual
Please
Hazard
The
bring attention
to i
!A
NOTIC
IAwARNIN&l
NOnCE
definitions
following
mportant information
CAUTION 1 lnd
E
read
defined
lnd
perSona
damage.
lnd
perSonal i
damage.
minor
Jndicares
Opt-ration o r maintenance th
no
Installer-
man
boiler> before installin
gi
Uller-
he-ating installer/service technician.
Jn:f'onnation
User - Ha\'t this
qualified service technidan, at
fajlure
sevtrt personal injur
da.mage.
W~itt
the In stallation certificate
terms
to r.he prestnce
icares pr
l injur-J'•
icares pr
icares presence
ptmna
t related
ual
and
.. ·tn.
This manual
to
in the CP numbtr
before
are
used
of
concerning
t.Sence
of
dearh
t.Sence
of
njur)
'• dearh
of
l inj
ury
speda
l
in
to
ptrso
nal inj
Read
all
all
other in
ManuaJ fo
comply wi
throughout
hazards
boiler serviced/inspected by a
y,
of vari
the life
of
hazards thar w
or
substa
hazards that can cause
or
substantial proper
hazards that
or proptrty
srructions
ury
instructions. induding this
for
g.
Perfonn steps in the order
is f
or
r your referen
th th
death or substantia] proptrty
in the space provided on
on
on insrallation.
ar
are i
or
proptrty
mation
use
only
lea
st annually.
e above could result in
page
this
ous risk
the product.
lll
nt ial
will
damage.
mportanr
shipped with
Refe
90
shown.
\Vhen
call
ing
or writing about the
have the boil
label and the
Consider piping and installati
boiler location.
Any claims for damage or shorrage in shipment
must
company by the consignee.
Commonwealth
When the boi
l-er
M..,.chu.setts, comply
This produ
fitter
If antifreeze is used, a reduced pressure back-flow preventer
d.,;ce
tf sidewa
ct
must
.
sha
ll
be
JI
\.'tnt or venr/air is insralled>
er
model nwnber
CP
number
be
filed
immedlatelyagainst
of
Massachusetts
is installed within the Commonwealth
with
<he
be
installed by a licensed plumber or
uStd
.
from
following.
boiler-
from
the
the boi
on
when determining
the
transportati on
see
instructions on
page 34.
proceeding
~WARIM
manual
cause
or
can cause
by
a
r to User's
ce.
if
not already
boiJtr
le
r jacket.
to
lt•ttls or
sevt-
rt
property
sevt-
rt
ty
bur
damage.
th
qualifi
ed
Please
raring
of
gas
When ..,,.,.;cing boiler-
To
before performing maintenance.
To
performing maintenance.
This boil
materials.
on
Boiler operation -
Do
to
Should
tMit
sup.
at
Do not
woter.
e
cian to inspect
the control system and any gas control that has bft.n
under
Combustion air -
DO
It a rltk
Carbon monoxide detector-
Fo
tor is requir
oxide dttecror must be wired
circuit
Fo
that
is
Boiler water-
Thoroughly
neo
exd1anger
due
Do
compounds
system
property
LNkoln
to P<8Yenl
In
wat-er will
exchangers reduces heat transfer,
ri
als,
by
Do
ca
Freeze protection fluid• -
NEVER
Use
systems. Foll
manufucturer.
placeme
m
I
Failure to adhere ro the guidelines
page
can resu
Cleath
or
avoid electric shock, disconnecr electr
avoid
severe
er
contains ceramic t'ibtr
Refe
1
.
r to the
06.
flow
page
not bloc.k
boiler
""erhNUng occur or g
off,
DO
t
~
ci
NOT
rculator.
P.Iy
ll in
severe
substantia] proptrty damage.
burns, allow
WARNING
of combustion or \
personal i
boiler ro cool before
and instructions
..
tum off or disconnect electri
Instead>
sh~r
off the gas supply
a l ocanon externaJ to the apphanct.
UM
thla
Immediately
wate
r.
NOT Insta
of
combustion air contamln.Uon.
r
OII'Cid
Exhaust uni
ed
as
the boil
r Direct
stro
V•nt
i.s
wirtd on the same electrica
ngly recommended.
flu
ted )
to
removeS<'dinlenl
can
to sedimtnr.
not
lL~t
JH:trole
in boiler
may
bedamage<t.
call a
tht
boiler and to
ll
combulllon air Intake whwe there
in the boil
er.
units, a carbon monoxide dttecror
sh
the system
be
damaged by build-up or cor
um-based
S)'Stem.
boiler H any
~h
qil3lifi
ts,
a carbon monoxi
er r
oom
..
ed s
rtp
l.act any
. The carbon mon-
on the
l d rcuir
(without boil er con-
TbehbUI-ellic.iencyheat
deaning
Gaskets
This
can
r
esu
damage.
boiler
0<
piping ,.....t
• ciOMd-toop system. Contin
make-
not
n cause heat exchanger to crac
only
sr.alling the n
moke-t~p
rtduct
an
<I
cause.s
up
water
add
cold
u.se
automoti\·t or standard glycol antifrtt:ze.
freeu-protectlon
ow
nt
boiler system that has used gl
woter. Use
boiler life. Min
tanure. Addition
can
cause intern
w.ter
to
aU guidelines gi,·
Thoroughly
ew
boiler.
be
repeiN<I
thlo boiler
ual
eraJ buil
overheats the mate-
of
oxyge
al corrosion.
hot
bolter. ThennaJ shock
k..
fluids
made
tn
dean
br.
ana flush
on
thi.s
njury,
ica
J supply
and
fiber~lass
<entilation
aupply
air
11111
to
cal
_.,under
ervice
techni-
va:
rt
of
de
detec
same
electri
cal
as
the boiler
ros
ion
or
and seals
lt in substantial
staling
in
the
ot once
ONLY
fre.sh
make-up
dup in heat
n carried in
for
hydronic
the antifreeze
apy
)'cO
re-
I before
-
Part num
ber
550-1+2-783/1012
5
GV90+
Series
2
oAs·FIRED
WATER
BOILER
-
Boiler
Manual
Prepare
Installations
Lo<a
l,
srat:t,
provincial, national codes, J
National
Standard for Controls
Boilers,
National
For Canada only: Bi49.i or Bl49.2 Installation Code
Canadian
The
GV90+
perrormance criteria when boiler underwent tests specified in
-latest
1
MOneE
High
GV90+
See
Figure 1 for estimated
input. Multiply the boiler
est
imated high aJtitude i
wi
ll
also
fur
ther info
No mo
s.soo
be
musr
kit instructions, page 10. Note that
checked (and adjus
N
OTICE
Fuel
ANSf/ASME
Ele
EJectricaJ
boiJt r
edirion.
1 For
rhe special instructions located
Insta
from
Al
bo
substantial proprrty damage.
altitude
boil6'
<Mirols
h
ave
a min
rmation.
difications
fee
t above
changed
DO
ar
for DIRECT
altitudes a1x
boiler
must
Gas Code, ANSI Z223.1
ctrical
Code
gas
manifold
th
e Commonwealth
ll
the boi
ti'lpplng
lowin
g.
iler faiJu
Installations
•utofililitAIIy
or
impact on input.
to the
St:a
level. For higher
to
aspttial
ted
if
NOT oldowall
alrirud~s
follow these
and
Safety
CSD-t, when
Code
Pa
rr 1 and any local codes.
and
kr
so
control S)'Stem componrnts
or
spraying water
these
compone
rt,
resulti ng in
inp
ut
at
sea
level
input
nput
. Note that the length
boiler should
high altitude switch.
necessary) followin
vtnt
abo\re
s.soo
VENT
app
we
s.soo
fee
location
codes:
aws,
regulations
- latest edition.
Devices for Automatically Fired
r~uirM.
con
tro
ls
m~
of
Massachusetts, read and foll
on
page 34
or rak'l
nts
to
become wet
severe
personal i
todutt input
altitude as a percentage
b)• this
Refer
be
nece
e-levations
the
gas
DIRECT EXHAUST
feeL
Si
lications (
t
wit
ptrc~ntage
to
the vent
ssary
. the air pressu
Refe
\<alve
outlet pressure
g insrructions on page 63.
dewa
JJ
ducted
and
and
safe
lighting
of
dur
njury,
h
ina~ing
of
the •tenting systttn
supplement l'
for
installatio
r ro the high altitude
APPUCAnONS
venting is only
combustion
ordinanc~.
CSA
C22
.1
and
other
ANSI Z21.13
this manual.
~
ing Optrntion.
cou
ow
protected
ld
cau~
a
death
or
alritudt.
of
St:a
level
to
obrain the
..,r
ns
up
to
re
switdl
mu~
be
allowed
air) nt
Figure
Figure
0
~
1 Estimaled GV90+ input at altitude
Altitude
(
fee
t )
1 000
2,000
3,000
4,000
5000
5,500
6,000
7,000 77
8,000 74
9.000 72
10,000
2
Service clearances (recommended)
%
Sea
leve
97
93
90
87
83
82
80
69
l
Input
TOP VIEW
W"'l
~
6'
i
ml"
36'
...
i%
-~"""
lir
8GIIL>r
rront
:w
••
I
W•ll
cr
oo:nn.ctlo-1!
'
-··
~
,.
....
>
Ve
M
OnCE
Service
When possible. insrall
shown in Figure 2 for best service
nr length
caJiyderates ro compensate for pressurt
See
the
alrirude
\'ll
]ue show-n in Figure 1
clearances
aJso
affects boil
d~rate
values
inst:a
Uartons, mulriply
GV90+
bo
given in
09
ilers
wir.h
access.
er
ro
Flooring
The
GV90+
bur
mu.sr
6
boiler is • ppr
never be install
Do n
ot
ins
used.
Fi r
~
or
subsran
ove
d for installation on combustible flooring,
ed on carpeting.
rall boil
can resul
tiaJ
er
on carpeting even if foundation
t,
causing severe personaJ i
property damage.
input-
Figure
ihe%
d~ermine
dea.rances at least as large lt.'i
the boil
&oss
109,
in
er
through
page 103. For high
Figure 1 rimes tht'
input
vs
sea leveL
njury,
auromati-
the
vcnL
death
i.-.
::1
3:
FRON
36"
rln
T VIEW
C~lna
R.,.,
hool
Fl
..
..-.
l•.an
num
l
I
~
-
••
!
Ql
ber
550-l-42-783/10
-·
s·
-
~-
j
12
GV90+
Serie
s 2
fiA!i
-fll
~o
w
_".,.
IIOlL-1!11
- BaU
er Manua
l
Prepare
boiler
location
Foundati.on
Providt a .sQiid br:lck
is
possible:
When
the
floor ca.n
Whto (hr:
boiJI(-r
When a high
bigh
c:-nOug
-as
the
t.Xmd(nsat~
Figure 3 Minimum fll<J!ldalion dimeosians (inches)
Boll
or
model
G~
GV90+S I GV90
• lnCI'tllk
e;mdcmioll
vf
/
GV90+4
heighl
!rnp
condc"nsate
Residential
or
<Q.ocmo
becoll)f
mbuntin_g
-profile
h tl:\at lhr: GV90+ c(mden,sat,t
condensaie
pump inl
w L
11!;
+6
16
if
nttded
iltlil<U~
puJnp.
ilHilluv~
v/Jttn
garage
foundation
flood~
ak:il
is n
ot l.e're
pump
t-r
c(ui.ne<tio
H'
LU
auo
2
2
re
inlet
301'
371'
u&erd.
Installation
~
pad
it
llny
l.
is u
sed,
provide a foWldaiion
cOnnectil)n
u.
-------=
~
---~--
oi'
is
at
the
least
(continued)
Figu
following
as
hfgli
""""
A ..Arta
+-·
~
::..,
B
C !ProVide 1,2) Fresh ait
re 4
Min
imum
ci~(J$
clearancas
mended
ure 2, page 6, inslali
$ervice
TOP
me
VIEW
~
...
4_:..
m
in
Fr
ont
adjact:n~
and
m\!S~
f
ot"
.se-rvict-.
iNo
o
tJ~r
etc
.)
n'my
..Aca.~DOOR
l~mst
1 5q. inch p
«>
allow
for
...
pplilnC'I:'
l,t
m.JwHel;l
IY
er
ac:-cos
~(tval
or
a.
in
ilh
fft'.AA
~
pccios<-~odl
UM)U
- whoo
lliSs than
clearances ol Fi
rocom
as
shown below:
Wall
t
10"
min
f~
El<>iler
t
op
Wal
l
d<l(tl'
mus
()
( l,he GV90,..boile.r
i.r
mowr
th~
samt
nir
upenin~tr.:
Btu'l1
.
~
lko
acct!1~ible.
(~x
haust
fpacc.",
Wfth
or
bolter input
•
1
l
1ln,
g-
al.
Precautions
Take the following
residmtiaJ garage. If the boiler is located
Z223.1,parngraph
Mount
garage ro assutrt the burner
18
Locate
\'fhi
the
inc.bes
or
de.
Minimum
IAWAHNING
I
Alwa
ys
provide ar least screwdri\'fr clearance
for rt:mO\'al
If the boiler c-annot
and iso
lati
an adjacent area.
The
space has
unpiped and
sptcial precautions when installing r.he builer ln u
5.1.
9:
bo
lltr a minimum
abO\~e
the
fl
protect
the
oor.
bolktr
of
18
and
ignition devices will
so
it
clearances
You
can
in.s
mll
GV%+
ure
2.
page 6 recommended servi
smaJ
Je:r than
I
nstallations with
ure
2,
shown in Figure 4.
of
fronr
on
valves
to
~
shown
page 6 musr ha\'f air
pane-l
be
serv~
so
it
can
be
equ
ipped with a
moved.
boiJers in spaces small
in Figu
clearances less th
for inspection
In
be
sl
in
a residential
Inches
cann
re 4.
openings si
place
id out
door
garage)~
above
the
be
ot
be
damaged by a muving
ce
dearances.
an
shown
ud
and
to
jackrt front panel
and
minor
sen·ice.
. pipe
the
boiler
of
rhe
space
and
so
boiler
can
ANSI
floor
of
the
no
J~
thon
er
thA
H Fig-
but
n
ever
lP Fig-
l
tKat.ed
St."t't'\'f'
with uruuus
krvic«< iu
be
ue<:cs.'icd.
as
SI
DE
VIEW
Coll
~
6
1'
mll
ll'
l
- Accessdoor
lhg
t ,.
+
m.,
1i
4.
co:::
11
6
l'I'W(
-i:
l
f'
NOllCE SPECIAL
FOR
AIR
~-lith
dta
&t:tlfic.e dt:tr'ances {Fig
no
klu
occess
s
door
LWO
iti.r
Each
ltl)t-nirtg, mlJst ba\
l
es~
t.lun J
iurut
uf
DO NOT
given
ure
60,
-
...
£
Flocn
OPENINGS: Flif
tan
ceo.
than shown In
must:
ypw.io&S
~uttre
tt,e-
GV90+
apply
In
Aguro
pa;.
50
Bo11~l
"
&i
dll
REQUIREMENTS
lt.'.-t
than
ure
be
lht
.
Agure
provided,fitted
a5
shllWn io
t:
inch ptr I
boilc:r iu the spacr.
air
aptnlng
42, page
it;,tiill•ti<lill
rec~:J"mm
2.
pagt 6).bul
.i
ft«
36
~
,r
"""
tndtd
4 - An
wlth
Fit.'l.trt'
nl'ea
nu
OOtl
Btuh
alzH
or
FJg
4
~
..
Part num
ber
550-1+2
-783/10 12
7
GV90+
Series
2
oAs·FIRED
WATER
BOILER
- Bo
ll
er
ManuaJ
Prepare
Check
orifice
The COf'l'tltCt ortflce plate must be
will
property damage. The
gas
the
plate -replace
resuJt in
ortflct
propane.
Natural gas:
For n
atura
l
gas
installations.
marking.
stamped with
saler. The boil
stamping.
It
must
anothe
er si
Figure 6.
be
the
r si
u,
7.t
is sramprd where
Propane:
For propane insrallarions,
with
the
redlwhtte
white plate boil
The
boiler
siu
ing. Figure 6.
Also
fill o
ut
lefrside
of
the jacker,abovethegas inlet opening. as shown in Figure 5,
plate
er
siu
is
co
is stamped where the
the
propane
boiler
severe
persona] in
bolltrls
plate. h MUST BE CONVERTED
Inspect
same
obrain the cor
nplac•
as
the
the
boiler
the
sUver
rtct
the
sliver
(continued)
if
necessary
used. FaiJu
jur
y.
death
or
substantial
shipped
size.
plate from
..
X
"'
with a natural
gas/air
If
the
ortflee
orifice
your
is shown in rhe plate
gas/air
orttlc•
rt
to
to
plate
who
, per following instructions. Ensure the
rrtct for the
label
in
GV90+ boil
1
'X
..
th e
com-ersion
er being installed.
is
shown in the plate stamp-
kit
and attac.b
do
so
uu
plate
le-
plate
r
~
to
the
Figure 6 Check
A
:R.emow
p
an~l
to
.m
m
~ide-Qf
housing.
B Co.
mp
lcte1t,el'fopane
connrsion label ind
«1
Wit
h
th.e
kit.
Insr.a.IJ
ld't t
ida
is
~the
on the skid
yo
u
~
ri6ce
11cce658t
Figure 6 Follow insv
,
f;Joil~
8$
~love
chocked
plate and
y.
j
s.cktt.
&oot
aa:~$
thf' bot-
t
he
bl
COP\ttniQn
labt.
l oo. j.:td:d
11$
Mlawn.
oo.lts ba
shown,
thr
n!pl.aoe
gas
or.
for corr
ect
ower
ud
-
ck,.
!Jn
til
g;oi/mr
it
if
uctJons to check
ijice plate
gas
o
r~ice
rx·
= boiler size)
plate
0<
replace
Orifice plate installation, when required
AcctsS the bottom
inspect the plate only.
To
musr read rhe same as ·the boil
Boltr
model
GV90+3
GV90+4
GV90+5
GV90+6
To repl
ace r.he plate . using a maooal
Figur
e6:
1.
Loose
n screws 1
2.
Remove
3.
PuiJ
the
4. Slide in the n
propane plate
5.
Rep
lace screws 3
formly. DO NOT overtighten. DO NOT exceed 40 inch-pound$
torque.
6. lknd down plate label rabat score mark
of Figure 6. it
comer
jAwARtM
I
of
tile blow·
Nat ural
and
er
housi
read
the
er Si7.t
gas
martdng
NG3SEC
NG4SEC
NG5SEC
NG6SEC
2 two full
ng
as shown in Figure 5.
marking
and
on
fuel, as foll
Ptopane
scn
wdrtver
turns.
the
screws 3 and 4.
gas/air
oriffice
plate
forward
ew
plate
as
shown in
nut
go
next to
and
4. Tighten
em
10.
DO
NOI'
use
electric
or tighten
move
onl
y,
usi
ng
4()
inch-pounds. the threaded holes could str
causing
an
properly seal the plate
leak. causingse\rere person
property damage.
r.
he gas/air boss saews. Hand-tighren
manuaJ
SCTtWdri\·er.Shou
inadequate
to
remove it.
Figu
re 6. T
the
bloww housing.
all four screws securely and uni-
as
shown in lower right
or
pnewnatic screwdri\·ers
ki
seal
of th e
orifice
to
the housing could
al
injur
y,
death or substantial
plate edge. It
ows:
mar1dng
LP3SEC
LP4SEC
LPSSEC
LP6SEC
or
nut
Qotver
he
nd
side
rhe torque excted
plate. Failure
resu
to
ip out,
lr in a
.
of
see.
a
re-
to
gas
1-4
.!ia'twi - follow
S
C:a~a.il:'
manifold
6 Fn,nl
7
8 Ptopule Otifict plate.RBDaoe6ideandWHIT.Eon
9
1 0 Orificepbte after bendtng along
~tion.,
$Me
$bcw.ttt mu.tt
llibtf
fll.de
4tbi:r (
ttd
Natw-a:lg:uotifio:e
\liu"b
lt
wl~
lt•itrt~t:Ubnt
lO
skit
r 1At
im.UJ
bouam vi
ew,
po;lnt
t
unl
~
n\11St
~
plate.SIIYE!R
IM
(I'Wa
WH'ITI:-d
dw
fot
l
~lns
campon
nu
dtull.t omiJkd
rd
-aif lltlt1 h
~rhou..~
de
Kote
ttte-
for propane
mack
and lir;htal.ins;
WARN
-
l.tbel
lNG
gM
th~
111
8
P3n
num
ber
SSQ-142-7831101'2
GV90+ Series
2
oAs·FIRED
WATER
BOILER
-
Boiler
Manual
Prepare
In
sta
ll
cond
I.
Btlo
re
plac
ing
lint, shown
Slop 1 Attach the
Step
2 Slide a
Slop3
Slop4
Step
5
IA
WARNNG
in Figu
nip
ple
(B)
scTtW
dra
in nipp
Slide r.he end
end
of tibe
Feed
the in-line
nection (D), guiding the
densate
Press
the in-lin e
(D)
and
Then tighten tl ie
The
flue
end
of
tile condensate drain n
Slide t
he
and i
nt:o r.he
vided
tc>
trap
tee
Sl
ide
l'he
con
densa
(E). Secure the condensate trap hose at each end with
hose
damps
Choc:k
I
Before
distttnce from the con
of th.e boiler mounting ralls. When the boiler is place io
position, rhe condensate
the
condensa
densate p
if
nt<tSSary.
the
en
sate trap
the
boiler
re 7. Items shown are pr
flue
draJn h
.
driver or
le (G).
boiler
in
pos
'irton,
ose
(C) to the in-liue
prnc
iJ
install the
O\'
through
of r.he screwdri\'fr or ptnci l inro the
flu
dra
in nipple
thro
drain
U-cl
the U-
e draJn b
ugh
amp
two
ose
(C).
flue
drain
(A)
assembly
flue
drain
hose thro
(G)
with r.ht screwdriver or ptnciJ.
flu
e draJn (
the seal r
flue
bose
(C) sho
(F) over the condensate trap tee (E)
holes
damp
A)
into th e
ing
until it reaches
connection b
uld
now
ipp
in the rai
and
l.
righren ro sec
ose
extend
le (G).
Atrach the two nuts pro-
ro the raiL
ends
of
the
te drain n
tho
rotating the boil
ipp
le (G)
(J}.
holght
ump
o1
te
pump
is used). Increase the foundation hefghl
condensate
trap
and r.he condensate trap tee
th
o condonsato
er into
densate
tee
inler connection
hose
pos
t~ oud
outlet musr
(continvedJ
condensate. trap
ided wi
rh
the
flue
drain
the condensare
open
into
the
flue
ugh the con-
flue
connection
the
srop
damp to
ure
ition,
secure
down
past
the
condensate
(H)
on
to
trep , ..
me
asu~
~
ro the bottmn
be
higher Lban
(wh
en a con-
boiler.
con-
.
.
the
the
tht>
outlot,
lhf"'
Figure 7 Insta
A
lo-Outdnin
B
Au..e
draln
nfpplt
c
Flu.t
dni:n bose
'f1u.t
c:anne:.don
0
E Co
n.;Jcnsalf'
F
u~~ud ooL~
•b
-)
G
Con
nipPle
H Con
H~·
J
tnq
den~itt
dn.lri
denAuo
lnlf'
d.amp~
ll
condens<~
•
let
(oot,
hcl.l;e
l
e
trap
Fint.hed
MMtnbty
Part num
ber
550-
14-2
-783/10 12
9
GV90+
Series
2
oAs·FIRED
WATER
BOILER
-
Bofler
ManuaJ
Prepare
Install high alti
when
1.
"IA"w"AR=
2.
3.
required
For installations at altitu
a. A special high altitude air pressure swirch
b.
The
gas
adjust~
IING
=~I
Failure
necessary>
or
gu
Obta
in the GV90+ hi
distributor. The hi
pressure switch.
See
Figure 8
a. Remove the
swirch
spade
b. Remove r.he factory-installed air pressure switch (loosen rop
screw and remove bottom screw holding switch
tt'r'iO
r panel).
c. lnsraU r.he high alri
tion.
d. Cart full
on
$hown in
e.
Replace the
swarch
)• replace the
the hose barb cloStSt
spade te:rmi
the
tude
(only above
de more th
valve
outler
if necessar
substantial
idelin
(sw
Fig"~$.
y)
per the instrucrions
ro
check
couJd
proptrty
e$ given
gh
altitude kit from
gh
altitude kir contains the high altitude air
itch shown with wi
two
(REO)
te:rmi
nal
r.ude
hOStS
Th¢whi!¢
two (RED) cont
naJ
boiler
air
pressure
an
pressure
gas
result in
in this manual
seuing must
valve
oudet pr
St'\'ff't
damage. Carefully follow the
res
contro
l wires from the air pressure
S.SOO
removed}.
(continued)
switch
5,500
personal injur
)'Ou
feet)
feet
abo\re
i.s
r~uirM.
bt
checked,
on
page 63.
essure and adjust,
r l
oca
l Weii-
sea
s.
to
jad:er in-
air pressure switch in the same loca-
on rhe
new
switch. with the
to
the electrical spade connecrors. as
hQI¢g~on !h~
rol wires on
s.
o!'h~rh~bar\>,
r.he
new pressurt:
level:
y,
dearh
Mcta
rtd
and
if
in
hose
Figure 8
1 lntmtw
2
3 Air
4 WHrTEb
5 ReD-
8
Figure 9 Follow instruct
Air
pressure switch
poliJII!:I
COl?
J~1
ld1
sid~
panel
pres-
tuft'
!M"itcb
oilli-
MoUnlin.l-i.::r"""
shown
bgtow
moun~ng
ions
to perloon the s teps
Rotate
!A
CAUTIO
After installing condensate line. inspecting (replacing
gas/alr orifice
the boll
Figu
re
These pantls may
completed.
the boi
N I Boileris shipp<d
and rora
and
t'r'
near its position.
9 shows
Bo
may have
rake pr
will
ted
Installing t
r.he
boiler with
bt
left
iler
i.s
h
ope
resuJt in
ler Into
eavy
sha
r precautions when mO\'ing. Failure
position
on
back side.lt must
inro correct position.
he
high allilude kit (
r.he
front and
off
if desir
ed
unr
il
rhe insrallarion h
and contain
rp edges.
St\'frt
s some sheet metal parts which
Wear giO\'fS
persona] in
jur
top
when h
y.
death
If
property damage.
Refer
to
Figure 9 for placement sequence
1 W
ear
hNYY gk>ves - cartfully roratt
base rail
2 Clip
sembly. Remove
3 Attach the )ack
pr
legs.
the
shipping strap securing the skid
O\<ided
in the accessory
th~
skid and strap.
tt
rtar
panel as shown using (4)
bag.
as foll
r.he
ows:
boiler over onto its
to
the boiler block as-
b<
taken
off
skid
if
necessary) r.he
required), m
panels replaced.
and
or
substanri
II
Ox
ove
as
bet-
ling and
to
do
S6
al
~»screws
n
10
P.an ntunber SS0-142-7M/1012
GV90+
Series
2
oAs·FIRED
WATER
BOILER-
Boiler
Manual
Prepare
Perform
Pressure test boiler
no
ted
pro<t<ding.
IA
WARNING
Prepare
Stop 1 Connec>t a
Step 2
Step
3 Rtmo
Step
4 Connect a nipple and shuroff
hydrostat
bel
ow)
or electrical supply. Remo
Use
I
bollar, using
interior pipi
piping connections to prevent them from
caus.e
boiler
for h)rd
Connect
also
be
ture gauge
nection as shown.
connection on the 1"
alr dwilng tbe
the
befor•
two
wrenches
ng
damage
lor
test-see
bose
from water supply to
rosraric test.
h
ose
ro boil
used
to
dra
ve
I" nipple. I" tee, bushing
from
611. Valve
boiler.
boiler
ic
pressure
attaching water
ve
wh.en dghtenlng water piping
one
of
rhe wrenches
from turning.
to boiler
Fallu~
components.
Figure
or
gas
jacket
to
to
10
test
(continvedJ
fill
Hose
is nor included with boiler.
er dr
ain
vahre.
Mak
e sure hose can
in boiler after test
and
pressure/tempera-
accesso
ry bag. Pipe to boiler supply con-
Use
pipe do
tee
pe
sparin
gly.
valve
to system supply
.
This
val~
w
ill
be
and nipple are not
piping
top
panel before
preve
nt
support
turnin
aod
drain
used
included
(exctpl
the
ro bl
as
at
boil~r
the boi
ll"r
goo~.Jid
boiler
eed
"ith
Figure 10
Pip
ing connecli
ons
for
hydr
osta
lic l
esl
Step
5 Connect a nipple and shuroff
Step
c-Onnec.ti.on
bleed
wi
th boil
6 Insta
the rear boil
at
drc.ula
alr
during the
er.
ll
a
o/4
• pipe plug in
er section, as shown. Plug
boiler.
Fill and
I. Connect
2. Fill boiler wirh
3. ·
4.
5.
6.
IA
WARNNG
1.
I
AWARMNGI Leaks
t~j•Of!Hj;l
pressure
611
when
wate
\'lllve.
Close
bl
eed val
Slow
ly reopen drain val
(or
1.5
times boiJ
75 PSI G)
Tesr
Make sure
out test.
Ls
reached
at this pressure for no more than
I
Do
expa.nd
personal injur
co~rant
Check
age
Do
pounds
occur, r
test
water supply through drain v
wate
r (
be
r flows from bl
ves.
tr
rel
on
nolleave boiler
and cause excessi
gauge pressure has
fo
r l
eaks.
mu
st
be
boiler, resulting in substantial property damage .
not use
petrO
in boiler
esu
lting in substantial properr,• damage.
valve
to system rerum
tor
flange
. This
valve
will
fill
Valve
and nipple are not included
the
rtlitf
va
h·e opening. rop
is
not
alve
,ltem
sure bl
eed
valves
at 4 and 5 are op01).
eed
valves,
ve
(item
2)
ief valv
e setti
<he pressure
unattended. A co
y,
death or substanti
Repair if
rtpa
ired aronce.
leum-based deaning or sealing
sysrem.
shur off water at
until test pressure of 45
ng-
NEVER
gauge.
10
minutes.
ld
ve
pressure, resulting in
al
property
been
maintained through-
found.
Failure
t:odoso
Severe
damage
be
1.lSled
incl
uded
2.
MORE
ll~ler
fill
dama.g
can
to
boila
to
of
wi
th
dta
ln
PSIG
than
rould
Si!\'t're
e.
dam·
CQm
wm
-
Drain
2. Dr
3.
4..
and
remo
1.
Disconne.:.t
al11 bobt:r
vidt.s
best
access
h~
after
cl.rnining..
Rto:m
JI)\'e l'lug {itmi
lso
la.tion
viti
boiler's temp«ature
ve fittingo
fi1l
water
hose
at drain vahll:
to dmln.
6)
from rditfvalve
\'ell: at<"
m.Luif'C!'d
Sc.'nSor.
from
water source.
or
out
hose, w
dost
drain
valve
rappU\8;
10 enable servicing
hic
hever pro-
tu
ld reJnovt
uf
th(
Part num
ber
550-14-2-783/1012
11
GV90+ Series
2
oAs·FIRED
WATER
BOILER
-
Boiler
ManuaJ
Install
water
Use two wrenches when tightening water piping
boller, using one
interior
piping
cause damage to boiler component:s.
The
be
to
This is
ci
cuJators.
i
piping
ronntction.s
cast
iron
kept
al
or
prevtn.t possib
done
rculators.
Fa
njury,
death or substanti
General piping I
Minimum
Figure
Additional
Follow
ASME
llmtt
standards
lnsta
and
\\fi
rro
Set
limit conrrol
pipe
siz:e
11
Provide
below (based on 20'F tempera
GV90+ 3 or 4
GV90+ 6 or 6
ing standard industry pracri
or Canadian
may
be
to determine·
JJ
a manual r
th
e isolation
re
the manual
l.
the manual r
boi
Boiler
limit
net<led. Consult locaJ
loop
controls
r
equir~men
if
e-set
valve.
reset
es-et limit control at least
St-rting
piping
of r.he wrenches
from
turning.
to
pre\re
heat exchanger r
above 1
DO
llu
nform
for
ler loop piping no smaller lhan li
needed.
high temperature limit
(maximum setring
4WF during
ility of
corrosion
auromaticall
NOT
~
ro comply could result in
boiler
pipe
limit in series with the boil
y, using the boiler's
rtmove
al
ati
on
loop
size,
ces.
if installation
ts,
an
additio
r~ui
Wir~
as
to
prevent
Failure
ro support the boiler
nt
them from turning could
eturn
temperature
all
times
due
to condensatio
or
ramprr
prope-rty
with these cir-
k\'t'rt
damage.
piping
ture ri
se)
Minimum
1"
i.s
to comply wi
nal
high temperature
remen
ts
for other
shown in Figure 67. page 56.
between
er limit con·
200F
above the boiler
2200F).
the
of
optrarion
interna
pe-rSOnal
sted
the boiler
at
boiler
mu.s~
n.
th
codes/
Air
separator
lnst•ll
ali
air N)>lrator
rnanua
l.
Fur
.single-1.onc--
in
Lht-
rrlllrn piping
aiJ.ows
m01,11lting
off
of
the
In
st a
ll reli
l
L
ln.stalJ
1. Connect discharge pip ing 10 safe di
tb
llow'i
r.be
s<poararor
ef valv
t<litf
val""
ng
guiddblt<-$
Figure 12 Install
(
4}~,.\i
.. ,
..
j®
,.....
" r
.syskr
a&-
:shown
aut.omatic
.
ONLY
in
and
pipe
in
tli<
e
as sbown in Figut.
Figure
relief
j·
r
'
pipi.ng
ns..
in
ait
as
install the
Figi,Jrt
J4> page 1
Vtor and
..
~pus·aJ
1$,
pt.~g-e-13
valve
shown
!Ur
dpatts
12.
.
ir1
th
is
-separator
4.
This
i(,o
tank
IOGition
•
Low
wa1er
A low water cutoff
radiation l
Use
low
type is rtcommended.
boiler. \"'ire contact as
cut-off, when required
dcwlc•
e-.-e
l or
by
~tain
wate
r cutoff designed for water instaJJations. Electrode probe-
If boil
er
units where they can
dling
air , u
se
pr~\rt
nt
Jation
of
damage
personal injury. dearh or substantial property damage.
is required when boil
stat~
or local codes or
Pur
chase and i
.shown
i.s
connected
in
Figur~
nstall
in tee in supply
67. page 56.
to
heating roil
be
fl
ow
control
gravity circulation during cooling cyde. Circu·
cold
r:o
the hear exchanger, causing possible
\'lllws
wat~r
through the boil
or other
Backflow prevent<!"
\"/here required by codes. install a backflow preventer in the cold
water
fill
pages. Install
Une, as
t2
a c.
shown
beck
\'alve
in
s
uggested
if
a
backflow
piping
pre't<enter
er
is insralled above
i
nsuranc~
s located in air han-
exposed
companies.
piping~
to
refrigerated
automatic
er coul
d r
diagram
s on fo
is not installed
mean
esuJt
seveTe
llowing
s to
in
Legend
)atlo.-t plug
lng.
2
fad<tls
i.n
gtb.:c:au.~racl
$ius.
alt.
proVIded
-C/J\'<r
fclr
unused rcllef V'
1
jad:et
the
unu>«i optnln
rn:rvtclt<L
3 Boil
4
5
6 Connect
er
relid' \'liiV< (from ll«c$$Ory bag)
'4"
x 3
••
nippl~.
provided in
~··
fditf
vah't tapping in back
\'31\'C,
min1mw'n1i,.
S..
flgur•1
oli\'
t
Jackt
W!U
r t
W6
re
lief
valVe
$'iU:
i
ti,I;Sed
for two bOtltr
.g
Wid>
acccssory-bag
.$b:ti<>n
c,l.ilicharg'e
3,
pogoo
r..art
plp.
ing
13
.
nwuber SSO-l42-7iU/IOil
.....
"~"''"'
op6i-
the
plug
to
rdid'
GV90+ Series
2
OAS·FIRED
WATER BOILER -
Boiler
Manual
Install
Figure
13 Relief valve installation guidelines
IAwARNIN61
To avoid
du•
per
Discharge line
ro rtli
safe place
discharge li
p~•ttn
or proptrty
disdlarge.
Dischar
po
\~vt
out its entire l
Discharge
f'rom
6'
discharge
The
plai
rial
37
Do not
place where
No
betweton r.he relief valw and boiler.
or in the discharge line. Do n
plug or pl
discharge line.
fur
filling and pressurizing
l
disdlarges flffly. If !he
Optne-w
Failure
guidelin
r.htin possib
jury, dear.h
da.mage.
water
w.-rd•m•ge
to relief VIIYe
loc•l
or st.te
ef
valve
of
disposaL Terminate the
nt
t
possibiliry
damage should r.he
ge
line
ssible
and
discharge connecti
line must pitch downward
the
valve
above
the
will
discharge line shall terminate
n,
nor thread
se
rviceable for temperatur
5°F
Or grt:ater.
pi
pt
(reezing could occur.
shuroft' valve sha
ace
the operati
ift
ing r.he le•;er. Make sure r.he
piping
or
op•mlon,
codM-
:
must
be
con
outlet
and
in a manner
of severt bums
must
be
as
be r.he
same sir.e
on r.hrough-
engr.
h.
and tenninart
floor
drain
bt
dearly
vis
ed,
with a mare-
the discharge ro
ll
be
any obstruction in the
on
or r.he \'al
vah'f fail
rate corr
rf'lief vah·
rf'liei'
ectly,
repl
ace
e.
to
comply with
es could resu
\•alw
ili
ty
of
or subsrantial property
lt
in failure or
to
optnate. resultin
se\·e:re person
acalclng
nected
run ro a
that
\'ll]vt
short
as
at least
where
ibl
e.
es
insralled
ve
after
system
valve
it with a
r.he
above
al
• •
will
as
the
any
o(
any
ot
by
s to
g
in-
(continued)
E
xpansion tank
Figure 14. page 14 and Figure 15. page 14 show typical insra llation
expansion tank. Al
shown in r.he suggested piping drawings. beginning wi
Ensure r.hat the expanslon tank
volume
ngs for detai
i
handle
in
and temperatu-re.
th
e expansion. These
r.
he system pipin
Diaphragm·
Refer
ro Figure
or
bladder-type
NOnCE
ll
an
Insta
manufacturtr
automatk
way$
locate r.he air separator and expansion tank
size
w
iJI
handle boil
Set'
tank manufacturer's instructions and rat-
ls.
Add
iri
onal ta
nks
may
be
added to the
ranks may
g.
UndeniZCid
from
th
the
fiU\•ah-e.
th
ecokt
locate this elsewhere in the system.
or
blaclcler-type tank:
14
,
page
expansion tanks cause system
e r.tli
ef
\'lllve
E\'entual
water
flllconntcUon at the expansion tank.
·14 for suggest
be
installed
and makeup water to
section
fallucecan
ed
piping when using a diaphragm-
expansion tank.
Diaphragm·
flU
prNSU'e
pressure
to
be
sure r
PSI G.
Operating pressure
sion abo\
avo
id weeping of relief vah·e.
's
instructions.
o.-
wi
a~nd
char
e:ad
ing
-e
cold
air
wnt
bladdor·typt expansion tank- Control
th th
e rank air char
ge
tank
with
tank
is
accurate. Boiler reli
of
fill
on
pressure
system. after temperaturt
, should not
top
of the air separator, per separator
th
Figure 17, page
er and system water
sysrem
by connecting
be
resul
ge
pressure. Always ched::
removed
ef
\oalve
exceed
Closed-type expansion tank:
Figure IS, page 14 shows suggested piping
sion tank, in which the air is dirtctly in contact with rank
Connect piping
fitting.
Slope
hori1..0nra
Always
(
a>'oids
heighr in the tank.
shown
NO
TICE
use a
). The
air bubbling
(Y:t,.
or ·W') from
any
horizontal
l pipe.
tank
fitting. such
fittlng
reduc
the
COI'I"eCt
air ro escape from the system and
of
th
e tank. This will
rdiefval
NEVER
dosed-type-expansion rank. The air
will
Cl~type
instructio-ns for
for
normal level and system water
va
t
ern
excttd
v.e
use
cause water-l
appr<>Ximately
lw
i.s
se
peca
ture expansion
24 PSIG
piping a minimum
as the
es grav
ity
<>Ugh
the
tank wate
aU
leaks in
due ro over-prtssuri:zarion.
an
automatic a
oggi
expansion tank-
ftUk'lg
12
·t for 30
PSJG.
to
a\ro
when
usingadosed-typeexpan-
the
air separaror t
of t
B&G
Tnnk-trol or Taco
flo
w of wate
the
system
result in water loss
ir
ng
of
the
PSIG
Operating pressu
abo\'e
id wetping
r In
r, and
provides
or
tank piping.
will
venr
in asysttm equipped wi
~moved
the expansion tank.
Follow
tank. Typical tank
when
the
i.s
co
ld. Note that boiler relitf
cold
fill
of
reli
op
outlet ro r.he tank
inch
the
plplng
cause water-logging
r.hrough the boiler
tank
tank
re
presSW"e
ef
vahre.
of
the
as
16.
if needed ro
r.o
tees
ware
r robe l
os
added through
t.
Always
locate
Never
from
sy.tem
is
ser for 30
expan
24
PSIG
to
warer.
per 5 feet of
Taco-Tro
to the
tank,
the
proper
fill
le:aks
alloo.v-
th
from rhesystem
man
ufac[Uru's
si'z:
ing provides
is
fill
ed to
the
of
sysrem. after
, should
not
t
-
l
a
Part num
ber 550-
14-2
-783/10 12
13
GV90+
Series
2
OAs-t'IRED
WATER BOILER -
Boil
er ManuaJ
Install
Figure
14
Pip
bladdllf•lype
1" N
water
ing to single-zone system using diaphr
expansio
PT (su
ppty from
piping
n tank.
1"tee, return to 1
Boiloc conn
(cononuedJ
"'
recuperator
®
t
agm
ectio
· or
ns
are
Figur
e 15 Pi
ping
closed-type expansion
lan
k
Pipe
NOnCE
NO
nCE
diaphragm-or
tom
of
the
Pipe dosed-
separator.
type
theairseparat
tank IOC'<ltion, as shown abc
1
Rtli
ef
vah·e discharge piping-
2
Isolation
3 F
iJI
4 Di
s
how
5 Air separator
t4
\<al\'d
valve
aphragm-type
n in the suggesttd pipi
provide with
with
diaphrngm
pi
pe air oudet to
dOS<-I)'pe
UUlk.s
bladder·l)'peexp
(air
in
contact with
or.
Alv.a
ys
connect
we and
stt- page t 2
txpanston
automatic air wnr ONLY
-typt expansion
expans
tank-
ng
drawings
ion
rank
ansion rank.s
water)
the
fill
line
in
the
al
ways
in this
when
ranks
when used
to
tank.s
to
to
the
ex
suggested
Legend
locate
as
manual
used
wi
th
the
bo
t·
the
top of
pan
sion
piping
l
8 Cold
7 S'r•l=
8 $ys\o:m
10 PfclsWe
11
12.
13 Tank fittlng
Jill
line.With
wb,..
rtquited
pi\lll'lit
~)
.u~plyp
n;wro
i'edllcing valVe
Quk-k>Jill
C
IU<M-
i
ll
the
b)'lll>ss
cyl"'
:~
ugg
esctd
.bac~owpteventerilr
by
c<ld•• t<et Figute
iuin
piping
valve, wbel) u
E'ltj>I'>Ml6o
piphl8
$
wh.m
1
ranlt-
d.rawiqp
15
USc~
sed
alw
oys
iu
thi5
Ch
eck valve
foi
typioil cOm-
!o.:a~e
o.<
Slwwu
manua
l
GV90+ Series
2 OAS·FIRED WATER BOILER -
Boiler
Manual
Install
Syste m
NOTICE
Ci
rculato
IAWARNING
Circulator flow
Size
r.
he temperature change needtd.
perature rise
formula, where
rate (in gpm). and
I
system c.irculators based
water
wa
te r piping me
Most piping
primary/seco n
These
GV90+ boiler , for the
oprration
For othe
McLain r
rs
Do
no
for
u.st elsewhere in
rtqu-irtd
w
ill
cause the
pr
operty
Ntver
GV90+
erarioon
damage
Failure
maJKe
flo
w.
(o r
drop
TD
BTUH
methods
dary
designs
of
the boiler
r piping
tprtktltath
t remove either
for pr
ope
boiler
damage
Install
another
bollcw. Forced
of
rhe boiler controls. Substantial pr
could
rtsult.
to
comply coul
and
nuisance shutdowns from insuffident
rate
on
} throu
is
temperature rue (o r drop),
is the hear load
FLOW =
Examplu
Consi
to
210,000
piping
:
der a sys
Btuh. Tbe
is
20'F.
tem loop for a system with
desir<d
temperature
Then
the required
210,000
FLOW =
20x
SIMPUREO:
Circulator
Th
e circulator
against the head Loss that
r.
he pipe si
engineering
ro residential systems.
units
or
I
AcAumN
For
20"
IOJTC)oraturo
head
te
needed and r.he resultant head loss using accepted
method
radia
nt
The following sim
I
cuJaror
tionsusingbaseboard (finned
r
heati ng.
requirement
mUISt
be
s. The slmp
and does n
tub
ing.
si:z:
adiatOrS
f.m
capable of delivering the
will
ing must
or
COn\rtctors.
coil uni
piping
thod
shown
con
ensure proper flow through the
methods>
•e.
of
the
r operation. Remo\•ing a
to
cou
ld result.
flow
d result
the
flow
You
gh
a circuit by using rhe foll
in th
necti
on
to
mo
st
effkient
and Lhe
consult your local Well-
the
GV90+ intern
system. Both
malfunction. Subsrantial
pump
In
can
cause
in unre-liab
rate required
can closely estimate
fo
r the circuit:
(continued)
s
i.s
manual u.se
the boil
and
heating
pumps
..
-.
improper
to
FLOW u flo
er l
oop
reliable
syst
em.
al
pumps
pump
wtth
ope-
le
~rfo
ac.b..ieve
tem
owi
art
the
op-
rry
r
ng
w
BTUH
TD
X 600
rot:al
heating load equal
drop
through the system
flow
rate
is:
21
600
occur
llfied
ot
pUfied
be limited ro residential applica
rs
=
drop,
FLOW • MBH
in
the piping. Dt-termi
pipe
~z.ing
include systems with
method for pipe
or
DO NOT apply for radtant
or commercial installations.
gpm
/10.
required
here is limited
cast iron), cast iron
fan
and
flow
ne
coil
cir-
Simplifie d
t.
lnsrall r.hr boiler and piping usi
.
-
-
layou
2.
Site r.he
heating system
head
a. Dettrmi
b. Calc.ulate the
To
MBH (I
Exampl
Btuh:
c.
Find the pipe site in Figure I 6 that has a
just larger than thar
d. Find
TEL
using the equivalent length
the same head
length of the circuit
TEL
circuit for residential baseboard, radiator
t
e.
Measure-r.he ltngth
oudet
1
f. Find r.he head loss for each circuit:
g.
NOTE.:
aU connected
3.
Example:
a.
Fo
MBH).
b. Flow= 45 MBH / 10 = 4.5 gpm.
c.
TEL=
d. From Figure 16, seifct I" pipe (max
e. Head loss = T
f. Selecr a circu l
head
NOnCE
Figure 16 Flow ra t
Pipe
size
(lnctoas)
~
1 8
1
14
11\
pip
e/c
ircul
rs
in
r.his
manual.
pip
ing and compontn
usi
ng
Figure-
1
IOOoSin
or
..5
all
piping
wtll
nt
r.he
heating load (Btuh) for each circuit.
flow
rate f
use a
200F
temperatu
,OOO's
ofBt
uh) by 10.
e-Flow for 20'F temp dr
FLOW=
r.
he
t:Otal
accounts
Is
usually_
35
required for the circuit.
equh
·alentlengr.h
for
losse
loss.
Add
to
close to
applicstions.
of
bsdc
to irs
inl
et. Then muldpl)• this length
to
ger
tht
approximate
TEL • 1.5
H
EAO •
X Circuit
TEL
X 0.04 (feet
Siu
sy
stem """der piping for the total
or
re
MBH I 10
s through 6ttin(!'
tllese numbers ro rhe
find
each circuit from rhe circulator
Length
z.ones.
r a circuir with heating l
Measur<d
1.
5 x 88
of
5.28
To use this method, limit the
finned-tube baseboard
board
the c.
of
into
<:Opper pi
MAX--
• 0
.04
I
length
feet = 132
EL
x 0.04 =
ato
r that can deliver ar least 4.5 gpm at a
fee
L (Read the NOTICE below.)
and
limit
irc.uit
cwo
or mort .
es
...
4 2 45
14 3 140
22
flo
requires more
tor
0.04
pe
(based
(G
Pt.l)
per
loot
ator sel
ng
the recommended piping
rs
for each circuit in rhe space
6.
At
the
bo 0.041oot
each
drc.uit using its
drop, just divide rhe
of
TEL
1.5
times the length
TEL
of
wate<
oad=
of circuit
fe.t.
132
x 0.04 = 5.28 fe.t.
to
3.9 gpm,or
w to 7.1 gpm.
fMt
hfHid Joss,.,- foot of
oo
water
Pipe
size
(l
nctoas)
:lli
•
ect
flow
rates lsted,
per
op
with 35,000
= 3.5 gpm
(TE
L)
oftht
pipe
r.hat
in
feet
.
the circuit.
(feet)
column)
45,000 Btuh
is
88
fffi.
flo
w= 8 gpm).
flow
If
flow
, split the drc.uit
at 140"F)
MAX--
• 0
ion
foot
of
max
flow
circuit.
and
valv es
would cause
measu~d
or
convec·
tbrou3:h l4"
use
the total load
.04
...
per
75
290
the
piP<>-
load
rate
by
of
the
times
flow
of
(=
45
I base-
(G
Pt.l)
loot
Part num
ber 550-
1+2-783/1012
15
GV90+
Series
2
o.Ali-FIIIW
WATia
IIOILER -
Boiler
Manual
Install
Figure 18
, ··-··- --··-
I
1
r---
\
...
1-,
'
I
'
I
Zqn~
(DO NOT apply
~
-"-
water
vallle
zoni
L
---
--
®~
Zone 3
·
L
Zone 2 1
L
Zo
~
piping
ng -
GV90
+3, GV90+4
to
GV90
+6)
(ZiY
10 3U•t•u
li
~
.liVI
h
l
- - " - •· - ·• - •·
----
~
----
lZCfle
2
Clrctl
!l
P-!Vlfll -
~Zona1o-rWfl~&ml
ne
1
_ .. -
(contrnued)
or
GV90 +5
~
..
-
'"l -...
..
- .. - ·· ._,
- • • I
-------------4
....
..
_,- ·-
ff_t
'
'
I
~
I
..
i
I
I
I Isolation 'ildvet
Aolomalk
2
di
aphr~m-typt ~n
lion u ). or conn«:t
ta.nk
ex;
DUpbra&m·
ty~
'
uud.
~ion
to~p
u:nk fiu.ins u in Fi
UJ'It
Boll or
GV90+3
GV90+4
GV90+5
air
'lftlt
6tuog (doted-rype
pantion tank). 10
or
af:n
( r
of
15
, f!t8t 14.)
Pipe
model
bbddtr-
sion tllnk,
dosed·typt
tl.nk.pipefrom
a.tr
upua
sizes
tor to
Legend
Zonewlft
(with
•
7
Hose
-
10
if
16 Cold
s·
(NPT),
Mains Circuits
1'
1l4'
bibb
8
Boile
r
prtsswt/~tmptn.·
"""8'"8'
Difft:rentia
putva
lw
watet
Fisure IS, page U for
typicd componen
minimum
pu.rse
l
pttsswt
fi.D
line-
14'
14'
va
lw
br·
8t'lt'!
tt
I
•
I •.:fl
: :
'
~
-
!_
--
-
-
--~
~
F
1
f
Figure 19
Bo<ief
mode
t3V90+3
GV90+4
1hesyslam
Ql
rculalor HEAD
l avallabls
S\'SlO<Il
e,
.o
~eot
0 6.SGPM
4-
.1 feet w.
Ill 9.7GPM
-
---
m
~
10
the clr
""
"'
c.
meet lhe tollowing r
Maldmum
cutt
longll\
L
103 lt!el
92feo
'M1nlmum
number of any of
oto
l 3
equ
irem6f"lts
lrcults circuit
when
load
40MBH
33MB
NOTICE
applyin~;~
Max
(0
H
Circuit
One-p
plication information
on two-
\vhethe:r the internal circuJaror
suff'ic
sys
rem> use
Figure 19, page 17.
Figure 18
f&el baseboard Summary
any
circuit
600
BWMoot)
67
feel (max 4 GPM any circuli)
55
feel (max
requirements
See
Flgure19
lpo
<1
- - systoms
pipe
baseboard
ient
flow
the a\'llilable head value given in
to a one
6.5 GPM
20'F
9.
3.3
on
this
sys
tems.
-pipe div
1018
7 GPM
1018
GPM any clrcuh)
-T
page
can
1
1
he
is
based
To
check
provide
erter
ap
tee
-
5.5
,
QV9(H.S•
f,ln
number S50-l4:l-783/ l 011
loti! "'""
08.7GPM
f1~lilat
3 53 MBH
eo
feel (max
30'F
6.7GPM
3.5
GPM any circuit)
drop
17
GV90+
Series
2
oAs·FIRED
WATER
BOILER
-
BaUer
Manual
Install
Sin
gle
-zo
Rad i
anr
heating
system supply
water temperarure
ing conditions.
supply water temperature
Figure
22
uses
rtmperaturt.
the suppt) • temperature limit control (irtm 14)
sys
tem from over-temperature conditions. Nore also that this piping
requires a separate system circulator,
fl
ow rat
es
of radlant and beat pump
Manual adjustment
zone systems because multi-zone sysrems
making it unlikely an acceprable
Figure
23,
page
You
may also apply the suggested piping
Fig
ure
24,
page
or outd
oor
reset
water
ne
rad
'-11 healing or
sys
tems
and
war:er
temperatures below
will
be
at least I
So
the piping must indude a method
to
rhe system.
two
'balancing val
Follow
the instructions
piping
heat
pump
SOOF
ves
lO
manually adjust
~low
as
system
of
the supply
20
or Figure
20
if
you wanr auromatic suppl
remptraturt
temperat
valve
24,
page 20 for multi-
contro
l.
(continued)
heal pump
systems usuaHy require.
1400F.
But
the boiler
to
1600F
dur
ing most opt.rot-
of
r
Mudng
rht
supply Wiiltr-
to adjust these valvts. huuU
as
shown to protect tht-
shown>
because
of
the hjgh
s.
u
~
is limited
will
cause
setting could
1.o
of
eir.her Figu
)•
temptralure regulation
to
varying !
be
found.
ne systems.
re
23>
page 20 or-
Ol,it.leL
the-
n-
single-
(load$.,
See-
Figure
22 Sin
h
jo
g!e.·zo
eat
na
PUII\P
"'
radi~t
heating
systom
"
01/90+
ot'
or
a
""'
.,-,
For additional information and altemativts in piping for radiant
ingsystems> con
J
/IOTIC
E 1 Tho system circulator
Adju
st
Use
\•alves
water, reducing su.pply
I. Subrract the design
rhis
number rbe temperature
2. Open val
3. Starr the
4. Let the sysrem warm up
5.
Note
(boiler supply).
6.
Slow
ly
tower th
in
~t<p
1. Example:
ture dtfferenc.e
until gauge 9 reads at least
tad.
\Veil-Mcla
stall«.
bal
anc
ing valv
17
and. 18
to
ware
system
v<
17 and
boiler and
the temper
dose
an
gauge 8 by ar least the
I.
Fo
do,.
system.
atu
re ar gauge 9 (sysrem supply) and gauge 8
\-alve
17 while opening
r a desi
gn
woUld
in.
,...,t
bo
supplied
es
mix boiler supply water with
r temperarure ro the sysrem.
supply rempe:rature from 1
va
l\·< 18
f'o
r about
supply
be
I
SOOF
SOOF
dtffennce
.
temperature
temperatu~
minus
lower than gauge 8.
15
minutes.
\•alvt
IOOOF
.
18 unr
of
1 00°f,
. or
dtfferenc•
SOOF. Set the
by
sys
tem return
50°F. CaU
ll
gauge 9
r.
he tempera-
hc:a
tho
In·
1't'"Jd
fOund
vn.J\ftl
t-
"'""
Lege11d
1 Isolation
2 A·utomaric air vrnt twilh
tank.),
s.ioncank
3
~i.ap.h.rayn·
(F'ordasti!·t)~expan·
sep~.mtort
5 S)?tt:m cirtu:b.tor
7 H
!
fl
IRHierr
~
Systt:m
10
R~tu.rn.
14
~
Upplyfempt:ramr~
tu
directed by the-n•stt m
16 Col
compa.n~nn
17
Ril..l
T&h'el.
or
oonnec
uo
diapfU'BJPll
tank ,fitting
l~
or
bl
adthec-typ
o
tarik 6ttingasiittf.lgurt
nSt" bibb
rtbtklw th¢
purg.e:Ya.h-e
~e(te:mpc-rarure
supPl~
terupen1twl! g:.uge
rem
pt:rof\l.fepu~
max
imum
dwar;er 6Uline-
ando_g
vai"Vt>.
t:
sion
tank.
gauge-
Umitconttoi-Sd:'!lt'9
'Ill~
Wig:ner
seef
igure
·fl'F't
d-type .
p¢
fm.rn
15~
the
apauSioll
e:xpa
t¢k
i.
(l.!Sed
1
topofilir
pagt 14.)
U!mpe:ra-
'Ylll<!'m
forrypfca
or Ill
(dose
exF*~.Oo
pi
for
.
ts~pagelA
n·
I
l
Part
number
550-1+2-783/1012
'!
S.l""""g""'="'
!:.----------.!
19
GV90+
Series
2
oAs·FIRED
WATER
BOILER
-
Boiler
ManuaJ
Install
Multi-zone
Mu
lti-zone systems require
ply
temperature
(zone-
\-alve
piping for these sysrtms.
I
AWARNJfG
Zone-valve
for
heating S)'Sttms and
system
Circul
remo,red. Provide a
I
NOTICE
NOTICE
NOTICE
I Provide an automat
sys
tem
whe
.aror zoning - The
water
radiant
becau.se
roning)
zoning-
circulation to
n
and
moto
r-Optr.ued val
desired
protect the radi
supp
The
to
the
rttu
rn water temperature
separat~
Baianc
lr).g,
val\·~
for one
the memory-stop v
isolarion_
Zoning wtth
transf
orme
former
zone
Do
to
vahres.
not
LIM R & C
piping
heating
auromatic regulation
of
wi
dely
varying
Figure 24 ( circularor zoning) show suggestfil
ic
ve
l)• water t
sugge
provide
assure good temperature
GV90+
circul
when
of
zon•
r to power the zone
hand
Alternath<ely,
tmptratu
ant
system from
sted piping uses a separate circulatot
the
internal circulatorS must n
atO
*"'lnKI
the
isolation
ah-e
valves- Provide a separate 24-voiL
le
the
total
coi'WMtCdons
system
load conditions.
temperature control valve
\vhich can
rt . This is required tn
excessive
hlgh
er
flow
is
l
ow.
r for each
- Substitute a memory-stop
valves
for
balanc.ing
valves.
rated
use
a 20ne
for
rconunuedJ
of
the
be
adjusred
temperarure.
typical
di.srri
buri
7.0
n ~
.
in each
flow
Size the trans-
load
of all
valve
20ne
zone valvt.
syst~m
Figure
for the
of
radian
on
in
ot
z.one
ro usc
as
well
conne.:
controller
sup-
the-
ted
2.3
or
be-
as
t
.
Figure
...
I
0
23
A~to
system
zooo
valva
~-.].
:~
-
•. zonol
-
Zon•"
c:>
1
"'
-·
0
"
'
t
Q
"'1PPiY
ZOflt
ng
--~-
<::I
¢1
•t_t\t
'!\
~ ~
~
.
temp regulation-
~
1'
••
r;o.
~·
'll
OV90
._
I
"t
I
Q
19..)
0
...
NOTIC
Outdoor
App
ly Figure
of
the supply water remperaturt.
and
an outdoor reset temperature control
Zoning wtth
E
circulatOT
one
from
boile
circulatOT
tem clrculalor
reset
23or
of
th e factory to
r.
Figure
circulaton
cann
ot
be
tbe zone circuJarors. lr must remain as shipp
You will
rela
ys
24
for any
n
~
or circul
must
Legend
Lsolatfon vatves
2 Automatic
connect to
3 Diaphragm-
type expansion
as
in
4
Zone
5
System
6 Flowlch
7 Hose bibb purge
8 Boiler pressurelt
9
System
10
Supply tempera tore
I I Differential presswe by-pass vatve
16
COld
air
vent (with
tank
or
bladder.rype
l~pa~
or
zone
eck
val
supply t
tanlr.
ci.rcuJato
ve
emperature
Figure
val\>e
,ater6Uline
6tting
vah-e
emperarure
- see
diaphragm-type
(
dosoecf-type
pipefromtopofairseparatortotank
14
.)
r
auto
matic mixing
Figure
- The GV90+ internal
removed from rhe boil
allow proper flow
a circularor for
ato
r zone controller.
be
supplltd
system
inrended forourdoor rtsel
Use
a motor-operated three-way vah
sy
expansion
expansion t
gauge
gauge
l~page
ank.
vaJ,-e
14fortyptcalcomponents
~ach
by
stem.
expansion
tank
if
used (
contr
ol
zone.
the
Installer.
tank)~
),
For
er
for
ins
The
closed-
fitting
sysrern
use
as
ed
ide
the
Provide
sys-
re-
or
Figure
...
I
0
ll
24 Auto system supply temp reguiat
ci
rculator zoning
ZOn.G
Q
2
~
"'
-
~
-
+
~
-
.,.
_
.,.
Zona 1
t,!::
r
\I
- -
£:>
¢3
:f#
-
~:
@ {
ri
•
GV90•
I
·
~
(?o
X
·~.
<::1
T
!~
iQO
·
~
951)1
-
..
I
0
Bb
20
Pan num
ber
5SO.I<t2-783110l2
GV90+
Series
2
oAs·FIRED
WATER
BOILER
-
BaUer
Manu
al
Install
Pipi
ng
snow
snow
Combination snow mdr/space hearing sysrems can have
temp
these systems
Figu
Select
which
60'F.
Zone-valve
fo
system
Circulato r zoning - The GV90+ internal circulators must
r
emoved.
melt/space
erature
re
25
(zone-\tal
an
automatic
can
bt
Any
S<tt
zoning-The
r sysrtm circulati
when the
Pro\ride
NOTICE
NO
TICE
water
melt
bel
ow
60'F,
~u.lre
ad
ing higher than 60'F
The retu
ar Jeasr
r
control operation
property damage.
Zoning
d
on each
these
for balancing
Do
automaric rerum water temperature as shown
ve
tempera[U~
justed tO pr
on
r
~turn
:a
St-parate
WF.
erur.n
ttmptrarurt. Fail
with
iagrams
side
in
each zone
not
use
systems
he
and
the
7.0ning) or Fi
O\'ide
suggest~
to
assure
good
water temperature is low.
circulator for
r-n
warer
Provide
problem
zone valves -
in this
section is
.
Substitu
in order
flow
R & C connections for
piping
or
combination
ati
ng
systems
return temperarure w
gu
re
26
(circuJaror
control
\'ll]vt
or motor-optTattd
a rerum water
will
also
pip
temptrat
ttmptrarure
and
urt
te a memory·stop val
as
well
as isolation.
rtmptraturt
be
acceptable.
ing
u.ses
ure
each
zone.
ro
apply
means
to do
so
s,
caus
ing
Each zone in the piping
shown wi
to
use
the
a separate circuhnol'
distr
the boiler must
can r
possible signifi
th
memory-~top
zone
(cootinu
rttu
ill
flu
7.0ning).
ibution in
to
regu
esu
an
iso
ve
vatve.
ctuat
of
lt
lation
for
edJ
rn
wafer:
e.
val
at
least
nllt
late the
in
boiltt
cant
valve
O'De
vah-e
So
in
~
l.hf
be-
bt
of
Figure
26
Aulo r
zoning
<::1
-1
•!
)ltC":i
r::::>
;;-
s
e\Um
temp regulation- circu lator
---
··==
Hcn
tingzono<&
C3
..
......r.
~
·1
I
•t-
--1
:
~
......
6
J)
"'
~
r
(j
..
£l
-·
--
:
~
<::3
_A
~·
·
~
·
~
=''1
fl
\\I
Pro
vjde a
separate
valves. Size
of
all
NO
TICE
I Isolation
2 AutomatK
3 Diaph
4
5 System or
6 Flow/check valve
7 Hose bibb
8 Boiler pressure/temperature
9 System suppty temperature
10 Retu
II
16 ColdwatertiJlline-
Zonl
circuJator cannot
one
from the
bo
iler.
circuJator rdays
tern circulator
vah>es
connect
type expansion tank, pipe &om top
as
Zo
Differential pressure by-pass
to
ragm-or
in
Figure
nevalve
rn
temperat
tone
p-urge ,.aJ
the transformer to
connected zone val
ng wtth elre!Jators- The
of
the
z.one
fa
ctory to allow
You
will
air
vent (with diaphragm-type expansion tan
tank fitting (
bladde
r.t
1
5,page 14.
circulator
,-e
ure a
ut
we
24~\·ol
t
transformer
han
ves.
be
removed
circulators.
n
eed
a circulator for
or ci
rcu
I'MIIt
bt
from
It
must remain
proper
lator
7.0
supplkld
Legend
dosed-type
ype expansion
)
omatic mixing valve
Figure I
gau~
gau~
vah-e
S,
page
expansion tank),
tank,.
of
air
separat
14 for typical
to
power
the
dle the
tota
l rat
ed
GV90+
ne controller. The
the
flow
by
if
internal
boiler
control
each
the
used
(For dosed·
or
to
com
system
fo
r
as shipped
in~d
7.0ne.
Provide
Installer.
k),
tank
fitting
ponents
zone
load
use
e
sy
or
as
the
..
Figure
26
Auto r
e\Um
zoning
S•\owmclt
M&texeM.ngor
F 1
"
~
t
r::::>
",
-----
·f
C3
Haating tonels)
C3
• 1l' ..
·~·
u. Q
''L
temp regulation-
~
; .
.,
~·
OVH•
zono;
C1
((I\
valve
Part num
ber 550-
14-2
-783/10 12
2J
GV90+ Series
2
oAs·FIRED
WATER
BOILER
-
Boiler
ManuaJ
Install
Wat
er chiller
Pi
pe
the boil
Install boiler, as
heating boiler.
Use
appropriate
See
Figur<
Install the
Figure
If boiler
th ey
can
automatic
NOnCE
NOnCE
NOnCE
er and
27 for
flow
27)
to
prevenr gravity circulation duri
is
con
nected
be
exposed
mellllS
Balancing, when
\'lllve for one
the
isolati
Zoning
transformer to
forme.r to handle
zo
Do
water
system s
wa
ter ch
shown>
\•atves
typ
/c.
bec
ne
not
so chilled medium
to
prto\'f
ical i
nstallAtion
.k
''31
to
heating coiJ
to
refrigerated
ro
pr.e\re
memory-stop
on.
wtth
vahoes.
u:se
piping
ill
er
as
shown in Figure 2?.
nt chilled
'" in
the
nt gra\rity
111qulrad
of
the isolation
zone valves -
power
the
Alte.rnati,-eJy,
R & C eonnecUons
medium
of
balanci
boiler
supply
s located in air handling uni
air
,
use
flo
circulati
- Subsriture a memor
valves
\'alve
for balandng flow as
Provide
the
zone
total rated l
use a zone
rco
nun
is
piped in
ng vah"
ng
the cooling
w c-Ontrol
on during cooling
from
entering boil
and
piping,
in
each
parall
check
as
shown in
cycle.
\..Uve.s
1.0
ts
or other
ne
a separate 24-volt
valves.
Size
the
oad
of a
ll
connected
valve
zone
ron troller.
for
zone vatve.
uedJ
el
with
er.
vruvt>
where
cycle.
y-sro
p
to
us
~
well
as
trans
~
Figure 27 Installing
water
clii
'7
~
.
0
•
Q
~
GV90+
ll~K
boiler
@
e::>
il
in
syslam
~
~
rJj
(!)
with
4ij
Q
NOTICE
Zoning with circulators- The
circulator cannot
one
of
the
from
the facto
boiler.
Yo-u
circulator relays or circulator zone controller.
Chilled water
as s
ts
how
()n rh
ranks,
air ven
be
removed from the boil
z.one
circul
atorS. It
ry
to
allow
will
need a circuJator for each
systems
n in
ese
ofren use dosed-type expansion
Figure
systems.
proper
27.
00
GV90+
must
flow
NOT
internal
rtma
in as shipped
control
z.o
insta
er for use as
ll
system
inside
ne.
PrO\ride
automatic
the
asou
Legend
Lsolatlon
2 Air separat
3
E.xp&Mion
application of a closed-type expan sion tank)
5
System
6
Fl
8
Boi
16 Coldwater
components
17 Balancing val
19 OliU
20
Strainer
21 Oleck
22
System
23
System
vatves
or
tank with tank fitting (piping shown for
circulator
owlcbe
ck
valve
ler pressureltemperat
6Uline- see Figure 15,page 14 f
\>e
er
valve
supply
return
we
gauge
or
typ
ical
22
Pan num
ber
550-142-783/10
12
GV90+
Series
2
fl4!i"f'Ot£u WA711'1
••~•1-ER
-
Boiler
Manua
l
Multiple
Placing
L
Loco
multiple
te mu
ltiple
boiler
bulit'n
to:
a.
Fig:u,rc.-28
b.
ngi!Tt
2.
Pnwidt
li.sttd
ab<>vt:
thdt
-r~mmuded
(
.)J'Ov
ide ut l
_givm
on
3.
Construct
ls
un
even
fOundatiOn
mem.lons
4. Cbatklioe boiJ
:r
oom
flo
$. Uoo'a(e, i!il:c:mbleand
instrucfior
6.
Pi'O\>
idc tll."aiance
piping,
r('r'
and
(s\1.1.:-rb-side
29
(baok-t<rbock).
the
de:arancd
to
pn>vid.~
t9St
th~
rt<:O
vase:
..s
.
A.I.Mf
boiler foundation
or
if
there ls a danger of
tO
allow
dlown
in
ft
IOCiltl
oc.
t.s
in
dlil
m11.uuat
fot
gas
pipi
ng_.
~pansion
(tt.hC:r
ac~rits.
the
installations
bolters
in
baiid
iOom accur
j,
or
indicated io
furaccw-
dim~siuo
rnt
nt'lt
fbllow
for clearance and
iUUStnJboo.~
l'm.~
on
mount
in.n:allat:ie)
the-Ul
~trations
tu.H
l
se-rvicing.
s
an:-
nOt
de-d
~ct
cl
local
oodrt.
if
bo
iler
room floor
flooding.
$pacif)g
Ol tight
f:Pu
udatiuu (lT boil
bOilers n«""rding
n or
YC'.rt~og
tank, primary
d.iug
If
:po~ihle,
e-a:rances.
S
ize
di-
.
eT
Ill
,
,
ait
drcul>l
-
Figure
--
Figure
28 Side-to-side
sh
owing
FifGOMME:NOED
w
------
29 Back·l
sh
owing
<>bad<
RECOMMENDED
mounti
~
61
" _
inslallalion
ol multiple GV90+ boilers.
clearanc
___,
___ ••·
es
--
•
o1
muniple GV90+ baii
clearances
O<s
f
)6
,
'
Controlling
multiple GV90
bolters
I. Multiple GV90+ boi
boiler contr
iso
lated con
bo
iler's T-T
Piping
I.
Set'
Contacr
not
cov~red.
2.
Always
primary/secondary circuit
in
this
oVseque
tact
termi
multllple
suggested
Weii-
pipe
tbe
manuaL
for ca
pipi
Mclain for
+
ler>
01
n
be
con
~rolled
ncing
syst~m
tha
t provides
ll
fo
r hear (connected
nal
s).
GV90+
ng diagr
boilers on a secondary
as
bolters
ams
in
this
assistance for systems
shown in the
us
ing any
to
the
manual.
loop
in a
txamp
an
les
1
...
J
~
!
'
-~··_..
_
__
.,.
--
•
-
u·-
I
~
--
" '
--
-:n
••
·
--
Part num
ber 550-
1+2-783/1012
23
GV90+
Series
2
oAs·FIRED
WATER
BOILER-
BaiiM ManuaJ
Multiple
Easy-Fit® plpl
1.
Main heade r
a.
New
syst<m -See
b. Replacing boil
u,
con
si
crosses
ure
nect
for
31. Siu
boiler
ng
and
E.asy-Fit•
ers
sysrem s
Easy
-Fit• manifolds
manifol
Installati
Man
ifold pi
page I 5.
in an existi
upp
ly
ds
to
handle
water
on
pt
siting.
ng
system -
and return
as
shown in Figure 30 or
toral
Witho
lines. Install
conn
ecre<L boil
piping
ur reducing
er
as shown.
2. Provide connecti
dose as possible to the mi
a. Use
b. U
t~
se
either tees (Figure 30) or crosses (Figure 31) f
for fo
ons
in main header for Easy-Fir'
dpoint
of multi
ur or
less boil
ers>
as
in
ple boilers.
Figure
30.
man
or
more boilers.
3.
Manifo
ld pla«ment
a.
To alterna
rt•terk
in
Fig
b. Return manifold must be on the rrturn si
supp
inS'
left
the
4. Connect
return connections
fl
ow rate
5.
Provide
s
hown
on r.he suppl)• and
may
r~uire
on each boiler when isolarton vah·
6. t
nsra
ll
ply piping as shown in pipi
sucrion si
7.
t
nsra
ll
system
8. Pipi
ng
a. Figure
b. Figure
locations
limits and
c.
Figure
piping dr
d. Figure 3S,page
ing heat exchanger
te s
pacing
the
sho
u
~ 30 an.d
ly mani
fold
in
this manual show flow
. For
sys
tem flowi
manifol
from
ds auo
Easy-Fi
for s
rt-
end
and
Fig
u
~ 31.
must be on
ng
rdingl
r»
manifold
using
copper
upp
ly
long-end
rhe
supply side
left to
righ
y.
branches
or
stet-!
and return
of
the
lines to boil
manifo
de
of
the main and
lds
as showt\
of r.he main. Draw-
in
system main from right to
t,
re't-erse
pipe,si
the locatio
to
boiler supply and
ud for
the
.
a O
ow/c
.berk v
alve
in piping diagr
r-eturn
the
use
in the supply piping of
ams
in thi.s
manual.lnstalf an isolation
of
each
boil
of
indi
vidual water level
es
er
as shown. Some local
art
installed.
eac
h boiler
controls and limits
main sysrem air eliminator and primary circulator in sup-
ng
diagrams. Place expanston tank Otl
de
of
syst.em circulator as shown.
acctSSOries
reoommendation drawin
30
and Figure 31 show details
32.
page
of
typical
or.her
33.
pa$e
awmgs
25
is a schema
boile
devices
26
and
of typ
28
shows
i.s
as
shown in drawin
gs.
gs:
of
Easy
-Fit• mani
tic
r pipi
piping drawi
ng
and
system
ng show
piping. including
often required by local codes.
Figure
34.
~e
27
art
r.h~-dimensionai
ical multiple boiler insraUarion.
recommended piping when
needed.
an
9. If desired, other primary/secondary piping arrangements
used.
When
NO
nCE
using isolation
may
requ-i~
pro vidi
limir for each
if omission
al
low
of the individual boiler isolation
the
we
of
limir for the entire multiple boiler
ng
boile
r. Consulr
a s
ingle water
\'ll]ves
on
a low
water conrrol
each boil
loca
level
J codes
conrrol
system.
er.
some codtS
and
add
ro
determine
valves
and
add
tees
or
Fig
ourput
ifolds
a!l
fi
't'e or
ers,
ns
of
required
as
val~
codt$"
folds.
ing r.h
iso
lat-
can
bt
iti
onal
ma)
iti
onal
Maximu.m connl!cted load
-
Figure
We
ll~
Easy-Fir"
Munllold
2..4 boll6tr.:
1
a,~anlt
5oo
8. boll
2 manifol.ds
Figure 31 IJou
t-
Cross./Dushfn
{by
olh~:~
Molh
Cap
-.
(by
ot
2·inoh
-3-
manifold-
inch manifold- 1400
4-inoh manifold- 2900
30
Single-eided
cU.ln
old
err.
I
r.l
Of'IQ
ond
g
...
~
)
..
.,
1.•
bte-s
ided EZ.fit
C.p,. (b_V athcr,f)
,-
~·
12-maxlmum
•.:
Wel
Weii-Mcl.ain
hertl
EZ~it
iot aa close
as
tac:IJta
i..Mclain
Easy
-Fit'
Manifold
Easy-Fit'
Manifold
pl!r
4SO
MBH
MBH
MBH
Head
er connection
.,
'·
1-toade<
,-(
,.
'
·"
ll
~
man®ld!
Maht
We
ii·Mclaln
Easy-Fit•
M
an~ol
~
8
bolle•s:
:tmon "rfolds
CQnnection
·.short
..
.00
l
o119
-.
ef'ld
Ma
in
d
24
l-\ln num
btr
SSG-14'1
-7llll101
'2
GV90+
Series
2
us-Fu
ltD
WA
tla 110
11.1!11
-
Boiler
Manu
al
Multiple
Figure
32 Piping schematic - typiClli f
boiler
...
.. (8'
1
·
~
VI
~
@@
®
~-
®
.....
water
or mufti pte GV90+ boilers, using We;I·
@ I
i>l.l
I
:>;
@
'
~
piping
...;(2)
>.
CD
t
-
~
~~
_L,
I
--
l;t =
\
..,
~J
J
---~
,_.
I I
(2)
)
j
--
(c()
nlinuedJ
@
@
=
Mcla
r-
I
>.
® >
'
-
in
Eas.)'
.f'
il man
ifolds
..
@)
(
3)
@
(!'
@
j
®'f®
;
'
=
~
~~
__,~-
I
r
..,.~
4
1_
,_
__)[
@
-=
Flow
/che
~
Gop
• e'"' FFi"'
p
age-
2'!1
~
Ea")'
•Fi"'
page-24
7 l!xpandoo
8
S}'J
tcml
air
JO
Pres:ru~
Legend-
ck~
~du.::in
(each
bailer
~
MntUiald
MluUfold
tank
elimi.o
----------------~------------------------~
(MJp
ply)-~J<>utaad
(,.IUlO)- by(>utaad
(dl
aphrogm
acor
g vaJ
typr)
~
sit•
I"'
ol>•per
Figure
II
Check
codes
12 Isolation
13 Watertlowswi.tch("·henused)
14
Supply water temperarure control (when used)
low
IS
16 Co
components
18 System supp
19 System return
20 (Not shown) Boiler relief
per GV90+
30
Long
32
valve
or
rbacJdlow
vaJ,-e
wa
.ter cutoff (when used) (place above primary header)
ld
water
6U
tine-
ty
Boi~
end
of
manifold
see
Manual
prevent
Figure I
valve
a:.
as required by applicable
S,
page
and
discharge
14
for
typical
piping. installed
Pan-number
ss
o..-•14:2:-783
/ lO
ll
25
GV90+
Series
2
OAs-f'IR£D
WATER
BOILER-
Boiler
Manual
Multiple
Figure
33
Pipi
ng
.
__...--
t
--......_.
(
..
boiler
layOOI
- Iypical tor multiple GV90+
water
~
-·j:
-:J
.....-·
....
..
,
-"
\
!
I
~
·
v
_ ..
"""·
~
(!)
piping
bQ
ilers, using Well-Mc
~
{
-··-··-"
•
---
11;
~
(continuooJ
lain
~
(j)
..
l
@
Easy-fit
........ ®
manijold<!
(2·boiler
t
system)
t
I Flow/
2 lliolation
3
4
5
6
7
8
9
t6 Cold
dlock
c..,.
E.uy"Fi'*
t;asy-Fi~
Primary
P~sion
Sy$tt.m
Systqm
pont:ots
valves
M>n
M-anifo1d
drculator
air
cf
automatic airvtml
water
va
lw
(I!Jllh
(""
••
.
ili>ld (supply)
(return) -
tank
(.diaphragm type)
bn
in atnr
611
Uo.e-see
21
boill!f
)
US<!d
)
-18)1JU
la}'"'
F!igur~
"32.
u
t~d-siu
Ut
and $iu
p;:~ge-
per P•8" 11
percp3ge
25
(or q'pkal
Legend-
2
~
cnm--
rigure'J3
~~~~~~~~----~~1
17 3-
WII)'diwrtiogvai••
$Witch cooneus
I
~
S)'Stem
supply
19 Syuem return
.20
Boiler
rc(~fva
BQi.Jer
Manual
"'21
lndired -Gua storage water
td
fO
ane
bOi
a.
~
ler
neq('d
io
Figure.J4
aJso ~ c;q,o
beader,
f
op"'""'
.acmM boiler
l
v·e
a~d~:arge:
Q(
tht~tm'4
~
th
thermo.stat wmi:Qals)
heaters-
Tbt
a
gecond.ary'copnc«ion off
ptgtt 27.
1
bjl
ptplo
OHW
"'fWISiat-valwend
g,
i~11t
aU¢
pq
~xa.mple-
indi~Ut
is
~"'llter
G\!'9()f
shown oonnect-
beater
coulj:)
the
ma1n
P.ut number
55()..142-783110
11
GV90+
Series
2 GAS•FIIIED
WATER
BOILER-
Boiler
Manual
Multiple
Figure
34 Piping
layout- typical for muniple GV90•
,,,
~·~··
I
'
~~
...
•
.e
~·
boiler
I
water
piping
!;>oilers
.
w~h
DHW storage heaters
(continued)
(4-l:;>oile
r system)
..
..
Jilnw
ft:
h«t-nlve.(ed
!
.boiMlocl
,.._
.
"""
•
l!tofy-,(:1,-M;n
llit.e~pace
~
1!.-yrF.tt
M•llifold
,.,
..,.u
.
&
'"""'
"'~
'I
£:(poao~l
otHant
1
!li)1
~m
til
riA'niaaiOr
9
s;
11cm_.,,unm:aai
J,a Cold
wuer-
·6D
fqr
fYJ*al
qv:npc
U:
S):ucom
...
1'.,.
jj
S,l
lll!
l"! IUIJRl
1JJ
Jkriler
rdid; 1o'
Jnsul
kd
re"
GY'oo-t
Pan
number
.ss
a-•e-783/ 1012
bqilerf
('<
~lMtd
i'*
(
rtq~pt,.
1
~
{retatnl-
(
Jiarhtayn
r
~lr ~~
Ji~:~~~
-RIL"
uwn
n
Afw
and
dldl.
JlolerMlntul
)
)
'-'
lilyoute.J
.._)CIIIi
lind
!Jpe)
Fqjure
'J.
-paF
,e
Jilti
n&o
•~
"U
27
GV90+
Series
2 OAS>f'IAED
WATER
BOtLER -
Boiler
ManuaJ
Multiple
Figure
36
Piping
layOUI
boiler
- typical f
~
,..
~
·-
...
water
or multiple GV90+ boil8fS, using isolaliQn excl1anger
Boiler-side
Heating
piping
circuit
system
circuit l
t
(contlnuedJ
u
l·
. -
f.
·~
--'
""=·'
...
..
.m
@ "'..:._
!)
U
ttl
aolation
~t
excm.nver tor.
I. la
rgt-
voluiUL'
.sy'Atm.t
wltb
m.ln
utl
tootua
t
ill
w~r
.
1.
Syitem.s
a-posed ta umuat
quantities
J.
Old
llllled
imidt
ti
...
rro~appticat
5.
Commu
p
6.
Kl_gbwar.erp~USU
"'qu
ill
PSIG
bclow
ol
-systtrns
with
ale
piping
on
oniu.
cial
lhtit~OS
.
lr-ing prtssure
b~
Ji.ng
sym.m
(!aU
hWldUlg!.)
.
maknl
p
watt:r~
s:tn•n lr
oontamt-
and
rust buildup
and
htat
disrrilo-.
i
ons.
strvia
W3ltr
rtaJ191.ications
rdief
setting
~
t
ba.n
.
&.
bigb
td
a
~
50
ooltS
1
Flow/che&vaM (ea
l WlbJfua \•aJvet (
j C.p
<
E•
lf·Fil•
byo
.3
F.ls:y
ow
6a
Headn:g
tf'
lib Htat tKba
1
~""""
A
S)'"lltetn.alr
Manifol
ul
and il,U
~
Rt-
M:an
ana
~7..!
~
tu~liidt
)
nseuhen4_.1&-
ranb (
dimlnuor
wh,en
fM:r
tfol
l
:!ft'
'Pap!-
dn:u
Ch boOtt}
w~
)
d (supplf
~
ili>phl'Ogm
pagt-l.t
llmiru)
1.4
Jat
or
)-
(t'ldbt
clrculunr
..
-lat·
•g~
rypt)
~~·
9 SfSttfW
I
~
Co
ld
I(; Cold
woe
""""
13
f(brlnj')'"""'
19
HearinJ'ys.ltm r
20
f5oik:r'
l~lp
"""""'
~
$ensor for
paa
Legend -
1hHOrn:l tf.:
wa.te:r
W3.t.E'r
32,
p.-
rdief
lng,
fnallllltd
BCP
d),
when UIC!
~
I
I
Figur&
air ftiU
~ppfy
catlnt~.."'lto
6Ji
line-see
25
(or
"PPir
eru
Y'lllve
ptt
{OOl~tt
d
Fttt'
rypi~l
cu
m
;md tllsdtiu¥t
G¥901
conuol
l
\1
mpo
Bofler
-
36
NO~
I. Coftll
2.
3.
4. liealirl
5.,
tr
htt1 ttcllangu fllll.nuf
~-.<ideao.Snol><
nqu.i.mnents
ft'Wf
Can.r.ac1
e:uhwga.
Kn.a
dp.aruion
a\~n.
•15tem
~
boiler and
~
Thb~Udt
ht:tt
fng
~
~n
ht:a1excban!Jff
ex.:hangH>
S'f'
and
iudh'\dll21 il00itla
-
shell~$id
ttn~
liS
tan diodu'eqllin!tl
plus
ii's
a-
beat
cscb:ang«
J,eyd
con
,sid<ari~"6
fl
ow
ttqtilmnenu..
manl1f
e.
UIOW!'I.
wn
relief
vaM
r!iping
11
'i
nok
may:
atutrer
and
t~cw
circuit
illi
ATCt
lll
\'e\
M rtqu
own
fot
and <i<i
tempuatll!'W
m
ror
ild113 heat
~ulm
~p
anlli
co
111\ll~
and
comi'Oft¢nll..
A('
I!
mt!tl,
indiv:fduitl
Jr«l
ha
t
f'X
·
DIIIIII'
mus
t
lu:
own
(ln
tmt.
J~eatins
28
P.art
nu
ulb«-
55()..
t
~2-7it.ll
101!
GV90+
Series
2 OAS·FIRED WATER BOILER -
Boiler
Manual
Venting
GV90+
suD!llled
lllll<in
d•acrtbedln
Every
00
appliance.
Inspect finished
thoroughly
dl
an
pro:vided
applicable
Fai
lure ro provide a
•ten
ptr$0nal in
If
NOTICE
tibe
cov-.ertd
can
in
staJiation>
assistance. Other configurations
be
available.
Where vent piping
en
mhNt•d
l inch
on
unbeated space.
Installations
r
equirementS
Fuel Gas
instaJiationsorCSA 8149.1 orB
for Canadian insta llations.
Use on
marual
tings.
If
used, • matonry
ONLY
vent
piping musr be instaJied
in dlis manual and
sealed. The chimney
only for
appliance or
to
the
straight.
an
d air pi
wi
th
cbimmey
ac~
teriiOr
The chim
m~r
alt)f
Fa
ll.u
personal injur
proper
&
air
bollero
with
olr ualng piping ond methode
bolter
NOT
com
carouldon end
thts m1oo11.
nwtt
common ve
to
ply wirh t
and with aU requirements
must
have
ven
ensu
-
bo
vented ond
tts own
nt
wi
th
any
t and
aJr
re aU
art
he instruct
general
piping
airtight
<Odes.
prope-rl)•-instaJJtd
t and air system
jury or
will
death.
cau..st
vent/air piping confignratlons
in
the
nor
bt
GV90+
app
lied for a particular
contact
boiler manual
Weii-Md.ain
lo
routed through
spac•> appt)• minimum
of
the
roil-faoed
length
Code,
fiberglass
of
the vent pipe
must compl
and
y wi
with the National
ANSI Z223.1 for
insulation
th
ly the materials listed in this
for
ven
t and
aJr
pipe
and
See
bo
and
Figure 40.
uood
air
pipet
page
chlmn•y
eo o PIPE
- The vent
aU
joints must be
33.
CHASE
and
as
instructed
musr be used
GV90+ boil
fireplace
chimney.
with
ping
ers.
NO
OTHER
can be connected
The chimney must be
no
offsets. and the
materials
must
comp
this instruction manual. The
must
be
fitted
with a sealed
optning..
of
be
ro
verify
rt
to comply could r
ry
through
the chim
in
ney
can be inspected.
ney
(and liner. if installed)
sptcted
ar
leasr once annu-
condition.
y.
death or substantia]
damage.
which
esu
lt
the in-
in
Yenll·
v•nt.
other
ions
of
seve-
re
for
may
in
the
locaJ
U.S.
149.2
fit
-
can
lor
a
ir
venr
ly
severe
When
common
The QVSIO+
applanc•.
the
boiler
may
vent. because the venr may
ANSI Z21.13.
rt:maining
removing a boller
bo
\"/hen an existing boiler
GV90+ boil
requires
cause a probl
is
on
the old common
vent
Its
system
..
r
cannot
er CANNOT
own
vent
em
for the appliances that rtmain on the old common
intended to
from
be
co...._
is
use
the existing common vent. The
and air piping,
be
roo
large.
check
for proper operati
vent
systm'l
an
..-ted
replaced with a
as
specified
The
following test. requi
.
existing
with..,.,
GV90+
in
this manual. This
on
of
the appliances
GV90+
Vent system verification
Ar
the time
followed
system
to
the
i
ngs
Existing
of
with
placed
removal
each
in
operati
of
appliance remaining connected tO the common \'tnting
<>n. whil
common vtnting sysrem
in the common
vent
·.-~nting
test
an
exis
ting boiler> the foll
e the o
rhe:r app
are not
in
system.
procedure
owing steps sha
liances
remaini
operation. Stal
any
ng
connected
unused
(The following is intended to test whether the spplisnces
remaining
sstlsfsctorlly.)
I.
Visually inspect the '\'tnting
and determine there is no bl
other detkiendes wbic.b could cause
2.
Te
windows
remaining conntcted
other
nor
fans,
ate at maximum
fireplace
3.
Place
structions.
4.
Te
burner
a
5.
Aft~r
to
~return
other gas-burning applian
Any
improper operati
so the installation con
- latesr edition. Correcr by redetermi
installations must
on
sn
existing vent system
st
·.-
~nt
syst~m-
and
Insofar as is practical. close aU building
all
doo
rs between the
to
spaces
of the buil
connected
such
as
r
ang~
to
dampers.
in operation
Adjust
st for
spillag~
operation.
cigarette,
cigar,
it has b«-n determined rhat
the common venting
doors,
ned
usi
ng
the appropri
comply with
ding. Tum on cloth
tbe common venting
hoods and bathroom exhausts, so th
sp.eed.
d:le
appliance
thermostat
at
draft
Use
the
or pipe.
windows.
on
of
f'o.rms
will
operate
sysrem for proper size and hori7.ontal pitch
ockage
or
restriction,
an
unsafe condition.
leakage, cor
rosion
doorS
spac~
in whi
ch the appliances
the common
Do not operate a summer exhaust
so
hood
rel
flame
system
exhaust
ce
to
common \'fnti
with the
·.-
~nting
sysrem
ar~
l
ocated
es dryers
system.
and
Tum
any
on
appliance
any
ey
will
fan
being inspected.
appliance w
ief
opening
of a matc.b
each
appliance remainingconntcted
F<>Uow
the l
ighting
ill
operate continuously.
aft~r
5 minutes
or
candle, or smoke from
properly \'fnts when tested as o
fans
.lireplacedampecs, and
their
Natio
pre't'iOUS
nal
ng
system
Fuel Gas
conditions
sho
uJd
Code,
of
be
corrected
ANSI
use.
sizing to approach the minimum size as
ate tabl
es
in Part 11
6149.1
or 8149.2 Installation
of
that
code
Code
. Canadian
exhaust
. Close
of
utJi
Z223.1
ot.,..
boiler.
red
b) •
ll
be
open
or
and
and
oper-
in-
main
ned
any
.
-
Part
number
550-14-2-783/10
12
29
GV90+
Series
2
oAs·FIRED
WATER
BOILER
-
Boiler
Manual
Venting
Provide
IA
WARMIMG
combustion
DIRECT
I
butdon
may
&
VENT
olr piping.
be
required.
air-
air:
- Tho lnotallotlon
DIRECT EXHAUST - The lnttlllotlon
combuatlon
ALL
APPLICAnON
combuatlon
lnc
M
Vent
1.
DIRECT
1.
2.
3.
and
air
v~nt
and
air pipi
r
oof
of
rhe buil
manual
configurations
ding.
See
Figure 39. page 32
and
VENT Installations
For
direct
venting.
bo
iler, following
a
ll
applicable codes.
Ventilation
u
~ 42.
page
If other app liances art located in r.he same
pr
O\ride
openings
the instructions
open
36.
If
combustio
as
direct~d
ventilation> the higher
in
reduced
air
openings
1lr
openlngt
In
th•
apace.
termination
ng
mu.sr
t~nninare
usi
ng onl)• one
piping material
combusti
ings are required for some spaces. See Fig-
shown
on
in Figure 42, page 36.
n and vtnrilatio n
above
and
component
general
mull
provide com-
In
oddhlon, vendlotlon openlngo
mutt
to the
boller
spac•.
S- Tho lnlllllodon
as
nCMidcld
options
our
the
sidewall
of
r.he
mer.hods
and
Figure 40. page 33 for allowable
s.
air
must
be
piped f'rom ou
in this
manua
space
with
air
open
the room
temperature in
li
fe.
does not
mUll
for
other
or
r.hrough
describfii in
tside
l.
and
compliant
the
GV%+ boiler,
ings are not provided
have
the
space may result
rconunuedJ
provide
provide
lppll-
the
r.h
is
ro
the
with
adequate
Combustion
Figure
36
Corrosive contaminants and sources
Producto
Spray
Permanent wave solutions
Chlorinated
Chlorine-based
Calcium cllloride used
Sodium chloride
Refrigerant leal<s
Paint or vamlsh removers
Hydrochloric acid/muriatic
Cemerlts and glues
Antistatic
Chlorine-type bleaches, detergents, and cleaning
solvents
to ovoid
cans containing chl
fabr
loood
air
contamination:
Ent...-e
not
lnRgure36
DO
Optn
a
Avoid areas
(rom laundry facilities. These
always contain conram i
waxes/cteaoo<s
thM
th•
contain
combutdon
any
of
the
.
NOT place
ings or inrake
swimming
swimming
used tor water softening
ic soft
ene<S
In
household laund<y rooms
combustion
term
pool>
for
subjtct
for
ro
oroA
iuorocarbo
pool chemicals
thawing
acid
used In clothes dryers
contaminants
inations
examp
exhaust
nants.
air
air supply
le.
artas
ns
wtll
near
fumes
w
ill
DIRECT
1.
Combustion
on dir
(S«- page 49 for a
pr
NOnCE
EXHAUST Installations
and
ect
O\ride
exhaust
r~uir
td
DO
NOT
at
alritud~s
fo
r DIRECT
alti
tudes
w nrll.arion
insra
ir
ope-ning i
air openi
sidewall v
abo\rt
above
llari
ons. Follow
ngs.
5>500
VENT
5>500
air
nstructions)
ent
applications (
must
DIRECT
feeL
feet
be prO\'ided
all
Sidewa
30
in
the
boiler
inst
ructions
and aU
EXHAUST
JJ
venting is only allowed
ducted
in
this
applicable
APPUCAnONS
combustion
room
manua
codes
air) at
ro
Adhesives
other
Exoossive dust and dirt
l
Areu
Dry
Swimming
Metal fabrication plants
Beau
Refrlgeratloo
Photo
Auto body shops
Plastic maoolacllJrlng plants
Fumiture
New
used
to
fasten bulldlng products and
simflar products
likely
to
hove
contamlnontt
dea:I\Jngllaundry areas and establshments
pools
ty
shops
repair shops
processing plants
I'Qf
inishing areas
bu
ilding construction
P-an
and
establishments
number
550-142
-783/1012