Weidmuller WI-I-O 9-U2-TC User Manual

Installation & Configuration Guide
WI-I/O-9-U2-TC - Thermocouple Adapter for WI-I/O-9-U2
Configuration
On the “I/O Configuration” web page select:
· Select Thermocouple type from the drop down list. Options are Type T, Type J, Type K.
· Select the Polarity from the drop down list (Normal or Reversed)
· Set Thermocouple Error Value to a value the integer registers (30003 and/or 30004) will go to during fail *
· Press “Save and Activate Changes” button.
Thermocouple Range @ Tamb (+10- +40)
Type Normal Reverse
Type T - 25°C to + 365°C - 200°C to + 70°C Type K Type J
Installation
The WI-I/O-9-U2-TC adaptor board plugs into the bottom 6 terminals on the WI-I/O-9-U2 terminal strip. A separate 14 way terminal strip is provided to allow connection to the remaining terminals.
Address locations
38005 = 32 bit Floating Point temperature value 38007 = 32 bit Floating Point Cold Junction value 30003 = Scaled 16 bit Analog value 30004 = Scaled 16 bit Cold Junction value
Analog Input Scale Examples
· For normal Polarity setting Zero and Span to 0 and 100 respectively will scale the register to read the temperature as an integer value, e.g. 148.25 °C will read 14825 or 26.51 °C will read 2651
· For normal Polarity, setting Zero and Span to 15019 and 682.6667 respectively will scale the register so that a temperature of -10 to 50°C will give a scaled range of 8192 to 49152
· For Reverse Polarity, setting Zero and Span to 30948 and 455.106 respectively will scale the register so that a temperature of -50 to 40°C will give a scaled range of 8192 to 49152
- 25°C to + 455°C - 200°C to + 70°C
- 10°C to + 345°C - 210°C to + 60°C
Connections
Caution:
ESD Sensitive pins. Use ESD handling precautions.
Thermocouple input terminals must be within +/- 5V of the WI-I/O-9-U2
Thermocouple Range @ Tamb (-40- +60)
Type Normal Reverse
Type T 0°C to + 330°C - 200°C to + 5°C Type K
Type J
If ‘Thermocouple
Polarity’ selection is
reversed
Thermocouple wires
must be swapped,
e.g. (red) to TC+ &
(blue) to TC-
Constantan
(red)
* Error Value is set in register 30003
when the thermocouple is open circuit.
* Error Value is set in register 30003
and 30004 when the thermocouple adaptor is not fitted
0°C to + 410°C - 200°C to + 5°C
15°C to + 300°C - 210°C to + 10°C
Thermocouple Adapter
-Ve
+Ve
N/C N/C
COM
TC-
TC+
Copper (blue)
Normal Type “T”
Thermocouple
(+24V)
PWR RF 232 485
WI-I/O 9-U2
6720005011
Dip Switches
D1 D2 D3 D4 D5 D6 D7 D8
1 2 3 4 5 6
GND+24V + - + GND+24V
AI 1 AI2
AI 1
All Dip Switches
AI2
­AI3 AI4
AO1 AO2
+ +
must be set to
the OFF position.
ON
Revision 1.6 - Oct 2011
Inst_WI-I/O-9-U2_TC_Adaptor_V1.6.vsd
Loading...