Weidmuller WI I-O 9-2 User Manual

WI-I/O 9-2
Antennas should be installed by experienced
2A
-
-
+
-
-
1
3
4
WI-
I/O 9
-2
+
-
+
-
DC Relay Supply
+
-
+
Voltage Free
Panel Supply
DC Load
Installation Guide
FCC Notice
This device complies with Part 15.247 of the FCC Rules. Operation is subject to the following two conditions:
1) This device may not cause harmful interference and
2) This device must accept any interference received, including interference that may cause undesired operation
THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS 1 DIVISION 2 GROUPS ABC AND D OR NON HAZARDOUS LOCATIONS ONLY
Aerial Installation
SURGE ARRESTOR (OPTIONAL)
COLINEAR ANTENNA
WEATHERPROOF CONNECTORS WITH “3M 23” TAPE
COAXIAL CABLE
1m minimum
STRESS RELIEF LOOP
WARNING!
EXPLOSION HAZARD
DO NOT DISCONNECT WHILE CIRCUIT IS LIVE UNLESS AREA IS KNOWN TO BE NON – HAZARDOUS
11-15VDC Supply or Optional 12V Backup Battery to 12 Amphour for AC/DC to 100 Amphour for Solar
COM
BAT+
AI 3+ AI 4+
GND
Digital Output Max 30VDC, 500mA
AI 6+
AI 5+
+24V
DOT COM
OUTPUT
NOTES
1. All I/O must be SELV.
CAUTION!
For continued protection against risk of fire, replace the module fuse only with the same type and rating
GND
ANT
WI-I/O
PROVIDE GOOD GROUND CONNECTION TO MAST, MODULE AND SURGE ARRESTOR
MAST
RADIO TELEMETRY MODULE
INPUTS
INSTALL AERIAL ABOVE LOCAL OBSTRUCTIONS
ANTENNA INSTALLATION
EARTH STAKE
IF GROUND CONDITION IS POOR
INSTALL MORE THAN 1 STAKE
contractors.
SOL
GND
SUP1
SUP2
SUP1
SOL
GND
SUP2
DI 3
DI 2
DI 1
DI 4
COM
+24V
+AI 2
+AI 1
WI-I/O 9-2 Installation
Power supply: (A) 12-24VAC 1.5 Amp CSA Certified Class 2
(C) Supply battery or 11-15VDC
(D) Solar panel with solar battery
AC Supply 12-24VAC min 15VAC for Battery Charging.
Do not earth SUP1 or SUP2 connections
12V Solar
max 20VDC max 30W panel
DC Supply 15-30VDC min 17VDC for Battery Charging
To Earth Connection
Digital Input
Contact OR Transistor Device
Loop Powered Analog Transducer
Choose option and wire as shown
Weidmuller Inc., v1.4
Ext. Powered AnalogTransducer