THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS I DIVISION 2 GROUPS A,B,C AND D HAZARDOUS LOCATIONS, OR NONHAZARDOUS LOCATIONS ONLY.
FCC Statutory Requirements
Unlicensed operation limits the radio power. High gain aerials may only be
used to compensate for cable losses.
Antenna Installation
Wavelengths
2.4 GHz = 13 cm
5 GHz = 6 cm
1 Wavelength
minimum
COLINEAR
ANTENNA
45 3
89 7 6
12
SURGE
ARRESTOR
(RECOMENDED)
MODULE
M4 x 5mm
ALL connections must be SELV (Safety Extra Low Voltage <50V AC & <120V DC)
Ethernet Port wiring is that of a hub or switch.
‘-' Supply terminal and 'M4 GND screw on rear of module' must be connected to EARTH /
GROUND as close as practical to the unit.
Module Power Supply -Ve terminal is not Isolated from Earth/GND
DIO channel can be wired as either input or output.
Care must be taken with antenna selection and proximity to the radio.
The non-metallic cover of the Wireless Ethernet Modem is considered to constitute an
electrostatic discharge hazard. Clean only with a damp cloth
The Wireless Ethernet Modem enclosure contains aluminum and is considered to constitute a
potential risk of ignition by impact or friction and must be taken into account during installation.
If the Wireless Ethernet Modem is installed as Category 3 equipment, then it shall be installed
in an Enclosure which maintains an ingress protection rating of IP54 and meets the enclosure
requirements of EN 50014 or EN60079-0.
If installed in a hazardous environment coaxial cable shall be installed in a metallic conduit as
per NEC requirements
WEATHERPROOF
CONNECTORS WITH
“3M 23” TAPE
COAXIAL CABLE
PROVIDE GOOD GROUND
CONNECTION TO MAST, MODULE
AND SURGE ARRESTOR
CONNECTION ON
REAR OF MODULE
NOTES
STRESS RELIEF
LOOP
MAST
INSTALL ANT ENNA ABOVE
LOCAL OBSTRUCTIONS FOR
MAXIMUM RADIO DISTANCE
IF GROUND CONDITIONS ARE
INSTALL MORE THAN
POOR,
ONE STA KE
Factory
Default Switch
RJ-45 Ethernet
Connection
Connect M4 screw terminal on
rear of module to GROUND for
surge protection
RS232 Connections
PC’s
RD
TD
SG
RTS
CTS
DSR
DTR
DCD
DB9
MALE
2
3
5
7
8
6
4
1
3
5
7
8
6
4
1
DCE HOSTMODEM
FEMALE
RD
TD
SG
RTS
CTS
DSR
DTR
DCD
DB9
2
PC’s, Dataloggers
2
RD
TD
SG
RTS
CTS
DSR
DTR
DCD
MODEM
DB9
MALE
2
3
5
7
8
6
4
1
RD
3
TD
5
SG
7
RTS
8
CTS
6
DSR
4
DTR
1
DCD
DCE HOST
DB9
MALE
BEWARE OF
GROUND LOOPS
* Connect to Ground
as close as possible to
the module.
RS485 Connections
HOST HOST
RS485 Resistor
Termination
9-30V
*
2A Fuse or
Circuit Breaker
*
DC Supply
Digital Output Wiring
MODULE
DIO
DC Load,
eg Relay
+
Max
30VDC
0.5A
+
-
WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT WHILE THE CIRCUIT IS LIVE OR UNLESS THE AREA IS KNOWN TO BE FREE OF IGNITABLE CONCENTRATIONS.
WARNING - EXPLOSION HAZARD - SUBSTITUTION OF ANY COMPONENT MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2.
Switch
COM
*
*
-
Installation Guide
REV 1.9
WI-MOD-E Wireless Ethernet
Weidmuller Feburary 2012