Weidmuller WI-MOD 9-D User Manual

WI-MOD-9-D
A
COLINEAR
EARTH STAKE
PROVIDE GOOD
Installation Guide
DO NOT DISCONNECT WHILE
AREA IS KNOWN TO BE NON
Statutory Requirements
FCC: Unlicensed operation limits the radio power. High gain aerials may only be used to compensate for cable losses.
THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS 1 DIVISION 2
GROUPS ABC AND D OR NON HAZARDOUS LOCATIONS
Antenna Installation
ANTENNA
WARNING !
EXPLOSION HAZARD
CIRCUIT IS LIVE UNLESS
HAZARDOUS
1m minimum
WI-MOD-9-D Wiring
Power Supply 10 – 30 VDC / 10 – 24 VAC 1.0 Amp CSA Certified Class 2
WI-MOD
B
RS485 Connection
10 – 30 +
VDC -
Connect “-”terminal to GROUND for surge protection
10 - 24
VAC
All connections to be SELV
CAUTION!
For continued protection against risk of fire, replace the internal module fuse only with the same type and rating
WI-MOD
+
-
WI-MOD
+
-
_
+
SURGE ARRESTOR (OPTIONAL)
INSTALL AERIAL ABOVE LOCAL OBSTRUCTIONS
COAXIAL CABLE
ANT
WI-MOD
GND
WEATHERPROOF CONNECTORS WITH “3M 23” TAPE
GROUND CONNECTION TO MAST, MODULE AND SURGE ARRESTOR
STRESS RELIEF LOOP
MAST
IF GROUND CONDITIONS ARE POOR, INSTALL MORE THAN ONE STAKE
RS232 Connections
PC’s PLC’s, Dataloggers
WI-MOD
DB9
MALE
DTE HOST
DB9
FEMALE
WI-MOD
DB9
MALE
DCE HOST
DB9
MALE
Weidmuller Inc., v1.5