Weidmuller WI I-O 9-3 User Manual

WI-I/O 9-3
Antennas should be installed by experienced contractors.
1
2
3
4
1
3
4
+
-
2A
+
-
not earth
Panel Supply
- +
-
+
HAZARDOUS
Installation Guide
FCC Notice
This device complies with Part 15.247 of the FCC Rules. Operation is subject to the following two conditions:
2) This device must accept any interference received, including interference that may cause undesired operation
THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS 1 DIVISION 2
GROUPS ABC AND D OR NON HAZARDOUS LOCATIONS
WARNING !
EXPLOSION HAZARD
DO NOT DISCONNECT WHILE CIRCUIT IS LIVE
11-15VDC Supply or Optional 12V Backup Battery to 12 Amphour for AC/DC to 100 Amphour for Solar
Analog Output externally powered. Loop is earthed (not floating)
UNLESS AREA IS KNOWN TO BE NON
BAT+
GND
COM COM DO 5 DO 6 DO 7 DO 8 +24V AO 5
AO 6
AO 7 AO 8
+24V
OUTPUTS
SURGE ARRESTOR (OPTIONAL)
INSTALL AERIAL ABOVE LOCAL OBSTRUCTIONS
COAXIAL CABLE
ANT
WI-I/O
GND
Aerial Installation
COLINEAR ANTENNA
WEATHERPROOF CONNECTORS WITH “3M 23” TAPE
MAST
PROVIDE GOOD GROUND CONNECTION TO MAST, MODULE AND SURGE ARRESTOR
1m minimum
STRESS RELIEF LOOP
EARTH STAKE
IF GROUND CONDITION IS POOR INSTALL MORE THAN 1 STAKE
NOTES
1. All I/O must be SELV.
CAUTION!
For continued protection against risk of fire, replace the module fuse only with the same type and rating
SOL
GND
SUP1
SUP2
WI-I/O 9-3
RADIO TELEMETRY MODULE
OUTPUTS
SOL
DO 2
DO 3
DO 1
GND
SUP1
SUP2
DO 4
COM
AO 1
AO 2
AO 3
AO 4
+24V
Power supply: (A) 12-24VAC 1.5 Amp CSA Certified Class 2
(B) 15-30VDC 1.5 Amp CSA Certified Class 2
(C) Supply battery or 11-15VDC
(D) Solar panel with solar battery
Choose option and wire as shown
Weidmuller Inc., v1.5
ANTENNA INSTALLATION
WI-I/O 9-3 Installation
AC Supply 12-24VAC min 15VAC for Battery Charging.
Do SUP1 or SUP2 connections
12V Solar
max 20VDC max 30W panel
DC Supply 15-30VDC min 17VDC for Battery Charging
To Earth Connection
Digital Output max 30VDC 500mA DC Relay Supply
Analog Output Loop Powered. Loop is earthed (not floating)