Weidmuller WAS5 PRO RTD, WAZ5 PRO RTD Operating Instructions Manual

Page 1
Beipackinformation 1
Operating Instructions15
Notice d’utilisation 27
Analogsignaltrenner
WAVE
ANALOG PRO RTD
aus der WAVESERIES
Page 2
15
Analogue Signal Isolators WAVESERIES WAVE
ANALOGUE PRO RTD
MODEL Order Number
Screw terminal connection WAS5 PRO RTD 8560700000 Tension clamp connection WAZ5 PRO RTD 8560710000
Please read these instructions before using the product and retain for future information.
Page 3
16
1. General instructions Warning! The analogue signal isolators of the WAVE
ANALOGUE PRO series
may only be installed by qualified personnel. Be sure not to connect the unit to power supply before appropriate installation. Do not select ranges during operation, because live parts are exposed during this process. Only use a screwdriver which is properly insulated against the voltage applied to the input when fine adjusting the potentiometers on the front. Be sure to observe the national regulations for installation and selection of cables.
Appropriate safety measures against electrostatic discharge (ESD) should be taken during assembly and adjustment work on the WAVE
ANALOGUE PRO.
2. Application
Analouge singnal isolators are used for galvanic isolation and conversion of temperature, resistance and potentiometer signals. Input and output signals are factory set according to type or can be calibrated/switched via DIP switches. It is not necessary to adjust the measurement range. A +/- 5% variation can be achieved in the respective range by connecting potentiometers for zero and span. The transmitted measurement signal is linear to the measured temperature.
Page 4
17
3. Configuration
3.1 Equipment
A screwdriver with a width of 2.5 mm is required to adjust the unit and to connect the wires to the terminals.
3.2 Opening the unit
Disconnect the plugs. Disengage the top part of the housing by carefully pressing the latches on both sides (1). Pull out the top part of the hous­ing and the electronics section until they lock (2).
3.3 Settings
Set input and output ranges, minimum input values and measuring span via the DIP switches SW1 and SW2 according to the following tables.
When activating variable setting SW 1/8 of the span or offset, it is possible to make additional adjust­ments via front potentiometers span and offset, accessible below cover (3)
Caution! Only use a screwdriver which is
properly insulated against the voltage applied to the input when fine adjusting the potentiometers on the front.
1
1
2
Zero
Span
SW2
SW1
3
Page 5
18
Selecting the inputs
SW1
Input 1 2 3
PT100 2-wire 1 1 1 PT100 3-wire 0 1 1 PT100 4-wire 1 0 1 R 2-wire 0 0 1 NI100 2-wire 1 1 0 NI100 3-wire 0 1 0 NI100 4-wire 1 0 0 Potentiometer 0 0 0
Selecting the minimum input value
SW1
min Rmin Potimin 4567
0º C 0 0%1111 –10º C 10 10%1110 –20º C 20 20%1101 –25º C 25 25%1100 –30º C 30 30%1011 –40º C 40 40%1010 –50º C 50 50%1001 –60º C 60 60%1000 –70º C 70 70%0111 –80º C 80 80%0110 –90º C 90 0101
Page 6
19
SW1
min Rmin Potimin 4567
–100º C 100 0100 –150 °C 150 0011 –200 °C 200 0010
Special range 0000
Activating the manual fine adjustment
SW1
manual calibration 8
off 0 on 1
1 = on 0 = off
Page 7
20
Selecting the measuring range
SW2
T R Poti 12345
40K 20 20% 11111 50K 25 25% 11110 60K 30 30% 11101 70K 35 35% 11100 80K 40 40% 11011
90K 45 45% 11010 100K 50 50% 11001 110K 55 55% 11000 120K 60 60% 10111 125K 62,5 62,5% 10110 130K 65 65% 10101 140K 70 70% 10100 150K 75 75% 10011 160K 80 80% 10010 170K 85 85% 10001 180K 90 90% 10000 190K 95 95% 01111 200K 100 100% 01110 250K 125 01101 300K 150 01100 350K 175 01011 400K 200 01010 450K 225 01001 500K 250 01000 550K 275 00111
Page 8
21
SW2
T R Poti 12345
550K 275 00111 600K 300 00110
650 K 325 00101
700K 350 00100 750K 375 00011 800K 400 00010 850K 425 00001 900K 450 00000
Selecting the output
SW2
Output 6 7
0…10 V 1 0 0…20 mA 0 0 4…20 mA 0 1
1 = on 0 = off
Page 9
Selecting the step response time
SW2
Step response 8
slow 1
fast 0
1 = on 0 = off
3.4 Terminal assignment of the sensors
Terminal assignment for 2-, 3-, 4-wires and potentiometers.
4-wires 3-wires 2-wires Potentiometer
Sensor +
Sensor -
Sensor -
Sensor -
22
Page 10
23
4. Mounting
The analogue signal isolators are mounted on standard TS 35 rails.
5. Electrical connection
Warning! For applications with high isolation voltages, take measures to
prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent devices!
5.1 Power supply
18…30 Vdc/approx. 1 W Voltage supply via cross-connections (see Cat. No. point 7)
Klemmenbelegung
1 Eingang + > 5 mA 2 Eingang + £ 500 mV / £ 5 mA 3 Eingang + > 500 mV 4 Eingang -
5 Ausgang + 6 Ausgang - 7 Versorgungsspannung 8 Versorgungsspannung
Anschlußquerschnitt max. 2,5 mm
2
Mehrleiteranschluß max. 1 mm
2
(zwei Leiter gleichen Querschnitts)
78
10
1
2
3
9
11
12
4
5
6
W
e d mü
ll eri
0V.
06
J
V/I
PS
WAS5 PRO RTD
Sense
4
8560700000
nc
5
6
nc
1
2
3
RTD
Sense
RTD
7
8
24V
cc
I
0/4...20mA
0...10V
V
9
0V
101112
cc
nc
Terminal assignments
1 Input RTD + 2 Input Sensor – 3 Input RTD – 4 Input Sensor + 5 not assigned 6 not assigned 7 Output 0/4…20 mA 8 Output 0…10 V
9 Output GND 10 Power supply + 24 Vdc (cross connected) 11 Power supply 0 V (cross connected) 12 not assigned
Wire cross-section max. 2.5 mm
2
Multi-wire conncection max. 1 mm
2
(two wires with same cross-section)
Page 11
24
92,4
90
38
111,4
73,4
17,5
mm
Cross-connections
for power supply
GND
24 Vdc
6. Dimensions
Page 12
25
7. Accessories (cross-connection) Designation Cat. No.
ZQV 2,5 N/2 yellow 169380 ZQV 2,5 N/2 red 171790 ZQV 2,5 N/2 blue 171799 ZQV 2,5 N/2 black 171808
Connection markers Designation Cat. No.
WS 10/5 Multicard for plotter marking 163501 WS 10/5 Neutral 106086
8. Notes on CE marking
The WAS5/WAZ5 RTD analog signal isolators are marked CE in accordan­ce with the EU directives 89/336/EEC "Electromagnetic Compatibility" and 73/23/EEC (low-voltage directive) detailing the Harmonized European Standards (EN). The declarations of conformity are held, according the above mentioned EU directive, article 10, for the authorizing body by:
Weidmüller Interface GmbH & Co. Postfach 30 30 D-32720 Detmold Tel. (05231) 14-0 Fax (05231) 14-2083
Page 13
26
Weidmüller Interface GmbH & Co. Postfach 30 30 D-32720 Detmold Tel. (0 52 31) 14-0 Fax (0 52 31) 14-20 83