15
Analogue Signal Isolators
WAVESERIES
WAVE
ANALOGUE PRO RTD
MODEL Order Number
Screw terminal connection
WAS5 PRO RTD 8560700000
Tension clamp connection
WAZ5 PRO RTD 8560710000
Please read these instructions before using the product
and retain for future information.

16
1. General instructions
Warning! The analogue signal isolators of the WAVE
ANALOGUE PRO series
may only be installed by qualified personnel. Be sure not to
connect the unit to power supply before appropriate installation.
Do not select ranges during operation, because live parts are
exposed during this process. Only use a screwdriver which is
properly insulated against the voltage applied to the input when
fine adjusting the potentiometers on the front.
Be sure to observe the national regulations for installation and
selection of cables.
Appropriate safety measures against electrostatic discharge
(ESD) should be taken during assembly and adjustment work on
the WAVE
ANALOGUE PRO.
2. Application
Analouge singnal isolators are used for galvanic isolation and conversion of
temperature, resistance and potentiometer signals. Input and output
signals are factory set according to type or can be calibrated/switched via
DIP switches. It is not necessary to adjust the measurement range.
A +/- 5% variation can be achieved in the respective range by connecting
potentiometers for zero and span. The transmitted measurement signal is
linear to the measured temperature.

17
3. Configuration
3.1 Equipment
A screwdriver with a width of 2.5 mm is required to adjust the unit and to
connect the wires to the terminals.
3.2 Opening the unit
Disconnect the plugs. Disengage the top part of
the housing by carefully pressing the latches on
both sides (1). Pull out the top part of the housing and the electronics section until they lock (2).
3.3 Settings
Set input and output ranges, minimum input values
and measuring span via the DIP switches SW1 and
SW2 according to the following tables.
When activating variable setting SW 1/8 of the span
or offset, it is possible to make additional adjustments via front potentiometers span and offset,
accessible below cover (3)
Caution! Only use a screwdriver which is
properly insulated against the voltage
applied to the input when fine adjusting
the potentiometers on the front.
1
1
2
Zero
Span
SW2
SW1
3

18
Selecting the inputs
SW1
Input 1 2 3
PT100 2-wire 1 1 1
PT100 3-wire 0 1 1
PT100 4-wire 1 0 1
R 2-wire 0 0 1
NI100 2-wire 1 1 0
NI100 3-wire 0 1 0
NI100 4-wire 1 0 0
Potentiometer 0 0 0
Selecting the minimum input value
SW1
min Rmin Potimin 4567
0º C 0 Ω 0%1111
–10º C 10 Ω 10%1110
–20º C 20 Ω 20%1101
–25º C 25 Ω 25%1100
–30º C 30 Ω 30%1011
–40º C 40 Ω 40%1010
–50º C 50 Ω 50%1001
–60º C 60 Ω 60%1000
–70º C 70 Ω 70%0111
–80º C 80 Ω 80%0110
–90º C 90 Ω 0101

19
SW1
min Rmin Potimin 4567
–100º C 100 Ω 0100
–150 °C 150 Ω 0011
–200 °C 200 Ω 0010
Special range 0000
Activating the manual fine adjustment
SW1
manual calibration 8
off 0
on 1
1 = on
0 = off

20
Selecting the measuring range
SW2
T R Poti 12345
40K 20 Ω 20% 11111
50K 25 Ω 25% 11110
60K 30 Ω 30% 11101
70K 35 Ω 35% 11100
80K 40 Ω 40% 11011
90K 45 Ω 45% 11010
100K 50 Ω 50% 11001
110K 55 Ω 55% 11000
120K 60 Ω 60% 10111
125K 62,5 Ω 62,5% 10110
130K 65 Ω 65% 10101
140K 70 Ω 70% 10100
150K 75 Ω 75% 10011
160K 80 Ω 80% 10010
170K 85 Ω 85% 10001
180K 90 Ω 90% 10000
190K 95 Ω 95% 01111
200K 100 Ω 100% 01110
250K 125 Ω – 01101
300K 150 Ω – 01100
350K 175 Ω – 01011
400K 200 Ω – 01010
450K 225 Ω – 01001
500K 250 Ω – 01000
550K 275 Ω – 00111

21
SW2
T R Poti 12345
550K 275 Ω – 00111
600K 300 Ω – 00110
650 K 325 Ω – 00101
700K 350 Ω – 00100
750K 375 Ω – 00011
800K 400 Ω – 00010
850K 425 Ω – 00001
900K 450 Ω – 00000
Selecting the output
SW2
Output 6 7
0…10 V 1 0
0…20 mA 0 0
4…20 mA 0 1
1 = on
0 = off

Selecting the step response time
SW2
Step response 8
slow 1
fast 0
1 = on
0 = off
3.4 Terminal assignment of the sensors
Terminal assignment for 2-, 3-, 4-wires and potentiometers.
4-wires 3-wires 2-wires Potentiometer
Sensor +
Sensor -
Sensor -
Sensor -
22

23
4. Mounting
The analogue signal isolators are mounted on standard TS 35 rails.
5. Electrical connection
Warning! For applications with high isolation voltages, take measures to
prevent accidental contact and make sure that there is
sufficient distance or insulation between adjacent devices!
5.1 Power supply
18…30 Vdc/approx. 1 W
Voltage supply via cross-connections
(see Cat. No. point 7)
Klemmenbelegung
1 Eingang + > 5 mA
2 Eingang + £ 500 mV / £ 5 mA
3 Eingang + > 500 mV
4 Eingang -
5 Ausgang +
6 Ausgang -
7 Versorgungsspannung
8 Versorgungsspannung
Anschlußquerschnitt max. 2,5 mm
2
Mehrleiteranschluß max. 1 mm
2
(zwei Leiter gleichen Querschnitts)
78
10
1
2
3
9
11
12
4
5
6
W
e d mü
ll eri
0V.
06
J
V/I
PS
WAS5 PRO RTD
Sense
4
8560700000
nc
5
6
nc
1
2
3
RTD
Sense
RTD
7
8
24V
cc
I
0/4...20mA
0...10V
V
9
0V
101112
cc
nc
Terminal assignments
1 Input RTD +
2 Input Sensor –
3 Input RTD –
4 Input Sensor +
5 not assigned
6 not assigned
7 Output 0/4…20 mA
8 Output 0…10 V
9 Output GND
10 Power supply + 24 Vdc (cross connected)
11 Power supply 0 V (cross connected)
12 not assigned
Wire cross-section max. 2.5 mm
2
Multi-wire conncection max. 1 mm
2
(two wires with same cross-section)

25
7. Accessories (cross-connection)
Designation Cat. No.
ZQV 2,5 N/2 yellow 169380
ZQV 2,5 N/2 red 171790
ZQV 2,5 N/2 blue 171799
ZQV 2,5 N/2 black 171808
Connection markers
Designation Cat. No.
WS 10/5 Multicard for plotter marking 163501
WS 10/5 Neutral 106086
8. Notes on CE marking
The WAS5/WAZ5 RTD analog signal isolators are marked CE in accordance with the EU directives 89/336/EEC "Electromagnetic Compatibility" and
73/23/EEC (low-voltage directive) detailing the Harmonized European
Standards (EN).
The declarations of conformity are held, according the above mentioned
EU directive, article 10, for the authorizing body by:
Weidmüller Interface GmbH & Co.
Postfach 30 30
D-32720 Detmold
Tel. (05231) 14-0
Fax (05231) 14-2083

26
Weidmüller Interface GmbH & Co.
Postfach 30 30
D-32720 Detmold
Tel. (0 52 31) 14-0
Fax (0 52 31) 14-20 83