Weidmuller UR67-MP-HP-16DI-12-60M, UR67-MP-78-16DO-12-60M, UR67-MP-78-8DIDO-12-60M, UR67-MP-HP-8DIDO-12-60M, UR67-MP-78-16DI-12-60M Series Manual

...
Remote-I/O-System u-remote UR67 I/O-Modules IP67 Multiprotocol Manual
Letʼs connect.
UR67-MP-HP-16DI-12-60M 2426270000 UR67-MP-HP-16DO-12-60M 2426280000 UR67-MP-HP-8DIDO-12-60M 2426290000
UR67-MP-78-16DI-12-60M 2426300000 UR67-MP-78-16DO-12-60M 2426310000 UR67-MP-78-8DIDO-12-60M 2426320000

Content

4.1 UR67-MP-HP-16DI-12-60M and UR67-MP-78-16DI-12-60M 8
4.2 UR67-MP-HP-16DO-12-60M and UR67-MP-78-16DO-12-60M 9
4.3 UR67-MP-HP-8DIDO-12-60M and UR67-MP-78-8DIDO-12-60M 10
Manufacturer
Weidmüller Interface GmbH & Co. KG Klingenbergstraße 16 D-32758 Detmold T +49 5231 14-0 F +49 5231 14-292083 info@weidmueller.com www.weidmueller.com
Document No. 2484940000
Revision 00/February 2017
22484940000/00/02.2017 Manual UR67-Multiprotocol
1 About this documentation

1 About this documentation | Symbols and notes

1.1 Symbols and notes

The safety notices in this documentation are designed ac­cording to the severity of the danger.
DANGER
Imminent danger to life!
Notes with the signal word “Danger” warn you of situations that will result in serious injury or death if you do not follow the instructions given in this manual.
WARNING
Possible danger to life!
Notes with the signal word “Warning” warn you of situations that may result in serious injury or death if you do not follow the instructions given in this manual.
CAUTION
The situation-dependent safety notices may contain the fol­lowing warning symbols:
Symbol Meaning
Warning against dangerous electrical voltage
Warning against electrostatically charged components
Warning against automatic startup
Observe the documentation
▶ All instructions can be identified by the black triangles
next to the text.
– Lists are marked with a tick.
21
Female connections with sockets are illustrated
4
using empty circles.
3
Risk of injury!
Notes with the signal word “Caution” warn you of situations that may result in injury if you do not follow the instructions given in this manual.
ATTENTION
Material damage!
Notes with the signal word “Attention” warn you of hazards that may result in material damage.
Text next to this arrow are notes that are not relevant to safety, but provide important infor­mation about proper and effective work proce­dures.
Male connections with pins are illustrated using
34
1
lled circles.
2

1.2 Complete documentation

The documentation is intended for trained elec­tricians who are familiar with national and inter­national laws, provisions and standards.
All documents can also be downloaded from the Weidmüller website.

1.3 Standard data structure

All information about the structure of data
(e.g.process data and parameters) refers to the
standard data format settings in the module parameters. These are shown in the Motorola format.
32484940000/00/02.2017 Manual UR67-Multiprotocol
2 Safety

2 Safety | General safety notice

This chapter includes general safety instructions on handling
the UR67 modules. Specic safety instructions for specic
tasks and situations are given at the appropriate places in the documentation.
All work may only be carried out by trained electricians who are familiar with the safety standards that apply to automation technology.
The documentation must be stored in such a way that it is accessible to operating staff at all times.

2.1 General safety notice

When working during ongoing operations, the emergency stop mechanisms must not be made ineffective.
If faults connected to a u-remote product cannot be rectied,
the product in question must be sent to Weidmüller. Wei­dmüller assumes no liability if the module is tampered with!
All connected devices must comply with the requirements
set out in EN61558-2-4 and EN61558-2-6. Only cables
and accessories that meet the requirements and provisions regarding safety, electromagnetic compatibility and, if neces­sary, telecommunications terminal equipment, as well as the
specications, may be installed. Information on the specic
cables and accessories that are permitted to be installed is provided in this manual or can be requested from Weidmül­ler.
Electrostatic Discharge
u-remote products can be damaged or destroyed by electro­static discharge. When handling the products, the neces-
sary safety measures against electrostatic discharge (ESD) according to IEC61340-5-1 and IEC61340-5-2 must be
observed. The packing and unpacking as well as the installa­tion and disassembly of a device may only be carried out by
qualied personnel.
Fusing
The operator must set up the equipment so that it is pro­tected against overloading. The upstream fuse must be designed so that it does not exceed the maximum load cur­rent. The maximum permissible load current can be found in the technical data. The operator must decide whether ad-
ditional surge protection is required according to IEC62305. Voltages that exceed +/-30V may cause the destruction of
the modules. A power supply with secure isolation must be used.
Earthing (functional earth FE)
Every UR67-MP module is equipped with an earth connec­tion, with the connection point labelled “XE”. Further infor­mation is available in chapters 5 and 6.
Shielding
Shielded lines are to be connected with shielded plugs in
compliance with the relevant standard (see chapter 6).

2.2 Intended use

The UR67-MP modules are decentral input and output de­vices in an Ethernet/IP network or a PROFINET network. The products are designed for use in industrial automa­tion and may only be used within the scope of the stated
technical specications. The devices to be connected must comply with the requirements set out in EN61558-2-4 and EN61558-2-6.
The industrial environment is labelled as such to ensure that consumers are not directly connected to the public low-volt­age network. Additional measures must be taken for use in the home, and in the business and commercial sectors. Any intervention in the products hardware or software other than described in this manual may only be realised by Wei­dmüller. Malfunction-free operation is only guaranteed if the housing is fully assembled. Observance of the documentation is also part of the intended use.
42484940000/00/02.2017 Manual UR67-Multiprotocol

2.3 Legal notice

The UR67-series products comply with the EU Directive
2014/30/EU (EMC Directive).
Components of the following free software products are inte­grated into the modules:
Component License Link
jQuery MIT jQuery-custom-
Select jQuery-i18n MIT jQuery-overs-
croll jQuery-ui MIT
JSZip MIT md5 (as part
of CryptoJS) snap-svg
underscore MIT
MIT
MIT
MIT Apache
license 2.0
https://github.com/jquery/jquery/blob/master/ LICENSE.txt
https://github.com/jquery/jquery/blob/master/ LICENSE.txt
https://github.com/jquery/jquery/blob/master/ LICENSE.txt
https://github.com/jquery/jquery/blob/master/ LICENSE.txt
https://github.com/jquery/jquery/blob/master/ LICENSE.txt
https://github.com/Stuk/jszip/blob/master/ LICENSE.markdown
https://code.google.com/archive/p/crypto-js/ wikis/License.wiki
https://github.com/adobe-webplatform/Snap. svg/blob/master/LICENSE
https://github.com/jashkenas/underscore/blob/ master/LICENSE
2 Safety | Legal notice
52484940000/00/02.2017 Manual UR67-Multiprotocol

3 System overview | Connection characteristics

3 System overview
UR67-MP-HP-X (2426270000, 2426280000, 2426290000) UR67-MP-78-X (2426300000, 2426310000, 2426320000)
u-remote IP67 modules for Ethernet/IP and PROFINET
The UR67-MP modules are multi-protocol modules which use either Ethernet/IP or PROFINET for eldbus communica­tion. The required protocol is selected on the module using the rotary switch.
The metal housing (zinc diecast, completely encapsulated)
ensures that the modules conform to the IP67 protection class. The output current is a maximum of 1.6 A per channel. The output circuits are electrically isolated from the rest of the network and from the sensor electronics. The modules with output functionality support a fail-safe
function, which can be used to set how a channel congured as an output is to respond to an impaired or interrupted eld-
bus communication.
The UR67-MP modules differ according to their I/O function­ality:
16 digital inputs (UR67-MP-xx-16DI-12-60M)16 digital outputs (UR67-MP-xx-16DO-12-60M) – 8 digital inputs and 8 digital outputs (UR67-MP-xx-
8DIDO-12-60M).
The UR67-MP modules feature two different connections for the power supply:

3.1 Connection characteristics

All connections are colour-coded and therefore cannot be mixed up:
Fieldbus network (green): D-coded, 4-pole M12 plug-in
connector (IN and OUT). The maximum transmission rate is 100Mbps.
I/O connections (black): 8 A-coded, 5-pole M12 plug-in
connectors
Power supply connections (grey), variant-specific:
L-coded, 5-pole M12 connector (IN and OUT).5-pole, 7/8“-connections (IN and OUT)
LED
Each I/O connection is assigned two status LEDs which
change colour and the frequency at which they ash ac­cording to the status of the respective connection (seesec- tion12).

3.2 Fieldbus characteristics

5-pole, L-coded M12 connections (UR67-MP-HP-xx) 5-pole, 7/8“-connections (UR67-MP-78-xx)
The integrated Ethernet switch with two connections allows for Ethernet/IP and PROFINET networks to be set up in a line or ring topology.
Ethernet/IP product characteristics
The rmware for the UR67-MP modules supports the De­vice Level Ring protocol (DLR) for simple ring topologies in accordance with the Ethernet/IP specication. DLR allows
modules to switch to an alternative ring segment in the event of an interruption to the connection. The DLR class of the modules is “Ring Node, Beacon Based”.
62484940000/00/02.2017 Manual UR67-Multiprotocol
3 System overview | Web server
PROFINET product characteristics
The UR67-MP modules support PROFINET IO device IRT
(Isochronous Real-Time). This allows time-critical process
data to be transmitted between the network components in real time. The UR67-MP modules use the following protocols:
– DCP: for the automatic allocation of IP addresses – LLDP: for device detection in the immediate surround-
ings (neighbourhood detection)
– SNMP: for monitoring network components
The UR67-MP modules support the “Device replacement without interchangeable medium” function. With this func­tion, modules in a PROFINET network can be exchanged for identical modules without having to reassign the device name using a programming device.
Alarm and diagnostic messages
The modules offer extended Ethernet/IP and PROFINET alarm and diagnostic messages.
Conguration and parameterisation
An EDS le (Ethernet/IP) or a GSDML le (PROFINET) is needed to congure and parameterise the module in the en-
gineering tool.
The current EDS and GSDML les can be down­loaded from the Weidmüller website.

3.4 Accessories

Protective caps
Protection class IP67 is only realised with a completely con­nected module. This means that all of the connections not being used must be provided with protective caps.
Size Usage Protective cap Order No.
M12 Sensor connection SAI-SK M12 9456050000
M12 Bus-out and power-out SAI-SK-M12-UNI 2330260000
M12 Bus-in and power-in SAI-SK M12 connector 1781520000
7/8“ Power-Out SAI-7/8-SK-P-F 1422760000
7/8“ Power-In SAI-7/8-SK-P-M 2007270000
Markers
Module and connection markers are available to label equip­ment. All of the markers can be printed using the Weidmüller
PrintJet ADVANCED (Order No. 1324380000).
Module Markers Order No.
UR67-MP-xx-xxx-60M ESG-M8/20 MC NE WS 1027290000
Conductors and connections
In order to select suitable cables, we recommend referring to
Weidmüller Catalogue 8 or the Product Congurator on the
Weidmüller-Website.

3.3 Web server

The web server can be used to display the UR67-MP module on a connected PC. This allows you to execute the following functions for test purposes or during commissioning or ser­vice work:
– Query the module status – Display and change the module parameters – Access diagnostic information – Operate the module in Force mode for testing purposes
The description of the web server can be found in chap-
ter10.
72484940000/00/02.2017 Manual UR67-Multiprotocol
IN OUT
X01
UR67-MP-78-16DI-12-60M
IN
4
8
3 7
6
5
2
A DIA B
XE
OUT
Lnk/Act
P2P1
U
S
16DI
A DIA B
A DIA B
A DIA B
x100
x10
x1
MS NS
BF DIA
0
E/IP
PN
0
0
BUS
1
12
11
10
2
1
7
6
5
4
3
9
8
4 Module descriptions
4.1 UR67-MP-HP-16DI-12-60M and
UR67-MP-78-16DI-12-60M

4 Module descriptions | UR67-MP-HP-16DI-12-60M and UR67-MP-78-16DI-12-60M

Left: Input module UR67-MP-HP-16DI-12-60M (Order No. 2426270000) Right: Input module UR67-MP-78-16DI-12-60M (Order No. 2426300000)
The UR67-MP modules are intended for the decentralised control in an Ethernet/IP network or a PROFINET network. The protocol is selected using the rotary switch.
Each module has eight connections (M12, 5-pole, A-coded) for signal lines as well as connections for the eldbus (M12, 4-pole, D-coded). The power supply is connected via 5-pole,
A-coded M12 or 7/8" connections.
The UR67-MP-xx-16DI-12-60M modules have 16digital in­puts (P-switching).
Diagnostic and status LEDs
LED Display Meaning
U
S
1–8 A Yellow Channel A status: On
1 –8 B White Channel B status: On Lnk/Act
P1, P2 BF/MS Green Device operational (Ethernet/IP)
BF/MS Off No error (PROFINET)
DIA/NS Green Connected: at least one existing connection (Ethernet/IP)
DIA/NS Off No diagnosis available (PROFINET)
LED displays (normal operation); for error messages, see chapter 12
detected
Green System/sensor power supply
Green Ethernet connection to another participant available, link
Product details for UR67-MP-HP-16DI-12-60M and UR67-MP-78-16DI-12-60M
1 Marker connection1 2 I/O connections1 (sensor/actuator) 3 Status LED connection1, channelA/channelB 4 Fieldbus and module status LEDs 5 Lnk/Act status LEDs 6 Rotary switch (for setting the protocol) 7 Fieldbus connection 8 M12 or 7/8" power supply connection 9 Module marker 10 Power supply status LED (U
system/sensor power supply)
S
11 Micro-USB port (not to be used by the customer) 12 Earth connection (M4 thread)
82484940000/00/02.2017 Manual UR67-Multiprotocol
4.2 UR67-MP-HP-16DO-12-60M and
IN OUT
X01
UR67-MP-78-16DO-12-60M
IN
4
8
3 7
6
5
2
A DIA B
XE
OUT
Lnk/Act
P2P1
USU
L
16DO
A DIA B
A DIA B
A DIA B
x100
x10
x1
MS NS
BF DIA
0
E/IP
PN
0
0
BUS
1
12
11
10
2
1
7
6
5
4
3
9
8
UR67-MP-78-16DO-12-60M
4 Module descriptions | UR67-MP-HP-16DO-12-60M and UR67-MP-78-16DO-12-60M
Left: Output module UR67-MP-HP-16DO-12-60M (Order No. 2426280000) Right: Output module UR67-MP-78-16DO-12-60M (Order No. 2426310000)
The UR67-MP modules are intended for the decentralised control in an Ethernet/IP network or a PROFINET network. The protocol is selected using the rotary switch.
Each module has eight connections (M12, 5-pole, A-coded) for signal lines as well as connections for the eldbus (M12, 4-pole, D-coded). The power supply is connected via 5-pole,
A-coded M12 or 7/8" connections. The UR67-MP-xx-16DO-12-60M modules have 16 digital
outputs (P-switching).
Diagnostic and status LEDs
LED Display Meaning
U
L
U
S
1–8 A Yellow Channel A status: On
1 –8 B White Channel B status: On Lnk/Act
P1, P2 BF/MS Green Device operational (Ethernet/IP)
BF/MS Off No error (PROFINET)
DIA/NS Green Connected: at least one existing connection (Ethernet/IP)
DIA/NS Off No diagnosis available (PROFINET)
LED displays (normal operation); for error messages, see chapter 12
Green Actuator power supply
Green System/sensor power supply
Green Ethernet connection to another participant available, link
detected
Product details for UR67-MP-HP-16DO-12-60M and UR67-MP-78-16DO-12-60M
1 Marker connection1 2 I/O connections1 (sensor/actuator) 3 Status LED connection1, channelA/channelB 4 Fieldbus and module status LEDs 5 Lnk/Act status LEDs 6 Rotary switch (for setting the protocol) 7 Fieldbus connection 8 M12 or 7/8" power supply connection 9 Module marker 10 Power supply status LED (U
actuator power supply, US system/sensor
L
power supply)
11 Micro-USB port (not to be used by the customer) 12 Earth connection (M4 thread)
92484940000/00/02.2017 Manual UR67-Multiprotocol
4.3 UR67-MP-HP-8DIDO-12-60M and
IN OUT
X01
UR67-MP-78-8DIDO-12-60M
IN
4
8
3 7
6
5
2
A DIA B
XE
OUT
Lnk/Act
P2P1
USU
L
8DIDO
A DIA B
A DIA B
A DIA B
x100
x10
x1
MS NS
BF DIA
0
E/IP
PN
0
0
BUS
1
12
11
2
1
7
6
5
4
3
9
8
10
UR67-MP-78-8DIDO-12-60M
4 Module descriptions | UR67-MP-HP-8DIDO-12-60M and UR67-MP-78-8DIDO-12-60M
Left: Input/Output module UR67-MP-HP-8DIDO-12-60M (Order No. 2426290000) Right: Input/Output module UR67-MP-78-8DIDO-12-60M (Order No. 2426320000)
The UR67-MP modules are intended for the decentralised control in an Ethernet/IP network or a PROFINET network. The protocol is selected using the rotary switch.
Each module has eight connections (M12, 5-pole, A-coded) for signal lines as well as connections for the eldbus (M12, 4-pole, D-coded). The power supply is connected via 5-pole,
A-coded M12 or 7/8" connections.
The UR67-MP-xx-16DI-12-60M modules have 8digital in­puts (P-switching) and 8digital outputs.
Diagnostic and status LEDs
LED Display Meaning
U
L
U
S
1–8 A Yellow Channel A status: On
1 –8 B White Channel B status: On Lnk/Act
P1, P2 BF/MS Green Device operational (Ethernet/IP)
BF/MS Off No error (PROFINET)
DIA/NS Green Connected: at least one existing connection (Ethernet/IP)
DIA/NS Off No diagnosis available (PROFINET)
LED displays (normal operation); for error messages, see chapter 12
Green Actuator power supply
Green System/sensor power supply
Green Ethernet connection to another participant available, link
detected
Product details for UR67-MP-HP-8DIDO-12-60M and UR67-MP-78-8DIDO-12-60M
1 Marker connection1 2 I/O connections1 (sensor/actuator) 3 Status LED connection1, channelA/channelB 4 Fieldbus and module status LEDs 5 Lnk/Act status LEDs 6 Rotary switch (for setting the protocol) 7 Fieldbus connection 8 M12 or 7/8" power supply connection 9 Module marker 10 Power supply status LED (U
actuator power supply, US system/sensor
L
power supply)
11 Micro-USB port (not to be used by the customer) 12 Earth connection (M4 thread)
102484940000/00/02.2017 Manual UR67-Multiprotocol
4 Module descriptions | Connector pin assignment
5
3
3

4.4 Connector pin assignment

I/O connections
M12, A-coded 16DI 16DO 8DIDO
1 24V n.c.
3
2
4
2 In B Out B
1
3 GND 0V GND 0V GND 0V
4 In A Out A
5 FE FE FE
ATTENTION
For the system/sensor power supply and the actua­tor power supply, please only use power supplies that
conform to PELV (Protective Extra Low Voltage) or SELV (Safety Extra Low Voltage) requirements. Power sup­plies in accordance with EN61558-2-6 (transformer) or EN60950-1 (switched-mode power supply) meet these
requirements.
Power supply connection
Plug-in connector Signal Function
M12, 5-pole, L-coded
1
5
4
3
OUT
1
2
3
IN
7/8"
5
2 4
1
1 U
2
2 GND_U
3 GND_U
5
4 UL (+24V)
4
5 FE (PE) Functional earth
1 GND_U
24
2 GND_U
1
3 FE (PE) Functional earth
4 U
5
5 U
(+24V)
S
(+24V)
S
(+24V)
L
L
S
L
S
24V (connections 1–4)
n.c. (connections 5–8)
In B (connections 1–4)
Out B (connections 5–8)
In A (connections 1–4)
Out A (connections 5–8)
System/sensor power supply
Earth/reference potential U
Earth/reference potential U Actuator power supply
(electrically isolated)
Earth/reference potential U
Earth/reference potential U
System/sensor power supply
Actuator power supply (electrogalvanised)
PROFINET Ethernet/IP
M12, 4-pole, D-coded Signal Function
21
4
3
1 TD+ Transmission data +
2 RD+ Receive data +
3 TD– Transmission data –
4 RD– Receive data –
ATTENTION
The product can be destroyed!
Never place the power supply (24VDC) on the signal
or data lines.
L
S
L
S
112484940000/00/02.2017 Manual UR67-Multiprotocol

4.5 Technical Data

4 Module descriptions | Technical Data
Technical data UR67-MP-xx-16DI-12-60M
(2426270000, 242630000)
UR67-MP-xx-16DO-12-60M
(2426280000, 2426310000)
UR67-MP-xx-8DIDO-12-60M
(2426290000, 2426320000)
Bus system
Protocol
Vendor name (for Ethernet/IP)
Product type, number (for Ethernet/IP)
Product type, string (for Ethernet/IP)
Product code (for Ethernet/IP)
VendorID (for PROFINET)
DeviceID (for PROFINET)
EDS file (for Ethernet/IP)
GSDML file (for PROFINET)
Data transmission rate
Transmission method
Auto-negotiation
Switch functionality
Ethernet protocols supported
Connection
34003 (for UR67-MP-HP-16DI-12-60M) 34000 (for UR67-MP-78-16DI-12-60M)
Ping, ARP, DHCP, HTTP, TCP/ IP, BOOTP, beacon-based DLR (Ethernet/IP)
Ping, ARP, LLDP, DCP, HTTP, TCP/ IP, SNMP (PROFINET)
Ethernet/IP, PROFINET
1015
7
General Purpose Discrete I/O
34004 (for UR67-MP-HP-16DO-12-60M) 34001 (for UR67-MP-78-16DO-12-60M)
0x0134 hex
0x18C6 hex
WM_xx_Vz.z-WI-UR67-yyyymmdd.eds
GSDML-Vx.x-WI-UR67-yyyymmdd.xml
10/100 Mbps, Full Duplex (Ethernet/IP)
100 Mbps, Full Duplex (PROFINET)
100BASE-TX
Supported
Integrated, 2 connections
IRT supported (PROFINET)
M12, 4-pole, D-coded
34005 (for UR67-MP-HP-8DIDO-12-60M) 34002 (for UR67-MP-78-8DIDO-12-60M)
Inputs
Number of digital channels
Channel type
Input wiring
Rated input voltage
Input current at 24VDC
Short-circuit-proof
Status indicator
Diagnosis indicator
Connection
Type 3 in acc. with IEC 61131-2 Type 3 in acc. with IEC 61131-2
Red LED for every M12 socket Red LED for every M12 socket
16 8
NO contact, P-switching NO contact, P-switching
24VDC 24VDC
typically 5mA typically 5mA
Yes Yes
Yellow LED (channel A)
White LED (channel B)
M12, 5-pole, A-coded M12, 5-pole, A-coded
Yellow LED (channel A)
White LED (channel B)
Outputs
Number of digital channels
Channel type
Output wiring
Rated output current per channel
Signal status “1”
Signal status “0”
1)
16 8
NO contact, P-switching NO contact, P-switching
typically 1.6A in acc. with IEC61131-2 typically 1.6A in acc. with IEC61131-2
1.6A 1.6A
max. 1.6A max. 1.6A
max. 1mA (specication as per standard) max. 1mA (specication as per standard)
1) In the case of inductive loads in utilisation category DC13 (in acc. withEN60947-5-1), the outputs can operate with currents of 0.5A and a frequency of 1Hz.
2) Technically possible and approved on the following conditions: looped system/sensor power supply – max. 2.5 A; minimum cross-section of power supply wire – 5 x 1.0 mm²; max. ambient temperature – 40°C (104°F)
122484940000/00/02.2017 Manual UR67-Multiprotocol
4 Module descriptions | Technical Data
Technical data UR67-MP-xx-16DI-12-60M
(2426270000, 242630000)
Signal level of the outputs
Signal status “1”
Signal status “0”
Short-circuit-proof
Max. current-carrying capacity per mo-
min. (U
max. 2V max. 2V
Yes Yes
9.0A (12A2)) 9.0A (12A2))
dule Overload-proof
Status indicator
Diagnosis indicator
Connection
Yes Yes
Yellow LED (channel A),
Red LED, for each channel Red LED, for each channel
M12 socket, 5-pole, A-coded M12 socket, 5-pole, A-coded
Electronics/sensor power supply
Rated voltage U
S
Voltage range
Electronics current consumption
Sensor voltage
Sensor current consumption
Polarity protection
Status indicator (US)
Connection
Actuator power supply
Rated voltage U
Aux
Voltage range
Potential isolation
Low voltage threshold
Delay time for low voltage detection
Polarity protection
Actuator power supply indicator (U
Connection
)
Aux
24 V DC (SELV/PELV)
24VDC ± 25%
Yes
typically 17 V
typically 300ms
Yes
Green/red LED
7/8" plug and socket, 5-pole (UR67-MP-HP-X) M12, 5-pole, L-coded (UR67-MP-78-X)
General data
Type of protection
Ambient temperature
Weight
Enclosure material
Vibration resistance – vibration
Vibration resistance – impact
Tightening torques
M12 plug-in connector
UR67-MP-xx-16DO-12-60M
(2426280000, 2426310000)
– 1V) min. (U
Aux
white LED (channel B)
24 V DC (SELV/PELV)
24VDC ± 25%
typically 60mA
min. (U
max. 200mA (at Tu 30°C)
7/8" plug and socket, 5-pole (UR67-MP-HP-X)
M12, 5-pole, L-coded (UR67-MP-78-X)
IP 67 (only when all ports are either used or sealed)
500g (UR67-MP-HP-X) 520g (UR67-MP-78-X)
Zinc diecast, nickel matt surface nish
– 1.5V)
System
Yes
Green/red LED
-20°C to +70°C
15 g / 5–500 Hz
50 g/11 ms
0.5 Nm
UR67-MP-xx-8DIDO-12-60M
(2426290000, 2426320000)
– 1V)
Aux
Yellow LED (channel A),
white LED (channel B)
1) In the case of inductive loads in utilisation category DC13 (in acc. withEN60947-5-1), the outputs can operate with currents of 0.5A and a frequency of 1Hz.
2) Technically possible and approved on the following conditions: looped system/sensor power supply – max. 2.5 A; minimum cross-section of power supply wire – 5 x 1.0 mm²; max. ambient temperature – 40°C (104°F)
132484940000/00/02.2017 Manual UR67-Multiprotocol
5 Installation and wiring

5 Installation and wiring | Preparations for installation

WARNING
Dangerous contact voltage!
▶ All installation and wiring work must be
carried out with the power supply discon­nected.
▶ Make sure that the place of installation
has been disconnected from the power supply!

5.1 Preparations for installation

Make sure that the permitted environmental conditions for
installation and operation are observed (see Technical data).
Installation position and dimensions
The modules must be installed on a level surface. The instal-
lation dimensions and tightening torques for the xings are
provided in the installation drawings on the following pages.
Unpacking the delivery
▶ Please check the delivery for completeness and transport
damage.
▶ Please report any transport damage immediately to the
respective transport company.

5.2 Installing the module and earth connection

▶ Drill the holes for the fixings (for the drilling dimensions,
see the installation drawings on the following pages).
▶ Affix each module with two screws and a washer (as per
DINEN ISO 7089).
▶ Observe the screw dimension and tightening torques indi-
cated.
Element Torque
M12 plug-in connector 0.5Nm
M12 protective cap 0.5Nm
The modules have an earth connection (“XE”) with an M4
thread for discharging interference currents and for EMC stability.
▶ Connect the earth connection to the reference earth via a
low-impedance connection.
If the mounting surface is earthed, the connection can be made directly via the mounting screws.
If the mounting surface is not earthed, use an earthing strap or a suitable cable!
▶ Connect the earthing strap or the FE cable to the earth
connection (“XE”) using an M4 screw.
ATTENTION
The product can be destroyed by elect­rostatic discharge!
u-remote products can be destroyed by elec­trostatic discharge.
▶ Please make sure that personnel and work
equipment are adequately earthed!
▶ Unpack the parts. ▶ Dispose of all packaging in accordance with the local dis-
posal guidelines. The cardboard packaging can be sent for paper recycling.
142484940000/00/02.2017 Manual UR67-Multiprotocol
Loading...