____
DATASHEET
Variable Speed Drives
Main Features
Reference : CFW700A06P0B2DBN1
Product code : 11545186
Product line : CFW700
Basic data
Power supply : 200-240 V
Input minimum-maximum voltage : 170-264 V
Number of phases
Input : 1/3
Output : 3
Supply voltage range 200-240 V 200-240 V
Overload regime Normal (ND) Heavy (HD) Normal (ND) Heavy (HD)
Rated current 6A 5
Overload current at 60 s 6,6A 6,6A
Overload current at 3 s 9A 10
Maximum applicable motor
Power (HP / kW) [1]Voltage/Frequency
Normal Overload (ND)
220V / 50Hz 1,5 / 1,1
220V / 60Hz 1,5 / 1,1 1,5 / 1,1
230V / 50Hz 2 / 1,5 1,5 / 1,1
230V / 60Hz 1,5 / 1,1 1,5 / 1,1
Dynamic braking [2] : Standard with braking
Electronic supply : Internal
Safety Stop : No
RFI internal filter [3] : Without filter
External filter : Not available
Link Inductor : Yes
Memory card : Not included in the product
USB port : Available in HMI
Line frequency : 50/60Hz
Line frequency range (minimum - maximum) : 48-62 Hz
Phase unbalance : less or equal to 3% of input rated line voltage
Transient voltage and overvoltage : Category III
Rated current of single-phase input
- Overload (ND) : 12,3A
- Overload (HD) : 10,25A
Rated current of three-phase input
- Overload (ND) : 6A
- Overload (HD) : 5 A
Power factor : 0,70 single-phase/0,94 three-phase
Displacement factor : 0,98
Rated efficiency : ≥ 97%
Maximum connections (power up cycles - on/off) per hour : 60
DC power supply : Allow
Standard switching frequency
- Overload ND : 5 kHz
- Overload HD : 5 kHz
Selectable switching frequency : 1,25; 2; 2,5; 5 and 10 kHz
Real-time clock : Not available
COPY Function : Yes, by MMF
Dissipated power:
Overload Overload (*)Mounting type
ND HD ND HD
Surface 130 W 120 W Not applicable Not applicable
Flange 25 W 25 W Not applicable Not applicable
Source available to the user
Output voltage : 24 Vcc
Maximum capacity : 500 mA
Control/performance data
Power supply : Switched-mode power supply
Control method : V/f, VVW, Sensorless and Encoder
Encoder interface : Available in inverter
Heavy Overload (HD)
1,5 / 1,1
16/08/2019
The information contained are reference
values. Subject to change without notice.
1 / 4
DATASHEET
Variable Speed Drives
Control/performance data
Control output frequency : 0 to 300 Hz
Frequency resolution : Equivalent to 1 rpm
V/F Control
- Speed resolution : 1% of rated speed
- Speed range : 1:20
VVW Control
- Speed resolution : 1% of rated speed
- Speed range : 1:30
Sensorless vector control
- Speed resolution : 0,5% of rated speed
- Speed range : 1:100
Vector control with encoder
- Speed resolution : 0,2% of nominal speed
- Speed range : Up to 0 rpm
Analog inputs
Quantity (standard) : 2
Levels : 0-10V, 0/4-20mA and -10-+10V
Impedance
- Impedance for voltage input : 400 kΩ
- Impedance for current input : 500 Ω
Function : Programmable
Maximum allowed voltage : ±15 Vdc
Digital inputs
Digital inputs - Quantity (standard) : 8
Activation : Active low and high
Maximum low level : 2 V
Minimum high level : 10 V
Input current : 7.5 mA
Maximum input current : 9.5 mA
Function : Programmable
Maximum allowed voltage : 30 Vcc
Analog outputs
Analogic outputs - Quantity (standard) : 2
Levels : 0 to 10V, 0 to 20mA and 4 to 20mA
RL for voltage output : 10 kΩ
RL for current output : 500 Ω
Function : Programmable
Digital outputs
Digital outputs - Quantity (standard) : 1 NO/NC relay and 4 transistor
Maximum voltage : 240 Vac and 30 Vdc
Maximum current : 0.75 A and 80 mA
Function : Programmable
Communication
- Modbus-RTU (Standard)
- Modbus/TCP (Not available)
- Profibus DP (with accessory: PROFIBUS DP-01)
- Profibus DPV1 (Not available)
- Profinet (Not available)
- CANopen (with acessory: CAN-01)
- DeviceNet (with accessory: CAN-01)
- EtherNet/IP (Not available)
- EtherCAT (Not available)
- BACnet (Not available)
Protections available
- Output overcurrent/short circuit
- Power supply phase loss
- Under/Overvoltage in power
- Overtemperature
- Motor overload
- IGBT's modules overload
- Fault/External alarm
- Output phase-ground short-circuit
- CPU or memory failure
Operation interface (HMI)
Avaliability : Included in the product
Installation : Local
Number of HMI buttons : 9
Display : Graphic LCD
Indication accuracy : 5% of rated current
Speed resolution : 1 rpm
Standard HMI degree of protection : IP56
____
16/08/2019
The information contained are reference
values. Subject to change without notice.