WEG Electric CFW11 Programming Manual

Summary

Chapter 0
Quick Parameter Reference, Faults and Alarms
Quick Parameter Reference ...............................................................................................................0-1
Quick Fault and Alarm Reference .....................................................................................................0-26
Chapter 1
Safety Notices
Chapter 2
General Information
Chapter 3
About the CFW-11
Chapter 4
Keypad (HMI)
Chapter 5
Programming Basic Instructions
5.7 Incompatibility Between Parameters ............................................................................................5-11
Summary
Chapter 6
Inverter Model and Accessories Identification
Chapter 7
Starting-Up and Settings
Chapter 8
Available Control Types
Chapter 9
Scalar Control (V/f)
9.4 V/f DC Voltage Limitation [27]...................................................................................................9-10
9.5 Start-up in the V/f Control Mode ................................................................................................9-13
Chapter 10
VVW Control
10.1 VVW Control [25] ...................................................................................................................10-3
10.2 Motor Data [43] .....................................................................................................................10-3
10.3 VVW Control Mode Start-up ....................................................................................................10-4
Chapter 11
Vector Control
11.1 Sensorless Control and with Encoder .......................................................................................11-1
11.2 I/f Mode (sensorless) ..............................................................................................................11-5
11.3 Self-Tuning .............................................................................................................................11-5
11.4 Optimal Flux for Sensorless Vector Control (only for constant torque loads) .................................11-6
11.5 Torque Control .......................................................................................................................11-7
11.6 Optimal Braking .....................................................................................................................11-8
11.7 Motor Data [43] ..................................................................................................................11-10
11.7.1 Adjustment of the Parameters P0409 to P0412 Based on the Motor Data Sheet .............11-14
11.8 Vector Control [29] ...............................................................................................................11-15
11.8.1 Speed Regulator [90] ................................................................................................11-15
11.8.2 Current Regulator [91] ..............................................................................................11-18
11.8.3 Flux Regulator [92] ...................................................................................................11-18
11.8.4 I/f Control [93] .........................................................................................................11-21
11.8.5 Self-Tuning [05] and [94] ..........................................................................................11-22
Summary
11.8.6 Torque Current Limitation [95] ...................................................................................11-26
11.8.7 DC Link Regulator [96] ..............................................................................................11-28
11.9 Start-up in the Vector Modes Sensorless and with Encoder .......................................................11-30
Chapter 12
Functions Common to All the Control Modes
12.1 Ramps [20] ...........................................................................................................................12-1
12.2 Speed References [21] ............................................................................................................12-3
12.3 Speed Limits [22]....................................................................................................................12-5
12.4 Multispeed [36] .....................................................................................................................12-6
12.5 Electronic Potentiometer [37] ...................................................................................................12-9
12.6 Zero Speed Logic [35] ............................................................................................................12-9
12.7 Flying Start/Ride-Through [44] ...............................................................................................12-11
12.7.1 V/f Flying Start ..........................................................................................................12-12
12.7.2 Vector Flying Start .....................................................................................................12-12
12.7.2.1 P0202=3 ......................................................................................................12-12
12.7.2.2 P0202=4 ......................................................................................................12-13
12.7.3 V/f Ride-Through .......................................................................................................12-13
12.7.4 Vector Ride-Through ..................................................................................................12-15
12.8 DC Braking [47]..................................................................................................................12-18
12.9 Skip Speed [48] ..................................................................................................................12-21
12.10 Search of Zero of the Encoder .............................................................................................12-22
Chapter 13
Digital and Analog Inputs and Outputs
13.1 I/O Configuration [07] ...........................................................................................................13-1
13.1.1 Analog Inputs [38] ......................................................................................................13-1
13.1.2 Analog Outputs [39] ...................................................................................................13-6
13.1.3 Digital Inputs [40] .....................................................................................................13-11
13.1.4 Digital Outputs / Relays [41] .....................................................................................13-19
13.2 Local Command [31] ...........................................................................................................13-28
13.3 Remote Command [32] ........................................................................................................13-28
13.4 3-Wire Command [33] .........................................................................................................13-33
13.5 Forward Run/Reverse Run Commands [34] .............................................................................13-33
Chapter 14
Dynamic Braking
14.1 Dynamic Braking [28] .............................................................................................................14-1
Chapter 15
Faults and Alarms
15.1 Motor Overload Protection ......................................................................................................15-1
15.2 Motor Overtemperature Protection ...........................................................................................15-2
15.3 Protections [45] ......................................................................................................................15-4
Summary
Chapter 16
Read Only Parameters [09]
16.1 Fault History [08] ....................................................................................................................16-8
Chapter 17
Communication [49]
17.1 RS-232 and RS-485 Serial Interface .........................................................................................17-1
17.2 CAN Interface – CANopen/DeviceNet ......................................................................................17-1
17.3 Anybus-CC Interface ...............................................................................................................17-2
17.4 Communication States and Commands ....................................................................................17-3
Chapter 18
SoftPLC [50]
18.1 SoftPLC .................................................................................................................................18-1
Chapter 19
Trace Function [52]
19.1 Trace Function ........................................................................................................................19-1
Chapter 20
PID Regulator [46]
20.1 Description and Definitions .....................................................................................................20-1
20.2 Commissioning ......................................................................................................................20-3
20.3 Sleep Mode ...........................................................................................................................20-7
20.4 Monitoring Mode Screens .......................................................................................................20-7
20.5 Connection of a 2-Wire Transducer .........................................................................................20-8
20.6 Parameters .............................................................................................................................20-8
20.7 Academic PID ......................................................................................................................20-14

Quick Parameter Reference, Faults and Alarms

0-1
0
Parameter Function Adjustable Range Factory Setting
User
Setting
Proprieties Groups Pag.
P0000 Access to Parameters 0 to 9999 0 - -
5-2
P0001 Speed Reference 0 to 18000 rpm - RO 09
16-1
P0002 Motor Speed 0 to 18000 rpm - RO 09
16-1
P0003 Motor Current 0.0 to 4500.0 A - RO 09
16-2
P0004 DC Link Voltage (Ud) 0 to 2000 V - RO 09
16-2
P0005 Motor Frequency 0.0 to 300.0 Hz - RO 09
16-2
P0006 VFD Status 0 = Ready
1 = Run 2 = Undervoltage 3 = Fault 4 = Self-Tuning 5 = Configuration 6 = DC-Braking 7 = STO
- RO 09
16-2
P0007 Motor Voltage 0 to 2000 V - RO 09
16-3
P0009 Motor Torque -1000.0 to 1000.0 % - RO 09
16-3
P0010 Output Power 0.0 to 6553.5 kW - RO 09
16-4
P0012 DI8 to DI1 Status Bit 0 = DI1
Bit 1 = DI2 Bit 2 = DI3 Bit 3 = DI4 Bit 4 = DI5 Bit 5 = DI6 Bit 6 = DI7 Bit 7 = DI8
- RO 09, 40
13-11
P0013 DO5 to DO1 Status Bit 0 = DO1
Bit 1 = DO2 Bit 2 = DO3 Bit 3 = DO4 Bit 4 = DO5
- RO 09, 41
13-19
P0014 AO1 Value 0.00 to 100.00 % - RO 09, 39
13-6
P0015 AO2 Value 0.00 to 100.00 % - RO 09, 39
13-6
P0016 AO3 Value -100.00 to 100.00 % - RO 09, 39
13-6
P0017 AO4 Value -100.00 to 100.00 % - RO 09, 39
13-6
P0018 AI1 Value -100.00 to 100.00 % - RO 09, 38, 95
13-1
P0019 AI2 Value -100.00 to 100.00 % - RO 09, 38, 95
13-1
P0020 AI3 Value -100.00 to 100.00 % - RO 09, 38, 95
13-1
P0021 AI4 Value -100.00 to 100.00 % - RO 09, 38, 95
13-1
P0023 Software Version 0.00 to 655.35 - RO 09, 42
6-2
P0027 Accessories Config. 1 0000h to FFFFh - RO 09, 42
6-2
P0028 Accessories Config. 2 0000h to FFFFh - RO 09, 42
6-2
P0029 Power Hardware Config Bit 0 to 5 = Rated
Current Bit 6 and 7 = Rated Voltage Bit 8 = EMC Filter Bit 9 = Safety Relay Bit 10 = (0)24V/(1)DC Link Bit 11 = (0)RST/(1)DC Link Bit 12 = Dyn.Brak. IGBT Bit 13 = Special Bit 14 and 15 = Reserved
- RO 09, 42
6-4
P0030 IGBTs Temperature U -20.0 to 150.0 °C - RO 09, 45
15-4
P0031 IGBTs Temperature V -20.0 to 150.0 °C - RO 09, 45
15-4
P0032 IGBTs Temperature W -20.0 to 150.0 °C - RO 09, 45
15-4
Quick Parameter Reference, Faults and Alarms
0-2
0
Parameter Function Adjustable Range Factory Setting
User
Setting
Proprieties Groups Pag.
P0033 Rectifier Temperature -20.0 to 150.0 °C - RO 09, 45
15-4
P0034 Internal Air Temp. -20.0 to 150.0 °C - RO 09, 45
15-4
P0036 Fan Heatsink Speed 0 to 15000 rpm - RO 09
16-5
P0037 Motor Overload Status 0 to 100 % - RO 09
16-5
P0038 Encoder Speed 0 to 65535 rpm - RO 09
16-6
P0039 Encoder Pulses Count 0 to 40000 0 RO 09
16-6
P0040 PID Process Variable 0.0 to 100.0 % - RO 09, 46
20-8
P0041 PID Setpoint Value 0.0 to 100.0 % - RO 09, 46
20-8
P0042 Time Powered 0 to 65535 h - RO 09
16-6
P0043 Time Enabled 0.0 to 6553.5 h - RO 09
16-7
P0044 kWh Output Energy 0 to 65535 kWh - RO 09
16-7
P0045 Fan Enabled Time 0 to 65535 h - RO 09
16-7
P0048 Present Alarm 0 to 999 - RO 09
16-8
P0049 Present Fault 0 to 999 - RO 09
16-8
P0050 Last Fault 0 to 999 - RO 08
16-8
P0051 Last Fault Day/Month 00/00 to 31/12 - RO 08
16-9
P0052 Last Fault Year 00 to 99 - RO 08
16-10
P0053 Last Fault Time 00:00 to 23:59 - RO 08
16-10
P0054 Second Fault 0 to 999 - RO 08
16-8
P0055 Second Flt. Day/Month 00/00 to 31/12 - RO 08
16-9
P0056 Second Fault Year 00 to 99 - RO 08 16-10
P0057 Second Fault Time 00:00 to 23:59 - RO 08 16-10
P0058 Third Fault 0 to 999 - RO 08 16-8
P0059 Third Fault Day/Month 00/00 to 31/12 - RO 08 16-9
P0060 Third Fault Year 00 to 99 - RO 08 16-10
P0061 Third Fault Time 00:00 to 23:59 - RO 08 16-10
P0062 Fourth Fault 0 to 999 - RO 08 16-8
P0063 Fourth Flt. Day/Month 00/00 to 31/12 - RO 08 16-9
P0064 Fourth Fault Year 00 to 99 - RO 08 16-10
P0065 Fourth Fault Time 00:00 to 23:59 - RO 08 16-10
P0066 Fifth Fault 0 to 999 - RO 08 16-8
P0067 Fifth Fault Day/Month 00/00 to 31/12 - RO 08 16-9
P0068 Fifth Fault Year 00 to 99 - RO 08 16-10
P0069 Fifth Fault Time 00:00 to 23:59 - RO 08 16-10
P0070 Sixth Fault 0 to 999 - RO 08 16-8
P0071 Sixth Fault Day/Month 00/00 to 31/12 - RO 08 16-9
P0072 Sixth Fault Year 00 to 99 - RO 08 16-10
P0073 Sixth Fault Time 00:00 to 23:59 - RO 08 16-10
P0074 Seventh Fault 0 to 999 - RO 08 16-8
P0075 Seventh Flt.Day/Month 00/00 to 31/12 - RO 08 16-9
P0076 Seventh Fault Year 00 to 99 - RO 08 16-10
P0077 Seventh Fault Time 00:00 to 23:59 - RO 08 16-10
P0078 Eighth Fault 0 to 999 - RO 08 16-8
P0079 Eighth Flt. Day/Month 00/00 to 31/12 - RO 08 16-9
P0080 Eighth Fault Year 00 to 99 - RO 08 16-10
P0081 Eighth Fault Time 00:00 to 23:59 - RO 08 16-10
P0082 Ninth Fault 0 to 999 - RO 08 16-9
P0083 Ninth Fault Day/Month 00/00 to 31/12 - RO 08 16-9
Quick Parameter Reference, Faults and Alarms
0-3
0
Parameter Function Adjustable Range Factory Setting
User
Setting
Proprieties Groups Pag.
P0084 Ninth Fault Year 00 to 99 - RO 08 16-10
P0085 Ninth Fault Time 00:00 to 23:59 - RO 08 16-10
P0086 Tenth Fault 0 to 999 - RO 08 16-9
P0087 Tenth Fault Day/Month 00/00 to 31/12 - RO 08 16-9
P0088 Tenth Fault Year 00 to 99 - RO 08 16-10
P0089 Tenth Fault Time 00:00 to 23:59 - RO 08 16-11
P0090 Current At Last Fault 0.0 to 4000.0 A - RO 08 16-11
P0091 DC Link At Last Fault 0 to 2000 V - RO 08 16-11
P0092 Speed At Last Fault 0 to 18000 rpm - RO 08 16-11
P0093 Reference Last Fault 0 to 18000 rpm - RO 08 16-12
P0094 Frequency Last Fault 0.0 to 300.0 Hz - RO 08 16-12
P0095 Motor Volt.Last Fault 0 to 2000 V - RO 08 16-12
P0096 DIx Status Last Fault Bit 0 = DI1
Bit 1 = DI2 Bit 2 = DI3 Bit 3 = DI4 Bit 4 = DI5 Bit 5 = DI6 Bit 6 = DI7 Bit 7 = DI8
- RO 08 16-12
P0097 DOx Status Last Fault Bit 0 = DO1
Bit 1 = DO2 Bit 2 = DO3 Bit 3 = DO4 Bit 4 = DO5
- RO 08 16-13
P0100 Acceleration Time 0.0 to 999.0 s 20.0 s - 04, 20 12-1
P0101 Deceleration Time 0.0 to 999.0 s 20.0 s - 04, 20 12-1
P0102 Acceleration Time 2 0.0 to 999.0 s 20.0 s - 20 12-1
P0103 Deceleration Time 2 0.0 to 999.0 s 20.0 s - 20 12-1
P0104 S Ramp 0 = Off
1 = 50% 2 = 100%
0 = Off - 20 12-2
P0105 1st/2nd Ramp Select. 0 = 1st Ramp
1 = 2nd Ramp 2 = DIx 3 = Serial/USB 4 = Anybus-CC 5 = CANOpen/ DeviceNet 6 = SoftPLC 7 = PLC11
2 = DIx CFG 20 12-3
P0120 Speed Ref. Backup 0 = Off
1 = On
1 = On - 21 12-3
P0121 Keypad Reference 0 to 18000 rpm 90 rpm - 21 12-4
P0122 JOG/JOG+ Reference 0 to 18000 rpm 150 (125) rpm - 21 12-4
P0123 JOG- Reference 0 to 18000 rpm 150 (125) rpm Vector 21 12-5
P0124 Multispeed Ref. 1 0 to 18000 rpm 90 (75) rpm - 21, 36 12-7
P0125 Multispeed Ref. 2 0 to 18000 rpm 300 (250) rpm - 21, 36 12-7
P0126 Multispeed Ref. 3 0 to 18000 rpm 600 (500) rpm - 21, 36 12-7
P0127 Multispeed Ref. 4 0 to 18000 rpm 900 (750) rpm - 21, 36 12-7
P0128 Multispeed Ref. 5 0 to 18000 rpm 1200 (1000) rpm - 21, 36 12-7
P0129 Multispeed Ref. 6 0 to 18000 rpm 1500 (1250) rpm - 21, 36 12-7
P0130 Multispeed Ref. 7 0 to 18000 rpm 1800 (1500) rpm - 21, 36 12-7
P0131 Multispeed Ref. 8 0 to 18000 rpm 1650 (1375) rpm - 21, 36 12-7
P0132 Max. Overspeed Level 0 to 100 % 10 % CFG 22, 45 12-5
Quick Parameter Reference, Faults and Alarms
0-4
0
Parameter Function Adjustable Range Factory Setting
User
Setting
Proprieties Groups Pag.
P0133 Minimum Speed 0 to 18000 rpm 90 (75) rpm - 04, 22 12-6
P0134 Maximum Speed 0 to 18000 rpm 1800 (1500) rpm - 04, 22 12-6
P0135 Max. Output Current 0.2 to 2xI
nom-HD
1.5xI
nom-HD
V/f and VVW 04, 26 9-7
P0136 Manual Torque Boost 0 to 9 1 V/f 04, 23 9-2
P0137 Autom. Torque Boost 0.00 to 1.00 0.00 V/f 23 9-2
P0138 Slip Compensation -10.0 to 10.0 % 0.0 % V/f 23 9-3
P0139 Output Current Filter 0.0 to 16.0 s 0.2 s V/f and VVW 23, 25 9-4
P0140 Dwell Time At Start 0.0 to 10.0 s 0.0 s V/f and VVW 23, 25 9-5
P0141 Dwell Speed At Start 0 to 300 rpm 90 rpm V/f and VVW 23, 25 9-5
P0142 Max. Output Voltage 0.0 to 100.0 % 100.0 % CFG and Adj 24 9-6
P0143 Interm.Output Voltage 0.0 to 100.0 % 50.0 % CFG and Adj 24 9-6
P0144 3Hz Output Voltage 0.0 to 100.0 % 8.0 % CFG and Adj 24 9-6
P0145 Field Weakening Speed 0 to 18000 rpm 1800 rpm CFG and Adj 24 9-6
P0146 Intermediate Speed 0 to 18000 rpm 900 rpm CFG and Adj 24 9-6
P0150 DC Regul. Type V/f 0 = Ramp Hold
1 = Ramp Accel.
0 = Ramp Hold CFG, V/f
and VVW
27 9-12
P0151 DC Regul. Level V/f 339 to 400 V
585 to 800 V 585 to 800 V 585 to 800 V 585 to 800 V 809 to 1000 V 809 to 1000 V 924 to 1200 V 924 to 1200 V
400 V (P0296=0) 800 V (P0296=1) 800 V (P0296=2) 800 V (P0296=3)
800 V (P0296=4) 1000 V (P0296=5) 1000 V (P0296=6) 1000 V (P0296=7) 1200 V (P0296=8)
V/f and VVW 27 9-12
P0152 DC Link Regul. P Gain 0.00 to 9.99 1.50 V/f and VVW 27 9-13
P0153 Dyn. Braking Level 339 to 400 V
585 to 800 V 585 to 800 V 585 to 800 V 585 to 800 V 809 to 1000 V 809 to 1000 V 924 to 1200 V 924 to 1200 V
375 V (P0296=0)
618 V (P0296=1)
675 V (P0296=2)
748 V (P0296=3)
780 V (P0296=4)
893 V (P0296=5)
972 V (P0296=6)
972 V (P0296=7) 1174 V (P0296=8)
- 28 14-1
P0154 Dyn. Braking Resistor 0.0 to 500.0 ohm 0.0 ohm - 28 14-2
P0155 Dyn. B. Resist. Power 0.02 to 650.00 kW 2.60 kW - 28 14-3
P0156 Overl.Curr.100% Speed 0.1 to 1.5xI
nom-ND
1.05xI
nom-ND
- 45 15-4
P0157 Overl.Curr. 50% Speed 0.1 to 1.5xI
nom-ND
0.9xI
nom-ND
- 45 15-4
P0158 Overl.Curr. 5% Speed 0.1 to 1.5xI
nom-ND
0.5xI
nom-ND
- 45 15-5
P0159 Motor Thermal Class 0 = Class 5
1 = Class 10 2 = Class 15 3 = Class 20 4 = Class 25 5 = Class 30 6 = Class 35 7 = Class 40 8 = Class 45
1 = Class 10 CFG 45 15-6
P0160 Speed Regul. Optimiz. 0 = Normal
1 = Saturated
0 = Normal CFG and
Vector
90 11-15
P0161 Speed Prop. Gain 0.0 to 63.9 7.4 Vector 90 11-16
P0162 Speed Integral Gain 0.000 to 9.999 0.023 Vector 90 11-16
P0163 LOC Reference Offset -999 to 999 0 Vector 90 11-17
P0164 REM Reference Offset -999 to 999 0 Vector 90 11-17
P0165 Speed Filter 0.012 to 1.000 s 0.012 s Vector 90 11-17
Quick Parameter Reference, Faults and Alarms
0-5
0
Parameter Function Adjustable Range Factory Setting
User
Setting
Proprieties Groups Pag.
P0166 Speed Diff. Gain 0.00 to 7.99 0.00 Vector 90 11-17
P0167 Current Prop. Gain 0.00 to 1.99 0.50 Vector 91 11-18
P0168 Current Integral Gain 0.000 to 1.999 0.010 Vector 91 11-18
P0169 Max. CW Torque Curr. 0.0 to 650.0 % 125.0 % Vector 95 11-26
P0170 Max. CCW Torque Curr. 0.0 to 650.0 % 125.0 % Vector 95 11-26
P0171 CW Torque Cur at Nmax 0.0 to 650.0 % 125.0 % Vector 95 11-27
P0172 CCW TorqueCur at Nmax 0.0 to 650.0 % 125.0 % Vector 95 11-27
P0173 Max Torque Curve Type 0 = Ramp
1 = Step
0 = Ramp Vector 95 11-28
P0175 Flux Proport. Gain 0.0 to 31.9 2.0 Vector 92 11-18
P0176 Flux Integral Gain 0.000 to 9.999 0.020 Vector 92 11-19
P0178 Rated Flux 0 to 120 % 100 % Vector 92 11-19
P0179 Maximum Flux 0 to 120 % 120 % Vector 92 11-19
P0181 Magnetization Mode 0 = General Enable
1 = Run/Stop
0 = General
Enable
CFG and
Encoder
92 11-20
P0182 Speed for I/F Activ. 0 to 90 rpm 18 rpm Sless 93 11-21
P0183 Current in I/F Mode 0 to 9 1 Sless 93 11-21
P0184 DC Link Regul. Mode 0 = With losses
1 = Without losses 2 = Enab/Disab DIx
1 = Without losses CFG and
Vector
96 11-28
P0185 DC Link Regul. Level 339 to 400 V
585 to 800 V 585 to 800 V 585 to 800 V 585 to 800 V 809 to 1000 V 809 to 1000 V 924 to 1200 V 924 to 1200 V
400 V (P0296=0) 800 V (P0296=1) 800 V (P0296=2) 800 V (P0296=3)
800 V (P0296=4) 1000 V (P0296=5) 1000 V (P0296=6) 1000 V (P0296=7) 1200 V (P0296=8)
Vector 96 11-29
P0186 DC Link Prop. Gain 0.0 to 63.9 18.0 Vector 96 11-30
P0187 DC Link Integral Gain 0.000 to 9.999 0.002 Vector 96 11-30
P0188 Voltage Proport. Gain 0.000 to 7.999 0.200 Vector 92 11-20
P0189 Voltage Integral Gain 0.000 to 7.999 0.001 Vector 92 11-20
P0190 Max. Output Voltage 0 to 690 V
0 to 690 V 0 to 690 V 0 to 690 V 0 to 690 V 0 to 690 V 0 to 690 V 0 to 690 V 0 to 690 V
209 V (P0296=0)
361 V (P0296=1)
380 V (P0296=2)
418 V (P0296=3)
456 V (P0296=4)
499 V (P0296=5)
546 V (P0296=6)
570 V (P0296=7)
656 V (P0296=8)
Vector 92 11-20
P0191 Encoder Zero Search 0=Off
1=On
0=Off - 12-22
P0192 Status Encoder Zero
Search
0=Off 1=Finished
0=Off RO 12-22
P0193 Day of the Week 0 = Sunday
1 = Monday 2 = Tuesday 3 = Wednesday 4 = Thursday 5 = Friday 6 = Saturday
0 = Sunday 30 5-3
P0194 Day 01 to 31 01 - 30 5-3
P0195 Month 01 to 12 01 - 30 5-3
P0196 Year 00 to 99 06 - 30 5-3
P0197 Hour 00 to 23 00 - 30 5-3
Quick Parameter Reference, Faults and Alarms
0-6
0
Parameter Function Adjustable Range Factory Setting
User
Setting
Proprieties Groups Pag.
P0198 Minutes 00 to 59 00 - 30 5-3
P0199 Seconds 00 to 59 00 - 30 5-3
P0200 Password 0 = Off
1 = On 2 = Change Pass.
1 = On - 30 5-4
P0201 Language 0 = Português
1 = English 2 = Español 3 = Deutsch
0 = Português - 30 5-4
P0202 Type of Control 0 = V/f 60 Hz
1 = V/f 50 Hz 2 = V/f Adjustable 3 = Sensorless 4 = Encoder 5 = VVW
0 = V/f 60 Hz CFG 05, 23, 24,
25, 90, 91, 92, 93, 94,
95, 96
9-5
P0203 Special Function Sel. 0 = None
1 = PID Regulator
0 = None CFG 46 20-9
P0204 Load/Save Parameters 0 = Not Used
1 = Not Used 2 = Reset P0045 3 = Reset P0043 4 = Reset P0044 5 = Load 60Hz 6 = Load 50Hz 7 = Load User 1 8 = Load User 2 9 = Load User 3 10 = Save User 1 11 = Save User 2 12 = Save User 3
0 = Not Used CFG 06 7-1
P0205 Read Parameter Sel. 1 0 = Not selected
1 = Speed Refer. # 2 = Motor Speed # 3 = MotorCurrent # 4 = DC Link Volt # 5 = Motor Freq. # 6 = MotorVoltage # 7 = Motor Torque # 8 = Output Power # 9 = Process Var. # 10 = Setpoint PID # 11 = Speed Refer. ­12 = Motor Speed ­13 = MotorCurrent ­14 = DC Link Volt ­15 = Motor Freq. ­16 = MotorVoltage ­17 = Motor Torque ­18 = Output Power ­19 = Process Var. ­20 = Setpoint PID -
2 = Motor Speed # - 30 5-4
P0206 Read Parameter Sel. 2 See options in P0205 3 = Motor Current # - 30 5-4
P0207 Read Parameter Sel. 3 See options in P0205 5 = Motor Freq. # - 30 5-4
P0208 Ref. Scale Factor 1 to 18000 1800 (1500) - 30 5-5
P0209 Ref. Eng. Unit 1 32 to 127 114 - 30 5-6
P0210 Ref. Eng. Unit 2 32 to 127 112 - 30 5-6
P0211 Ref. Eng. Unit 3 32 to 127 109 - 30 5-6
P0212 Ref. Decimal Point 0 = wxyz
1 = wxy.z 2 = wx.yz 3 = w.xyz
0 = wxyz - 30 5-5
P0213 Full Scale Read 1 0.0 to 200.0 % 100.0 % CFG 30 5-7
P0214 Full Scale Read 2 0.0 to 200.0 % 100.0 % CFG 30 5-7
P0215 Full Scale Read 3 0.0 to 200.0 % 100.0 % CFG 30 5-7
P0216 HMI Display Contrast 0 to 37 27 - 30 5-7
Quick Parameter Reference, Faults and Alarms
0-7
0
Parameter Function Adjustable Range Factory Setting
User
Setting
Proprieties Groups Pag.
P0217 Zero Speed Disable 0 = Off
1 = On
0 = Off CFG 35, 46 12-10
P0218 Zero Speed Dis. Out 0 = Ref. or Speed
1 = Reference
0 = Ref. or Speed - 35, 46 12-10
P0219 Zero Speed Time 0 to 999 s 0 s - 35, 46 12-11
P0220 LOC/REM Selection Src 0 = Always LOC
1 = Always REM 2 = LR Key LOC 3 = LR Key REM 4 = DIx 5 = Serial/USB LOC 6 = Serial/USB REM 7 = Anybus-CC LOC 8 = Anybus-CC REM 9 = CANop/DNet LOC 10 = CANop/DNet REM 11 = SoftPLC LOC 12 = SoftPLC REM 13 = PLC11 LOC 14 = PLC11 REM
2 = LR Key LOC CFG 31, 32, 33,
110
13-28
P0221 LOC Reference Sel. 0 = Keypad
1 = AI1 2 = AI2 3 = AI3 4 = AI4 5 = Sum AIs > 0 6 = Sum AIs 7 = E.P. 8 = Multispeed 9 = Serial/USB 10 = Anybus-CC 11 = CANop/DNet 12 = SoftPLC 13 = PLC11
0 = Keypad CFG 31, 36, 37,
38, 110
13-28
P0222 REM Reference Sel. See options in P0221 1 = AI1 CFG 32, 36, 37,
38, 110
13-28
P0223 LOC FWD/REV Selection 0 = Always FWD
1 = Always REV 2 = FR Key FWD 3 = FR Key REV 4 = DIx 5 = Serial/USB FWD 6 = Serial/USB REV 7 = Anybus-CC FWD 8 = Anybus-CC REV 9 = CANop/DNet FWD 10 = CANop/DNet REV 11 = AI4 Polarity 12 = SoftPLC FWD 13 = SoftPLC REV 14 = AI2 Polarity 15 = PLC11 FWD 16 = PLC11 REV
2 = FR Key FWD CFG 31, 33, 110 13-29
P0224 LOC Run/Stop Sel. 0 = I,O Keys
1 = DIx 2 = Serial/USB 3 = Anybus-CC 4 = CANop/DNet 5 = SoftPLC 6 = PLC11
0 = I,O Keys CFG 31, 33, 110 13-30
P0225 LOC JOG Selection 0 = Disable
1 = JOG Key 2 = DIx 3 = Serial/USB 4 = Anybus-CC 5 = CANop/DNet 6 = SoftPLC 7 = PLC11
1 = JOG Key CFG 31, 110 13-30
P0226 REM FWD/REV Sel. See options in P0223 4 = DIx CFG 32, 33, 110 13-29
Quick Parameter Reference, Faults and Alarms
0-8
0
Parameter Function Adjustable Range Factory Setting
User
Setting
Proprieties Groups Pag.
P0227 REM Run/Stop Sel. See options in P0224 1 = DIx CFG 32, 33, 110 13-30
P0228 REM JOG Selection See options in P0225 2 = DIx CFG 32, 110 13-30
P0229 Stop Mode Selection 0 = Ramp to Stop
1 = Coast to Stop 2 = Fast Stop
0 = Ramp to Stop CFG 31, 32, 33, 3413-30
P0230 Dead Zone (AIs) 0 = Off
1 = On
0 = Off - 38 13-1
P0231 AI1 Signal Function 0 = Speed Ref.
1 = No Ramp Ref. 2 = Max.Torque Cur 3 = Process Var. 4 = PTC 5 = Not Used 6 = Not Used 7 = PLC Use
0 = Speed Ref. CFG 38, 95 13-2
P0232 AI1 Gain 0.000 to 9.999 1.000 - 38, 95 13-3
P0233 AI1 Signal Type 0 = 0 to 10V/20mA
1 = 4 to 20 mA 2 = 10V/20mA to 0 3 = 20 to 4 mA
0 = 0 to
10V/20mA
CFG 38, 95 13-5
P0234 AI1 Offset -100.00 to 100.00 % 0.00 % - 38, 95 13-4
P0235 AI1 Filter 0.00 to 16.00 s 0.00 s - 38, 95 13-4
P0236 AI2 Signal Function See options in P0231 0 = Speed Ref. CFG 38, 95 13-2
P0237 AI2 Gain 0.000 to 9.999 1.000 - 38, 95 13-3
P0238 AI2 Signal Type 0 = 0 to 10V/20mA
1 = 4 to 20 mA 2 = 10V/20mA to 0 3 = 20 to 4 mA 4 = -10 to +10V
0 = 0 to
10V/20mA
CFG 38, 95 13-5
P0239 AI2 Offset -100.00 to 100.00 % 0.00 % - 38, 95 13-4
P0240 AI2 Filter 0.00 to 16.00 s 0.00 s - 38, 95 13-4
P0241 AI3 Signal Function 0 = Speed Ref.
1 = No Ramp Ref. 2 = Max.Torque Cur 3 = Process Var. 4 = PTC 5 = Not Used 6 = Not Used 7 = PLC Use
0 = Speed Ref. CFG 38, 95 13-2
P0242 AI3 Gain 0.000 to 9.999 1.000 - 38, 95 13-4
P0243 AI3 Signal Type 0 = 0 to 10V/20mA
1 = 4 to 20 mA 2 = 10V/20mA to 0 3 = 20 to 4 mA
0 = 0 to
10V/20mA
CFG 38, 95 13-5
P0244 AI3 Offset -100.00 to 100.00 % 0.00 % - 38, 95 13-4
P0245 AI3 Filter 0.00 to 16.00 s 0.00 s - 38, 95 13-4
P0246 AI4 Signal Function 0 = Speed Ref.
1 = No Ramp Ref. 2 = Max.Torque Cur 3 = Process Var. 4 = Not Used 5 = Not Used 6 = Not Used 7 = PLC Use
0 = Speed Ref. CFG 38, 95 13-3
P0247 AI4 Gain 0.000 to 9.999 1.000 - 38, 95 13-4
P0248 AI4 Signal Type 0 = 0 to 10V/20mA
1 = 4 to 20 mA 2 = 10V/20mA to 0 3 = 20 to 4 mA 4 = -10 to +10 V
0 = 0 to
10V/20mA
CFG 38, 95 13-5
Quick Parameter Reference, Faults and Alarms
0-9
0
Parameter Function Adjustable Range Factory Setting
User
Setting
Proprieties Groups Pag.
P0249 AI4 Offset -100.00 to 100.00 % 0.00 % - 38, 95 13-4
P0250 AI4 Filter 0.00 to 16.00 s 0.00 s - 38, 95 13-4
P0251 AO1 Function 0 = Speed Ref.
1 = Total Ref. 2 = Real Speed 3 = Torque Cur.Ref 4 = Torque Current 5 = Output Current 6 = Process Var. 7 = Active Current 8 = Output Power 9 = PID Setpoint 10 = Torque Cur.> 0 11 = Motor Torque 12 = SoftPLC 13 = PTC 14 = Not Used 15 = Not Used 16 = Motor Ixt 17 = Encoder Speed 18 = P0696 Value 19 = P0697 Value 20 = P0698 Value 21 = P0699 Value 22 = PLC11 23 = Id* Current
2 = Real Speed - 39 13-6
P0252 AO1 Gain 0.000 to 9.999 1.000 - 39 13-8
P0253 AO1 Signal Type 0 = 0 to 10V/20mA
1 = 4 to 20 mA 2 = 10V/20mA to 0 3 = 20 to 4 mA
0 = 0 to
10V/20mA
CFG 39 13-10
P0254 AO2 Function See options in P0251 5 = Output Current - 39 13-6
P0255 AO2 Gain 0.000 to 9.999 1.000 - 39 13-8
P0256 AO2 Signal Type 0 = 0 to 10V/20mA
1 = 4 to 20 mA 2 = 10V/20mA to 0 3 = 20 to 4 mA
0 = 0 to
10V/20mA
CFG 39 13-10
P0257 AO3 Function 0 = Speed Ref.
1 = Total Ref. 2 = Real Speed 3 = Torque Cur.Ref 4 = Torque Current 5 = Output Current 6 = Process Var. 7 = Active Current 8 = Output Power 9 = PID Setpoint 10 = Torque Cur.> 0 11 = Motor Torque 12 = SoftPLC 13 = Not Used 14 = Not Used 15 = Not Used 16 = Motor Ixt 17 = Encoder Speed 18 = P0696 Value 19 = P0697 Value 20 = P0698 Value 21 = P0699 Value 22 = Not Used 23 = Id* Current 24 to 71 = Exclusive WEG Use
2 = Real Speed - 39 13-7
P0258 AO3 Gain 0.000 to 9.999 1.000 - 39 13-8
Quick Parameter Reference, Faults and Alarms
0-10
0
Parameter Function Adjustable Range Factory Setting
User
Setting
Proprieties Groups Pag.
P0259 AO3 Signal Type 0 = 0 to 20 mA
1 = 4 to 20 mA 2 = 20 to 0 mA 3 = 20 to 4 mA 4 = 0 to 10 V 5 = 10 to 0 V 6 = -10 to +10V
4 = 0 to 10 V CFG 39 13-10
P0260 AO4 Function See options in P0257 5 = Output Current - 39 13-7
P0261 AO4 Gain 0.000 to 9.999 1.000 - 39 13-8
P0262 AO4 Signal Type 0 = 0 to 20 mA
1 = 4 to 20 mA 2 = 20 to 0 mA 3 = 20 to 4 mA 4 = 0 to 10 V 5 = 10 to 0 V 6 = -10 to +10V
4 = 0 to 10 V CFG 39 13-10
P0263 DI1 Function 0 = Not Used
1 = Run/Stop 2 = General Enable 3 = Fast Stop 4 = FWD Run 5 = REV Run 6 = 3-Wire Start 7 = 3-Wire Stop 8 = FWD/REV 9 = LOC/REM 10 = JOG 11 = Increase EP 12 = Decrease EP 13 = Not Used 14 = Ramp 2 15 = Speed/Torque 16 = JOG+ 17 = JOG­18 = No Ext. Alarm 19 = No Ext. Fault 20 = Reset 21 = PLC Use 22 = Manual/Auto 23 = Not Used 24 = Disab.FlyStart 25 = DC Link Regul. 26 = Progr. Off 27 = Load User 1/2 28 = Load User 3 29 = DO2 Timer 30 = DO3 Timer 31 = Trace Function
1 = Run/Stop CFG 20, 31, 32,
33, 34, 37,
40, 44, 46
13-12
P0264 DI2 Function See options in P0263 8 = FWD/REV CFG 20, 31, 32,
33, 34, 37,
40, 44, 46
13-12
P0265 DI3 Function See options in P0263 0 = Not Used CFG 20, 31, 32,
33, 34, 37, 40, 44, 45,
46
13-12
Quick Parameter Reference, Faults and Alarms
0-11
0
Parameter Function Adjustable Range Factory Setting
User
Setting
Proprieties Groups Pag.
P0266 DI4 Function 0 = Not Used
1 = Run/Stop 2 = General Enable 3 = Fast Stop 4 = FWD Run 5 = REV Run 6 = 3-Wire Start 7 = 3-Wire Stop 8 = FWD/REV 9 = LOC/REM 10 = JOG 11 = Increase EP 12 = Decrease EP 13 = Multispeed 14 = Ramp 2 15 = Speed/Torque 16 = JOG+ 17 = JOG­18 = No Ext. Alarm 19 = No Ext. Fault 20 = Reset 21 = PLC Use 22 = Manual/Auto 23 = Not Used 24 = Disab.FlyStart 25 = DC Link Regul. 26 = Progr. Off 27 = Load User 1/2 28 = Load User 3 29 = DO2 Timer 30 = DO3 Timer 31 = Trace Function
0 = Not Used CFG 20, 31, 32,
33, 34, 36, 37, 40, 44,
45, 46
13-12
P0267 DI5 Function See options in P0266 10 = JOG CFG 20, 31, 32,
33, 34, 36, 37, 40, 44,
45, 46
13-12
P0268 DI6 Function See options in P0266 14 = Ramp 2 CFG 20, 31, 32,
33, 34, 36, 37, 40, 44,
45, 46
13-12
P0269 DI7 Function See options in P0263 0 = Not Used CFG 20, 31, 32,
33, 34, 37, 40, 44, 45,
46
13-12
Quick Parameter Reference, Faults and Alarms
0-12
0
Parameter Function Adjustable Range Factory Setting
User
Setting
Proprieties Groups Pag.
P0270 DI8 Function 0 = Not Used
1 = Run/Stop 2 = General Enable 3 = Fast Stop 4 = FWD Run 5 = REV Run 6 = 3-Wire Start 7 = 3-Wire Stop 8 = FWD/REV 9 = LOC/REM 10 = JOG 11 = Increase EP 12 = Decrease EP 13 = Not Used 14 = Ramp 2 15 = Speed/Torque 16 = JOG+ 17 = JOG­18 = No Ext. Alarm 19 = No Ext. Fault 20 = Reset 21 = Not Used 22 = Manual/Auto 23 = Not Used 24 = Disab.FlyStart 25 = DC Link Regul. 26 = Parametriz.Off 27 = Load User 1/2 28 = Load User 3 29 = DO2 Timer 30 = DO3 Timer 31 = Trace Function
0 = Not Used CFG 20, 31, 32,
33, 34, 37, 40, 44, 45,
46
13-12
P0275 DO1 Function (RL1) 0 = Not Used
1 = N* > Nx 2 = N > Nx 3 = N < Ny 4 = N = N* 5 = Zero Speed 6 = Is > Ix 7 = Is < Ix 8 = Torque > Tx 9 = Torque < Tx 10 = Remote 11 = Run 12 = Ready 13 = No Fault 14 = No F070 15 = No F071 16 = No F006/21/22 17 = No F051/54/57 18 = No F072 19 = 4-20mA OK 20 = P0695 Value 21 = Forward 22 = Proc. V. > PVx 23 = Proc. V. < PVy 24 = Ride-Through 25 = Pre-Charge OK 26 = Fault 27 = Time Enab > Hx 28 = SoftPLC 29 = Not Used 30 = N>Nx/Nt>Nx 31 = F > Fx (1) 32 = F > Fx (2) 33 = STO 34 = No F160 35 = No Alarm 36 = No Fault and No Alarm 37 = PLC11
13 = No Fault CFG 41 13-19
Quick Parameter Reference, Faults and Alarms
0-13
0
Parameter Function Adjustable Range Factory Setting
User
Setting
Proprieties Groups Pag.
P0276 DO2 Function (RL2) 0 = Not Used
1 = N* > Nx 2 = N > Nx 3 = N < Ny 4 = N = N* 5 = Zero Speed 6 = Is > Ix 7 = Is < Ix 8 = Torque > Tx 9 = Torque < Tx 10 = Remote 11 = Run 12 = Ready 13 = No Fault 14 = No F070 15 = No F071 16 = No F006/21/22 17 = No F051/54/57 18 = No F072 19 = 4-20mA OK 20 = P0695 Value 21 = Forward 22 = Proc. V. > PVx 23 = Proc. V. < PVy 24 = Ride-Through 25 = Pre-Charge OK 26 = Fault 27 = Time Enab > Hx 28 = SoftPLC 29 = Timer 30 = N>Nx/Nt>Nx 31 = F > Fx (1) 32 = F > Fx (2) 33 = STO 34 = No F160 35 = No Alarm 36 = No Fault and No Alarm 37 = PLC11
2 = N > Nx CFG 41 13-19
P0277 DO3 Function (RL3) See options in P0276 1 = N* > Nx CFG 41 13-19
P0278 DO4 Function 0 = Not Used
1 = N* > Nx 2 = N > Nx 3 = N < Ny 4 = N = N* 5 = Zero Speed 6 = Is > Ix 7 = Is < Ix 8 = Torque > Tx 9 = Torque < Tx 10 = Remote 11 = Run 12 = Ready 13 = No Fault 14 = No F070 15 = No F071 16 = No F006/21/22 17 = No F051/54/57 18 = No F072 19 = 4-20mA OK 20 = P0695 Value 21 = Forward 22 = Proc. V. > PVx 23 = Proc. V. < PVy 24 = Ride-Through 25 = Pre-Charge OK 26 = Fault 27 = Time Enab > Hx 28 = SoftPLC 29 = Not Used 30 = N>Nx/N>Nx 31 = F > Fx (1) 32 = F > Fx (2) 33 = STO 34 = No F160 35 = No Alarm 36 = No Fault/Alarm 37 = Not Used
0 = Not Used CFG 41 13-19
Quick Parameter Reference, Faults and Alarms
0-14
0
Parameter Function Adjustable Range Factory Setting
User
Setting
Proprieties Groups Pag.
P0279 DO5 Function See options in P0278 0 = Not Used CFG 41 13-19
P0281 Fx Frequency 0.0 to 300.0 Hz 4.0 Hz - 41 13-25
P0282 Fx Hysteresis 0.0 to 15.0 Hz 2.0 Hz - 41 13-25
P0283 DO2 ON Time 0.0 to 300.0 s 0.0 s - 41 13-25
P0284 DO2 OFF Time 0.0 to 300.0 s 0.0 s - 41 13-25
P0285 DO3 ON Time 0.0 to 300.0 s 0.0 s - 41 13-25
P0286 DO3 OFF Time 0.0 to 300.0 s 0.0 s - 41 13-25
P0287 Nx/Ny Hysteresis 0 to 900 rpm 18 (15) rpm - 41 13-26
P0288 Nx Speed 0 to 18000 rpm 120 (100) rpm - 41 13-26
P0289 Ny Speed 0 to 18000 rpm 1800 (1500) rpm - 41 13-26
P0290 Ix Current 0 to 2xI
nom-ND
1.0xI
nom-ND
- 41 13-26
P0291 Zero Speed Zone 0 to 18000 rpm 18 (15) rpm - 35, 41, 46 13-26
P0292 N = N* Band 0 to 18000 rpm 18 (15) rpm - 41 13-27
P0293 Tx Torque 0 to 200 % 100 % - 41 13-27
P0294 Hx Time 0 to 6553 h 4320 h - 41 13-27
P0295 ND/HD VFD Rated Curr. 0 = 3.6A / 3.6A
1 = 5A / 5A 2 = 6A / 5A 3 = 7A / 5.5A 4 = 7A / 7A 5 = 10A / 8A 6 = 10A / 10A 7 = 13A / 11A 8 = 13.5A / 11A 9 = 16A / 13A 10 = 17A / 13.5A 11 = 24A / 19A 12 = 24A / 20A 13 = 28A / 24A 14 = 31A / 25A 15 = 33.5A / 28A 16 = 38A / 33A 17 = 45A / 36A 18 = 45A / 38A 19 = 54A / 45A 20 = 58.5A / 47A 21 = 70A / 56A 22 = 70.5A / 61A 23 = 86A / 70A 24 = 88A / 73A 25 = 105A / 86A 26 = 427A / 427A 27 = 470A / 470A 28 = 811A / 811A 29 = 893A / 893A 30 = 1216A / 1216A 31 = 1339A / 1339A 32 = 1622A / 1622A 33 = 1786A / 1786A 34 = 2028A / 2028A 35 = 2232A / 2232A 36 = 2A / 2A 37 = 527A / 527A 38 = 1000A / 1000A 39 = 1500A / 1500A 40 = 2000A / 2000A 41 = 2500A / 2500A 42 = 600A / 515A 43 = 1140A / 979A 44 = 1710A / 1468A 45 = 2280A / 1957A 46 = 2850A / 2446A 47 = 105A / 88 A 48 = 142A / 115A 49 = 180A / 142A 50 = 211A / 180A
- RO 09, 42 6-6
Quick Parameter Reference, Faults and Alarms
0-15
0
Parameter Function Adjustable Range Factory Setting
User
Setting
Proprieties Groups Pag.
P0296 Line Rated Voltage 0 = 200 - 240 V
1 = 380 V 2 = 400 - 415 V 3 = 440 - 460 V 4 = 480 V 5 = 500 - 525 V 6 = 550 - 575 V 7 = 600 V 8 = 660 - 690 V
According to
inverter model
CFG 42 6-7
P0297 Switching Frequency 0 = 1.25 kHz
1 = 2.5 kHz 2 = 5.0 kHz 3 = 10.0 kHz
2 = 5.0 kHz CFG 42 6-7
P0298 Application 0 = Normal Duty
1 = Heavy Duty
0 = Normal Duty CFG 42 6-8
P0299 DC-Braking Start Time 0.0 to 15.0 s 0.0 s V/f, VVW
and Sless
47 12-18
P0300 DC-Braking Stop Time 0.0 to 15.0 s 0.0 s V/f, VVW
and Sless
47 12-19
P0301 DC-Braking Speed 0 to 450 rpm 30 rpm V/f, VVW
and Sless
47 12-20
P0302 DC-Braking Voltage 0.0 to 10.0 % 2.0 % V/f and VVW 47 12-20
P0303 Skip Speed 1 0 to 18000 rpm 600 rpm - 48 12-21
P0304 Skip Speed 2 0 to 18000 rpm 900 rpm - 48 12-21
P0305 Skip Speed 3 0 to 18000 rpm 1200 rpm - 48 12-21
P0306 Skip Band 0 to 750 rpm 0 rpm - 48 12-21
P0308 Serial Address 1 to 247 1 CFG 113 17-1
P0310 Serial Baud Rate 0 = 9600 bits/s
1 = 19200 bits/s 2 = 38400 bits/s 3 = 57600 bits/s
0 = 9600 bits/s CFG 113 17-1
P0311 Serial Bytes Config. 0 = 8 bits, no, 1
1 = 8 bits, even,1 2 = 8 bits, odd, 1 3 = 8 bits, no, 2 4 = 8 bits, even,2 5 = 8 bits, odd, 2
3 = 8 bits, no, 2 CFG 113 17-1
P0312 Serial Protocol 1 = TP
2 = Modbus RTU
2 = Modbus RTU CFG 113 17-1
P0313 Comm. Error Action 0 = Off
1 = Ramp Stop 2 = General Disab. 3 = Go to LOC 4 = LOC Keep Enab. 5 = Cause Fault
0 = Off - 111 17-3
P0314 Serial Watchdog 0.0 to 999.0 s 0.0 s CFG 113 17-1
P0316 Serial Interf. Status 0 = Off
1 = On 2 = Watchdog Error
- RO 09, 113 17-1
P0317 Oriented Start-up 0 = No
1 = Yes
0 = No CFG 02 10-5
P0318 Copy Function MemCard 0 = Off
1 = VFD -> MemCard 2 = MemCard -> VFD
1 = VFD ->
MemCard
CFG 06 7-2
P0319 Copy Function HMI 0 = Off
1 = VFD -> HMI 2 = HMI -> VFD
0 = Off CFG 06 7-3
Quick Parameter Reference, Faults and Alarms
0-16
0
Parameter Function Adjustable Range Factory Setting
User
Setting
Proprieties Groups Pag.
P0320 FlyStart/Ride-Through 0 = Off
1 = Flying Start 2 = FS / RT 3 = Ride-Through
0 = Off CFG 44 12-11
P0321 DC Link Power Loss 178 to 282 V
308 to 616 V 308 to 616 V 308 to 616 V 308 to 616 V 425 to 737 V 425 to 737 V 486 to 885 V 486 to 885 V
252 V (P0296=0) 436 V (P0296=1) 459 V (P0296=2) 505 V (P0296=3) 551 V (P0296=4) 602 V (P0296=5) 660 V (P0296=6) 689 V (P0296=7) 792 V (P0296=8)
Vector 44 12-16
P0322 DC Link Ride-Through 178 to 282 V
308 to 616 V 308 to 616 V 308 to 616 V 308 to 616 V 425 to 737 V 425 to 737 V 486 to 885 V 486 to 885 V
245 V (P0296=0) 423 V (P0296=1) 446 V (P0296=2) 490 V (P0296=3) 535 V (P0296=4) 585 V (P0296=5) 640 V (P0296=6) 668 V (P0296=7) 768 V (P0296=8)
Vector 44 12-16
P0323 DC Link Power Back 178 to 282 V
308 to 616 V 308 to 616 V 308 to 616 V 308 to 616 V 425 to 737 V 425 to 737 V 486 to 885 V 486 to 885 V
267 V (P0296=0) 462 V (P0296=1) 486 V (P0296=2) 535 V (P0296=3) 583 V (P0296=4) 638 V (P0296=5) 699 V (P0296=6) 729 V (P0296=7) 838 V (P0296=8)
Vector 44 12-17
P0325 Ride-Through P Gain 0.0 to 63.9 22.8 Vector 44 12-17
P0326 Ride-Through I Gain 0.000 to 9.999 0.128 Vector 44 12-17
P0327 F.S. Current Ramp I/f 0.000 to 1.000 s 0.070 s Sless 44 12-12
P0328 Flying Start Filter 0.000 to 1.000 s 0.085 s Sless 44 12-12
P0329 Frequency Ramp F.S. 2.0 to 50.0 6.0 Sless 44 12-12
P0331 Voltage Ramp 0.2 to 60.0 s 2.0 s V/f and VVW 44 12-14
P0332 Dead Time 0.1 to 10.0 s 1.0 s V/f and VVW 44 12-14
P0340 Auto-Reset Time 0 to 255 s 0 s 45 15-8
P0342 Motor Unbal.Curr.Conf 0 = Off
1 = On
0 = Off CFG 45 15-9
P0343 Ground Fault Config. 0 = Off
1 = On
1 = On CFG 45 15-9
P0344 Current Lim. Conf. 0 = Hold - FL ON
1 = Decel. - FL ON 2 = Hold - FL OFF 3 = Decel.- FL OFF
1 = Decel. - FL ON CFG, V/f
and VVW
26 9-7
P0348 Motor Overload Conf. 0 = Off
1 = Fault/Alarm 2 = Fault 3 = Alarm
1 = Fault/Alarm CFG 45 15-9
P0349 Ixt Alarm Level 70 to 100 % 85 % CFG 45 15-10
P0350 IGBTs Overload Conf. 0 = F, w/ SF rd.
1 = F/A, w/ SF rd. 2 = F, no SF rd. 3 = F/A, no SF rd.
1 = F/A, w/ SF rd. CFG 45 15-10
P0351 Motor Overtemp. Conf. 0 = Off
1 = Fault/Alarm 2 = Fault 3 = Alarm
1 = Fault/Alarm CFG 45 15-11
Quick Parameter Reference, Faults and Alarms
0-17
0
Parameter Function Adjustable Range Factory Setting
User
Setting
Proprieties Groups Pag.
P0352 Fan Control Config. 0 = HS-OFF,Int-OFF
1 = HS-ON,Int-ON 2 = HS-CT,Int-CT 3 = HS-CT,Int-OFF 4 = HS-CT,Int-ON 5 = HS-ON,Int-OFF 6 = HS-ON,Int-CT 7 = HS-OFF,Int-ON 8 = HS-OFF,Int-CT
2 = HS-CT,Int-CT CFG 45 15-12
P0353 IGBTs/Air Overtmp.Cfg 0 = HS-F/A,Air-F/A
1 = HS-F/A, Air-F 2 = HS-F, Air-F/A 3 = HS-F, Air-F
0 = HS-F/A,Air-F/A CFG 45 15-13
P0354 Fan Speed Config. 0 = Off
1 = Fault
1 = Fault CFG 45 15-13
P0356 Dead Time Compens. 0 = Off
1 = On
1 = On CFG 45 15-13
P0357 Line Phase Loss Time 0 to 60 s 3 s - 45 15-14
P0359 Motor Current Stabil. 0 = Off
1 = On
0 = Off V/f and VVW 45 15-14
P0372 DC-Braking Curr Sless 0.0 to 90.0 % 40.0 % Sless 47 12-20
P0397 Slip Compens. Regen. 0 = Off
1 = On
1 = On CFG and
VVW
25 10-3
P0398 Motor Service Factor 1.00 to 1.50 1.00 CFG 05, 43, 94 11-10
P0399 Motor Rated Eff. 50.0 to 99.9 % 67.0 % CFG and
VVW
05, 43, 94 10-3
P0400 Motor Rated Voltage 0 to 690 V
0 to 690 V 0 to 690 V 0 to 690 V 0 to 690 V 0 to 690 V 0 to 690 V 0 to 690 V 0 to 690 V
220 V (P0296=0)
440 V (P0296=1)
440 V (P0296=2)
440 V (P0296=3)
440 V (P0296=4)
575 V (P0296=5)
575 V (P0296=6)
690 V (P0296=7)
690 V (P0296=8)
CFG 05, 43, 94 11-11
P0401 Motor Rated Current 0 to 1.3xI
nom-ND
1.0xI
nom-ND
CFG 05, 43, 94 11-11
P0402 Motor Rated Speed 0 to 18000 rpm 1750 (1458) rpm CFG 05, 43, 94 11-11
P0403 Motor Rated Frequency 0 to 300 Hz 60 (50) Hz CFG 05, 43, 94 11-12
Quick Parameter Reference, Faults and Alarms
0-18
0
Parameter Function Adjustable Range Factory Setting
User
Setting
Proprieties Groups Pag.
P0404 Motor Rated Power 0 = 0.33hp 0.25kW
1 = 0.5hp 0.37kW 2 = 0.75hp 0.55kW 3 = 1hp 0.75kW 4 = 1.5hp 1.1kW 5 = 2hp 1.5kW 6 = 3hp 2.2kW 7 = 4hp 3kW 8 = 5hp 3.7kW 9 = 5.5hp 4kW 10 = 6hp 4.5kW 11 = 7.5hp 5.5kW 12 = 10hp 7.5kW 13 = 12.5hp 9kW 14 = 15hp 11kW 15 = 20hp 15kW 16 = 25hp 18.5kW 17 = 30hp 22kW 18 = 40hp 30kW 19 = 50hp 37kW 20 = 60hp 45kW 21 = 75hp 55kW 22 = 100hp 75kW 23 = 125hp 90kW 24 = 150hp 110kW 25 = 175hp 130kW 26 = 180hp 132kW 27 = 200hp 150kW 28 = 220hp 160kW 29 = 250hp 185kW 30 = 270hp 200kW 31 = 300hp 220kW 32 = 350hp 260kW 33 = 380hp 280kW 34 = 400hp 300kW 35 = 430hp 315kW 36 = 440hp 330kW 37 = 450hp 335kW 38 = 475hp 355kW 39 = 500hp 375kW 40 = 540hp 400kW 41 = 600hp 450kW 42 = 620hp 460kW 43 = 670hp 500kW 44 = 700hp 525kW 45 = 760hp 570kW 46 = 800hp 600kW 47 = 850hp 630kW 48 = 900hp 670kW 49 = 1000hp 736kW 50 = 1100hp 810kW 51 = 1250hp 920kW 52 = 1400hp 1030kW 53 = 1500hp 1110kW 54 = 1600hp 1180kW 55 = 1800hp 1330kW 56 = 2000hp 1480kW 57 = 2300hp 1700kW 58 = 2500hp 1840kW
Motor
max-ND
CFG 05, 43, 94 11-12
P0405 Encoder Pulses Number 100 to 9999 ppr 1024 ppr CFG 05, 43, 94 11-13
P0406 Motor Ventilation 0 = Self-Vent.
1 = Separate Vent. 2 = Optimal Flux
0 = Self-Vent. CFG 05, 43, 94 11-14
P0407 Motor Rated Power Fac 0.50 to 0.99 0.68 CFG and
VVW
05, 43, 94 10-4
Quick Parameter Reference, Faults and Alarms
0-19
0
Parameter Function Adjustable Range Factory Setting
User
Setting
Proprieties Groups Pag.
P0408 Run Self-Tuning 0 = No
1 = No Rotation 2 = Run for I
m
3 = Run for T
m
4 = Estimate T
m
0 = No CFG, VVW
and Vector
05, 43, 94 11-22
P0409 Stator Resistance 0.000 to 9.999 ohm 0.000 ohm CFG, VVW
and Vector
05, 43, 94 11-23
P0410 Magnetization Current 0 to 1.25xI
nom-ND
I
mag-ND
- 05, 43, 94 11-24
P0411 Leakage Inductance 0.00 to 99.99 mH 0.00 mH CFG and
Vector
05, 43, 94 11-24
P0412 Tr Time Constant 0.000 to 9.999 s 0.000 s Vector 05, 43, 94 11-25
P0413 Tm Time Constant 0.00 to 99.99 s 0.00 s Vector 05, 43, 94 11-26
P0520 PID Proportional Gain 0.000 to 7.999 1.000 - 46 20-9
P0521 PID Integral Gain 0.000 to 7.999 0.043 - 46 20-9
P0522 PID Differential Gain 0.000 to 3.499 0.000 - 46 20-9
P0523 PID Ramp Time 0.0 to 999.0 s 3.0 s - 46 20-10
P0524 PID Feedback Sel. 0 = AI1 (P0231)
1 = AI2 (P0236) 2 = AI3 (P0241) 3 = AI4 (P0246)
1 = AI2 (P0236) CFG 38, 46 20-10
P0525 Keypad PID Setpoint 0.0 to 100.0 % 0.0 % - 46 20-11
P0527 PID Action Type 0 = Direct
1 = Reverse
0 = Direct - 46 20-11
P0528 Proc. V. Scale Factor 1 to 9999 1000 - 46 20-11
P0529 Proc.V. Decimal Point 0 = wxyz
1 = wxy.z 2 = wx.yz 3 = w.xyz
1 = wxy.z - 46 20-12
P0530 Proc. V. Eng. Unit 1 32 to 127 37 - 46 20-12
P0531 Proc. V. Eng. Unit 2 32 to 127 32 - 46 20-12
P0532 Proc. V. Eng. Unit 3 32 to 127 32 - 46 20-13
P0533 PVx Value 0.0 to 100.0 % 90.0 % - 46 20-13
P0534 PVy Value 0.0 to 100.0 % 10.0 % - 46 20-13
P0535 Wake Up Band 0 to 100 % 0 % - 35, 46 20-13
P0536 P0525 Autom. Setting 0 = Off
1 = On
1 = On CFG 46 20-14
P0550 Trigger Signal Source 0 = Not selected
1 = Speed Refer. 2 = Motor Speed 3 = Motor Current 4 = DC Link Volt. 5 = Motor Freq. 6 = Motor Voltage 7 = Motor Torque 8 = Process Var. 9 = Setpoint PID 10 = AI1 11 = AI2 12 = AI3 13 = AI4
0 = Not selected - 52 19-1
P0551 Trigger Level -100.0 to 340.0 % 0.0 % - 52 19-1
Quick Parameter Reference, Faults and Alarms
0-20
0
Parameter Function Adjustable Range Factory Setting
User
Setting
Proprieties Groups Pag.
P0552 Trigger Condition 0 = P0550* = P0551
1 = P0550* <>P0551 2 = P0550* > P0551 3 = P0550* < P0551 4 = Alarm 5 = Fault 6 = DIx
5 = Fault - 52 19-2
P0553 Trace Sampling Period 1 to 65535 1 - 52 19-3
P0554 Trace Pre-Trigger 0 to 100 % 0 % - 52 19-3
P0559 Trace Max. Memory 0 to 100 % 0 % - 52 19-3
P0560 Trace Avail. Memory 0 to 100 % - RO 52 19-4
P0561 Trace Channel 1 (CH1) 0 = Not selected
1 = Speed Refer. 2 = Motor Speed 3 = Motor Current 4 = DC Link Volt. 5 = Motor Freq. 6 = Motor Voltage 7 = Motor Torque 8 = Process Var. 9 = Setpoint PID 10 = AI1 11 = AI2 12 = AI3 13 = AI4
1 = Speed Refer. - 52 19-4
P0562 Trace Channel 2 (CH2) See options in P0561 2 = Motor Speed - 52 19-4
P0563 Trace Channel 3 (CH3) See options in P0561 3 = Motor Current - 52 19-4
P0564 Trace Channel 4 (CH4) See options in P0561 0 = Not selected - 52 19-4
P0571 Start Trace Function 0 = Off
1 = On
0 = Off - 52 19-5
P0572 Trace Trig. Day/Month 00/00 to 31/12 - RO 09, 52 19-5
P0573 Trace Trig. Year 00 to 99 - RO 09, 52 19-5
P0574 Trace Trig. Time 00:00 to 23:59 - RO 09, 52 19-5
P0575 Trace Trig. Seconds 00 to 59 - RO 09, 52 19-5
P0576 Trace Function Status 0 = Off
1 = Waiting 2 = Trigger 3 = Concluded
- RO 09, 52 19-6
P0680 Logical Status Bit 0 to 4 = Not Used
Bit 5 = 2nd Ramp Bit 6 = Config. Mode Bit 7 = Alarm Bit 8 = Running Bit 9 = Enabled Bit 10 = Forward Bit 11 = JOG Bit 12 = Remote Bit 13 = Subvoltage Bit 14 = Automatic(PID) Bit 15 = Fault
- RO 09, 111 17-3
P0681 Speed in 13 bits -32768 to 32767 - RO 09, 111 17-3
P0682 Serial/USB Control Bit 0 = Ramp Enable
Bit 1 = General Enable Bit 2 = Run Forward Bit 3 = JOG Enable Bit 4 = Remote Bit 5 = 2nd Ramp Bit 6 = Reserved Bit 7 = Fault Reset Bit 8 to 15 = Reserved
- RO 09, 111 17-1
Quick Parameter Reference, Faults and Alarms
0-21
0
Parameter Function Adjustable Range Factory Setting
User
Setting
Proprieties Groups Pag.
P0683 Serial/USB Speed Ref. -32768 to 32767 - RO 09, 111 17-1
P0684 CANopen/DNet Control See options in P0682 - RO 09, 111 17-1
P0685 CANop./DNet Speed Ref -32768 to 32767 - RO 09, 111 17-1
P0686 Anybus-CC Control See options in P0682 - RO 09, 111 17-2
P0687 Anybus-CC Speed Ref. -32768 to 32767 - RO 09, 111 17-2
P0692 Operation Mode Status Bit 0 = Orient.Startup
Bit 1 = Not Used Bit 2 = Self Tuning Bit 3 = AutoGuided P318 Bit 4 = Copy Function Bit 5 = Copying MMF Bit 6 = Reprogram.Inv. Bit 7 = Aux Supply 24V Bit 8 = Incomp. Param. Bit 9 to 15 = Incomp. Code
- RO 09, 111 17-3
P0693 Operation Mode
Command
Bit 0 = Abort Startup Bit 1 = Not Used Bit 2 = Abort SelfTun. Bit 3 = Abort P0318 Bit 4 = Reserved Bit 5 = Abort MMF Copy Bit 6 and 7 = Reserved Bit 8 = Update Depend. Bit 9 to 15 = Reserved
- RO 09, 111 17-3
P0695 DOx Value Bit 0 = DO1
Bit 1 = DO2 Bit 2 = DO3 Bit 3 = DO4 Bit 4 = DO5
- RO 09, 111 17-3
P0696 AOx Value 1 -32768 to 32767 - RO 09, 111 17-3
P0697 AOx Value 2 -32768 to 32767 - RO 09, 111 17-3
P0698 AOx Value 3 -32768 to 32767 - RO 09, 111 17-3
P0699 AOx Value 4 -32768 to 32767 - RO 09, 111 17-4
P0700 CAN Protocol 1 = CANopen
2 = DeviceNet
1 = CANopen CFG 112 17-1
P0701 CAN Address 0 to 127 63 CFG 112 17-1
P0702 CAN Baud Rate 0 = 1 Mbit/s
1 = Reserved 2 = 500 Kbit/s 3 = 250 Kbit/s 4 = 125 Kbit/s 5 = 100 Kbit/s 6 = 50 Kbit/s 7 = 20 Kbit/s 8 = 10 Kbit/s
0 = 1 Mbit/s CFG 112 17-1
P0703 Bus Off Reset 0 = Manual
1 = Automatic
1 = Automatic CFG 112 17-1
P0705 CAN Controller Status 0 = Disabled
1 = Auto-baud 2 = CAN Enabled 3 = Warning 4 = Error Passive 5 = Bus Off 6 = No Bus Power
- RO 09, 112 17-1
P0706 RX CAN Telegrams 0 to 65535 - RO 09, 112 17-1
P0707 TX CAN Telegrams 0 to 65535 - RO 09, 112 17-2
P0708 Bus Off Counter 0 to 65535 - RO 09, 112 17-2
Quick Parameter Reference, Faults and Alarms
0-22
0
Parameter Function Adjustable Range Factory Setting
User
Setting
Proprieties Groups Pag.
P0709 CAN Lost Messages 0 to 65535 - RO 09, 112 17-2
P0710 DNet I/O instances 0 = ODVA Basic 2W
1 = ODVA Extend 2W 2 = Manuf.Spec. 2W 3 = Manuf.Spec. 3W 4 = Manuf.Spec. 4W 5 = Manuf.Spec. 5W 6 = Manuf.Spec. 6W
0 = ODVA
Basic 2W
- 112 17-2
P0711 DNet Read Word #3 -1 to 1499 -1 - 112 17-2
P0712 DNet Read Word #4 -1 to 1499 -1 - 112 17-2
P0713 DNet Read Word #5 -1 to 1499 -1 - 112 17-2
P0714 DNet Read Word #6 -1 to 1499 -1 - 112 17-2
P0715 DNet Write Word #3 -1 to 1499 -1 - 112 17-2
P0716 DNet Write Word #4 -1 to 1499 -1 - 112 17-2
P0717 DNet Write Word #5 -1 to 1499 -1 - 112 17-2
P0718 DNet Write Word #6 -1 to 1499 -1 - 112 17-2
P0719 DNet Network Status 0 = Offline
1 = OnLine,NotConn 2 = OnLine,Conn 3 = Conn.Timed-out 4 = Link Failure 5 = Auto-Baud
- RO 09, 112 17-2
P0720 DNet Master Status 0 = Run
1 = Idle
- RO 09, 112 17-2
P0721 CANopen Comm. Status 0 = Disabled
1 = Reserved 2 = Comm. Enabled 3 = ErrorCtrl.Enab 4 = Guarding Error 5 = HeartbeatError
- RO 09, 112 17-2
P0722 CANopen Node State 0 = Disabled
1 = Initialization 2 = Stopped 3 = Operational 4 = PreOperational
- RO 09, 112 17-2
P0723 Anybus Identification 0 = Disabled
1 = RS232 2 = RS422 3 = USB 4 = Serial Server 5 = Bluetooth 6 = Zigbee 7 = Reserved 8 = Reserved 9 = Reserved 10 = RS485 11 = Reserved 12 = Reserved 13 = Reserved 14 = Reserved 15 = Reserved 16 = Profibus DP 17 = DeviceNet 18 = CANopen 19 = EtherNet/IP 20 = CC-Link 21 = Modbus-TCP 22 = Modbus-RTU 23 = Profinet IO 24 = Reserved 25 = Reserved
- RO 09, 114 17-2
Quick Parameter Reference, Faults and Alarms
0-23
0
Parameter Function Adjustable Range Factory Setting
User
Setting
Proprieties Groups Pag.
P0724 Anybus Comm. Status 0 = Disabled
1 = Not Supported 2 = Access Error 3 = Offline 4 = Online
- RO 09, 114 17-2
P0725 Anybus Address 0 to 255 0 CFG 114 17-2
P0726 Anybus Baud Rate 0 to 3 0 CFG 114 17-2
P0727 Anybus I/O Words 2 = 2 Words
3 = 3 Words 4 = 4 Words 5 = 5 Words 6 = 6 Words 7 = 7 Words 8 = 8 Words 9 = PLC11 Board
2 = 2 Words CFG 114 17-3
P0728 Anybus Read Word #3 0 to 1499 0 CFG 114 17-3
P0729 Anybus Read Word #4 0 to 1499 0 CFG 114 17-3
P0730 Anybus Read Word #5 0 to 1499 0 CFG 114 17-3
P0731 Anybus Read Word #6 0 to 1499 0 CFG 114 17-3
P0732 Anybus Read Word #7 0 to 1499 0 CFG 114 17-3
P0733 Anybus Read Word #8 0 to 1499 0 CFG 114 17-3
P0734 Anybus Write Word #3 0 to 1499 0 CFG 114 17-3
P0735 Anybus Write Word #4 0 to 1499 0 CFG 114 17-3
P0736 Anybus Write Word #5 0 to 1499 0 CFG 114 17-3
P0737 Anybus Write Word #6 0 to 1499 0 CFG 114 17-3
P0738 Anybus Write Word #7 0 to 1499 0 CFG 114 17-3
P0739 Anybus Write Word #8 0 to 1499 0 CFG 114 17-3
P0740 Profibus Comm. Status 0 = Disabled
1 = Not Supported 2 = Access Error 3 = Offline 4 = Online
- RO 09, 115 -
P0800 Phase U Book 1 Temper -20.0 to 150.0 °C - CFW-11M
and RO
09, 45 16-13
P0801 Phase V Book 1 Temper -20.0 to 150.0 °C - CFW-11M
and RO
09, 45 16-13
P0802 Phase W Book 1 Temper -20.0 to 150.0 °C - CFW-11M
and RO
09, 45 16-13
P0803 Phase U Book 2 Temper -20.0 to 150.0 °C - CFW-11M
and RO
09, 45 16-13
P0804 Phase V Book 2 Temper -20.0 to 150.0 °C - CFW-11M
and RO
09, 45 16-14
P0805 Phase W Book 2 Temper -20.0 to 150.0 °C - CFW-11M
and RO
09, 45 16-14
P0806 Phase U Book 3 Temper -20.0 to 150.0 °C - CFW-11M
and RO
09, 45 16-14
P0807 Phase V Book 3 Temper -20.0 to 150.0 °C - CFW-11M
and RO
09, 45 16-14
P0808 Phase W Book 3 Temper -20.0 to 150.0 °C - CFW-11M
and RO
09, 45 16-14
P0809 Phase U Book 4 Temper -20.0 to 150.0 °C - CFW-11M
and RO
09, 45 16-14
P0810 Phase V Book 4 Temper -20.0 to 150.0 °C - CFW-11M
and RO
09, 45 16-14
P0811 Phase W Book 4 Temper -20.0 to 150.0 °C - CFW-11M
and RO
09, 45 16-14
Quick Parameter Reference, Faults and Alarms
0-24
0
Parameter Function Adjustable Range Factory Setting
User
Setting
Proprieties Groups Pag.
P0812 Phase U Book 5 Temper -20.0 to 150.0 °C - CFW-11M
and RO
09, 45 16-14
P0813 Phase V Book 5 Temper -20.0 to 150.0 °C - CFW-11M
and RO
09, 45 16-14
P0814 Phase W Book 5 Temper -20.0 to 150.0 °C - CFW-11M
and RO
09, 45 16-14
P0832 DIM1 Function 0 = Not Used
1 = Extern Fault 2 = Refrig. Fault 3 = Overtemp. Brk 4 = Overtemp. Ret. 5 = High Temp. Ret
0 = Not Used CFW-11M 45, 40 15-15
P0833 DIM2 Function See options in P0832 0 = Not Used CFW-11M 45, 40 15-15
P0834 DIM1 DIM2 Status Bit 0 = DIM1
Bit 1 = DIM2
- CFW-11M and RO
09, 40 16-14
P1000 SoftPLC Status 0 = No Application
1 = Install. App. 2 = Incompat. App. 3 = App. Stopped 4 = App. Running
0 = No Application RO 09, 50 18-1
P1001 SoftPLC Command 0 = Stop Program
1 = Run Program 2 = Delete Program
0 = Stop Program CFG 50 18-1
P1002 Scan Cycle Time 0 to 65535 ms - RO 09, 50 18-1
P1010 SoftPLC Parameter 1 -32768 to 32767 0 CFG 50 18-1
P1011 SoftPLC Parameter 2 -32768 to 32767 0 CFG 50 18-1
P1012 SoftPLC Parameter 3 -32768 to 32767 0 CFG 50 18-1
P1013 SoftPLC Parameter 4 -32768 to 32767 0 CFG 50 18-1
P1014 SoftPLC Parameter 5 -32768 to 32767 0 CFG 50 18-1
P1015 SoftPLC Parameter 6 -32768 to 32767 0 CFG 50 18-1
P1016 SoftPLC Parameter 7 -32768 to 32767 0 CFG 50 18-1
P1017 SoftPLC Parameter 8 -32768 to 32767 0 CFG 50 18-1
P1018 SoftPLC Parameter 9 -32768 to 32767 0 CFG 50 18-1
P1019 SoftPLC Parameter 10 -32768 to 32767 0 CFG 50 18-1
P1020 SoftPLC Parameter 11 -32768 to 32767 0 CFG 50 18-1
P1021 SoftPLC Parameter 12 -32768 to 32767 0 CFG 50 18-1
P1022 SoftPLC Parameter 13 -32768 to 32767 0 CFG 50 18-1
P1023 SoftPLC Parameter 14 -32768 to 32767 0 CFG 50 18-1
P1024 SoftPLC Parameter 15 -32768 to 32767 0 CFG 50 18-1
P1025 SoftPLC Parameter 16 -32768 to 32767 0 CFG 50 18-1
P1026 SoftPLC Parameter 17 -32768 to 32767 0 CFG 50 18-1
P1027 SoftPLC Parameter 18 -32768 to 32767 0 CFG 50 18-1
P1028 SoftPLC Parameter 19 -32768 to 32767 0 CFG 50 18-1
P1029 SoftPLC Parameter 20 -32768 to 32767 0 CFG 50 18-1
P1030 SoftPLC Parameter 21 -32768 to 32767 0 CFG 50 18-1
P1031 SoftPLC Parameter 22 -32768 to 32767 0 CFG 50 18-1
P1032 SoftPLC Parameter 23 -32768 to 32767 0 CFG 50 18-1
P1033 SoftPLC Parameter 24 -32768 to 32767 0 CFG 50 18-1
P1034 SoftPLC Parameter 25 -32768 to 32767 0 CFG 50 18-1
P1035 SoftPLC Parameter 26 -32768 to 32767 0 CFG 50 18-1
P1036 SoftPLC Parameter 27 -32768 to 32767 0 CFG 50 18-1
P1037 SoftPLC Parameter 28 -32768 to 32767 0 CFG 50 18-1
P1038 SoftPLC Parameter 29 -32768 to 32767 0 CFG 50 18-1
Loading...
+ 224 hidden pages