Motors | Automation | Energy | Transmission & Distribution | Coatings
Frequency Inverter
Convertidor de Frecuencia
Inversor de Frequência
CFW300
User's Manual
Manual del Usuario
Manual do Usuário
User’s Manual
Series: CFW300
Language: English
Document Nº: 10003325037 / 00
Models: Frame Sizes A and B
Publishing Date: 11/2015
Summary of Reviews
The information below describes the revisions made to this manual.
English
VersionReviewDescription
--R00First edition
ATTENTION!
Check the frequency of the power supply.
In case the power supply frequency is different from the factory setting (check
P403), it is necessary to set:
P204 = 5 for 60 Hz. P204 = 6 for 50 Hz.
It is only necessary to set these parameters once.
Refer to the programming manual of the CFW300 for further details about the
programming of parameter P204.
8.1 POWER DATA ...........................................................................................31
8.2 ELECTRONICS/GENERAL DATA ...........................................................32
8.2.1 Considered Standards ..................................................................33
APPENDIX A - FIGURES .................................................................... 110
APPENDIX B - TECHNICAL SPECIFICATIONS ................................ 113
Safety Instructions
1 SAFETY INSTRUCTIONS
This manual provides information for the proper installation and operation of the CFW300
frequency inverter.
It has been written to be used by qualified personnel with suitable training or technical
qualification for operating this type of equipment. The personnel shall follow all the safety
instructions described in this manual and/or defined by the local regulations. Failure to comply
with the safety instructions may result in death, serious injury, and equipment damage.
1.1 SAFETY WARNINGS IN THE MANUAL
The following safety notices are used in the manual:
DANGER!
The procedures recommended in this warning have the purpose of protecting the
user against death, serious injuries and considerable material damage.
ATTENTION!
The procedures recommended in this warning have the purpose of avoiding
material damage.
NOTE!
The information mentioned in this warning is important for the proper
understanding and good operation of the product.
1.2 SAFETY WARNINGS IN THE PRODUCT
The following symbols are attached to the product, serving as safety notices:
English
High voltages are present.
Components sensitive to electrostatic discharge.
Do not touch them.
Mandatory connection to the protective ground (PE).
Connection of the shield to the ground.
CFW300 | 1
Safety Instructions
1.3 PRELIMINARY RECOMMENDATIONS
English
DANGER!
Always disconnect the main power supply before touching any electrical
component associated to the inverter. Several components can remain charged
with high voltages or remain in movement (fans) even after the AC power is
disconnected or switched off.
Wait at least ten minutes after turning off the input power for the complete
discharge of the power capacitors.
Always connect the grounding point of the inverter to the protection earth (PE).
DANGER!
The XC10 connector does is not USB compatible, therefore, it cannot be
connected to USB ports.
This connector only serves as the interface between the CFW300 frequency
inverter and its accessories.
NOTES!
Frequency Inverter may interfere with other electronic equipment. In order to
reduce these effects, take the precautions recommended in the Chapter 3
INSTALLATION AND CONNECTION on page 9.
Read the user's manual completely before installing or operating the inverter.
Do not perform any withstand voltage test!
If necessary, contact the manufacturer.
ATTENTION!
Electronic boards have components sensitive to electrostatic discharges.
Do not touch directly on components or connectors.
If necessary, first touch the grounding point of the inverter, which must be
connected to the protection earth (PE) or use a proper grounding strap.
2 | CFW300
2 GENERAL INFORMATION
2.1 ABOUT THE MANUAL
General Information
This manual contains information for the proper installation and operation of the inverter,
commissioning, main technical features and how to identify the most usual problems of the
different models of inverters of the CFW300 line.
ATTENTION!
The operation of this equipment requires detailed installation and operation
instructions provided in the quick installation guide, user's manual, programming
manual and communication manuals. The guides are provided in print with their
respective accessory, or can be obtained at WEG website - www.weg.net. A
printed copy of the files can be requested at your local WEG dealer.
NOTE!
It is not the intention of this manual to present all the possibilities for the application
of the CFW300, as well as WEG cannot take any liability for the use of the CFW300
which is not based on this manual.
Part of the figures and tables are available in the annexes, which are divided into APPENDIX
A - FIGURES on page 110 for figures and APPENDIX B - TECHNICAL SPECIFICATIONS on
page 113 for technical specifications.
For further information, refer to the programming manual.
2.2 ABOUT THE CFW300
The CFW300 frequency inverter is a high-performance product which allows speed and torque
control of three-phase induction motors. This product provides the user with the options of
vector (VVW) or scalar (V/f) control, both programmable according to the application.
English
In the vector mode (V VW ), the operation is optimized for the motor in use, obtaining a better
performance in terms of speed regulation.
The scalar mode (V/f) is recommended for simpler applications, such as the activation of most
pumps and fans. In such cases it is possible to reduce the losses in the motor and the inverter
using the "V/f Quadratic", which results in energy savings. The V/f mode is used when more
than a motor is activated by an inverter simultaneously (multimotor applications).
The frequency inverter CFW300 also has functions of PLC (Programmable Logic Controller)
by means of the SoftPLC (integrated) feature. For further details regarding the programming of
those functions, refer to the SoftPLC user's manual of the CFW300.
The main components of the CFW300 can be viewed in the blocks diagrams of Figure 2.1 on
page 4, for frame size A 220 V, Figure 2.2 on page 5 for frame size A 110 V and Figure
2.3 on page 6 for frame size B 220 V.
CFW300 | 3
General Information
English
supply
S/L2/N (+UD)
R/L1/L (-UD)
Power
T/L 3
1
1
2
Filter RFI
5
PE
Single-phase /
three-phase
rectifier
Power
Preload
DC Link
capacitor
bank
Rsh
Inverter
with IGBT
transistors
U/T1
V/T2
Motor
3~
W/T3
PE
HMI (remote)
3
Control
Digital inputs
(DI1 to DI4)
Analog input
(AI1)
Sources for electronics and interfaces between
HMI
4
4
1
DC power supply connection available for specific models only
2
Three-phase power supply connection available for specific models only
3
Available as accessory
4
Number of Inputs/O utputs depends o n the I/O expansion ac cessory used
5
Available as accessory only in models single-phase
power and control
Control
board
with
CPU
16 bits
RS-485
3
Interfaces (RS-232,
RS-485, USB,
CANopen, Dev iceNet,
Profibus DP or
Bluetooth)
Flash Memory
Module
PC
Software
3
WPS
Analog
output
(AO1)
Digital
output
DO1
(R L1)
4
4
3
Figure 2.1: Block diagram of CFW300 for frame size A 220 V
4 | CFW300
Power
supply
L1/L
L2/N
Filter
RFI
1
PE
Single-phase /
three-phase rectifier
Preload
Power
Control
Rsh
DC Link
capacitor
bank
Sources for electronics and interfaces
between power and control
Inverter
with IGBT
transistors
General Information
U/T1
Motor
V/T2
3~
W/T3
PE
1
HMI (remote)
English
Digital inputs
(DI1 to DI4)
Analog input
(AI1)
HMI
2
Control
board
with
CPU
16 bits
Interfaces (RS-232,
CANopen, Dev iceNet,
2
Flash Memory
1
Available as accessory
2
Number of Inputs/O utputs depends o n the I/O expansion ac cessory used
Figure 2.2: Block diagram of CFW300 for frame size A 110 V
RS-485
1
RS-485, USB,
Profibus DP or
Bluetooth)
Module
PC
Software
1
WPS
Analog
output
(AO1)
Digital
output
DO1
(R L1)
2
2
1
CFW300 | 5
General Information
English
R/L1/L
Power
supply
S/L2/N
T/L 3
Digital inputs
(DI1 to DI4)
Analog input
Filter RFI
(AI1)
5
Three-phase
rectifier
PE
Power
Control
HMI
3
3
11
+UD-UD +BRBR
Preload
Sources for electronics and interfaces between
44
Rsh
DC Link
capacitor
bank
power and control
Control
board
with
CPU
16 bits
Inverter
with IGBT
transistors
Braking
IGBT
RS-485
Interfaces (RS-232,
RS-485, USB,
CANopen, Dev iceNet,
Profibus DP or
Bluetooth)
Flash Memory
Module
U/T1
V/T2
Motor
3~
W/T3
PE
2
HMI (remote)
2
2
2
PC
Software
WPS
Analog
output
(AO1)
Digital
output
DO1
(R L1)
3
3
DC power supply connection
1
Available as accessory
2
3
Number of Inputs/O utputs depends o n the I/O expansion ac cessory used
Braking resistor connection
4
Available as accessory only in models single-phase
5
Figure 2.3: Block diagram of CFW300 for frame size B 220 V
2.3 TERMINOLOGY
Tab le 2 .1: Terminology of the CF W300 inverters
Product
and Series
E.g.: CFW300A01P6S2NB20------
CFW300
Available options
Refer to Table 2.2 on page 7
NB = without braking reostática Sx = special
DB = with braking reostáticaBlank = standard
20 = IP20Hx = special hardware
6 | CFW300
Model Identification
Frame
Size
Rated
Current
Phase
Number
Rated
Voltage
Brake
Degree of
Protection
Hardware
Version
Software
Version
Blank =
standard
software
General Information
Tab le 2 .2 : Available options for each field of the nomenclature according to the rated current and voltage of the inverter
Frame Size
A
B
Output Rated
Current
01P6 = 1.6 A
02P6 = 2.6 A
04P2 = 4.2 A
06P0 = 6.0 A
01P6 = 1.6 A
02P6 = 2.6 A
04P2 = 4.2 A
06P0 = 6.0 A
07P3 = 7.3 A
01P6 = 1.6 A
02P6 = 2.6 A
04P2 = 4.2 A
06P0 = 6.0 A
07P3 = 7.3 A
01P6 = 1.6 A
02P6 = 2.6 A
04P2 = 4.2 A
06P0 = 6.0 A
07P3 = 7.3 A
10P0 = 10.0 AB = single-phase or three-phase power supply or DC
15P2 = 15.2 AT = three-phase power supply or DC
S = single -phase power supp ly
T = three-phase power supply
D = DC power supply3 = 280...340 Vdc
N° of Phases
Rated
Volta ge
1 = 110...127 Vac
2 = 200...240 Vac
2 = 200...240 Vac or
280...340 Vdc
Brake
NB
DB
English
2.4 IDENTIFICATION LABEL
The identification label is located on the side of the inverter. For further details on positioning
the label, refer to Figure A2 on page 110.
Model (Inverter
intelligent code)
Serial number
Production order
Rated input data
(voltage, current and
frequency)
Figure 2.4: Description of the CFW300 identification label
CFW30 0 Side Label
Manufacturing date
(14 corresponds to the
week and I to the year)
WEG stock item
Rated output data
(voltage, current
and frequency)
CFW300 | 7
General Information
2.5 RECEIVING AND STORAGE
English
The CFW300 is supplied packed in a cardboard box. There is an identification label affixed to
the outside of the package, identical to the one affixed to the side of the inverter.
Verify whether:
The CFW300 identification label corresponds to the purchased model.
Any damage occurred during transportation.
Report any damage immediately to the carrier.
If the CFW300 is not installed soon, store it in a clean and dry location (temperature between
-25 ºC and 60 ºC (-13 ºF and 140 ºF)), with a cover to prevent dust accumulation inside it.
ATTENTION!
When the inverter is stored for a long period, it becomes necessary to perform
the capacitor reforming. Refer to the procedure recommended in Section 6.4
PREVENTIVE MAINTENANCE on page 28 of this manual.
8 | CFW300
3 INSTALLATION AND CONNECTION
3.1 MECHANICAL INSTALLATION
Installation and Connection
3.1.1 Environmental Conditions
Avoid:
Direct exposure to sunlight, rain, high humidity or sea-air.
Inflammable or corrosive gases or liquids.
Excessive vibration.
Dust, metallic particles or oil mist.
Environment conditions permitted for the operation of the inverter:
Temperature surrounding the inverter: 0 ºC to 50 ºC ( 32 ºF to 122 ºF) - IP20.
For temperatures surrounding the inverter higher than the specifications above, it is necessary
to apply a 2 % of current derating for each degree Celsius, limited to an increase of 10 ºC (50 ºF).
Air relative humidity: 5 % to 95 % non-condensing.
Maximum altitude: up to 1000 m (3.300 ft) - rated conditions.
From 1000 m to 4000 m (3.300 ft to 13.200 ft) - 1 % of current derating for each 100 m
above 1000 m of altitude.
Pollution degree: 2 (according to EN50178 and UL508C), with non-conductive pollution.
Condensation must not originate conduction through the accumulated residues.
3.1. 2 Positioning and Mounting
English
The external dimensions and fixing holes, and the inverter net weight (mass) are shown in
Figure B1 on page 116.
Mount the inverter in the upright position on a flat and vertical surface. Allow the minimum
clearances indicated in Figure B2 on page 117, in order to allow the circulation of the cooling
air. Do not install heat sensitive components right above the inverter.
ATTENTION!
When installing two or more inverters vertically, respect the minimum clearance
A + B (as shown in Figure B2 on page 117) and provide an air deflecting plate
so that the heat rising up from the lower inverter does not affect the top inverter.
Provide independent conduits for the physical separation of signal, control and
power cables (refer to Section 3.2 ELECTRICAL INSTALLATION on page 10).
3.1. 2.1 Cabinet Mounting
For inverters installed inside cabinets or metallic boxes, provide proper exhaustion, so that the
temperature remains within the allowed range. Refe r to the dissipated powers i n Table B2 on page 114.
CFW300 | 9
Installation and Connection
As a reference, Table 3.1 on page 10 shows the air flow of rated ventilation for each model.
English
Cooling Method: internal fan with air flow upwards.
Tab le 3 .1: Air flow of the internal fan
ModelCFMI/sm3/min
A
B
17. 08.020.48
3.1.2.2 Surface Mounting
Figure B2 on page 117 illustrates the CFW300 installation procedure for surface mounting.
3.1. 2.3 DIN-Rail Mounting
The CFW300 inverter can also be mounted directly on a 35 mm-rail, in accordance with
DIN EM 50.022. For further details, refer to Figure B2 on page 117.
3.2 ELECTRICAL INSTALLATION
DANGER!
The following information is merely a guide for proper installation. Comply with
applicable local regulations for electrical installations.
Make sure the AC power supply is disconnected before starting the installation. The CFW300 must not be used as an emergency stop device. Provide other
devices for that purpose.
3.2 .1 Identification of the Power Terminals and Grounding Points
The power terminals can be of different sizes and configurations, depending on the model of
the inverter, according to Figure B3 on page 118. The location of the power, grounding and
control connections are shown in Figure B3 on page 118.
Description of the power terminals:
L/L1, N/L2, L3 (R,S,T): power supply connection.
U, V and W: connection for the motor.
-UD: negative pole of the DC power supply.
+UD: positive pole of the DC power supply.
+BR, BR: connection of the braking resistor (available for frame size B models).
PE: grounding connection.
The maximum tightening torque of the power terminals and grounding points must be checked
in Figure B3 on page 118.
10 | CFW300
Installation and Connection
DANGER!
Observe the correct DC power supply connection, polarity and terminal positions.
3.2.2 Circuit Breakers, Fuses, Grounding and Power
ATTENTION!
Use proper cable lugs for the power and grounding connection cables. Refer
to Table B1 on page 113 for recommended wiring, circuit breakers and fuses.
Keep sensitive equipment and wiring at a minimum distance of 0.25 m (9.85 in)
from the inverter and from the cables connecting the inverter to the motor.
ATTENTION!
Residual differential interrupter (DR):
When used in the inverter supply, it must have a pick-up current of 300 mA. Depending on the installation conditions, such as motor cable length and type,
multi-motor drive, etc., the DR interrupter may trip. Check with the manufacturer
the most suitable type for operation with inverters.
NOTE!
The wire gauges listed in Table B1 on page 113 are guiding values. Installation
conditions and the maximum permitted voltage drop must be considered for
the proper wiring sizing.
English
CFW300 | 11
Installation and Connection
3.2.3 Power Connections
English
PE
Power
supply
Negative pole of the DC power supply (-UD)
Disconnecting
PE
+UD-UD
Fuses
switch
Positive pole of the DC power supply (+UD)
UPE
V W
Shielding
Only available for the specific models of frame A (see Table 2.2 on page 7).
(a) Frame size A DC power supply
PE L1 L2L3
U V WPE
Fuses
Disconnecting
switch
PEW V U
Power
supply
PEW V U
PE
L1/L
L2/N
L3
*
12 | CFW300
Shielding
(*) The power ter minal L3 is not available in mo dels of frame size A si ngle-phase
(b) Frame size A single-phase and three-phase power supply
PE L2L1
Installation and Connection
PE
Power
supply
Negative pole of the DC power supply (-UD)
+UD-UD
L3
Fuses
Disconnecting
switch
Positive pole of the DC power supply (+UD)
English
U V WPE+BR BR
PE L2L1
U V WPEBR+BR
L3-UD
Shielding
(c) Frame size B DC power supply
Fuses
Disconnecting
switch
+UD
PEW V U
Power
supply
PEW V U
PE
L1/L
L2/N
L3
Shielding
Only available for the 10-A model (see Table 2.2 on page 7).
(d) Frame size B single-phase and three-phase power supply
Figure 3.1: (a) to (d) Power and grounding connections
CFW300 | 13
Installation and Connection
3.2.3.1 Input Connections
English
DANGER!
Provide a disconnect device for the inverter power supply. This device must cut
off the power supply whenever necessary (during maintenance for instance).
ATTENTION!
The power supply that feeds the inverter must have a grounded neutral.
NOTE!
The input power supply voltage must be compatible with the inverter rated
voltage.
Power factor correction capacitors are not needed at the input (L/L1, N/L2,
L3) and must not be installed at the output (U, V, W).
Power supply capacity
Suitable for use in circuits capable of delivering not more than 30.000 A
/ 240 V).
In case the CFW300 is installed in power supplies with current capacity over 30.000 A
symmetrical at (127
rms
it is necessary to use proper protection circuits for those power supplies, such as fuses or
circuit breakers.
3.2.3.2 Power Supply Reactance
In a general way, the inverters of the CFW300 line can be installed directly in the power supply,
without reactance in the supply. However, check the following:
,
rms
In order to prevent damages to the inverter and assure the expected useful life, you must
have a minimum impedance that provides a line voltage drop of 1 %. If the line impedance
(due to the transformers and cabling) is below the values listed in this table, we recommend
the use of a line reactance.
For the calculation of the line reactance necessary to obtain the desired percentage voltage
drop, use:
V
L = 1592 . ΔV .
I
s, rat
. f
e
[ μH]
Seeing that:
ΔV - desired line drop, in percentage (%).
V
- phase voltage in the inverter input, in volts (V).
e
I
- rated current of the inverter output.
s, rat
f - line frequency.
14 | CFW300
Installation and Connection
3.2.3.3 Dynamic Braking
NOTE!
The dynamic braking is available from frame size B.
Refer to Table B1 on page 113 for the following specifications of the dynamic braking: maximum
current, resistance, effective current (*) and cable gauge.
English
Input power
supply
power supply
Contactor
Command
Figure 3.2: Installation of brake resistor
Relay
Thermostat
R
S
T
BR+BR
Brake
resistor
(*) The effective braking current can be calculated as follows:
= I
max
tbr
.
5
I
effective
√
(min)
Seeing that: tbr corresponds to the sum of the braking actuation times during the most severe
cycle of five minutes.
The power of the brake resistor must be calculated considering the deceleration time, the inertia
of the load and of the resistive torque.
Procedure to use the dynamic braking:
Connect the brake resistor between the power terminals +BR and BR.
Use a twisted cable for the connection. Separate these cables from the signal and control
wiring.
Dimension the cables according to the application, observing the maximum and effective
currents.
CFW300 | 15
Installation and Connection
If the brake resistor is mounted within the cabinet of the inverter, consider its energy when
dimensioning the ventilation of the cabinet.
English
DANGER!
The internal braking circuit and the resistor may be damaged if the latter is not
properly dimensioned and/or if the voltage of the input power supply exceeds the
maximum value permitted. In order to avoid the destruction of the resistor or risk
of fire, the only guaranteed method is the inclusion of a thermal relay in series with
the resistor and/or a thermostat in contact with its housing, connected in such
a way to disconnect the input power supply of the inverter in case of overload,
as shown in Figure 3.2 on page 15.
Set P151 at maximum value when using dynamic braking.
The voltage level on the DC Link for activation of the dynamic braking is defined by the
parameter P153 (level of the dynamic braking).
Refer to the CFW300 programming manual.
3.2.3.4 Output Connections
ATTENTION!
The inverter has an electronic motor overload protection that must be adjusted
according to the driven motor. When several motors are connected to the same
inverter, install individual overload relays for each motor.
The motor overload protection available in the CFW300 is in accordance with
the UL508C standard. Note the following information:
1. Trip current equal to 1.2 times the motor rated current (P401).
ATTENTION!
If a disconnect switch or a contactor is installed at the power supply between the
inverter and the motor, never operate it with the motor spinning or with voltage
at the inverter output.
The characteristics of the cable used to connect the motor to the inverter, as well as its
interconnection and routing, are extremely important to avoid electromagnetic interference in
other equipment and not to affect the life cycle of windings and bearings of the controlled motors.
Keep motor cables away from other cables (signal cables, sensor cables, control cables, etc.),
according to Item 3.2.6 Cable Separation Distance on page 18.
When using shielded cables to install the motor:
Follow the recommendations of IEC60034-25.
Use the low impedance connection for high frequencies to connect the cable shield to the
grounding.
16 | CFW300
Installation and Connection
3.2.4 Grounding Connections
DANGER!
The inverter must be connected to a protective ground (PE). Use a minimum wire gauge for ground connection equal to the indicated in
Table B1 on page 113.
Connect the inverter grounding connections to a ground bus bar, to a single
ground point or to a common grounding point (impedance ≤ 10 Ω).
The neuter conductor of the line that feeds the inverter must be solidly
grounded; however, this conductor must not be used to ground the inverter.
Do not share the grounding wiring with other equipment that operate with high
currents (e.g.: high voltage motors, welding machines, etc.).
3.2.5 Control Connections
The control connections must be made in accordance with the specification of the connector
of the CFW300 control board. Functions and typical connections are presented in Figure 3.3 on
page 17. For further details on the specifications of the connector signals, refer to Chapter
8 TECHNICAL SPECIFICATIONS on page 31.
1
223344556677889
DI1DI1
1
(External supply)
DI4DI4
DI2DI2
DI3DI3
(a) NPN Configuration
24 V
(b) PNP Configuration
GNDGND
(+) A I1 (-)
(0 a 20) mA
(4 a 20) mA
(+) A I1 (-)
(0 a 20) mA
(4 a 20) mA
Figure 3.3: (a) and (b) Signals of C300 control card connector
GNDGND
Counter
clockwise
AI1
(0 a 10) V
Counter
clockwise
AI1
(0 a 10) V
1010111112
+10 V+10 V
Clockwise Clockwise
9
ConnectorDescription
1DI1Digital input 1
2DI2Digital input 2
3DI3Digital input 3
DO1-RL-CDO1-RL-C
DO1-RL-NCDO1-RL-NC
4DI4Digital input 4
DO1-RL-NODO1-RL-NO
5GNDReference 0 V
6AI1Analog input 1
7GNDReference 0 V
8AI1Analog input 1
12
9+10 VReference +10 Vdc
10DO1-RL-NCDigital output 1
11DO1-RL-CDigital output 1
12DO1-RL-NODigital output 1
(*) For further information, refer to the detailed specification in
Section 8.2 ELECTRO NICS/GENERAL DATA on page 32.
(Current)
(Tension)
for potentiometer
(NC contact of relay 1)
(Common point of relay 1)
(NO contact of relay 1)
(*)
English
NOTE!
The CFW300 inverters are supplied with the digital inputs configures as active
low (NPN). In order to change the configuration, check the use of parameter
P271 in the programming manual of the CFW300.
Analog input AI1 is set for input 0 to 10 V, in order to change, check parameter
P233 of the programming manual.
CFW300 | 17
Installation and Connection
For the correct connection of the control, use:
English
1. Gauge of the cables: 0.5 mm² (20 AWG) to 1.5 mm² (14 AWG).
2. Maximum torque: 0.5 N.m (4.50 lbf.in).
3. Wiring of the connector of the control board with shielded cable and separated from the
other wiring (power, command in 110 V / 220 Vac, etc.), according to Item 3.2.6 Cable
Separation Distance on page 18. If those cables must cross other cables, it must be done
in perpendicularly among them, keeping the minimum separation distance of 5 cm at the
crossing point. Connect the shield according to the figure below:
Insulate with tape
Inverter
side
Do not ground
Figure 3.4: Shield connection
4. Relays, contactors, solenoids or coils of electromechanical brake installed close to the
inverters may occasionally generate interference in the control circuitry. To eliminate this
effect, RC suppressors (with AC power supply) or freewheel diodes (with DC power supply)
must be connected in parallel to the coils of these devices.
5. When using the external HMI (refer to Chapter 7 ACCESSORIES on page 30), the cable
that connects to the inverter must be separated from the other cables in the installation,
keeping a minimum distance of 10 cm (3.95 in).
3.2.6 Cable Separation Distance
Provide separation between the control and the power cables according to Table 3.2 on page 18.
Tab le 3 .2 : Separation distance between cables
Output Rated
Current of t he
Inverter
≤ 24 A
Cable Length
≤ 100 m (330 ft)
> 100 m (330 ft)
Minimum
Separation
Distance
≥ 10 cm (3.95 in)
≥ 25 cm (9.85 in)
3.3 INSTALLATIONS ACCORDING TO EUROPEAN DIRECTIVE OF
ELECTROMAGNETIC COMPATIBILITY
The CFW300 inverters feature external RFI filter to reduce electromagnetic interference (refer
to Chapter 7 ACCESSORIES on page 30). Those inverters, when properly installed, meet
the requirements of the directive of electromagnetic compatibility.
These inverters were developed for professional applications only. Therefore, the limits for
emission of harmonic currents established by the EN 61000-3-2 and EN 61000-3-2/A 14
standards are not applicable.
18 | CFW300
Installation and Connection
3.3.1 Control Connections
1. Shielded output cables (motor cables) with the shield connected at both ends, motor and
inverter, with low-impedance connection for high frequency.
Maximum motor cable length and conducted and radiated emission levels according to Table
B3 on page 115.
2. Shielded control cables, and keep them away from other cables according to table 3.2 of
the user's manual.
3. Grounding of the inverter according to instructions of item Item 3.2.4 Grounding Connections
on page 17.
4. Grounded power supply.
5. Use short wiring to ground the external filter or inverter.
6. Ground the mounting plate using a flexible braid as short as possible. Flat conductors have
lower impedance at high frequencies.
7. Use sleeves for cable conduits whenever possible.
3.3.2 Emission and Immunity Levels
EMC Phenomenon
Emission:
Mains Terminal Disturbance Voltage
Frequency Range: 150 kHz to 30 MHz
Electromagnetic Radiation Disturbance
Frequency Range: 30 MHz to 1000 MHz
Immunity:
Electrostatic Discharge (ESD)IEC 61000-4-24 kV for contact discharge and 8 kV for air discharge
Definition of Standard IEC/EM 61800-3: "Adjustable Speed Electrical Power Drives
Systems"
Environments:
First Environment: environments that include domestic installations, as well as establishments
directly connected without intermediate transformer to a low-voltage power supply network
which supplies buildings used for domestic purposes.
CFW300 | 19
Installation and Connection
Second Environment: aincludes all establishments other than those directly connected to a
English
low-voltage power supply network that supplies buildings used for domestic purposes.
Categories:
Category C1: inverters with a voltage rating less than 1000 V and intended for use in the First
Environment.
Category C2: inverters with a voltage rating less than 1000 V intended for use in the First
Environment, not provided with a plug connector or movable installations. They must be installed
and commissioned by a professional.
Category C3: inverters with a voltage rating less than 1000 V and intended for use in the
Second Environment only (not designed for use in the First Environment).
NOTE!
A professional is a person or organization familiar with the installation and/or
commissioning of inverters, including their EMC aspects.
3.3.3 Characteristics of the RFI Filter
CFW300 inverters are installed with external filter when it is intended to reduce the disturbance
conducted from the inverter to the power line in the high frequency band (>150). It is observe
the maximum levels of conducted emission of electromagnetic compatibility standards, such
as EN 61800-3 and EN 55011.
For further details, refer to Section 3.3 INSTALLATIONS ACCORDING TO EUROPEAN DIRECTIVE
OF ELECTROMAGNETIC COMPATIBILITY on page 18.
For further information about the RFI filter model, refer to Table 7.1 on page 30.
The figure below demonstrate the connection of the filter to the inverter:
Signal and control wiring
External input
RFI filter
L1/L L1
L2/N L2
PE PE
Metal panel (when necessary)
1...12
XC1
L1/L
CFW300
L2/N
PE
Protective ground
U
V
W
PE
Motor
Power
supply
Transformer
Grounding
PE
rod
Figure 3.5: Connection of the RFI filter - general conditions
20 | CFW300
Keypad (HMI) and Basic Programming
4 KEYPAD (HMI) AND BASIC PROGRAMMING
4.1 USE OF THE KEYPAD TO OPERATE THE INVERTER
Through the HMI, it is possible to command the inverter, visualize and adjust all of its parameters.
The Keypad features the following functions:
Enables/disables the inverter via
Selects (toggles) display
between the parameter
number and its value
(position/content).
Decreases the frequency,
parameter number or
parameter value.
Figure 4.1: HMI keys
Increases the frequency,
parameter number and
parameter value.
acceleration/deceleration ramp
(start/stop, according to P229).
Resets the inver ter after a fault
event.
4.2 INDICATIONS ON THE HMI DISPLAY
Inverter status
Direction of
rotation
Unit of measurement
(it refers to the value
of the main display)
English
Main display
Figure 4.2: Display areas
Bar graph to
monitor the
variable
4.3 OPERATING MODES OF THE HMI
When energizing the inverter, the initial state of the keypad remains in the start-up mode as
long as there is no fault, alarm, undervoltage or any key is pressed.
The setting mode is composed of two levels: level 1 allows the navigation through the
parameters. And level 2 allows the edition of the parameter selected at level 1. At the end of
this level the modified value is saved when the key is pressed.
Figure 4.3 on page 22 illustrates the basic navigation of the operating modes of the HMI.
CFW300 | 21
Keypad (HMI) and Basic Programming
English
It is the initial state of the HMI after its successful power-up
(without the occurrence of faults, alarms or undervoltage)
Press key to go to level 1 of the setting mode - selection
of parameters. Pressing any other key also switches to
setting mode
Level 1:
This is the first level of the setting mode. The parameter
number is shown on the main display
Use keys and to find the desired parameter Press key to go to level 2 of the setting mode - change
of the parameter values
Level 2:
The parameter value is shown on the main display Use keys and to set the new value in the selected
parameter
Press key to confirm the modification (save the new
value). After confirming the modification, the HMI returns to
level 1 of the setting mode
NOTE!
When the inverter is in the fault state, the main display indicates the number
of the fault in the format Fxxx. Navigation is allowed after activation of key .
NOTE!
When the inverter is in the alarm state, the main display indicates the number
of the alarm in the format Axxx. The navigation is allowed after the activation of
key ; thus, the indication "A" goes to the unit of measurement display until the
situation causing the alarm is solved.
Monitoring Mode
Setting Mode
Figure 4.3: HMI operating modes
Monitoring
Setting
level 1
Setting
level 2
22 | CFW300
NOTE!
A list of parameters is presented in the quick reference of the parameters. For
further information about each parameter, refer to the CFW300 programming
manual.
5 FIRST TIME POWER-UP AND START-UP
5.1 START-UP PREPARATION
First Time Power-Up and Start-Up
The inverter must have already been installed according to Chapter 3 INSTALLATION AND
CONNECTION on page 9.
DANGER!
Always disconnect the main power supply before making any connection.
1. Check if the power, grounding and control connections are correct and firm.
2. Remove all the materials left behind from the installation work from inside the inverter or the
cabinet.
3. Verify the motor connections and if its voltage and current are within the inverter rated value.
4. Mechanically uncouple the motor from the load. If the motor cannot be uncoupled, make
sure that any speed direction (forward or reverse) will not result in personnel injury and/or
equipment damage.
5. Close the inverter or cabinet covers.
6. Measure the power supply and verify if it is within the allowed range, according to Chapter
8 TECHNICAL SPECIFICATIONS on page 31.
7. Apply power to the input: close the input disconnecting switch.
8. Check the result of the first time power-up:
The HMI display indicates:
English
Figure 5.1: HMI display when powering up
5.2 START-UP
This section describes the power-up of the inverter with HMI operation, using the minimum
connections of Figure 3.1 on page 13 and without connections in the control terminals.
Furthermore, two types of control will be considered: V/f control (scalar) and vector control
VV W. For further details on the utilization of these types of control refer to the CFW300
programming manual.
CFW300 | 23
First Time Power-Up and Start-Up
DANGER!
English
High voltages can be present, even after the disconnection of the power supply.
Wait at least 10 minutes for full discharge.