WEG CFW-11M RB User Manual

Motors | Automation | Energy | Transmission & Distribution | Coatings
Frequency Inverter
CF W-11M R B
User's Manual
REGENERATIVE
FREQUENCY
CONVERTER MANUAL
Series: CFW-11M RB
Language: English
Document: 10000874747 / 02
Models: 600...2850 A / 380...480 V
427...2028 A / 660...690 V
04/2019
Summary of Revisions
Indice
The information below describes the reviews made in this manual.
Versión Revision Description
- R00 First edition
- R01 Updating of the tables, notes and general revision
- R02 General revision
Index
1 SAFETY INSTRUCTIONS .............................................................. 1-1
1.1 SAFETY WARNINGS IN THE MANUAL .................................................... 1-1
1.2 SAFETY WARNINGS IN THE PRODUCT ................................................... 1-1
1.3 PRELIMINARY RECOMMENDATIONS ...................................................... 1-2
2 GENERAL INSTRUCTIONS .......................................................... 2-1
2.1 ABOUT THE MANUAL ............................................................................ 2-1
2.2 TERMS AND DEFINITIONS ..................................................................... 2-1
2.3 ABOUT THE CFW-11M RB ...................................................................... 2-4
2.4 IDENTIFICATION LABELS FOR THE UC11 ............................................... 2-8
2.5 IDENTIFICATION LABELS FOR THE UP11 ............................................... 2-9
2.6 CFW-11M RB MODEL SPECIFICATION (SMART CODE) ........................... 2-9
2.7 RECEIVING AND STORAGE .................................................................. 2-10
3 INSTALLATION AND CONNECTION ........................................... 3-1
3.1 INSTALLATION ENVIRONMENT ............................................................. 3-1
3.2 LIST OF COMPONENTS .......................................................................... 3-1
3.3 MECHANICAL INSTALLATION ................................................................ 3-3
3.3.1 Keypad Installation at the Cabinet Door or Command Panel
(Remote keypad) .................................................................................... 3-8
3.4 ELECTRICAL INSTALLATION ................................................................... 3-8
3.4.1 Pre-charge Circuit ........................................................................ 3-8
3.4.2 Bus Bars ...................................................................................... 3-10
3.4.3 DC Link Fuses .............................................................................. 3-10
3.4.4 General Connection Diagram and Layout ................................... 3-11
3.4.5 UP11 Connections ....................................................................... 3-19
3.4.6 UC11 Connections ...................................................................... 3-23
3.4.7 Input Filter .................................................................................. 3-25
3.4.7.1 Basic Definitions .............................................................. 3-25
3.4.7.2 Type of Filters .................................................................. 3-26
3.4.7.3 Filter 1 ............................................................................ 3-26
3.4.7.4 Filter 2 ............................................................................ 3-27
3.4.7.5 Filter Type Selection ........................................................ 3-29
3.4.7.6 Filter Components ........................................................... 3-30
3.4.8 Synchronism ................................................................................ 3-34
3.4.9 Control Connections .................................................................... 3-36
3.4.10 Typical Control Connection ........................................................ 3-40
3.5 INSTALLATION ACCORDING TO THE EUROPEAN DIRECTIVE OF
ELECTROMAGNETIC COMPATIBILITY ........................................................ 3-41
3.5.1 Conformal Installation ................................................................ 3-41
3.5.2 Standard Definitions ................................................................... 3-42
3.5.3 Emission and Immunity Levels ..................................................... 3-43
3.5.4 External RFI Filters ...................................................................... 3-43
4 KEYPAD AND DISPLAY ................................................................ 4-1
4.1 INTEGRAL KEYPAD - HMI - CFW11 ........................................................ 4-1
4.2 PARAMETERS ORGANIZATION ............................................................... 4-3
Index
5 FIRST TIME POWER-UP AND START-UP ....................................... 5-1
5.1 PREPARATIONS FOR THE START-UP ........................................................ 5-1
5.1.1 Procedures for the First Time Power-up/Start-up ........................... 5-1
5.2 START-UP ............................................................................................... 5-2
5.2.1 Password Setting in P0000 ............................................................ 5-3
5.2.2 Oriented Start-Up .......................................................................... 5-3
5.3 SETTING DATE AND TIME ...................................................................... 5-5
5.4 BLOCKING PARAMETERS MODIFICATION .............................................. 5-5
5.5 HOW TO CONNECT TO A PC ................................................................ 5-6
5.6 FLASH MEMORY MODULE ...................................................................... 5-6
6 TROUBLESHOOTING AND MAINTENANCE ................................ 6-1
6.1 OPERATION OF THE FAULTS AND ALARMS ............................................ 6-1
6.2 FAULTS, ALARMS, AND POSSIBLE CAUSES ............................................. 6-2
6.3 SOLUTIONS FOR THE MOST FREQUENT PROBLEMS .............................. 6-7
6.4 INFORMATION FOR CONTACTING TECHNICAL SUPPORT ..................... 6-7
6.5 PREVENTIVE MAINTENANCE ................................................................. 6-8
6.5.1 Cleaning Instructions .................................................................. 6-10
7 ACCESSORIES ............................................................................. 7-1
7.1 ACCESSORIES ........................................................................................ 7-1
8 TECHNICAL SPECIFICATIONS ..................................................... 8-1
8.1 POWER DATA ......................................................................................... 8-1
8.2 ELECTRICAL / GENERAL SPECIFICATIONS .............................................. 8-4
8.2.1 Codes and Standards .................................................................... 8-4
8.3 MECHANICAL DATA ............................................................................... 8-5
Safety Instructions

1 SAFETY INSTRUCTIONS

This manual provides information for the proper installation and operation of the regenerative frequency converter CFW-11M RB.
Only trained and qualified personnel should attempt to install, start-up, and troubleshoot this type of equipment.

1.1 SAFETY WARNINGS IN THE MANUAL

The following safety warnings are used in this manual:
DANGER!
The procedures recommended in this warning have the purpose of protecting the user against dead, serious injuries and considerable material damage.
ATTENTION!
The procedures recommended in this warning have the purpose of avoiding material damage.
1
NOTE!
The text intents to supply important information for the correct understanding and good operation of the product.

1.2 SAFETY WARNINGS IN THE PRODUCT

The following symbols are attached to the product and require special attention:
Indicates a high voltage warning.
Electrostatic discharge sensitive components. Do not touch them.
Indicates that a ground (PE) must be connected securely.
Indicates that the cable shield must be grounded.
Indicates a hot surface warning.
C F W -11M R B |1-1
Safety Instructions
1

1.3 PRELIMINARY RECOMMENDATIONS

DANGER!
Only qualified personnel familiar with the CFW-11M RB regenerative frequency converter and associated equipment should plan or implement the installation, start-up and subsequent maintenance of this equipment. These personnel must follow all the safety instructions included in this Manual and/or defined by local regulations. Failure to comply with these instructions may result in death, serious injury, and equipment damage.
NOTE!
For the purposes of this manual, qualified personnel are those trained and able to:
1. Install, ground, power-up and operate the CFW-11M RB according to this manual and the effective legal safety procedures.
2. Use protection equipment according to the established regulations.
3. Provide first aid.
DANGER!
Always disconnect the main power supply before touching any electrical component associated to the converter. Several components can remain charged with high voltages and/or in movement (fans) even after the AC power supply is disconnected or switched off. Wait at least 10 minutes to assure a total discharge of the capacitors. Always connect the equipment frame to the protection earth (PE) at the suitable connection point.
ATTENTION!
Electronic boards have components sensitive to electrostatic discharges. Do not touch directly on components or connectors. If necessary, touch the grounded metallic frame before or use an adequate grounded wrist strap.
Do not perform any withstand voltage test!
If necessary, consult WEG.
NOTE!
Regenerative frequency converter may interfere with other electronic equipment. In order to reduce these effects, take the precautions recommended in the chapter 3 - Installation and Connection.
NOTE!
Read this manual completely before installing or operating the converter.
1-2 | CFW-11M RB
Safety Instructions
ATTENTION!
When in operation, electric energy systems – such as transformers, converters, motors and cables – generate electromagnetic fields (EMF), posing a risk to people with pacemakers or implants who stay in close proximity to them. Therefore, those people must stay at least 2 meters away from such equipment.
1
C F W -11M R B |1-3
1
Safety Instructions
1-4 | CFW-11M RB

2 GENERAL INSTRUCTIONS

2.1 ABOUT THE MANUAL

This manual presents how to install, to start-up, the main characteristics and shows how to troubleshoot the most common problems of the CFW-11M RB converter series.
For information on other functions, accessories and operation conditions please refer to the following manuals:
ATTENTION!
The operation of this equipment requires installation instructions and detailed operation provided in the user manual, programming manual and manuals/guides for kits and accessories. The user manual and the parameters quick reference are supplied in a hard copy together with the converter. The other manuals are available at www.weg.net. A printed copy of the files available on WEG’s website can be requested at your local WEG dealer.
General Instructions
2
; Programming Manual, with a detailed description of the parameters and advanced functions of the
C F W -11M R B .
; I/O Expansion Module Manual.

2.2 TERMS AND DEFINITIONS

Regenerative Frequency Converter: three-phase switching frequency converter “boost type” (amplifier)
that converts the AC voltage from the power supply to a DC voltage (DC Link). It has the capability of absorbing the energy of the power supply (AC) or to recover the energy back to the power supply, being used as a DC voltage source to supply voltage to several output inverter.
Output inverter: frequency inverter fed by the DC link bus bar supplied by the regenerative converter. It is responsible for the motor control.
Normal Duty Cycle (ND): converter duty cycle that defines the maximum continuous operation current (I
) and overload current conditions (110 % for 1 minute). The ND cycle is selected by setting P0298
nom-ND
(Application) = 0 (Normal Duty (ND)). The inverter overload conditions are reflected in the regenerative converter.
I
: converter rated current for use with the normal duty (ND) cycle.
nom-ND
Overload: 1.1 x I
nom-ND
/ 1 minute.
Heavy Duty Cycle (HD): converter duty cycle that defines the maximum continuous operation current (I
) and overload current conditions (150 % for 1 minute). The HD cycle is selected by setting P0298
nom-HD
(Application) = 1 (Heavy Duty (HD)). The inverter overload conditions are reflected in the regenerative converter.
I
: converter rated current for use with the heavy duty (HD) cycle.
nom-HD
Overload: 1.5 x I
nom-HD
/ 1 minute.
C F W -11M R B |2-1
2
General Instructions
Current Imbalance (%):
Imbalance of power unit X - phase Y =
IYX - I
I
I
= IY1 + IY2 + ... + I
YAVG
N
YN
Where: N = number of power units. IYN = phase current Y (U, V or W) of the N power unit (P0815 to P0829). I
= average current of phase Y.
YAVG
Pre-charge Circuit: charges the DC bus capacitors with limited current, which avoids higher peak currents at the converter power-up.
DC Bus: converter intermediate circuit; DC voltage obtained from the AC input voltage rectification or from an external power supply; feeds the output IGBTs converter bridge.
YAVG
YAVG
x 10 0
Power modules U, V, and W: set of two IGBTs of the regenerative converter input phases R, S, and T.
IG BT: Insulated Gate Bipolar Transistor; basic component of the power modules U, V and W. The IGBT
works as an electronic switch in the saturated (closed switch) and cut-off (open switch) modes.
NTC: resistor which resistance value in ohms decreases proportionally to the temperature increase; used as a temperature sensor in power modules.
HMI: Human Machine Interface: it is a device that allows the visualization and modification of the converter parameters. The CFW-11 HMI presents keys for the regenerative converter control, navigation keys and a graphic LCD display.
FLASH Memory: non-volatile memory that can be electronically written and erased.
RAM Memory: Random Access Memory (volatile).
USB: Universal Serial Bus; is a serial bus standard that allows devices to be connected using the ”Plug
and Play” concept.
PE: Protective Earth.
RFI Filter: Radio-Frequency Interference Filter for interference reduction in the Radio-Frequency range.
PWM: Pulse Width Modulation; pulsed voltage at the input of the regenerative converter.
Switching Frequency: frequency of the IGBTs switching, normally expressed in kHz.
General Enable: when activated, the converter controls the voltage at the DC bus. When deactivated,
this function immediately blocks the PWM pulses. The General Enable function may be controlled through a digital input set to this function.
Heatsink: metal device designed to dissipate the heat generated by the power semiconductors.
2-2 | CFW-11M RB
Amp, A: ampères.
°C: Celsius degree.
°F: Fahrenheit degree.
AC: alternated current.
General Instructions
DC: direct current.
CFM: Cubic Feet per Minute; unit of flow.
cm: centimeter.
ft: foot.
hp: horse power = 746 Watts; unit of power, used to indicate the mechanical power of electrical motors.
Hz: hertz.
in: inch.
kg: kilogram = 1000 grams.
kHz: kilohertz = 1000 Hertz.
l/s: liters per second.
lb: pound.
2
m: meter.
mA: miliampère = 0.001 Ampère.
min: minute.
mm: millimeter.
ms: millisecond = 0.001 seconds.
N.m.: newton meter; unit of torque.
rms: root mean square; effective value.
rpm: revolutions per minute; unit of speed.
s: second.
V: volts.
Ω: ohms.
C F W -11M R B |2-3
2
General Instructions

2.3 ABOUT THE CFW-11M RB

The regenerative frequency converter is a bidirectional three-phase boost type AC/DC converter that generates higher DC voltage than the line peak voltage. These converter are commonly known as AFE (Active Front End) drives. The CFW-11M RB line utilizes the “RB” sulfix which states for Regenerative Braking because it has the natural capacity of allowing the energy to flow from the converter to the power supply when the motor is braking. The DC voltage generated by the regenerative converter is used to feed other inverter power units that are controlling three-phase motors.
The CFW-11M RB regenerative converter is a high performance product that allows three-phase power supply rectification with the following advantages:
; Low input current harmonic distortion.
; Capacity of recovering energy back to the power supply (regeneration) allowing high braking torque levels.
The CFW-11M RB line presents a modular structure with the possibility of assembling up to five power units (UP11 - Books), one control unit (UC11) and interconnection cables. The control unit (UC11) is able to control up to 5 (five) UP11’s.
The UP11 are directly feed via DC link bus bar and the UC11 is fed via the +24 Vdc power supply. Figure
2.1 shows an application sample.
The UP11 power units control is done by the UC11 control unit. The control unit is composed by the CFW-11M RB control rack line, the IPS1 board and the CSR11 synchronism board. The IPS1 board exchange signals with all UP11 units. The CSR11 synchronism board supervises the power supply, measuring the voltage values and synchronizing the control.
U P11
U P11
Filter
U P11
U C11 R B
Output inverter
Motor
2-4 | CFW-11M RB
CC11 R BC SR11 IPS1
Figure 2.1 - Configuration sample with 3 UP11
General Instructions
The CFW-11M RB can be provided as a complete panel (AFW-11M RB) or as a panel mounting kit for local assembly in a panel. The output inverter stage (CFW-11M) is needed for the mounting kit assembly.
The panel mounting kit is composed by the control unit set and the power units (UP11), which quantity varies according to the CFW-11M RB model. The control unit set is composed by the control unit (UC11), the cable set needed for the connection between the IPS1 board and the power units and the ribbon cable to connect the IPS1 board to the CC11 RB board.
Supply
Power section
220 V Ext.
Pre-
Charge
Input
filter
Control UC11
Feedback
- voltage
- current
U P11
Capac.
Bank
U P11
Capac.
Bank
2
+
DC Bus Bar
-
PE
HMI (remote)
Digital
inputs
(DI1 to DI6)
IPS1 Electronics power supplies and
USB
inter face between power and control
HMI
CC11 RB
Control
board
with
CPU 32 bit "RISC"
FLASH
memory
module
(Slot 5)
CSR
Figure 2.2 - CFW-11M RB block diagram
Accessories
I/O expansion
(Slot 1 - white)
Analog outputs
(AO1 and AO2)
Digital outputs
DO1 (RL1) to
DO3 (RL3)
C F W -11M R B |2-5
2
General Instructions
NOTE!
Additional itens are need for the assembly of the complete unit, such as output inverter, DC fuses in the DC link bus bar connection, external pre-charge circuit and filter.
NOTE!
It is not necessary to add a current transformer (CT) for output short circuit protection to the ground since each UP11 module has its own internal protection.
Keypad
Front cover
Control rack
DC Bus capacitors
PSB1 board – switched
mode power supply
CIM1 board – Interface
with the control
IPS1 shield
IPS1 shield base
IPS1 board - interface between power and control
Figure 2.3 - UC11 main components
DC Bus
IGBTs module decoupling capacitors
Set of IGBTs modules gate resistor board gate driver board
Hall effect CT
Output reactor
2-6 | CFW-11M RB
Fan
Figure 2.4 - UP11 main components
U C11
General Instructions
U P11
N1 N2 N3 N4 N5 N6
CC11 R B
Keypad
External
supply
(*) Tolerance: ±10 %.
Current: 4 A.
Power supply
24 Vdc
XC60
UP
UN
VP
XC60
IPS1
(*)
XC9
VN WP
WN
XC40
Figure 2.5 - UP11: Connections between the IPS1 and the CIM1 interface boards
+UD
- UD
XP XN
XC3 XC5
PS B1
XC40
CI M1
2
+ 5 V
+UD
- UD
+ 15 V
XC3
XP
XN
+ 20 V
XC5
CI M1
Figure 2.6 - UP11: Connections between the CIM1 interface board and the PSB1 power supply board
CI M1
XC4A XC4AB
XC33
Ext. 220 V
XC16BXC16A
V5V4
Power Section Fans
Figure 2.7 - UP11: Connections between the CIM1 interface board and the fans
C F W -11M R B |2-7
General Instructions
2
558
+UD
10
11
10
TCU
11
10
11
U
+UD
8
10
11
10
TCV
+UD
TCW
V
L1
(0,5 %)
UOUT
VOUT
WOUT
W
11
10
11
10
11
10
11
10
11
CI M1
XC1U
XC14U
XC64U
XC1V
XC14V
XC64V
XC1W
XC14W XC64W
XW
-UD
GDB5
XC1 XC2
XC4
CRG9
1 2 3 4 5 8
XC14
XU
GDB5
XC1
XC4
XC2
CRG9
-UD
4
3
1
XC14
XV
GDB5
XC4XC1
XC2
CRG9
-UD
4
1
223
XC14
Figure 2.8 - UP11: Connections between the CIM1 interface board, gate driver boards, modules and sensors for the output voltage and
output current
NOTE!
The synchronism connection diagram is presented at figure 3.46.

2.4 IDENTIFICATION LABELS FOR THE UC11

The UC11 identification label is located on the control rack.
WEG part number
Serial number
Manufacturig date
Figure 2.9 - UC11 identification label
Identification label
U C11 m o d el
2-8 | CFW-11M RB
Figure 2.10 - Location of the identification label
General Instructions

2.5 IDENTIFICATION LABELS FOR THE UP11

There are two identification labels, one located at the converter front cover and another inside the UP11, close to the fans.
Manufacturing date
U P11 M o d el
WEG part number
Converter net weight
Rated input data (voltage, rated currents
for use with Normal Duty (ND) and Heavy
Duty (HD) cycles, frequency)
Current specifications for use with the
Normal Duty (ND) cycle
Current specifications for use with the
Heavy Duty (HD) cycle
Available certifications
(24 corresponds to week and I to year) Serial number
Maximum surrounding air temperature
Rated output data (voltage, number of power phases, rated currents for use with Normal Duty (ND) and Heavy Duty (HD) cycles, overload currents for 1 min and 3 s, and frequency range)
2
Figure 2.11 - UP11 identification label
Figure 2.12 - Location of the identification labels

2.6 CFW-11M RB MODEL SPECIFICATION (SMART CODE)

In order to specify the CFW-11M RB it is necessary to, fill in the desired voltage and current values in the respective fields for the nominal supply voltage and the rated input current for normal duty (ND) cycle in the smart code according to the example of the table 2.1.
C F W -11M R B |2-9
2
General Instructions
Table 2.1 - Smart code
Converter Model Available Option Kits
Refer to Chapter 8 for the CFW-11M RB list
of models and for the complete technical
Example BR CFW11M 0470 T 5 O RB _ _ _ _ Z
Field description
Available options
Market identification (defines the manual language and the factory settings)
2 characters T =
WEG CFW-11M frequency converter series
Rated current for Normal Duty (ND) cycle
specifications
Number of output phases
three­phase
Nominal voltage Option kit Braking Special
4 = 380...480 V 5 = 500...600 V 6 = 660...690 V
O =
product with option kit
Ex.: CFW11M0470T5ORBZ corresponds to a CFW-11M RB regenerative braking converter, 470 A three­phase, with power supply voltage from 500 V to 600 V. An converter for 380 / 480 V would be specified as CFW11MXX XXT4ORBZ and for 660 / 690 V voltage it would be specified as CFW11MXXXXT6ORBZ (where XXX X is replaced by the converter current). The possible options for the converter nominal current in normal duty (ND) cycle are showed in the table 2.2, according to the rated input voltage.
Refer to the chapter 7 for more
details on the options.
Special software
Blank = standard S1= special software n°1
RB = Regenerative Braking
hardware
Blank = standard H1= special hardware n°1
Character that identifies the end of the code
Table 2.2 - Nominal currents at normal duty cycle (ND)
380 / 480 V 500 / 600 V 660 / 690 V
0600 = 600 A 1140 = 1140 A 1710 = 1710 A 2280 = 2280 A 2850 = 2850 A
0470 = 470 A
0893 = 893 A 1340 = 1340 A 1786 = 1786 A 2232 = 2232 A
0427 = 427 A
0811 = 811 A 1217 = 1217 A 1622 = 1622 A 2028 = 2028 A

2.7 RECEIVING AND STORAGE

The CFW-11M RB power units, as well as the control sets, are supplied packed in wooden boxes (refer to the figure 2.14).
Figure 2.13 - Power unit packing
There are identification labels outside these boxes, the same as the ones fixed on the respective products.
2-10 | CFW-11M RB
General Instructions
In order to open the box:
1. Put the control set box on a table with the help of two people; for the power units put the box on the floor.
2. Open the wood crate.
3. Remove all the packing material (the cardboard or styrofoam protection) before removing the converter.
Check the following items once the converter is delivered:
; Verify that the product identification label corresponds to the model number on your purchase order.
; Inspect the product for external damage during transportation.
In case of any damage, immediately report it to the carrier responsible for delivering your product.
If the products are not installed immediately, store them in a clean and dry place (temperature between
-25 °C (-13 °F) and 60 °C (140 °F)) with a cover to prevent the contamination with dust.
ATTENTION!
Capacitor reforming is required if the converter or power units are stored for long periods of time without power. Refer to the procedures in item 6.5 - table 6.3.
2
Figure 2.14 - Do not tilt the power units
C F W -11M R B |2-11
2
General Instructions
2-12 | CFW-11M RB

3 INSTALLATION AND CONNECTION

This chapter provides information on installing and wiring the CFW-11M RB. The instructions and guidelines listed in this manual shall be followed to guarantee personnel and equipment safety, as well as the proper operation of the converter.

3.1 INSTALLATION ENVIRONMENT

Avoid installing the converter in an area with:
; Direct exposure to sunlight, rain, high humidity, or sea-air.
; Inflammable or corrosive gases or liquids.
; Excessive vibration.
; Dust, metallic particles, and oil mist.
Installation and Connection
3
Environment conditions for the proper operation of the converter:
; Temperature:
Models CFW11M...T4:
-10 °C to 45 °C (14 °F to 113 °F) - nominal conditions (measured around the converter). From 45 °C to 55 °C (113 °F to 131 °F) - 2 % current reduction for every Celsius degree (or 1.11 % each °F) above 45 °C (113 °F). Models CFW11M...T5 and CFW11M...T6:
-10 °C to 40 °C (14 °F to 104 °F) - nominal conditions (measured around the converter). From 40 °C to 55 °C (104 °F to 131 °F) - 2 % current reduction for every Celsius degree (or 1.11 % each °F) above 40 °C (104 °F).
; Humidity: from 5 % to 90 % non-condensing.
; Altitude: up to 1000 m (3.300 ft) - standard conditions (no derating required).
; From 1000 m to 4000 m (3.300 ft to 13.200 ft) - 1 % of current derating for each 100 m (or 0.3 %
each 100 ft) above 1000 m (3.300 ft) altitude.
; From 2000 m to 4000 m (6.600 ft to 13.200) - 1.1 % of maximum voltage derating for each 100 m
(or 0.33 % each 100 ft) above 2000 m (6.600 ft) up to 4000 m (13.200 ft) maximum altitude.
; Pollution degree: 2 (according to EN50178 and UL508C) with non-conductive pollution. Condensation
shall not originate conduction through the accumulated residues.

3.2 LIST OF COMPONENTS

The panel mounting kit is composed by the control set and by UP11 power units, whose number varies according to the current. The control set contains the UC11 control unit, the necessary cable sets for the connections between the IPS1 and the power units, and the flat cable that connects the IPS1 board to the CC11 RB control board.
C F W -11M R B |3-1
Installation and Connection
Table 3.1 - Currents and configuration in 380 / 480 V
3
Nominal Current (A)
ND HD
600 515 1 1140 979 2 1710 1468 3 2280 1957 4 2850 2446 5
Table 3.2 - Currents and configuration in 500 / 600 V
Nominal Current (A)
ND HD
470 380 1
893 722 2 1340 1083 3 1786 1444 4 2232 1805 5
Table 3.3 - Currents and configuration in 660 / 690 V
Nominal Current (A)
ND HD
427 340 1
811 646 2 1217 969 3 1622 1292 4 2028 1615 5
Number of Power Units UP11-02
Number of Power Units UP11-01
Number of Power Units UP11-01
Each cable set contains one optical fiber and one DB-25 cable. Both cables are for the connections between the IPS1 board (control unit) and the CIM1 board (power unit).
Table 3.4 - Cable sets
Weg Part
Number
10411757 2350 (92.52) 2550 (100.39) 10509891 2800 (110.24) 3000 (118.11) 10411758 3400 (133.86) 3600 (141.73) 10411759 3900 (153.54) 4100 (161.42)
Optical Fiber Length
mm (in)
DB-25 Cable Length
mm (in)
The cable sets that come with the control sets are described in the table 3.5.
Table 3.5 - Number of cable sets
Number of Power Units Number of Cable Sets
1 1X 10411757 2 2X 10411757
3
4
5
2X 10411757 1X 10509891
2X 10411757 1X 10509891 1X 10411758
2X 10411757 1X 10509891 1X 10411758 1X 10411759
The panel integrator is responsible for the other components of the panel, such as, the power bus bars, the pre-charge circuit, the panel fans, the protection fuses, input filter, etc.
3-2 | CFW-11M RB
Installation and Connection
VENTILADOR DO PAINEL (QUANDO NECESSÁRIO)
SAÍDA DE AR
SAÍDA DE AR
150
ABERTURA DE VENTILAÇÃO
NA SUPERFÍCIE FRONTAL DO
PAINEL
VENTILADOR DO PAINEL (QUANDO NECESSÁRIO)
SAÍDA DE AR
SAÍDA DE AR
150
ABERTURA DE VENTILAÇÃO
NA SUPERFÍCIE FRONTAL DO
PAINEL
VENTILADOR DO PAINEL (QUANDO NECESSÁRIO)
SAÍDA DE AR
SAÍDA DE AR
150
ABERTURA DE VENTILAÇÃO
NA SUPERFÍCIE FRONTAL DO
PAINEL
VENTILADOR DO PAINEL (QUANDO NECESSÁRIO)
SAÍDA DE AR
SAÍDA DE AR
150
ABERTURA DE VENTILAÇÃO
NA SUPERFÍCIE FRONTAL DO
PAINEL

3.3 MECHANICAL INSTALLATION

The power units must be properly secured in the drive cabinet, making it possible the easy withdrawal and reinsertion in case of maintenance. The fastening must also be done so that it prevents panel transportation damage.
The “Panel Mounting Rack” accessory simplifies the mounting of the power units and allows their simple fastening and movement. Refer to the section 7.1 for more details.
Ø22.5 hoisting eyes - weight 171 kg (377 lb)
3
Figure 3.1 - UP11: hoisting eyes
Figure 3.2 - Mounting of the UP11 side by side without lateral spacing
C F W -11M R B |3-3
Installation and Connection
250
VENTILADOR DO PAINEL (QUANDO NECESSÁRIO)
ENTRADA DE AR
ABERTURA DE VENTILAÇÃO
NA SUPERFÍCIE FRONTAL DO
PAINEL
584,9
56,5
221,9 221,9
85
18,9
18,9
193
175
211
RODAS (ROLAMENTOS) REVESTIDAS
550,6
61,5
8,9
Panel fan (when required)
SAÍDA DE AR
Outlet air
3
250
(9. 84)
Note: dimensions in mm (in).
SAÍDA DE AR
Outlet air
Figure 3.3 - Clearence requirements for air circulation
Inlet air
150
150
(5.91)
Ventilation
openings on
frontal panel
surface
The UP11 wheels facilitate its insertion into and withdrawal from the panel (figure 3.4).
211 (8.3)
175 (6.9)
85 (3.3)
221.9 (8.7)221.9 (8.7)
61.5
(2.4)
584.9 (23)
56.5 (2.22)
18.9 (0.7)
Note: dimensions in mm (in).
18.9 (0.7) 19 3 (7.6 )
Wheels (ball-bearings) covered with
nylon for movement in the cabinet
Figure 3.4 - UP11: bottom view
8.9 (0.3)
550.6 (21.7)
3-4 | CFW-11M RB
195
195
24.9
509.8
19 5 (7. 7 )
125
125 (4.9)
Figure 3.5 - Fixing holes of the power unit
25.3
25.3 (1)
Installation and Connection
3
SUPORTES PARA
Supports for top
FIXAÇÃO SUPERIOR
DO DRIVE
fixing of the
module
509.8 ( 20 .1)
9.2 (0.4)
9.2
14.514.5
100.5 100.5
24.9 (1)
97.5
97.5 ( 3.8)
100.5 (4) 100.5 (4)
14. 5 ( 0.6)14. 5 ( 0.6)
19 5 (7. 7 )
Note: dimensions in mm (in).
Figure 3.6 - Supports for top fixing
Mounting of the UC11 at the panel door: Control rack with flange mounting and IPS1 module mounted inside the panel door. The control rack is secured with four M3 screws (recommended tightening torque:
0.5 N.m).
C F W -11M R B |3-5
3
Installation and Connection
C F W-11 Interface card power-control
143 mm (5.62 in)
Figure 3.7 - Example of the mounting of the control rack and its base
Figure 3.8 - Final mounting aspect
3-6 | CFW-11M RB
Installation and Connection
Note: dimensions in mm (in).
Ø 5.2 (4x)
(0.20)
Figure 3.9 - Control rack fixing and the necessary cuts
283,6 (11.17)
190 (7.48)
143 .3 (5.64)
286.5 (11.28)
18 6 . 5 (7. 3 4 )
7 (0.27)
R8 (4x)
(0.32)
93.3
(3.67)
2 (0.08)
11
(0.43)
290 ( 11. 4 2)
7 (0.27)
3
41.5
(1.63)
292 ( 11. 5 )
M6 (4x) for the IPS1
Note: dimensions in mm (in).
Figure 3.10 - IPS1 module base fixing
module fixing
The IPS1 module base is fixed with four M6 bolts (recommended tightening torque: 8.5 N.m).
The power unit total air outflow is 1150 m3/h (320 l/s; 677 CFM). It is recommended an outflow of 1350 m3/h (375 l/s; 795 CFM) per power unit at the air exhaustion.
C F W -11M R B |3-7
Installation and Connection

3.3.1 Keypad Installation at the Cabinet Door or Command Panel (Remote keypad)

28 .5 [1.12]
23.5
[0.93]
35.0 [1.38]
16.0 [0.63]
3
113 . 0 [4 . 45]
65.0 [2.56]
Note: dimensions in mm [in].
Figure 3.11 - Data for the HMI installation at the cabinet door or command panel
103.0 [4.06]
23.4 [0.92]
The keypad frame accessory can also be used to fix the HMI as mentioned in the table 7.1.

3.4 ELECTRICAL INSTALLATION

DANGER!
The following information is merely a guide for proper installation. Comply with applicable local regulations for electrical installations.
DANGER!
Make sure the AC power supply is disconnected before starting the installation.
4.0 [0.16] (3X)
ATTENTION!
The CFW-11M RB can be connected in circuits with symmetrical short circuit capability up to 150000 Arms (480 V/690 V maximum).
ATTENTION!
Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protection must be provided in accordance with applicable local standards.

3.4.1 Pre-charge Circuit

The resistors of the pre-charge circuit must be sized according to the following criteria:
- Maximum voltage.
- Maximum energy.
- Power overload capacity of the resistors during the pre-charge period (energy dissipation capacity).
The characteristics of the resistors must be obtained with their manufacturer.
3-8 | CFW-11M RB
Loading...
+ 65 hidden pages