You are required to thoroughly read all installation instructions and
product safety information before beginning the installation of this
product. FAILURE TO COMPLY WITH PROPER INSTALLATION
AND MAINTENTENANCE INSTRUCTIONS COULD RESULT IN
PROPERTY DAMAGE, PERSONAL INJURY AND/OR DEATH.
Watts is not responsible for damages resulting from improper installation and/or maintenance.
Do not use with water that is microbiologically unsafe or of
unknown quality without adequate disinfection before or after
the system.
Local building or plumbing codes may require modifications to the
information provided. You are required to consult the local building
and plumbing codes prior to installation. If this information is not
consistent with local building or plumbing codes, the local codes
should be followed.
Save manual for future reference.
Refer to enclosed for operating parameters to ensure proper use
with your water supply.
IOM-WQ-PWBWGAC-PWBWMZ-PWBWCAL
PWBWGAC
PWBWMZ
PWBWCAL
Table of Contents Pages
Important Safety Information – Read All .......................2
Instructions Before Using.................................. 2
Caution: Read and follow the information in this
manual to minimize the risk of electric shock or per-
!
sonal injury.
Important: If you are unsure about installing your Watts
water lter, contact a Watts representative or consult a
professional plumber.
Important: This system must be installed in compliance with applicable state province and local codes,
law, and regulations.
READ Instructions Before Using
• After reading these instructions completely, obtain all the
materials and tools needed for installation.
NOTE: Failure to install the system correctly voids the warranty.
• Perform installation according to state, province and local
plumbing codes.
Use only lead-free solder and flux for sweat-solder connec-
tions, as required by state, province and federal codes.
• Handle all components of the system with care. Do not drop,
drag or turn components upside down.
• Be sure the oor under the water lter system is clean, level
and strong enough to support the unit.
• The system uses 24 volt-60Hz electrical power. Always use
the transformer supplied.
Plug transformer into an indoor 120 VAC, grounded outlet.
Properly ground the system to conform with all codes and
ordinances.
• Install the system in a protected area. Be sure electric outlet
and transformer do not come in contact with water. For more
information on where to install the lter see the Installation
Considerations section of this manual.
Do not attempt to treat water over 110°F (43°C) with the
system. Always connect the system to the main water supply pipe before the water heater.
Do not expose the system to freezing temperatures. Water
freezing in the system causes equipment damage.
Do not install in direct sunlight. Ultraviolet rays from the sun
may cause damage.
• Minimum inlet water pressure is 30psi. Maximum inlet water
pressure is 125psi. Use a pressure reducing valve if necessary.
Caution:
• Do not use with water that is microbiologically
!
unsafe or of unknown quality.
• Test the water periodically to verify that the
system is performing satisfactorily.
• Discard small parts remaining after the installation.
2
Filter Anatomy
1
6
2
3
4
5
7
ITEM #DESCRIPTION
1Valve
2Bypass
3Tank
4Distributor
5Filter Media (Calcite, Carbon, or Micro Z™)
6Faceplate/Controls
7Gravel Underbed
3
Specications
Feed Water Parameters
!
Do not use this system on water that is microbiologically
unsafe or of unknown quality without adequate disinfection
before or after the system !
Minimum inlet pressure: 30 psig
Maximum operating pressure: 125 psig
Minimum water temperature: 34°F (1°C)
Maximum water temperature: 110°F (43°C)
Power
Voltage: 120VAC
Frequency: 60Hz
Power consumption: 7 Watts Maximum
Installation
Location: Indoors (Protect from direct sunlight)
Minimum ambient temperature: 34°F (1°C)
Maximum ambient temperature: 122°F (50°C)
Drain Flow Rates - The drain system these lters
are plumbed to must be able to accept the listed drain
volumes for a period of 27 minutes.
Micro Z™ Filters
9" X 48", 1 cubic ft. 7 gpm
10" X 54", 1.5 cubic ft. 7 gpm
12" X 52", 2 cubic ft. 10 gpm
13" X 65", 3 cubic ft. 15 gpm
Carbon Filters:
9" X 48", 1 cubic ft. 4 gpm
10" X 54", 1.5 cubic ft. 5 gpm
12" X 52", 2 cubic ft. 7 gpm
13" X 65", 3 cubic ft. 9 gpm
16" X 65", 4 cubic ft. 15 gpm
Calcite Filters:
9" X 48", 1 cubic ft. 7 gpm
10" X 54", 1.5 cubic ft. 7 gpm
12" X 52", 2 cubic ft. 10 gpm
13" X 65", 3 cubic ft. 15 gpm
MODEL NO.VALVEMINERAL TANK
SIZE
MEDIA CUBIC
FOOT
GRAVEL
(LBS)
SERVICE FLOW*
(GPM)
PRESSURE DROP
(PSI)
BACK WASH
(GPM)
FLOOR SPACE
LXWXH
PWBWMZ1Time Clock9" X 48"110915716" X 10" X 55"
PWBWMZ15Time Clock10" X 54"1.5101015716" X 11" X 62"
PWBWMZ2Time Clock12" X 52"23010151017" X 13" X 60"
PWBWMZ3Time Clock13" X 65"34015151518" X 14" X 74"
MODEL NO.VALVEMINERAL TANK
SIZE
MEDIA CUBIC
FOOT
GRAVEL (LBS)SERVICE FLOW*
(GPM)
PRESSURE DROP
(PSI)
BACK WASH
(GPM)
FLOOR SPACE
LXWXH
PWBWGAC1Time Clock 9" X 48"1103.7<15416" X 10" X 55"
PWBWGAC15Time Clock10" X 54"1.5105.5<15516" X 11" X 62"
PWBWGAC2Time Clock12" X 52"2307.4<15717" X 13" X 60"
PWBWGAC3Time Clock13" X 65"34011.1<15918" X 14" X 74"
PWBWGAC4Time Clock16" X 65"46014.8<151520" X 17" X 74"
MODEL NO.VALVEMINERAL TANK
SIZE
MEDIA CUBIC
FOOT
GRAVEL
(LBS)
PEAK SERVICE
FLOW (GPM)*
PRESSURE DROPBACK WASH
(GPM)
FLOOR SPACE
L X W X H
PWBWCAL1Time Clock9" X 48"1105<15716" X 10" X 55"
PWBWCAL15Time Clock10" X 54"1.5107<15716" X 11" X 62"
PWBWCAL2Time Clock12" X 52"23010<151017" X 13" X 60"
PWBWCAL3Time Clock13" X 65"34015<151518" X 14" X 74"
*Note: Peak service flow rate is for intermittent use only and is not to be interpreted as continuous service flow rate capability. These systems are designed to treat the domestic water used in a
single family dwelling. For irrigation water treatment or higher volume applications please contact your Watts representative.
4
Setup
Unpack and check the system components for damage or missing
parts.
Make sure that the bypass valve and plumbing yoke are properly
connected to each other and to the control valve with the mounting
clips. Make certain that the drain line flow control fitting is installed
properly on the drain port of the control valve. Systems that are 13”
in diameter and larger are not loaded with media. These systems
must be loaded with media before placing into service. To load a
system follow the below steps.
1. Cap the top open end of the distributor tube with tape and plastic sheeting to keep foreign debris from entering the distributor
tube. This cap must be secure and not come off during media
loading.
2. Place the distributor tube, screen end down, into the mineral
tank and center it in the bottom. The top of the distributor tube
should be flush with the top of the tank.
3. Make sure the plastic and tape cap is secure to the top of the
distributor tube, place a funnel on the top of the tank and load
first the gravel then the filter media into the tank. The cap must
not come off of the distributor tube during the loading of the
media.
4. Remove the plastic cap from the distributor tube. DO NOT PULL
UP ON THE DISTRIBUTOR TUBE when removing the cap. The
distributor tube top must remain flush with the top of the tank.
5. Clean any media from the threads and top of the mineral tank.
6. Lubricate the O-rings on the bottom of the control valve (distributor pilot O-ring and top of tank O-ring). Use non-petroleum
based silicone lubricant only.
7. Place the control valve on top of the tank. When doing this step,
seat the top of the distributor tube inside the centered O-ring
sealed port on the bottom of the valve first then press the valve
down until the tank threads come in contact with the valve
threads. This ensures that the distributor tube is properly seated
into the bottom of the control valve. Thread the valve on to the
tank clockwise. Be careful not to cross thread the valve or over
tighten it. A hand tight snug fit is appropriate for the control valve
torque. A wrench is not necessary. Do not use thread sealant or
PTFE tape on the valve base threads.
8. The system is now ready for installation.
Installation Considerations
Consider the following points when determining where to install
the filter:
• Place the system as close as possible to a sewer drain.
• Do not install the lter where it would block access to the water
heater, or access to the main water shutoff, water meter, or electrical panels.
• Install the lter in a place where water damage is least likely to oc-
cur if a leak develops.
• A 120VAC electrical outlet is needed to plug in the transformer.
• Always connect the system to the main water supply pipe before
the water heater.
• Install the system where it will not be subject to temperatures
outside of the limits stated in the Specification section or to direct
sunlight.
• Make sure the installation surface is smooth, level, and sturdy
enough to support the weight of the wetted system.
5
Installation
1. Turn off gas or electric supply to the water heater.
2. Turn off the main water supply to pipes to be cut and drain the
house water pipes.
3. Open both hot and cold faucets.
4. Move the filter assembly into installation position.
• Be sure the oor under the water lter system is clean, level and
strong enough to support the unit.
5. Plumb IN and OUT connections to and from filter.
• Be sure the incoming water supply is connected to the INLET
port of the valve.
• The valve body of the control is marked with arrows indicating
the proper flow direction.
• Connections are illustrated below.
Drain
8. Fully open two (2) cold water faucets near the water filter.
9. Fully open the house main water shutoff valve. Observe a steady
flow from both faucets.
10. Close the cold water faucets.
11. Check plumbing work for leaks and fix immediately if any are
found.
12. Connect electrical power by plugging the transformer into a
(120 VAC) outlet.
13. Remove the cover from the valve. Press and hold the “Extra
Cycle” button until the flashing “BW” symbol appears in the
Parameter Display.
6. Connect and route the valve drain line using rigid piping or hose.
Use the same size plumbing for the drain line as the fitting for
the drain connection. The smallest units have a
the larger sized units have a
use the same size plumbing as the connection to ensure proper
backwash flow. Properly secure the end of the drain line.
Note: Leave an air gap of at least 1
drain plumbing and the drain point.
CAUTION: If making a soldered copper installation, do all sweat
soldering before connecting pipes to the bypass valve. Torch
heat will damage plastic parts.
CAUTION: When turning threaded pipe ttings onto plastic t-
tings, use care not to cross-thread.
CAUTION: Use PTFE tape on all external pipe threads. Do not
use pipe joint compound.
CAUTION: Support inlet and outlet plumbing in some manner
(use pipe hangers) to keep the weight off of the valve ttings.
7. Place bypass valve in "bypass" position as shown below.
3
⁄4" connection. It is important to
1
⁄2" between the end of the
1
⁄2" connection,
14. Unplug the valve when the “BW” symbol stops flashing and the
countdown timer appears. This keeps the valve in an extended
backwash for the initial startup.
15. Open the outlet bypass valve fully.
16. Open the inlet bypass valve slightly. Open the valve just until you
hear water flowing.
17. Observe the drain flow. It may take several minutes for the filter
vessel to fill up with water and begin to flow to drain.
18. After all the air is purged from the vessel and a steady drain flow
is observed, allow the unit to backwash for 2 hours with the inlet
valve open slightly.
19. Fully open the inlet bypass valve and allow the unit to backwash
for 30 minutes.
20. After 30 minutes, observe the drain flow. If the drain flow is clear
proceed to the next step. If the drain flow is still cloudy, allow it
to continue to backwash until it is clear.
6
Installation continued
22. Plug the unit back in to the electrical outlet and allow it to finish
the flush cycle. This will take approximately 20 minutes.
23. Set the time of day. Press and hold either the Up or Down buttons until the programming icon replaces the service icon and
the parameter display reads TD. Adjust the displayed time with
the Up and Down buttons. When the desired time is set, press
the Extra Cycle button to resume normal operation. The unit will
also return to normal operation after 5 seconds if no buttons are
pressed.
24. Turn on the gas or electric supply to the water heater after all air
has been purged from the house's plumbing system and water
heaters.
Controller
The factory default program settings should be adequate for most
installations. See the ProFlo SXT Service Manual included with the
unit for advanced programming options.
Filter Operation
As water enters the filter, it passes through the filter media. Over
time, suspended solids accumulate in the filter media and need to be
rinsed out. This is accomplished by performing a backwash. During
backwash the filter is in automatic bypass allowing unfiltered water
to pass downstream. The automatic backwash is initiated based on
time and is normally set to occur in the middle of the night.
This System Has Three Positions:
1. Backwash Position
Backwash is a rapid upward flow of water that loosens the filter bed
and flushes dirt and sediment captured in the bed out to the drain.
2. Fast Rinse Position
Fast Rinse is a fast flow of water down through the filter bed that
follows a Backwash. This packs the filter bed for the next service
cycle.
3. Service Position
When the filter is In Service, water is flowing through the system and
sediment is being removed from your water if it’s a Micro Z™ filter.
If it’s a carbon filter, it removes chlorine, tastes, odors, and organics
from your water. If your system contains calcite media your water's
acidic pH will be raised closer to a value of 7.
Replenishing Calcite Filter Bed Media
As low pH water is neutralized by the calcite filter media a small
amount of calcite dissolves into the water. Over a period of time
calcite media will need to be added to the system so that it can
continue to perform properly. The need to add calcite media to the
system can be verified by performing a pH test on the treated water.
If the results of the pH test show a value below 6.5 pH units contact
your system installer or local water treatment professional to have
the media bed replenished.
Troubleshooting
PROBLEMCAUSESOLUTION
1. Loss of Water PressureSediment buildup in filter bed
2. Drain Flows ContinuouslyForeign material in control
3. Wrong time of dayPower OutageReset time of day. Be sure power supply in uninterrupted
4. Controller Cycles ContinuouslyFaulty timer board or microswitchReplace defective components
5. Unfiltered water in house
Note: Error codes appear in the service display.
ERROR CODECAUSESOLUTION
(Err 0)Drive motor is stalledSee above troubleshooting table, #5-B
(Err 1)Drive water runs continuouslySee above troubleshooting table, #4
(Err 2)There has been more than 99 days since the last regenerationInitiate a manual regeneration
(Err 3)Control Board memory failureReplace control board
A. Bypass in Bypass positionA. Move Bypass to service position
B. Valve stalled in backwashB. Have valve serviced
C. Media needs to be replacedC. Have system serviced
A. Perform a manual backwash
B. Make sure unit is plugged in
C. Replace media
Remove piston assembly and inspect bore, remove foreign
material & check control in various ports
7
LIMITED WARRANTY: Certain Watts Pure Water products come with a limited warranty from Watts Regulator Co. Other products may have no warranty or are covered by the original manufacturer’s
warranty only. For specic product warranty information, please visit www.watts.com or the published literature that comes with your product. Any remedies stated in such warranties are exclusive and
are the only remedies for breach of warranty. EXCEPT FOR THE APPLICABLE PRODUCT WARRANTY, IF ANY, WATTS MAKES NO OTHER WARRANTIES, EXPRESS OR IMPLIED. TO THE FULLEST EXTENT
PERMITTED BY APPLICABLE LAW, WATTS HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, AND IN NO EVENT SHALL WATTS BE LIABLE, IN CONTRACT, TORT, STRICT LIABILITY OR UNDER ANY OTHER LEGAL THEORY, FOR
INCIDENTAL, INDIRECT, SPECIAL OR CONSEQUENTIAL DAMAGES, INCLUDING, WITHOUT LIMITATION, LOST PROFITS OR PROPERTY DAMAGE, REGARDLESS OF WHETHER IT WAS INFORMED ABOUT
THE POSSIBILITY OF SUCH DAMAGES.